Emerson Fisher FIELDVUEDVC6200 SIS Instruction Manual

Instruction Manual Supplement
D103798X012
DVC6200 SIS
November 2013
Fisherr FIELDVUE™ DVC6200 SIS Functionality with User-Provided Pushbutton
The FIELDVUE DVC6200 SIS digital valve controller can be used with a userprovided pushbutton for the purpose of initiating or cancelling a partial stroke test and for manual reset purposes. The pushbutton will connect to the Auxiliary Terminals.
The procedures contained in this Instruction Manual Supplement are to be considered as a guideline only and should be modified to address site‐specific requirements. Use these procedures in conjunction with the Safety manual (D103601X012) and Instruction Manual (D103557X012). In addition, exercise good engineering practices and abide by specific plant safety guidelines for safe operation.
WARNING
This instruction manual supplement is not intended to be used as a stand-alone document. It must be used in conjunction with the following documents: Safety manual for DVC6200 SIS Digital Valve Controller (D103601X012) Fisher FIELDVUE DVC6200 SIS Instruction Manual (D103557X012)
Failure to use this instruction manual supplement in conjunction with the above referenced manuals could result in personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining either of these documents, contact your Emerson Process Management sale office.
www.Fisher.com
DVC6200 SIS
November 2013
Instruction Manual Supplement
D103798X012
Configuring Push Button Partial Stroke Test using ValveLink™ Software
After the successful completion of Setup Wizard select Instrument Setup > Detailed Setup and find the Initial Setup tab. Find the Aux Terminal Mode parameter and set it to Push Button Partial Stroke Test.
Running a Partial Stroke Test via Pushbutton
Press the pushbutton for more than 3 seconds but less than 10 seconds to short the auxiliary terminals. The partial stroke test will initiate. Once it is complete, the Diagnostic Data Available Alert will appear and a Partial Stroke Test Signature can be viewed using ValveLink software.
Canceling a Partial Stroke Test via Pushbutton
After the partial stroke test has begun, press the pushbutton briefly to short the auxiliary terminals. This will cancel the partial stroke test. ValveLink software will indicate that the partial stroke test was aborted by the user.
2
Loading...
+ 2 hidden pages