The Liebert AC8 is ideal for coordinated control of systems with redundant equipment, such as
multiple environmental units or pumps. When the AC8 controller detects an alarm in an operating
device, the AC8 enables a standby device and controls the device in alarm as configured, either
leaving that device operating or disabling it.
The AC8 controller can also balance usage of devices by rotating units through Operating and
Standby modes according to a user-defined schedule. This helps keep redundant equipment operating
efficiently and only when needed. The AC8 can perform routine testing of standby devices and alert
personnel if a standby device fails an operating test and requires attention.
The staging feature permits standby devices to be turned on or off when a sensor detects specified
levels. For example, the AC8 might be configured to turn on a fan when the temperature reaches
75°F, then turn on a second fan at 80°F. When the temperature falls below 80°F, the second fan is
turned off; when it drops below 75°F, the first fan is turned off.
Another capability of the AC8 is monitoring the status of connected devices and keeping personnel
apprised through local alarming. The AC8 employs local alarming and remote paging services to keep
personnel on-site and at remote locations apprised of the status of equipment.
The AC8 controller can interface with anything that closes an electrical contact. To improve process
efficiency and troubleshooting, the controller tracks data in three types of logs: alarm, event and trend.
The AC8 has a local LCD interface and a remote dial-up interface.
When an alarm condition arises, the AC8 displays alarm information, sounds an audible alarm,
changes the state of the common alarm relay and turns connected devices on or off according to user
configuration. If configured, the controller also sends pager notifications. See 1.6 - Typical Configu-ration for a more detailed example.
Introduction
1.1Methods of Viewing and Configuring the AC8
The AC8 features access through two interfaces that allow users to configure the unit, silence alarms,
back up logs, and perform many other functions to keep a large or small operation running smoothly
and safely.
• LCD—liquid crystal display on the front of the panel
• Service Terminal Interface—accessible via computer connected directly through an RS232
port or remotely through the AC8’s onboard modem
These interfaces permit easy access and configuration of the AC8, allowing users to view data, silence
alarms and have full access to information stored in the controller, including logs of alarms and events.
One more interface—Liebert’s SiteScan Web enterprise monitoring system—is primarily for monitoring, though SiteScan also provides some configuration functions.
1.2Data Logs
The three types of data logs—alarm history, event history and trend data of analog sensor readings—
can be viewed on the LCD on the front of the AC8 and downloaded through onboard communications
ports.
1.3Transformer Module
A Transformer Module converts 115VAC or 230VAC to 24VAC.
1.4Available Alarms
The alarms available with the AC8 are:
• Discrete input alarm
(for each digital input)
•High setpoint
• Low setpoint
• Loss of power
• Low battery
• Check battery
• Battery unplugged
• Internal modem fault
• No standby available
• Standby device
failed
1
• No restart available
• Emergency power
alarm
1.5Outside Enclosure Overview
BAR CODE
NO
SENS
The AC8’s controller board comes in an enclosure that is 2-3/4" deep and has a built-in liquid crystal
display (LCD) and a key lock, as shown in Figure 1. The enclosure is made of metal to accommodate
secure conduit fittings and protect components against environmental debris.
Figure 1AC8 enclosure—external features
The enclosure
has knockouts
and access slots
on top and
bottom for
cables and wires.
Introduction
LCD for configuration
and operation
Key lock
The enclosure houses the controller board and Transformer Module, as shown in Figure 2.
The enclosure must be secured to a wall, either flush-mounted or recessed in the wall, as described in
2.0 - Installation. Knockouts and access slots on the top and bottom allow easy connection of wires
and cables (see 3.0 - Wiring and Connections) with either mounting type.
Figure 2AC8 enclosure—internal features
Transformer Module
Back of LCD
On/Off switch
for Transformer
Module
Ground wire
for LCD
Power receptacle
(115VAC model only)
TB5: COMMON ALARM
(TERMINAL BLOCKS ROTATED IN VIEW)
NO C NC NO C NC
(BOTTOM)
(TOP)
LS1
TB7:
START
BAR CODE
LIEBERT
MODEM
J11: PHONE
PIN 3-TIP
ON
PIN 4-RI"N"G
+
ENABLE
P11
AUDIBLE
R402
ALARM
R26
Q11
TOP
TB3:
RELAY
OUTPUTS
(BOTTOM)
(BOTTOM)
(TOP)
8
4
7
3
6
2
5
1
(BOTTOM)
(BOTTOM)
(TOP)
8
4
7
3
6
2
5
1
TB2:
CONTACT
ASSREV
TB9: ANALOG
GROUND
ALL CIRCUITS;
CLASS 2
INPUTS
1-2 TOP
3-4 BOTTOM
(TOP)
—
——
+
+ +
485
—
+—+
(BOTTOM)
—
+
Controller Board
Knockouts and
access slots
(top and bottom)
2
1.6Typical Configuration
BAR CODE
Figure 3 shows an example of external devices connected to the AC8’s controller board. Up to eight
devices may be connected to the eight digital inputs and eight digital outputs. There may be up to four
analog sensors connected to the analog inputs, and up to two devices connected to the control relay
outputs. The EPOP connection allows for one device, possibly a UPS or generator input actuated
during a power failure.
Remote access is available via SiteScan Web and through the modem, which enables pager notifications and use of the Service Terminal Interface. A computer may be connected to the RS232 port, providing access to the features of the Service Terminal Interface.
Figure 3Typical Configuration
TB7:
START
24V INPUT
BATTERY
RS232
ON
Phone
line
P23:
BATTERY
VBATT
J11: PHONE
PIN 3-TIP
PIN 4-RING
LCD
CONTRAST
BAR CODE
LIEBERT
Introduction
Contact relay
TB5: COMMON ALARM
RELAY OUTPUTS
NO C NC
LS1
+
ENABLE
P11
AUDIBLE
Q11
TP1
GND
ON
ON
DIP
S2
1
2345678
OFF
MODEM
MODEM
OUTPUT1
DS56
OUTPUT2
DS54
OUTPUT3
DS63
OUTPUT4
DS61
OUTPUT5
DS60
OUTPUT6
DS62
OUTPUT7
DS55
OUTPUT8
DS57
CTRLLOCK
DS59
DS83
SENLOCK
DS58
CAN TX
CMN ALR
DS84
DS53
CAN RX
MOPF PROG574 TX574 RX485 RX485 TX
INPUT1
INPUT2
INPUT3
INPUT4
DS70
INPUT5
DS67
INPUT6
DS66
INPUT7
DS65
INPUT8
DS64
R334
C71
1-2 TOP
3-4 BOTTOM
485
(TOP)
—
——
+
+ +
AG
422
TB9: ANALOG
—
+—+
(BOTTOM)
GROUND
—
+
(TOP)
NO C NC
BOTTOM
TOP
PFM5 PFM2
TB1
EPOP INPUT
EPOP
P19
EPOP
DIS EN
TB1, TB2 INPUTS:
DRY CONTACTS ONLY.
TB3, TB4, TB5
OUTPUT RELAY
RATINGS: 24V, 3A
CLASS 2 ONLY.
RELAY
OUTPUTS
(TOP)
4
3
2
1
(TOP)
REV
4
3
2
1
TB2:
CONTACT
ASS
INPUTS
TB1: EPOP
CONTACT
INPUT
TB4:
(BOTTOM)
NC
NC
C
C
NO
NO
2
(BOTTOM)
8
7
6
5
(BOTTOM)
8
7
6
5
Input 1 &Output 1
output
Humidity
lockout
DEVICES CONNECTED TO
DIGITAL INPUTS & OUTPUTS
ZONE 1 DEVICES
Device 1
connected to
Device 2
connected to
Input 2 & Output 2
SiteScan Web
Analog inputs
EPOP contact
input
Generator
3
Liebert
Challenger
3000
ZONE 2 DEVICES
Device 3
connected to
Input 3 &Output 3
Liebert
Himod
Liebert
Challenger
3000
Device 4
connected to
Input 4 & Output 4
Liebert
Himod
1.7Controller Board Overview
BAR CODE
The AC8’s controller board has connectors for eight digital inputs, four analog inputs, eight digital
outputs, two control relay outputs and an EPOP contact input, as shown below. The board comes complete with light emitting diodes (LEDs) to display the status of connected devices, a battery pack for
short-term backup, communications ports, power connections and other features necessary to control
your operation.
C - EIA422 LEDsIndicates the connection status between the AC8 and SiteScan Web.1.8:LED Indicators
D - Audible hornProvides audible notification when an alarm occurs.N/A
E - Audible horn
jumper
F - Common Alarm
connectors
G - Digital output
status LEDs
H - Control relay
outputs
I - Manual Override
Switch (outputs)
Power switch for the controller board. When switched off, the battery
pack is disabled.
Provides battery backup during a power loss to maintain normal
operation of the panel for a minimum of 10 minutes. The analog inputs
will not be functional during a power loss (P/N 133455P1).
2.4:Connect Power to the AC8
2.4.2: Connecting the Battery Pack
7.9.4: Connect Battery
Jumper to disable the audible horn (factory default is enabled).N/A
The two common alarm connections are used to connect to a secondary
warning device such as a horn, light or Building Management System
(BMS). When an alarm is present, the contacts close and the external
warning device is activated/notified. The common alarm contacts may
be configured to be reset with the Silence button/command.
Each output has an LED to indicate its status: ON/OFF (energized/deenergized).
Each of the two output connections is a two-state point: ON/OFF
(energized/de-energized). Digital and analog inputs may be mapped to
either or both relays to trigger change in state.
An example of a control relay output point is a humidity lock-out.
Placing the switch in the ON position will turn ON, or energize, all eight
outputs simultaneously. This switch removes all automatic output control
from the AC8.
3.0:Wiring and Connections
3.4:Connecting Common Alarm
7.4:Setup System - Setup Common
1.8:LED Indicators
3.0:Wiring and Connections
3.2.4: Connecting Control Relay
5.9:View Control Status
7.11: Setup System - Setup I/O Matrix
7.12: Override Output
The factory default is OFF (outputs controlled by programming).
4
Outputs
Alarm
Outputs
Table 1Controller board components (continued)
ItemDescriptionFor more information, see:
J - Digital output
connectors
K - Status LEDsIndicates the operational status of the controller board.1.8:LED Indicators
L - Digital output
loss-of-power
jumper
M - Digital input
connectors
N - Digital input
status LEDs
O - EPOP contact
input
P - EPOP jumper
Q - Analog ground
connector
R - Analog input
connectors
S - 12VDC/24VDC
analog input jumper
T - SiteScan Web
connector (EIA422)
U - EIA485 connectorNot presently usedN/A
V - Serial interface
connector (RS232/
EIA574)
W - Phone line
connector
X - Power receptacle
(Transformer Module)
Y - Power On/Off
switch (Transformer
Module)
Z - 24VAC connector
(Transformer Module)
AA - ModemOn-board modem with 9600 baud rate.
BB - Modem status
LEDs
CC - DIP switch 1DIP switch used for resetting password to default.7.9.1: Change Password
DD - LCD connectorConnection for the LCD on the enclosure door.N/A
EE - LCD contrast
adjustment
FF - Battery pack
connector
GG - 24VAC power
connector
HH - Transformer
Module
Each of the eight output connections is a two-state point: ON/OFF
(energized/de-energized).
An example of a field digital output point is an air unit On/Off control
circuit.
One of eight output jumpers. Each digital output has a jumper to set the
fail-safe position of the output point when power fails. The OFF position
makes the contact Normally Open (factory default). The ON position
makes the contact Normally Closed.
Note: The jumper position has no effect on the contact when the AC8
has power.
Each of the eight input connections is a two-state point: ON/OFF
(energized/de-energized).
An example of a field digital input point is a common alarm contact on an
air unit.
Each input has an LED to indicate its status: ON/OFF (energized/deenergized).
The emergency power operation (EPOP) input connection is a two-state
point: ON/OFF (energized/de-energized).
An example of an EPOP input point is a UPS or a generator.
Jumper to enable or disable emergency power operation (EPOP). Factory
default is disabled.
Connection for an externally powered analog sensor that needs a
reference to ground.
Each of the four input connections accepts a 4/20 mA signal.
An example of a field analog input point is a temperature sensor.
Jumper to select voltage supplied for two-wire analog sensors. The
jumper supplies all four analog input connectors with the same voltage.
Factory default is 24VDC.
Connection to monitor AC8 from Liebert’s SiteScan Web graphical
monitoring package.
Connection for laptop or video terminal. Used for configuration and
monitoring using the Service Terminal Interface. Requires a null modem
cable for connectivity
(P/N 201258P1).
Connection for phone line. Used for pager notifications, service phone
number, and configuration and monitoring using the Service Terminal
Interface. Requires an RJ11 connector.
115VAC power receptacle to power laptop during configuration and
diagnostics. Receptacle not available on 230VAC Transformer Module.
Power switch to turn power On/Off to both Transformer Module 24VAC
connectors and power receptacle.
One of the two 24VAC connectors for power (the second is also on the
right side of the Transformer Module near the top). Each connector is
rated for 40VA.
Indicates the operational status of the modem.1.8:LED Indicators
Adjustment contrast for the LCD on the enclosure door.N/A
Connection for battery pack lead.2.4.2: Connecting the Battery Pack
Power connection for the controller. Requires 24VAC.2.4:Connect Power to the AC8
Transformer Module used to convert 115VAC or 230VAC to 24VAC.2.4.1: Termination and Mounting
3.0:Wiring and Connections
3.2.2: Connecting Digital Outputs
5.6:View Output Status
7.7:Setup System - Setup Outputs
3.2.3: Setting the Digital Output
Jumpers
7.7.5: Configure Output for Loss of
Power (“Fail-Safe”)
3.0:Wiring and Connections
3.2.1: Connecting Digital Inputs
5.5:View Input Status
7.3:Setup System - Setup Inputs
1.8:LED Indicators
3.0:Wiring and Connections
3.2.5: Connecting the Emergency
Power Operation (EPOP) Input
3.2.6: Setting the EPOP Jumper
3.3.2: Connecting the Analog Ground
3.0:Wiring and Connections
3.3:Connecting Analog Inputs
5.5:View Input Status
7.5:Setup System - Setup Sensor
3.3.1: Setting the 12VDC/24VDC
Analog Power Jumper
3.0:Wiring and Connections
3.5:EIA422 SiteScan Web
Connector
3.6.1: RS232 Connector
A.2:Connecting to the Service
Terminal Interface
3.6.2: Phone Line Connector
7.8:Setup System - Setup Modem &
Pagers
7.9.6: Setup Serv Ph Num - Enter
Phone Number
A.2:Connecting to the Service
Terminal Interface
2.4.1: Termination and Mounting
3.0:Wiring and Connections
2.4.1: Termination and Mounting
3.0:Wiring and Connections
2.4.1: Termination and Mounting
3.0:Wiring and Connections
7.8:Setup System - Setup Modem &
Pagers
Introduction
5
1.8LED Indicators
BAR CODE
The AC8’s controller board has LED indicators that show the status of inputs, outputs and the common alarm, as well as the modem, SiteScan Web and EPOP connections.
Introduction
EIA422
EIA422
SS Web
EPOP
SiteScan Web
& EPOP
LEDs
DS50
DS49
DS68
Modem LEDs
MODEM
DS77TX
DS76RX
DS74DTR
DS75DCD
TB7:
START
24V INPUT
P23:
BATTERY
ON
BATTERY
LCD
CONTRAST
VBATT
J11: PHONE
PIN 3-TIP
PIN 4-RING
BAR CODE
LIEBERT
TP1
GND
ON
ON
DIP
S2
1
2345678
OFF
DS83
CAN TX
DS84
CAN RX
MODEM
MODEM
485
(TOP)
—
+
422
(BOTTOM)
—
+
TB5: COMMON ALARM
RELAY OUTPUTS
(TOP)
NO C NC
NO C NC
LS1
+
ENABLE
P11
AUDIBLE
Q11
OUTPUT1
DS56
OUTPUT2
DS54
OUTPUT3
DS63
OUTPUT4
DS61
OUTPUT5
DS60
OUTPUT6
DS62
OUTPUT7
DS55
OUTPUT8
DS57
CTRLLOCK
DS59
SENLOCK
DS58
CMN ALR
DS53
MOPF PROG574 TX574 RX485 RX485 TX
INPUT1
INPUT2
INPUT3
INPUT4
DS70
INPUT5
DS67
INPUT6
DS66
INPUT7
DS65
INPUT8
DS64
R334
C71
1-2 TOP
3-4 BOTTOM
——
+ +
AG
TB9: ANALOG
—
+—+
GROUND
BOTTOM
TOP
PFM5 PFM2
TB1
EPOP INPUT
EPOP
P19
EPOP
DIS EN
TB1, TB2 INPUTS:
DRY CONTACTS ONLY.
TB3, TB4, TB5
OUTPUT RELAY
RATINGS: 24V, 3A
CLASS 2 ONLY.
RELAY
OUTPUTS
(TOP)
4
3
2
1
(TOP)
REV
4
3
2
1
TB2:
CONTACT
ASS
INPUTS
TB1: EPOP
CONTACT
INPUT
TB4:
(BOTTOM)
NC
NC
C
C
NO
NO
2
(BOTTOM)
8
7
6
5
(BOTTOM)
8
7
6
5
Table 2LED indicators summary
LED TypeLEDColorDescription
EIA422
LEDs
EPOP LED
Modem
LEDs
Output
LEDs
Status
LEDs
Input
LEDs
422 TXGreenAC8 is transmitting information over the EIA422 port
422 RXGreenAC8 is receiving information over the EIA422 port
EPOP INRedIndicates Emergency Power Operation is open or in alarm
TXGreenAC8 is transmitting information via the modem
RXGreenAC8 is receiving information via the modem
DTRGreenIndicates data terminal is ready (DTR)—lights up when modem is dialing
DCDGreenIndicates data carrier is detected (DCD)—lights up when modem has connection
OUTPUT1GreenIndicates output is ON or energized
OUTPUT2GreenIndicates output is ON or energized
OUTPUT3GreenIndicates output is ON or energized
OUTPUT4GreenIndicates output is ON or energized
OUTPUT5GreenIndicates output is ON or energized
OUTPUT6GreenIndicates output is ON or energized
OUTPUT7GreenIndicates output is ON or energized
OUTPUT8GreenIndicates output is ON or energized
CTRLLOCKGreenIndicates Control Relay 2 is ON or energized
SENLOCKGreenIndicates Control Relay 1 is ON or energized
CMN ALRGreenIndicates Common Alarm Relay is ON or energized
MOPGreen
Indicates the microprocessor is operating properly (MOP)—must be on before AC8
will function
FPROGGreenIndicates firmware is being upgraded—lights up during upgrade process
574 TX or 232 TXGreenAC8 is transmitting information via the RS232 port
574 RX or 232 RXGreenAC8 is receiving information via the RS232 port
Figure 4 shows a typical sequence of how the AC8 functions after detecting a change in a monitored
device. Many responses depend on configuration settings. This example shows what happens when a
digital input changes state—assuming the input is defined as alarmable—and when the condition
returns to normal.
Figure 4Example of typical sequence
RESPONSES TO AN ALARMRETURN-TO-NORMAL SEQUENCE
Introduction
ALARM CONDITION DETECTED
A device connected to the AC8
changes state.
RETURN TO NORMAL
The device that triggered the alarm
returns to its normal state.
The alarm is cleared
The horn sounds (audible horn on
the controller board—silence horn by
pressing any key on the LCD keypad)
(automatically if Unlatched; must be
cleared manually if Latched)
The horn stops sounding
(if user hasn’t silenced it)
UNIVERSAL MONITOR
05-SEP-02 14:04:13
V5.100.0
PRESS =STATUS/SETUP
ESC
The LCD flashes
(except during setup)
UNIVERSAL MONITOR
05-SEP-02 14:04:13
V5.100.0
PRESS =STATUS/SETUP
ESC
Pager numbers are dialed
(up to four configured pagers)
Service number is dialed
The LCD stops flashing
Pager numbers & service
number are dialed
Return-to-normal message sent
(if configured)
User setup determines output
control (for example, the device
in alarm might be disabled and a
standby device set to operate)
DEVICE_1 ALARM
CONTACT CLOSED
30-SEP-04 16:23:04
DEVICE_1 ALARM
CONTACT CLOSED
DEVICE_4 STARTED
30-SEP-04 16:23:10
Entry in Alarm Log
Condition (
& state (
ALARM)
CONTACT CLOSED)
Entry in Active Alarm Log
Condition (
& state (
ALARM)
CONTACT CLOSED)
Entry in Event Log
Status change
(DEVICE_4 STARTED)
ALARMS CLEARED
30-SEP-04 16:24:04
DEVICE_1 STARTED
DEVICE_2 STARTED
DEVICE_3 STARTED
DEVICE_4 OFF
30-SEP-04 16:24:06
Entry in Alarm Log
ALARMS CLEARED)
(
Entry in Event Log
Actions in response to event
(DEVICE_1 STARTED,
DEVICE_4 OFF
)
7
2.0INSTALLATION
This section provides instructions for installing, mounting and connecting power to the AC8.
2.1Installation Considerations
The AC8 must be installed indoors and may be mounted on the surface of a wall or flush-mounted,
depending on the user’s application, the location of equipment and sensors to be monitored and the
type of wall the unit will be mounted on.
The AC8 should be mounted where it can be easily accessed. On-site personnel would access the unit
through the LCD on its front cover, service terminal connected to the RS232 port or through SiteScan.
For off-site monitoring, the AC8 should be placed near communications means such as a telephone
line connection that would permit remote access.
In addition to the communications connections, the site also must have electrical service and must
permit connecting the unit’s eight digital inputs, eight digital outputs and four analog inputs.
The wall material must be capable of supporting the weight of the AC8: see 8.0 - Specifications.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
Installation
2.1.1 Unpacking and Preliminary Inspection
• Before unpacking the AC8, inspect the shipping carton for damage or signs of mishandling, such
as gashes or holes in the carton or severely flattened corners.
• Open the shipping crates carefully. Use care to avoid puncturing the container with sharp objects
that might damage the contents.
• Inspect the AC8 and all included components for damage.
• If any damage from shipping or mishandling is observed, immediately file a damage claim with
the shipping agency and forward a copy to:
• Backup Battery - installed in unit (not connected or charged)
• RS232 Configuration Cable
8
2.2Surface-Mounting the AC8
NOTE
Removing the conduit knockouts before mounting the AC8 on the wall will ease installation
and prevent strain on the mounting hardware and wall. It is imperative to remove the
knockouts if the unit is to be flush-mounted.
After determining where to place the unit, check to ensure that you have all the hardware required to
install the panel on the surface of a wall. Obtain the needed tools and material.
Required tools
• Electric drill (if surface is too hard to drive screws without pilot holes)
• Screwdriver
• Marker to denote layout of holes
• Four screws, each #10
2.2.1Mounting the Panel
CAUTION
!
Check building plans and other relevant documents to determine whether mounting the AC8
at the selected location might cause cutting or otherwise damaging electrical or
communication wiring or pipes.
1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5).
2. Drill holes, if required, to install the four #10 screws that will secure the AC8 to the wall. Clean
up the debris.
3. If the wall material is not strong enough to hold the screws securely, use wall anchors.
4. Install the top two screws—the screw heads must be small enough to slip through the larger,
bottom portion of the pear-shaped mounting slot in the AC8 (see inset in Figure 5). The screws
must also be large enough to extend over the edges of the top of the mounting slot.
5. Hang the AC8 on the screws, letting the panel slip down until the screws are in the smaller, upper
portion of the slot.
6. Tighten the screws until they are snug.
7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.
Installation
Figure 5Mounting dimensions
Mounting Slot
ENCLOSURE
12"
(304.8mm)
0.213"
(5.4mm)
16"
(406.4mm)
AC8
back plate
0.375"
(9.6mm)
0.213" (5.4mm)
Bottom hole diameter
9
2.3Flush-Mounting the AC8
NOTE
Removing the conduit knockouts before mounting the AC8 on the wall will ease installation
and prevent strain on the mounting hardware and wall. It is imperative to remove the
knockouts if the unit is to be flush-mounted.
The rectangular access doors on the top and bottom of the AC8 must be reversed so they slide
the opposite direction. Leaving the doors as shipped from the factory prevents them from being
opened when the panel is flush mounted in a wall.
The AC8 may be flush-mounted according to company practices—either with screws through the sides
of the panel into wall supports or with hanging hardware that attaches to the back of the panel. After
determining how and where to place the unit, check to ensure that you have all the hardware
required to install the panel in the wall. Obtain the needed tools.
Required tools
•Saw
• Electric drill
• Screwdriver
• Marker to denote layout of the hole to accommodate the AC8
• Mounting hardware
2.3.1Mounting the Panel
Installation
CAUTION
!
Check building plans and other relevant documents to determine whether mounting the AC8
at the selected location might cause cutting or otherwise damaging electrical or
communication wiring or pipes.
1. Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template.
2. Drill a pilot hole for the saw blade, if required.
3. Use the saw to cut out the marked section of the wall (if not new construction).
4. Rest the AC8 in the wall and mark where mounting screws will be inserted into the wall studs or
other support member.
5. Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the
debris.
6. Reverse the slide direction of the rectangular access doors on the top and bottom of the AC8.
Leaving the doors as shipped from the factory prevents them from being opened when the panel is
flush mounted in a wall.
7. Attach any field-supplied mounting hardware.
8. Reinsert the assembly into the wall.
9. Insert and tighten the screws or wall anchors.
10
2.4Connect Power to the AC8
The AC8 must be supplied with 115VAC or 230VAC; the power supplied must match the rating of the
unit’s Transformer Module. For information, consult your local dealer, Liebert representative or the
Liebert Worldwide Support Group.
The AC8 must be installed on a branch circuit protected by a certified 15A overcurrent device.
WARNING
!
Check that power is removed from wires prior to installation.
CAUTION
!
The AC8 is designed for use on properly grounded (earthed) 115VAC or 230VAC power, 60Hz
or 50Hz. The ground wire for the power lead must be wired to the earth ground terminal (stud
located next to the 24VAC terminal block).
This equipment is intended to be installed by a qualified and certified electrician who must
review and approve customer supplied wiring and circuit breakers, verify correct input and
grounded (earthed) connections to ensure compliance with technical standards and national
and local electrical codes.
WARNING
!
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.
The switch is in the top left corner of the unit, just below the battery pack.
2.4.1Termination and Mounting
Installation
WARNING
!
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.
The switch is at the bottom of the unit.
Input Power Connections
To connect electrical power to the Transformer Module:
1. Install electrical wiring from utility power to the Transformer Module.
2. Use copper wires only; proper wiring to use for power is 14/2 AWG copper wire with ground.
3. For the TM230 only: strip wires 3/8" (9.6mm).
Note: For the TM115, wires are pre-stripped 0.4" (10.2mm) at the factory.
4. Connect the wiring as follows:
TM115TM230Connection Type
White wireNeutral (L2)Neutral
Black wireLine (L1)Power (Line)
Green wireGround leadGround
5. Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in
Figure 6 or to the TM230 connectors as shown in Figure 7.
11
Installation
24 VAC Output Power Connections
To connect to the 24VAC outputs:
1. Install electrical wiring from device requiring 24VAC power to the Transformer Module.
2. Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip
wire 1/4".
3. There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as
shown in Figures 6 and 7. TB1 and TB2 are NOT polarity sensitive.
4. Secure the wires to the connector.
Figure 6Power wiring to TM115Figure 7Power wiring to TM230
TM115
Wire nuts
connecting
electrical
wiring
Troubleshooting - Transformer Module
A common problem and possible solution are shown in the table below. For further information or if
you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
ProblemPossible SolutionReplacement Fuse Part Numbers
24VAC power
not available
from TB1 or TB2
Check fuse for respective
output (TB1 or TB2).
2.4.2Connecting the Battery Pack
Before connecting input power to the AC8, connect
the panel’s backup battery (factory-supplied) to the
jumpers so it will begin charging when electrical
power to the AC8 is switched on.
Knockout for
external wiring
Ground
24VAC output
(TB1)
• LITTLEFUSE 218002
or
• BUSSMANN GDC-2A
TM230
Neutral
(L2)
Knockout for
external wiring
Ground
Line (L1)
24VAC output
(TB1)
Battery pack
NOTE
If the battery is not hooked up BEFORE the
AC8 is switched on, it will trigger an alarm.
To connect the battery pack, insert the battery
leads into the jumpers as shown at right.
(To disconnect the battery pack, remove the
battery leads from the jumpers.)
Obtaining a Replacement Battery Pack
To obtain a replacement battery pack, contact your
local dealer or Liebert representative. The Liebert
part number is 133455P1.
WARNING
!
To prevent the risk of fire or explosion, replace only with 7.2 V rechargeable NiCad battery pack.
CAUTION
!
Dispose of the battery properly by sending it back to Liebert Corporation or an approved
battery recycling facility.
2.4.3Turning On the AC8
After connecting the backup battery, turn on the power On/Off switches to the AC8 and the Transformer Module (see 1.7 - Controller Board Overview for location of switches).
Battery pack connector
12
Wiring and Connections
3.0WIRINGAND CONNECTIONS
CAUTION
!
Switch OFF electric power to the AC8 before installing any wiring to the unit or changing
input or output connections. The Power On/Off switch is in the top left corner of the unit, just
below the battery pack.
3.1Wiring Specifications
Input and output connections to the AC8 may be made in any order—it is not necessary, for example,
to make all input connections before making any output connections. Use copper conductors only for
all wiring.
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
18 AWG*
(recommended)
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
18 AWG*
(recommended)
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
750 ft. (225m)
20 AWG22 AWG
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
750 ft. (225m)
750 ft. (225m)
20 AWG22 AWG
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
1000 ft. (300m)N/A
3000 ft. (900m)N/A
N/AN/A
150 ft. (45m)
150 ft. (45m)
150 ft. (45m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
Dry Contact
24VAC@3A
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
(24VDC,
10 mA)
24VAC
@3A
24VAC
@1.3A
115VAC
@4A
230VAC
@0.5A
13
3.2Connecting Digital Inputs and Digital Outputs
The digital inputs, digital outputs and control relay outputs are found on the right side of the AC8’s
printed wiring assembly board. Each set has two terminal blocks—one green, the other black:
• Digital inputs: two terminal blocks, with four inputs per block (8 inputs total)
• Digital outputs: two terminal blocks, with four outputs per block (8 outputs total)
• Control relay outputs: two terminal blocks, with one output per block (2 outputs total)
Each input is tied to an output with the same number:
• Input 1 is tied to Output 1 (default name: Device_1)
• Input 2 is tied to Output 2 (default name: Device_2)
• Input 3 is tied to Output 3 (default name: Device_3)
.
.
.
• Input 8 is tied to Output 8 (default name: Device_8)
Up to eight devices may be connected to the AC8. Each device must be connected to an input and an
output with the same number.
To determine the proper wire size, see Table 4 - Wiring specifications.
NOTE
Each terminal block is a removable, two-part assembly to permit easier connection of more
than one input at a time. If making multiple connections, grasp the upper portion of a block
and pull firmly to the right until the assembly pulls apart.
After making the connections, push the removed piece back into the portion attached to the
printed wiring assembly until the terminal block pieces lock together.
Wiring and Connections
Connecting Liebert Environmental Units
For Liebert environmental units, follow these steps (be sure to connect the same device to inputs and
outputs with the same number—one device to Input 1 and Output 1, another to Input 2 and Output 2,
and so on):
• Connect a digital input from the AC8 to the Common Alarm Relay of the environmental unit:
terminals 75/76 or TB1-6, TB1-7.
• Connect a digital output (numbered the same as the input) from the AC8 to the Remote Shutdown
(Power Control) of the environmental unit: terminal 37/38 or TB1-4, TB1-5.
3.2.1Connecting Digital Inputs
To connect a digital input:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout
to permit wire entry into the AC8
enclosure.
3. Bring the wire(s) into the AC8 enclosure
through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the
stripped end of the wire into the terminal
block.
5. Tighten the screw until it holds the wire
snugly.
NOTE
Connect digital inputs to
nonpowered (dry) contacts only.
PFM2
PFM5
TB1
EPOP INPUT
EPOP
RELAY
OUTPUTS
(TOP)
4
3
2
1
(TOP)
REV
4
3
2
1
TB2:
CONTACT
ASS
INPUTS
(BOTTOM)
8
7
6
5
(BOTTOM)
8
7
6
5
NUMBERING KEYS Note numbering begins
with 1 at the bottom and
proceeds up to 4 (green);
and 5 up to 8 (black)
DIGITAL INPUT
TERMINAL BLOCKS
14
Wiring and Connections
F
M
3.2.2Connecting Digital Outputs
To connect a digital output:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to
permit wire entry into the AC8 enclosure.
3. Bring the wire(s) into the AC8 enclosure
through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the
stripped end of the wire into the terminal
block.
5. Tighten the screw until it holds the wire
snugly.
CAUTION
!
To reduce the risk of fire or electric
shock, do not interconnect the outputs
of different Class 2 circuits.
3.2.3Setting the Digital Output Jumpers
Each digital output has an associated jumper to define its operation when power is interrupted and
there is no battery backup to the board. This puts the AC8 in a fail-safe mode and ensures proper
functioning when the board has no power or battery backup.
P
RELAY
OUTPUTS
(BOTTOM)
(TOP)
8
4
7
3
6
2
REV
1
(TOP)
4
3
2
1
5
(BOTTOM)
8
7
6
5
PFM2
PFM5
DIGITAL OUTPUT
TERMINAL BLOCKS
NUMBERING KEYS Note numbering begins
with 1 at the bottom and
proceeds up to 4 (green);
and 5 up to 8 (black)
The AC8 comes from the factory with all digital output jumpers in the OFF position (Normally Open).
The jumper setting for each digital output can be changed to ON (Normally Closed). The settings are
shown in Table 5.
Table 5Digital output jumper settings
Setting
(power loss & no battery backup)
OFFNormally Open
ONNormally Closed
Output status
To change the output jumper setting:
1. Find the respective black output jumper on
the circuit board, shown in the illustration,
using the following guide.
JumperAssociated output
PFM1Output 1
PFM2Output 2
PFM3Output 3
PFM4Output 4
PFM5Output 5
PFM6Output 6
PFM7Output 7
PFM8Output 8
2. Decide whether your configuration requires
Digital output jumpers
Digital output jumpers
TB4:
(BOTTO
NC
NC
C
C
PFM8
FF
PFM3
NO
NO
2
RELAY
OUTPUTS
(BOTTOM)
(TOP)
8
4
7
3
6
2
REV
1
(TOP)
4
3
2
5
(BOTTOM)
8
7
6
PFM2
PFM5
the jumper to be OFF or ON.
3. Set the jumper as needed:
• Set the jumper to OFF by placing the black jumper on the middle and top pins.
• Set the jumper to ON by placing the black jumper on the middle and bottom pins.
15
3.2.4Connecting Control Relay Outputs
5
F
To connect a control relay output:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to
permit wire entry into the AC8 enclosure.
3. Bring the wire(s) into the AC8 enclosure
through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the
PFM8
FF
PFM3
stripped end of the wire into the terminal
block.
5. Tighten the screw until it holds the wire
snugly.
CAUTION
!
To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2
RELAY
OUTPUTS
(TOP)
circuits.
3.2.5Connecting the Emergency Power Operation (EPOP) Input
The emergency power operation, or EPOP, input connector block (TB1) is at the bottom right corner of
the AC8 printed circuit board, just below the digital inputs.
To determine the proper wire size, see Table 4 - Wiring specifications.
To connect to the EPOP input:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to permit
wire entry into the AC8 enclosure.
3. Bring the wire into the AC8 enclosure through a
conduit knockout or access slot.
4. Loosen each screw and slip the stripped end of the
wire into the terminal block.
5. Tighten each screw until it holds the wire snugly.
3.2.6Setting the EPOP Jumper
The EPOP contact input has an associated jumper to
enable or disable emergency power operation (EPOP).
The AC8 comes from the factory with the EPOP jumper in
the Disabled position (DIS); it may be changed to Enabled
(EN).
To change the EPOP jumper setting:
1. Find the black EPOP jumper on the circuit board, as
shown at right. The jumper is at the bottom right
corner of the board just below the EPOP contact input
(see 1.7 - Controller Board Overview).
2. Decide whether your configuration requires the jumper to be enabled or disabled.
3. Set the jumper as needed:
• To enable EPOP, place the black jumper on the middle and right pins. The right side of the
EPOP
jumper
jumper is labeled EN for Enabled.
TB4:
NC
C
NO
(BOTTOM)
(BOTTOM)
NC
C
NO
2
Wiring and Connections
RELAY OUTPUT
TERMINAL BLOCKS
NUMBERING KEYS Relay 1 at left (green);
Relay 2 at right (black)
P
PFM5
REV
1
(TOP)
4
3
2
1
TB2:
CONTACT
ASS
INPUTS
TB1
EPOP INPUT
EPOP
P19
EPOP
DIS EN
TB1, TB2 INPUTS:
DRY CONTACTS ONLY.
TB1: EPOP
CONTACT
INPUT
EPOP
input
(BOTTOM)
8
7
6
5
NOTE
When the EPOP jumper is set to Enabled, a Normally Closed contact must be attached or an
alarm will be generated and the outputs will default to the EPOP operation setting.
• To disable EPOP, place the black jumper on the middle and left pins. The left side of the
jumper is labeled DIS for Disabled.
16
3.3Connecting Analog Inputs
The analog input connector blocks are at the bottom center of the AC8 printed circuit board, as shown
below right. The blocks are two-part assemblies to permit easier connections. To determine the proper
wire size, see Table 4 - Wiring specifications.
To connect an input:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to permit wire entry into the AC8 enclosure.
3. Bring the wire(s) into the AC8 enclosure through a
conduit knockout or access slot.
4. Loosen the appropriate screw and slip the stripped
end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.
3.3.1Setting the 12VDC/24VDC Analog Power Jumper
The analog power jumper sets the common voltage
that is applied to all of the analog input connections.
The jumper permits the user to modify the voltage
supplied to the sensors, according to the power
requirements.
The factory default position is 24VDC; it may be
changed to 12VDC.
To change the analog power jumper setting:
1. Find the black analog jumper on the circuit board,
as shown at right. The jumper is at the bottom of
the board near the middle (see 1.7 - Controller Board Overview).
2. Decide whether your configuration requires the jumper to be 24VDC or 12VDC.
3. Set the jumper as needed:
• To set the jumper to the 24VDC position, place the black jumper on the middle and right pins.
• To set the jumper to the 12VDC position, place the black jumper on the middle and left pins.
Analog
power
jumper
485
—
+
422
M)
+
—
Analog
inputs
——
++
+—+
Wiring and Connections
Analog
ground
1-2 TOP
3-4 BOTTOM
AG
—
TB9: ANALOG
GROUND
3.3.2Connecting the Analog Ground
The AC8 features an analog ground connection
for four-wire sensors that have an external
power source. Such a four-wire sensor requires
a reference to ground because they get power
from an external power source.
A two-wire transducer, which does not have an
external power source, does not need to be
connected to the analog ground.
The analog ground connector has two
terminals, each of which can accommodate two
wires. This is adequate to connect four sensors
that require a reference to ground because they
get power from an external power source.
Connect the analog ground to an external
four-wire sensor, as shown in the illustration at
right.
TB10: COMMS
Four-wire
transducer
Sensor
with
external
power
(TOP)
(BOTTOM)
+
+
+
4/20mA
Output
Analog
input
—
24V Input
1-2 TOP
3-4 BOTTOM
+
—
Analog
ground
TB9: ANALOG
GROUND
24V from
external
power
source
17
3.4Connecting Common Alarm Outputs
T
P
)
(
T
E
4
N
11
M
S
8
+
TB10: COMMS
4
The common alarm relay, found in the top right corner of the
AC8, permits the user to connect auxiliary notification
equipment, such as lights, horns and sirens, to the AC8. To
determine the proper wire size, see Table 4 - Wiring specifications.
There are two connectors for the common alarm output. However,
the connectors are not individual relay outputs. The connectors
should be treated as a double-pole, double-throw (DPDT) relay.
The common alarm relay is energized whenever an alarm occurs.
To connect an output:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to permit wire entry
into the AC8 enclosure.
3. Bring the wire(s) into the AC8 enclosure through a conduit
knockout or access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.
3.5EIA422 SiteScan Web Connector
The AC8 will interface with Liebert’s SiteScan Web enterprise monitoring
system. SiteScan can be used to monitor analog and digital equipment from
a host computer and also to perform some configuration.
To connect the SiteScan host computer to the AC8:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to permit wire entry into the
AC8 enclosure.
3. Bring the wire(s) into the AC8 enclosure through a conduit knockout or
access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into
the terminal block.
5. Tighten the screw until it holds the wire snugly.
3.6Communications Connections
The AC8’s Service Terminal Interface offers full configuration
and monitoring capability via the RS232 port and the phone
line connector (see A.2 - Connecting to the Service Terminal Interface). The phone line connector is also used
for pager notifications and service phone number options.
Wiring and Connections
TB5: COMMON ALARM
RELAY OUTPUTS
ON ALAR
NO C NC
BOTTOM
TOP
NO C NC
ENABLE
P
AUDIBLE
Q11
Common alarm outputs
TB10: COMM
EIA422 SiteScan Web
connector
Serial interface connector
(RS232/EIA574)
(TOP)
(TOP)
(BOTTOM)
TB3, TB4,
OUTPUT R
RATINGS: 2
CLASS 2 O
—
+
422
—
+
TB4:
NC
C
NO
N
T
P
3.6.1RS232 Connector
The RS232 port requires a null modem cable.
• Connect one end of the cable to the AC8’s RS232 port, as
shown at right.
• Connect the other end to the COM1 port of a laptop
computer or video terminal.
3.6.2Phone Line Connector
The Phone Line Connector requires an RJ11 connector.
• Connect one end of the connector to the AC8’s phone line
connector, shown at right.
• Connect the other end to a telephone wall jack.
18
RJ11: PHONE
PIN 3-TIP
PIN 4-RING
MODEM
Phone line connector
(TOP)
(BOTTOM)
4
+
Overview of Menus
4.0OVERVIEWOF MENUS
There are two ways to access the AC8: the LCD on the front of the enclosure and the Service Terminal
Interface, which is accessible through any computer using a communications program. Many viewing
and configuration tasks can be performed through either interface, but some are available only
through the Service Terminal Interface.
• Step-by-step instructions for all functions appear in Sections 5.0 through 7.0. These instructions
use examples of LCD screens to illustrate most functions, except those not available via the LCD.
• Examples of all Service Terminal Interface screens appear in Appendix A - Service Terminal
Interface, along with instructions on how to connect to the Service Terminal Interface.
Table 6 lists all AC8 functions and shows whether they can be performed through the LCD interface
Clear Active Alarms✔✔ page 76page 114
Clear the Alarm Log ✔✔ page 76page 114
Clear the Event Log ✔✔ page 77page 115
Clear the Trend Logs✔✔ page 77page 115
Enter AC8 Phone Number—✔page 51page 101
Enable Modem Diagnostic Messages—✔page 51page 101
Change Modem Dial Prefix—✔page 51page 101
Change Modem Hang Up Delay After a Call—✔page 51page 101
Pager Number & PIN✔✔ page 53page 100
Communications Check—✔page 55page 100
LCD
Service
Terminal
Instructions on
using function
Service Terminal
screen examples
19
4.1Opening Screen Overview
The AC8 displays the Opening Screen at startup, as shown in Figure 8.
• If any alarms are active, the Current Alarm screen appears. (Pressing any key on the LCD keypad
will silence the audible alarm.)
• If any analog input sensors are connected, the LCD screen will alternately display the Opening
Screen and a screen showing the analog value of each sensor.
If no alarms are present, the Main Menu appears.
4.2Main Menu Overview
The Main Menu offers access to all functions within the panel. As shown in Table 7, the functions are
organized into three sections with step-by-step instructions.
Table 7Primary functions overview
SectionDescription
These features are available to all users. This permits all personnel to check the
5.0 - View Status Options
(both LCD and Service
Terminal Interface)
6.0 - Silence Alarm & Backup
Log Files (Service
Terminal Interface only)
7.0 - System and Control
Options (some functions
available via Service
Terminal Interface only)
status of any monitored equipment or location. From this menu, any user may:
• View current monitoring data—active alarms and the status of inputs and outputs
• View data stored in alarm, event and trend logs
• View pager numbers
• View auto sequencing and standby testing status
These features—available via the Service Terminal Interface only—allow users to:
• Silence the audible alarm
• Back up the alarm, event and trend logs
These options require a password. Authorized users may:
• Configure the AC8
• Override automatic control of outputs to force an output ON or OFF
• Clear active alarms and delete all records in the alarm, event and trend logs
Overview of Menus
4.3LCD Menu Overview
Figure 8 shows an overview of the initial screens available through the LCD interface. For comparable information about the Service Terminal Interface screens, see A.3 - Overview of Menus.
Figure 8LCD Menu overview
“View Status” selected
> VIEW STATUS
SYSTEM AND CONTROL
↑↓=NEXT
View Status Menu
(All users - no password)
VIEW ACTIVE ALARMS
VIEW ALARM LOG
VIEW EVENT LOG
VIEW TREND LOG
VIEW INPUT STATUS
VIEW OUTPUT STATUS
VIEW PAGER NUMBERS
VIEW OPERATION
VIEW CONTROL STATUS
↵=SELECT
Opening Screen
LIEBERT AC8
DD-MON-YY HR:MM:SS
PRESS
VX.XXX.X
↵=STATUS/SETUP
Main Menu
VIEW STATUS
SYSTEM AND CONTROL
↑↓=NEXT
See Section
5.0
See Section
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
↵=SELECT
(If any alarms detected)
Current Alarm screen
(see 5.1 - View Active Alarms)
“System & Control” selected
VIEW STATUS
> SYSTEM AND CONTROL
↑↓=NEXT
↵=SELECT
System & Control Menu
(Password required)
SETUP SYSTEM
OVERRIDE OUTPUT
CLEAR ALARMS & LOGS
See Section
7.0
See Section
7.2
7.12
7.13
20
5.0VIEW STATUS OPTIONS
NOTE
For ease of understanding, this section uses the LCD interface to illustrate most instructions,
except for features that are available only through the Service Terminal Interface. All Service
Terminal Interface screens appear in Appendix A - Service Terminal Interface.
The View Status menu allows any user to view currently active alarms, monitoring data stored in the
alarm, event and trend logs, the status of all inputs and outputs, and the four pager numbers. The
arrows
This section presents step-by-step instructions for each of the following options:
Figure 9 shows the main options available from the View Status menu.
Figure 9Menu overview - View Status menu
↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item.
• View Active Alarms• View Trend Log• View Pager Numbers
• View Event Log• View Output Status• View Control Status
Opening Screen
DD-MON-YY HR:MM:SS
PRESS ↵=STATUS/SETUP
View Status Options
LIEBERT AC8
VX.XXX.X
Main Menu
> VIEW STATUS
SYSTEM AND CONTROL
↑↓=NEXT↵=SELECT
View Status
VIEW ACTIVE ALARMS
VIEW ALARM LOG
VIEW EVENT LOG
VIEW TREND LOG
VIEW INPUT STATUS
VIEW OUTPUT STATUS
VIEW PAGER NUMBERS
VIEW OPERATION
VIEW CONTROL STATUS
View Status options
View Active AlarmsView Alarm LogView Event LogView Trend Log
> ACTIVE ALARM 22/22
SENSOR_1101.0 DEG
HIGH SETPOINT ALARM
SENSOR_2 ------ DEG
SENSOR PROBLEM
DEVICE_7 ALARM
CONTACT OPEN
BATTERY
CHECK BATTERY
See
Section
5.1
> ALARM RECORD 99/99
SENSOR_280.0 DEG
HIGH SETPOINT ALARM
29-AUG-0509:29:10
MODEM
INTERNAL FAULT
29-AUG-0509:20:00
DEVICE_8 ALARM
CONTACT CLOSED
29-AUG-0507:30:00
See
Section
5.2
> EVENT RECORD 99/99
PAGER
UNSUCCESSFUL PAGE
07-MAY-0510:07:00
DEVICE_1 FORCE ON
CONTACT CLOSED
06-MAY-0502:47:03
DEVICE_8 ON
CONTACT OPEN
05-MAY-0505:22:17
See
Section
5.3
SENSOR TO VIEW?
> SENSOR_1
SENSOR_2
SENSOR_3
SENSOR_4
> TREND LOG 100/100
SENSOR_175.4 DEG
NORMAL
28-AUG-0515:45:51
See
Section
5.4
View Input StatusView Output StatusView Pager NumbersView OperationView Control Status
INPUT / STATUS
> SENSOR_1 +80.00 DEG
SENSOR_2 ------ DEG
SENSOR_3
SENSOR_4 +79.50 RH
DEVICE_1 NORMAL
DEVICE_2 ALARM
DEVICE_3 EVENT
DEVICE_4 ALARM
DEVICE_5 ALARM
DEVICE_6 EVENT
DEVICE_7 NORMAL
DEVICE_8 NORMAL
See
OUTPUT / STATUS
Sec.
> DEVICE_1 ALARM
5.5
DEVICE_2 OPERATING
DEVICE_3 OPERATING
DEVICE_4 OPERATING
DEVICE_5 STANDBY
DEVICE_6 NOT USED
DEVICE_7 NOT USED
DEVICE_8 NOT USED
See
Sec.
> PAGER NUMBER 1
5.6
VIEW PAGER NUMBER
VIEW PAGER PIN
PAGER 1 NUMBER
9,,18005551212##
PAGER TO VIEW?
PAGER NUMBER 2
PAGER NUMBER 3
PAGER NUMBER 4
See
Sec.
5.7
PAGER 1 PIN
01234567891011121344
SELECT ZONE FOR
>ZONE 1
AUTO SEQUENCING ON
DAY 01 OF 02 (08:55)
STANDBY TESTING OFF
VIEWING
See
CONTROL STATUS
Sec.
RELAY 1 OFF
5.8
RELAY 2 OFF
See
Sec.
5.9
21
View Status Options
5.1View Active Alarms
The Active Alarm screen displays all alarms that are occurring, up to a
maximum of 22.
A Current Alarm screen appears automatically whenever an alarm
occurs—except during setup. This screen can display only the two most
recent active alarms. To view any other active alarms, use the View
Active Alarms feature.
You may view active alarms at any time by using the following steps:
• From the Main Menu, use the arrows
shown at right, and then press Enter ↵.
• From the View Status Menu, use the arrows
Active Alarms and press Enter ↵.
5.1.1Active Alarms
The Active Alarms screen displays up to 22 records; it shows any active
alarm and any Latched alarm that has not been cleared. Examples of
alarms include inputs in alarm status, a low battery condition and a
loss of connection to an analog input. When any alarms are present, the
Active Alarms screen shows descriptive details for each alarm:
• the source of the alarm (for example,
• the status of an input or output (
• a brief description of the problem (
BATTERY)
If there are no active alarms, the screen displays the message:
NO ALARMS PRESENT
↑↓ tochoose View Status, as
↑↓ tochoose View
SENSOR_1 or BATTERY)
101.0 DEG)
HIGH SETPOINT ALARM or CHECK
Main Menu
> VIEW STATUS
SYSTEM AND CONTROL
↑↓=NEXT
↵=SELECT
View Status Menu
> VIEW ACTIVE ALARMS
VIEW ALARM LOG
VIEW EVENT LOG
VIEW TREND LOG
VIEW INPUT STATUS
VIEW OUTPUT STATUS
VIEW PAGER NUMBERS
VIEW OPERATION
VIEW CONTROL STATUS
Active Alarms
> ACTIVE ALARM 22/22
SENSOR_1101.0 DEG
HIGH SETPOINT ALARM
SENSOR_2------ DEG
SENSOR PROBLEM
DEVICE_7ALARM
CONTACT OPEN
BATTERY
CHECK BATTERY
Viewing Additional Screens
There may be up to 22 records of alarm data.
• To view additional records, use the arrows
↑↓.
• To return to the previous screen, press the ESC key.
Clearing Active Alarms
To clear all active alarms, see 7.13 - Clear Alarms & Logs. Alarm records are stored in the Alarm
Log.
22
Loading...
+ 98 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.