Emerson ACE97 Instruction Manual

Instruction Manual Form 5665
November 2011
Type ACE97 Pad-Depad Valve
Type ACE97
DEPAD PILOT VALVE
DEPAD MAIN VALV E
W8161
ACTUATOR
GAS INLET
Figure 1. Type ACE97 Pad-Depad Valve (NPS 1/2 / DN 15 Pad Valve / 1 NPT Depad Valve Shown)
!
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, re and/or chemical contamination causing property damage and personal injury or death.
VENT
PAD VALVE
TO TANK
Fisher® pad-depad valves must be installed, operated, and maintained in accordance with federal, state, and local codes, rules and regulations, and Emerson Process Management Regulator Technologies, Inc. (Regulator Technologies) instructions.
www.sherregulators.com
D102773X012
Type ACE97
Specications
Ratings and specications for the Type ACE97 Pad-Depad valve are listed in the Specications section below. Factory specications are stamped on the nameplate fastened to the actuator of the valve.
Pad (Tank Blanketing) Specications
Pad Body Sizes and End Connection Styles
1/2, 1, and 2 NPT NPS 1/2, 1, and 2 / DN 15, 25, and 50 CL150 RF
Maximum Operating Inlet Pressure
(1)
200 psig / 13,8 bar
Maximum Main Valve Inlet Pressure
(1)
200 psig / 13,8 bar
Inlet Operating Ranges
(1)
NPS 1/2 / DN 15 pad valve:
25 to 200 psig / 1,7 to 13,8 bar
NPS 1 and 2 / DN 25 and 50 pad valves:
25 to 50 psig / 1,7 to 3,4 bar 51 to 120 psig / 3,5 to 8,2 bar 121 to 200 psig / 8,3 to 13,8 bar
Control Pressure Ranges
(1)
See Table 1
Maximum and Minimum Differential Pressures
25 psig / 1,7 bar minimum 200 psig / 13,8 bar maximum
Maximum Backpressure
(1)
20 psig (1,4 bar)
Flow Coefcients for Relief Valve Sizing (110% of rated Cv)
NPS 1/2 / DN 15:
Cv 0.2 use Cv 0.22 Cv 0.4 use Cv 0.44
NPS 1 / DN 25:
Cv 1 use Cv 1.1 Cv 2 use Cv 2.2 Cv 4 use Cv 4.4 Cv 7.5 use Cv 8.25 Cv 10 use Cv 11
NPS 2 / DN 50:
Cv 20 use Cv 22 Cv 45 use Cv 50 Cv 60 use Cv 66
Depad (Vapor Recovery) Specications
Depad Body Sizes
1 and 2 NPT NPS 3 and 4 / DN 80 and 100
Depad Pressure Ranges
See Table 1
Valve Coefcients (110% of rated Cv)
1 NPT:
Cv 3 use Cv 3.3 Cv 6 use Cv 7 Cv 12 use Cv 13 Cv 17 use Cv 19
2 NPT:
Cv 20 use Cv 22 Cv 35 use Cv 39 Cv 70 use Cv 77
NPS 3 / DN 80:
Cv 90 use Cv 99 Cv 115 use Cv 127 Cv 140 use Cv 154
NPS 4 / DN 100:
(1)
Cv 150 use Cv 165 Cv 200 use Cv 220 Cv 280 use Cv 308
General Type ACE97 Specications
Pressure Registration
External
Temperature Capabilities
Nitrile (NBR):
-20° to 180°F / -29° to 82°C
Fluorocarbon (FKM):
0° to 212°F / -18° to 100°C
Ethylenepropylene (EPDM - FDA):
-20° to 212°F / -29° to 100°C
Peruoroelastomer (FFKM):
-20° to 212°F / -29° to 100°C
Approximate Weights
NPS 1/2 x 1 x 1 / DN 15 x 25 x 25:
70 pounds / 32 kg
NPS 1 x 2 x 2 / DN 25 x 50 x 50:
105 pounds / 48 kg
NPS 2 x 3 x 3 / DN 50 x 80 x 80:
175 pounds / 79 kg
(1)
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
2
E0005
CAGE
INLET
OPEN PILOT
INLET PRESSURE
ATMOSPHERIC PRESSURE
TANK PRESSURE
PILOT LOADING PRESSURE
VENT HEADER PRESSURE
INLET BLEED PRESSURE
LOADING PRESSURE EXHAUSTED BACK TO TANK
REGULATOR
POPPET
O-RING SEAT
INLET BLEED
ROLLING DIAPHRAGM
INERT GAS IN
MAIN VALVE SPRING
ACTUATOR
PAD VALVE
Figure 2. Type ACE97 Pad On / Depad Off
DEPAD PILOT
ADJUSTABLE DEADBAND
CONTROLLED PRESSURE RANGE SPRING
SENSING CONNECTION
DIAGNOSTIC PORT
Type ACE97
ON/OFF DIAGNOSTIC GAUGE
DEPAD MAIN VALVE
VENT
TANK CONNECTION
Table 1. Actuator Spring Pressure Ranges
CONTROL PRESSURE RANGES SPRING FREE LENGTH SPRING WIRE DIAMETER
Pad Setpoint Depad Setpoint (Above Pad)
inches w.c. mbar inches w.c. mbar
0.5 to 3- 1 to 7 4 to 10 10 to 25 3.08 78,2 0.105 2,67
0.5 to 7 1 to 17 4 to 6 10 to 15 4.0 102 0.092 2,34
3 to 13 7 to 32 4 to 16 10 to 40 3.73 94,7 0.156 3,96
4 to 10 10 to 25
0.5 to 1.4 psig 34 to 97 mbar 0.25 to 1 psig 17 to 69 3.8 96,5 0.250 6,35
1.0 to 2.2 psig 69 to 152 mbar 0.25 to 2 psig 17 to 138 3.8 96,5 0.313 7,95
1. Two nested springs are used (See Figure 12).
(1)
16 to 78 40 to 194
(1)
If a leak develops or if the unit or outlet continually vents gas, service to the unit may be required. Failure to correct
INCHES mm INCHES mm
3.73
2.90
94,7
73,7
0.156
0.250
personnel when installing, operating, and maintaining the Type ACE97
pad-depad valve. trouble could result in a hazardous condition. Only a qualied person must install or service the unit.
Installation, operation, and maintenance
Introduction
Scope of the Manual
procedures performed by unqualied personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Use qualied
This instruction manual provides installation, startup, maintenance, and parts ordering information for the Type ACE97 Pad-Depad valve (Figure 1). The product photo may vary depending on the size of the valve ordered.
3,96
6,35
3
Type ACE97
LOADING PRESSURE EXHAUSTED BACK TO TANK
DEPAD PILOT
ON/OFF DIAGNOSTIC GAUGE
CAGE
INLET
E0004
INLET PRESSURE
ATMOSPHERIC PRESSURE
TANK PRESSURE
PILOT LOADING PRESSURE
VENT HEADER PRESSURE
CLOSED PILOT
Product Description
REGULATOR
POPPET
O-RING SEAT
ROLLING DIAPHRAGM
CONTROLLED PRESSURE RANGE SPRING
ACTUATOR
SENSING CONNECTION
DIAGNOSTIC
MAIN VALVE SPRING
INERT GAS IN
PAD VALVE
PORT
Figure 3. Type ACE97 Pad Off / Depad On
Principle of Operation
DEPAD MAIN VALVE
Vent
TANK CONNECTION
VENT
The Type ACE97 Pad-Depad valve is a self-contained, pilot-operated valve that maintains a blanket of inert gas on top of a stored product to protect it from atmospheric contamination. It reduces combustibility, decreases vaporization, controls vapor space pressure during pump-in and pump-out operations, and prevents the tank from entering a vacuum condition and collapsing upon itself. The Type ACE97 valve provides excellent and accurate pressure control of the vapor space in the
tank. Blanketing pressure is kept to a minimum in order
to conserve the use of blanketing gas.
Pad (tank blanketing) is used to describe the process of replacing the vapor space of a storage tank with
an inert gas.
Depad (vapor recovery) is used to describe the process of relieving or venting the vapor space as a result of pressure rise.
Tank and vapor recovery connections are available to meet most customer requirements. A Single Array Manifold (S.A.M) provides a single tank and sensing connection and is required for tanks having a single nozzle. Accessories include gauges, purge meters, pressure switches, and check valves.
Type ACE97 pilot-operated valves (except for the NPS 1/2 / DN 15 pad valve) control the vapor space pressure over a stored liquid. The unit is stainless steel and is controlled by a very large actuator diaphragm. The oversized actuator diaphragm offers high sensitivity to changes in tank pressure. When a storage tank cools and tank vapors condense, Type ACE97 pad (tank blanketing) valves replace the condensing vapors with an inert gas to prevent internal tank pressure from decreasing. Positive tank pressure prevents outside air from contaminating the product and reduces the possibility of atmospheric pressure collapsing the tank.
Additionally, Type ACE97 valves provide depad (vapor recovery) capabilities through the depad main valve and depad pilot valve. When the temperature outside the tank rises causing the vapor inside the tank to expand, Type ACE97 depad valve vents the excess tank pressure to a safe place.
4
Type ACE97
E0006
CAGE
INLET
CLOSED PILOT
INLET PRESSURE
ATMOSPHERIC PRESSURE
TANK PRESSURE
PILOT LOADING PRESSURE
VENT HEADER PRESSURE
LOADING PRESSURE EXHAUSTED BACK TO TANK
REGULATOR
POPPET
O-RING SEAT
ROLLING DIAPHRAGM
MAIN VALVE SPRING
INERT GAS IN
ACTUATOR
PAD VALVE
Figure 4. Type ACE97 Pad Off / Depad Off
DEPAD PILOT
ADJUSTABLE DEADBAND
CONTROLLED PRESSURE RANGE SPRING
SENSING CONNECTION
DIAGNOSTIC PORT
ON/OFF DIAGNOSTIC GAUGE
DEPAD MAIN VALVE
TANK CONNECTION
VENT
NPS 1 and 2 / DN 25 and 50 Pad Valves (Figure 2)
When tank pressure decreases below the pad setpoint (due to pump-out operations or thermal cooling), the actuator diaphragm moves downward pushing open the pad pilot. This creates ow from the pad loading chamber to downstream. When pad loading pressure decreases, the force created by inlet pressure on the pad main valve plug overcomes the main spring force and opens the main valve plug allowing ow through the pad valve to the tank. Once tank pressure reaches pad setpoint, the pad pilot closes, pad loading pressure equalizes with inlet pressure and the pad
valve closes.
NPS 1/2 / DN 15 Pad Valve (Not Shown)
The NPS 1/2 / DN 15 pad valve has a main valve only. When tank pressure decreases below the pad setpoint the actuator diaphragm moves downward pushing the valve plug open and allowing ow through the pad valve to the tank.
Depad (Figure 3)
When tank pressure increases above the depad setpoint (due to pump-in operations or thermal heating), the actuator diaphragm moves upward and pushes open the depad pilot. This releases depad loading pressure (nitrogen or other supply gas). When depad pilot loading pressure decreases, the depad main valve opens by a spring and allows ow from the tank to the vent or recovery system.
The blanketing (padding) gas is used as the pilot uid. The link between the actuator and the depad main valve is provided by the depad pilot valve, which is located on top of the actuator. The depad pilot valve is connected to the actuator by an adjustable coupling, which can be rotated to adjust the depad setpoint. A locknut is provided on the depad pilot valve to secure the setpoint adjustment.
5
Type ACE97
BLANKETING GAS SUPPLY LINE
E0629
INLET PRESSURE GAUGE
INLET VALVE
LINE STRAINER
NORMAL TANK VENT
PAD DIAGNOSTIC GAUGE
BLANKETING GAS CONNECTION
DEPAD DIAGNOSTIC GAUGE
TANK VALVE
LIQUID
VAPOR SPACE
TANK VAPOR SPACE PRESSURE GAUGE
SENSING CONNECTION
VALVE TANK
CONNECTION
EMERGENCY
TANK VENT
VENT CONNECTION
SENSING LINE
SHUTOFF VALVE
Figure 5. Type ACE97 Pad-Depad Valve Installation
Installation and Startup
!
Personal injury, equipment damage, or leakage due to escaping accumulated gas or bursting of pressure-containing parts may result if this gas blanketing system is overpressured or installed where service conditions could exceed the limits given in the Specications section or on the valve nameplate, or where conditions exceed any ratings of the adjacent piping, piping connections, or compatibility of valve materials with process uids.
To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices (as required by Title 49, Part 192, of the U.S. Code of Federal Regulations, by the National Fuel Gas Code Title 54 of the National Fire Codes of the National Fire Protection Agency, or by other applicable codes) to prevent service conditions from exceeding those limits.
Additionally, physical damage to the
tank blanketing system could result in
personal injury and property damage
due to escaping gas or tank contents.
To avoid such injury and damage,
install the tank blanketing valve in
a safe location.
The Type ACE97 Pad-Depad valve is assembled and preset to the customer specied pressure and setpoint. The pressure ranges of the valve are stamped on the nameplate attached to the upper actuator case.
1. Use qualied personnel when installing, operating, and maintaining valves. Before installing, inspect the main valve, pilot, and tubing for any shipment damage or foreign material that may have collected. Ensure that the body interior is clean and the pipelines are free of foreign material. Apply pipe compound only to the external pipe threads with a threaded body, or use suitable line gaskets and good bolting practices with a anged body.
2. Inspect the nameplate on the upper actuator case. It displays the model number, serial number, blanketing gas supply pressure range, maximum
inlet pressure, Cv value, and set pressures. These
6
Type ACE97
must agree with the system that you are Padding (blanketing) or Depadding (recovering). The serial number will be needed in any communication with your local Sales Ofce.
3. Clean the gas padding (blanketing) supply lines of all dirt and foreign material before connecting them to the Type ACE97 Pad-Depad valve.
4. The valve should be mounted above the tank
with the actuator case in a horizontal position.
Four connections are required (see Figure 5):
a. Blanketing gas supply to the valve b. Vapor recovery/process connection (vent) c. System tank connection d. Sensing line to the tank
Piping Considerations
Piping must be capable of supporting the weight of the system. Use pipe supports when necessary. Refer to Figure 5.
Inlet Piping
The padding (blanketing) gas supply line should be equipped with a Number 100 mesh strainer to remove dirt and pipe scale. Inlet piping must be sized to adequately deliver padding (blanketing) gas at the specied inlet pressure under full ow conditions.
CAUTION
Undersized piping may inadequately deliver Padding (blanketing) gas at the specied inlet pressure under full ow conditions. This may result in unacceptable performance under high demand conditions.
Outlet Piping
Valve outlet is piped into the tank vapor space. Outlet piping should be self-draining to the tank and of equal or greater size than the Type ACE97 valve tank connection. The valve should be situated above and as close as possible to the tank vapor space for best performance.
CAUTION
Unnecessarily long or restricted outlet piping may result in poor setpoint control.
Sensing Line
The sensing line should be 1/2-inch / 13 mm tubing or pipe, must slope toward the tank, and should not contain low points (or traps) that could catch liquid. The sensing line must enter the tank above the liquid level at a point that senses the vapor space pressure and is free from turbulence associated with tank nozzles or vents.
Note
Best control is obtained when both connections to the tank are separate. If the tank has only one available nozzle, contact Regulator Technologies for alternate methods of installation. A Single Array Manifold (S.A.M.) is available for such situations.
Vent Connection
The vent connection must be self-draining, facing away from the valve, and of equal or greater size than the valve tank connection.
Tank Venting
The tank may require normal and emergency vents. The Type ACE97 Pad-Depad valve does not perform these functions, it only controls the vapor space
pressure under process conditions.
Diagnostic Gauges
An on/off diagnostic gauge is mounted on the depad main valve at the inlet to the cylinder. The face on the gauge is marked to indicate whether the main pad valve is opened, closed, or throttled.
Shutoff Valves
Note
Safety considerations may dictate shutoff valves between the tank and Type ACE97 valve.
Inlet (isolation) valves are desirable for servicing the Type ACE97 valve. If this valve was not ordered with
an inlet pressure gauge, it is advisable to install a
gauge between the inlet isolation (full-port) valve and the padding (blanketing) valve.
7
Type ACE97
TUBING
ADJUSTING SCREW
COUPLING
ACTUATOR
E0678
Figure 6. Unthreading the Adjusting Coupling
Startup, Adjustment, and Shutdown
CAUTION
If required, tank vents (normal and emergency) must be in place and operating.
LOCKNUT
E0679
Figure 7. Changing the Pad Setpoint
Adjustment
The setpoint of this unit is factory set. If an adjustment is to be made, it should be made in small increments while the unit is controlling tank pressure. It is difcult to make eld adjustments due to the slow changes in
tank pressure.
To change the pad (blanketing) setpoint:
Startup
CAUTION
Always open the tank shutoff valve prior to the inlet shutoff valve. Failure to do so could result in inlet pressure being applied to the actuator casing, potentially damaging it. Refer to Figure 5.
1. Open the tank and sensing line shutoff valves
(between the Type ACE97 valve and tank).
2. A tank vapor space pressure gauge should be
installed and visible.
3. Slowly open the inlet shutoff valve (to the pad valve) and leave it fully open.
4. Monitor the tank vapor space pressure.
1. Disconnect the tubing from the depad pilot valve
(See Figure 6).
2. Loosen the locknut (See Figure 7), but maintain its position in relation to the adjusting coupling. Doing so leaves the depad setpoint unchanged.
3. Separate the depad pilot valve from the actuator by unthreading and removing.
4. Unthread and remove the adjusting coupling.
5. Increase the pad setpoint by turning the adjusting screw clockwise. (Turning the screw counterclockwise decreases the setpoint). See Figure 7.
6. Replace the depad adjusting collar against the locknut to re-establish the depad setpoint.
To change the depad setpoint:
1. Loosen the locknut below the adjusting coupling.
2. Rotate the collar to change the setpoint. (The bottom of the coupling—nearest the locknut—is left-hand threaded).
3. Tighten the locknut.
8
Type ACE97
Table 2. Diagnostic Analysis Pressure Ranges
DIAGNOSTIC STATUS
Equal to inlet supply pressure
Slightly below inlet supply pressure
Well below inlet supply pressure
Pilot and main valves are closed.
Tank pressure is at or above set pressure.
Pilot valve supplies gas to tank. Tank
pressure is just below set pressure.
Pilot and main valves are both
supplying gas to the tank. Tank
pressure is below setpoint.
Shutdown
In any installation it is important to open and close valves slowly and to close the inlet shutoff valve rst when shutting down the system.
Maintenance
Valve parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection and replacement of parts depend on the severity of service conditions and the requirements of local, state, and federal regulations. Due to the care Regulator Technologies takes in meeting all manufacturing requirements, use only replacement parts manufactured or furnished by Regulator Technologies.
All O-rings, gaskets, and seals should be lubricated with a good grade of general purpose lubricant and installed gently rather than forced into position. Approved lubricants, sealants, thread protectors, and adhesives are as follows:
Lubricants: Dow Corning® #111, Dow Corning® #3452 Chemical Resistant Lubricant
Thread Protector: Anti-Seize
Sealant: Loctite® PST #592,
Polytetrauoroethylene (PTFE) Tape
Adhesive: Loctite® #222
Be certain that nameplates are updated to accurately indicate any eld changes in equipment, materials,
service conditions, or pressure settings.
Monthly Maintenance
1. Visually inspect the unit to ensure tight connections, tight seals, and safe operation.
2. Observe the pad and depad (tank blanketing
and vapor recovery) pressures.
3. Inspect the inlet pressure for the proper range (stamped on the valve nameplate).
Table 3. Diagnostics Table: Cv 1 through 4, Inlet Pressure Range Spring 25 to 50 psig / 1,7 to 3,4 bar
ACTUAL INLET SUPPLY
PRESSURE TO VALVE
psig bar psig bar psig bar psig bar
25 1,7 24 1,7 9 0,62 2 0,14
30 2,1 29 2,0 13 0,90 6 0,41
35 2,4 34 2,3 16 1,1 9 0,62
40 2,8 39 2,7 20 1,4 13 0,90
45 3,1 44 3,0 24 1,7 17 1,2
50 3,4 49 3,4 28 1,9 21 1,4
Table 4. Diagnostics Table: Cv 1 through 4, Inlet Pressure Range Spring 51 to 120 psig / 3,5 to 8,3 bar
ACTUAL INLET SUPPLY
PRESSURE TO VALVE
psig bar psig bar psig bar psig bar
51 3,5 50 3,4 29 2,0 5 0,35
60 4,1 59 4,1 36 2,5 12 0,83
70 4,8 69 4,8 43 3,0 19 1,3
80 5,5 79 5,4 51 3,5 27 1,9
90 6,2 89 6,1 59 4,1 34 2,3
100 6,9 99 6,8 66 4,5 42 2,9
110 7,6 109 7,5 74 5,1 50 3,4
120 8,3 119 8,2 81 5,6 57 3,9
Pressure when Pilot Starts to Open Pressure when Main Valve Starts to Open Pressure when Main Valve is Fully Open
Pressure when Pilot Starts to Open Pressure when Main Valve Starts to Open Pressure when Main Valve is Fully Open
DIAGNOSTIC PORT PRESSURE
DIAGNOSTIC PORT PRESSURE
9
Type ACE97
Table 5. Diagnostics Table: Cv 1 through 4, Inlet Pressure Range Spring 121 to 200 psig / 8,3 to 13,8 bar
ACTUAL INLET SUPPLY
PRESSURE TO VALVE
psig bar psig bar psig bar psig bar
121 8,3 120 8,3 74 5,1 30 2,1
130 9,0 129 8,9 81 5,6 37 2,5
140 9,6 139 9,6 88 6,1 45 3,1
150 10,3 149 10,3 96 6,6 53 3,6
160 11,0 159 10,9 104 7,2 60 4,1
170 11,7 169 11,7 111 7,6 68 4,7
180 12,4 179 12,3 119 8,2 75 5,2
190 13,1 189 13,0 127 8,8 83 5,7
200 13,8 199 13,7 134 9,2 91 6,3
Pressure when Pilot Starts to Open Pressure when Main Valve Starts to Open Pressure when Main Valve is Fully Open
Table 6. Diagnostics Table: Cv 7.5 through 10, Inlet Pressure Range Spring 25 to 50 psig / 1,7 to 3,4 bar
DIAGNOSTIC PORT PRESSURE
ACTUAL INLET SUPPLY
PRESSURE TO VALVE
psig bar psig bar psig bar psig bar
25 1,7 24 1,7 11 0,76 0 0,00
30 2,1 29 2,0 14 0,96 3 0,21
35 2,4 34 2,3 17 1,2 6 0,41
40 2,8 39 2,7 21 1,4 9 0,62
45 3,1 44 3,0 24 1,7 13 0,89
50 3,4 49 3,4 27 1,9 16 1,1
Pressure when Pilot Starts to Open Pressure when Main Valve Starts to Open Pressure when Main Valve is Fully Open
DIAGNOSTIC PORT PRESSURE
Table 7. Diagnostics Table: Cv 7.5 through 10, Inlet Pressure Range Spring 51 to 120 psig / 3,5 to 8,3 bar
ACTUAL INLET SUPPLY
PRESSURE TO VALVE
psig bar psig bar psig bar psig bar
51 3,5 50 3,4 24 1,7 3 0,21
60 4,1 59 4,1 30 2,1 9 0,62
70 4,8 69 4,8 36 2,5 15 1,0
80 5,5 79 5,4 42 2,9 22 1,5
90 6,2 89 6,1 49 3,4 28 1,9
100 6,9 99 6,8 55 3,8 34 2,3
110 7,6 109 7,5 61 4,2 41 2,8
120 8,3 119 8,2 68 4,7 47 3,2
Pressure when Pilot Starts to Open Pressure when Main Valve Starts to Open Pressure when Main Valve is Fully Open
DIAGNOSTIC PORT PRESSURE
Table 8. Diagnostics Table: Cv 7.5 through 10, Inlet Pressure Range Spring 121 to 200 psig / 8,3 to 13,8 bar
ACTUAL INLET SUPPLY
PRESSURE TO VALVE
psig bar psig bar psig bar psig bar
121 8,3 120 8,3 63 4,3 31 2,1
130 9,0 129 9,0 69 4,8 37 2,5
140 9,6 139 9,6 75 5,2 43 3,0
150 10,3 149 10,3 82 5,6 49 3,4
160 11,0 159 10,9 88 6,1 56 3,9
170 11,7 169 11,7 94 6,9 62 4,3
180 12,4 179 12,3 101 7,0 68 4,7
190 13,1 189 13,0 107 7,4 75 5,2
200 13,8 199 13,7 113 7,8 81 5,6
Pressure when Pilot Starts to Open Pressure when Main Valve Starts to Open Pressure when Main Valve is Fully Open
10
DIAGNOSTIC PORT PRESSURE
Loading...
+ 22 hidden pages