Appendix A.2.3UPS Configuration - Liebert FS and Liebert Series 610, 600T or 600 . . . . . . . . . . . . . 88
Appendix A.2.4Liebert FS Configuration - Single Liebert FS on Liebert Series 610/600T/600 DC Bus89
Appendix A.2.5Liebert FS Configuration - Multiple Liebert FS Units on Liebert Series 610/600T/600
This manual contains important instructions that should be followed during installation and maintenance of your Liebert FS.
WARNING
!
The installation of the Liebert FS must comply with applicable national, federal, state and
local codes.
ONLY qualified service personnel should perform maintenance on the Liebert FS
system. When performing maintenance with any part of the equipment, service personnel
and test equipment should be standing on rubber mats. The service personnel should wear
insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should
be standing by to assist and summon help in case an accident should occur.
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the Liebert FS system should be kept free of puddles of water,
excess moisture and debris.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system. Observe all safety precautions in this manual before
handling, installing or operating the UPS system.
This equipment contains circuits that are energized with high voltage. Only test
equipment designed for troubleshooting and for use with those voltages should be used.
Always check with an AC and DC voltmeter to ensure safety before making contact or using
tools. Even when the power is turned Off, dangerously high electric charges may exist within
the UPS.
WARNING
!
Exercise extreme care when handling Liebert FS cabinets to avoid equipment damage or
injury to personnel. Refer to Section 3.0 and Section 4.0 for equipment handling
information and installation procedures.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
others approved for use in fighting electrical fires.
WARNING
!
Extreme caution is required when performing maintenance.
Be constantly aware that the Liebert FS contains high DC as well as AC voltages. With input
power off and the battery disconnected, high voltage at filter capacitors and power circuits
should be discharged within 30 seconds. However, if a power circuit failure has occurred, you
should assume that high voltage may still exist after shutdown. Check with a voltmeter
before making contact.
Check for voltage with both AC and DC voltmeters prior to making contact.
WARNING
!
When the Liebert FS is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the Liebert FS chassis frame by using
rubber mats.
Some components within the cabinets are not connected to chassis ground. Any contact
between floating circuits and the chassis is a lethal shock hazard. Exercise caution that the
test instrument exterior does not make contact either physically or electrically with earth
ground.
1
DISCONTINUED
PROD U C T
CAUTION
!
Do not loosen or tamper with vacuum components and fittings.
CAUTION
!
This unit contains components sensitive to electrostatic discharge.
CAUTION
!
Do not remove plug-in printed circuit cards during operation. Improper removal of a card can
cause severe damage to the unit.
CAUTION
!
The 110/230VAC must remain connected at all times to ensure reliable backup power to
Liebert FS auxiliaries.
CAUTION
!
Do not use this unit for other than its intended use.
CAUTION
!
A qualified electrician must perform all electrical connections.
All wiring size and installation must comply with all applicable local, regional and national
regulations (e.g., National Electric Code for USA).
Safety Precautions
Read this manual thoroughly, paying special attention to the sections that apply to you, before working with the Liebert FS.
Under typical operation and with all cabinet doors closed, only normal safety precautions are necessary. The area around the Liebert FS should be kept free from puddles of water, excess moisture or
debris.
Special safety precautions are required for procedures involving handling, installation and maintenance of the Liebert FS. Observe precautions in 7.0 - Maintenance before as well as during performance of any maintenance procedure on the Liebert FS.
This equipment contains circuitry that is energized with high voltage. Only test equipment designated for troubleshooting should be used. This is particularly true for oscilloscopes. Always check
with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the
power is turned Off, dangerously high voltage may exist at the capacitor banks.
ONLY qualified service personnel should perform maintenance on the Liebert FS. When performing
maintenance with any part of the equipment under power, service personnel and test equipment
should be standing on rubber mats. The service personnel should wear insulating shoes for isolation
from direct contact with the floor (earth ground).
One person should never work alone. A second person should be standing by to assist and summon
help in case an accident should occur.
2
DISCONTINUED
PROD U C T
1.0GENERAL SYSTEM INFORMATION
1.1General Information
1.1.1Safety Considerations
Read and follow the instructions in this manual before interacting with the system. This document
contains important information and instructions for your Liebert FS. All procedures defined in the
manual related to unpacking, installing and operating the unit must be followed.
Refer to this manual before contacting Liebert Services for technical assistance.
WARNING
!
Failure to recognize electrical hazards could prove fatal. Failure to abide by instructions
provided herein may void your warranty.
1.1.2Requesting Assistance from Liebert
If you require assistance for any reason, contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378). Have the following information available:
Table 1System information
Date Purchased
Date Installed
Location
System Model Number
System Serial Number
Interconnected UPS Manufacturer
Interconnected UPS Model
Software Version; Primary *
Software Version; Secondary *
Software Version; Bootloader *
General System Information
3
DISCONTINUED
PROD U C T
1.2General System Description
The Liebert FS is a flywheel energy storage system, a mechanical battery that stores energy in the
form of a rotating mass. This energy is immediately convertible to useful electric power.
The Liebert FS is available with a wide performance range up to 200kW as a single unit configuration.
Figure 1Liebert FS
General System Information
The Liebert FS is configured as a two-terminal plus ground DC flywheel power system and is used as
a functional replacement for or an availability supplement to a bank of chemical batteries for an
Uninterruptible Power System. Like a chemical battery bank, Liebert FS receives charge and float
power from the two terminal UPS DC bus and returns power to the same DC bus whenever the bus
voltage droops below a programmable threshold level.
Integrated into a UPS, the Liebert FS is used as the alternate source of power to supply DC power to
the UPS inverter if the AC supply voltage (UPS input) is outside the acceptable range. The Liebert FS
supplies power to the UPS inverter until the utility power is restored, until an alternate power source
is available, or until the Liebert FS’ energy is exhausted.
One or more Liebert FS units may be integrated into UPS and can be put in parallel as shown in
Figures 2 and 3, to achieve higher power output or higher ride-through duration.
4
DISCONTINUED
PROD U C T
General System Information
Figure 2Single Liebert FS unit or multiple Liebert FS units integrated into a UPS system
UPS Block Diagram
UPS
Utility
Power
EMER SO
Network Power
N
Liebert FS Unit 1
AC
DC Bus
DC
Lieber t
EMER SO
Network Power
N
Liebert FS Unit 2Liebert FS Unit N
DC
Loads
AC
Lieber t
EMER SO
Net wor k P ow er
N
Lieber t
Figure 3Liebert FS unit(s) integrated into UPS system for ride-through to backup generator
UPS Block Diagram
Utility
Power
ATS
Backup
Generator
AC
DC Bus
DC
Loads
UPS
EMERSO
Net wor k P ow er
N
DC
Lieber t
EMER SO
Net wor k P ow er
N
Lieber t
AC
EMER SO
Netw ork P ow er
N
Lieber t
Liebert FS Unit 1 Liebert FS Unit 2Liebert FS Unit N
5
DISCONTINUED
PROD U C T
General System Information
Figure 4One or more Liebert FS units in parallel with one or more battery strings, battery cabinets or
batteries in racks
UPS Block Diagram
UPS
Utility
Power
AC
DC Bus
DC
DC
Loads
AC
EMERSON
Net wor k P ower
Liebert
FS Unit 1
Lieber t
EMERSON
Net wor k P ower
Lieber t
Liebert
FS Unit 2
1.2.1General Specifications
Table 2 summarizes the technical specifications of the Liebert FS.
Table 2General system specifications
Rated Power Delivery
Input Voltage (DC)360 through 600 VDC; > 530 VDC required for 200kW
Output Voltage (DC)350 through 590 VDC; > 520 VDC required for 200kW
Input Voltage Aux. (AC)85 VAC – 265 VAC (47-63Hz)
Operating Temperature-20°C to 50°C (-4°F to 122°F)
Non-Operating Temperature-20°C to 80°C (-4°F to 176°F)
Dimensions (W x D x H)63 x 83 x 180 cm (25 x 33 x 71 in)
Total Weight590 kg (1,300 lb)
EMERSON
Net wor k P ower
Liebert
Lieber t
Battery 1
FS Unit N
Dependent upon the duration required;
refer to Figure 5
Battery 2Battery N
For more-detailed technical specifications, refer to Technical specifications on page 148.
6
DISCONTINUED
PROD U C T
1.2.2Features and Benefits
The Liebert FS provides clean constant DC output to the DC bus, at the user-selected, regulated voltage, until the stored energy is depleted. See Figure 5 for a graphic representation of the performance
power and duration curves of single and paralleled unit combinations.
Key Technological Features
• Active magnetic bearings
• Internal, integrated vacuum system
• Synchronous reluctance motor-generator
• Fiber composite flywheel
• Unique patented safety system
Key Customer Benefits
• High reliability
• Significantly increased power supply reliability
• Low total cost of ownership
• Operational flexibility
• Environmentally friendly
• Easy to install and easy to operate.
• Low standby losses
• Small footprint
• Lightweight
• Reliable, cost effective power systems for UPS ride-through needs
General System Information
1.2.3Applicable Standards and Certification
For distribution in North America, the Liebert FS is listed to the following Underwriter’s Laboratory
(UL) applicable requirements:
• UL 508, Standard for Safety for Electrical Industrial Control Equipment;
• UL 1004, Standard for Safety for Electric Motors;
• UL 1248, Standard for Safety for Engine-Generator Assemblies;
The Liebert FS is designed in accordance with the applicable sections of the requirements published by:
• National Fire Protection Association (NFPA)/National Electric Code (NEC)
• National Electrical Manufacturer's Association (NEMA)
• Occupational Safety & Health Administration (OSHA)
The Liebert FS is also listed to the following Canadian Standards as determined by UL (cUL):
• CSA-C22.2 No. 100-04, “Motors and Generators,”
• CSA-C22.2 No. 14-95, “Industrial Control Equipment,”
The "Uniform Building Code (UBC) Zone 4" certification requirements.
7
DISCONTINUED
PROD U C T
For distribution in Europe, the Liebert FS is CE-marked and meets the applicable requirements of
Output Power vs. Ride-Through Time
DC Output Power (kWb)
the following European directives:
“Low Voltage Directive” 73/23/EEC and its amendments by the directive 93/68/EEC;
“Machinery Directive” 98/037/EEC and its amendments by the directive 98/79/EEC;
• IEC/EN 60439-1:1999—“Low-voltage switchgear and control gear assemblies Part 1: Type-
tested and partially type-tested assemblies”
• IEC/EN 60204-1:1997—“Safety of machinery - Electrical equipment of machines Part 1: Gen-
eral requirements”
• EN 1127-1:1997—“Explosive atmospheres: Explosion prevention and protection Part 1: Basic
concepts and methodology”
• Machinery Directive Annex 1—“Essential Health and Safety Requirements Relating to the
Design and Construction of Machinery and Safety Components”
“Electromagnetic Compatibility (EMC) Directive” 89/336/EEC and its amendments by the direc-
tives 92/31/EEC and 93/68/EEC.
Figure 5Liebert FS DC power duration for one or multiple units in parallel
2400 kW-sec delivered
GTX model, 520 VDC, with filter
General System Information
1000
900
800
700
600
500
400
300
200
100
(Vbus=540V, Vreg=520V)
5 Units
4 Units
3 Units
2 Units
1 Unit
0
1217
22
27323742475257
Ride-Through Time, Seconds
12 seconds at 200kW (max. power)
kWb = Refers to Kilowatts on the DC bus of the UPS system
Discharge Voltage = 520VDC
@ 520 VDC min
The Liebert FS is integrated into UPS systems as shown in Figures 2 through 4 and Figures 6
and 7.
8
DISCONTINUED
PROD U C T
Figure 6Integrating a single Liebert FS unit into a UPS system
UPS Block Diagram
Bypass
Breaker
Bypass
Static
Switch
General System Information
GRID
Utility
Feeder
Breaker
UPS
Input
Breaker
UPS
Rectifier
EMERSON
Netw ork Pow er
UPS
DC
Bus
Lieber t
UPS
Output
Breaker
CRITICAL
AC LOADS
Liebert FS
Several Liebert FS units can be put in parallel to achieve higher power output and higher ridethrough duration (see Figure 7). One or more Liebert FS units may also be connected in parallel with
a UPS battery plant (valve- regulated or wet cells) to provide an overall incremental reliability and
life improvement for the DC battery plant. In this situation, the Liebert FS unit would be connected
in parallel with the battery plant (through its own disconnect device) to the UPS DC Bus.
Figure 7Integrating multiple Liebert FS units into a UPS system
Bypass
GRID
Utility
Feeder
Breaker
Bypass Breaker
UPS
Input
Breaker
EMERSON
Netw ork P ow er
Liebert FS
Unit #1
Static
Switch
UPS
Rectifier
Liebert
UPS Block Diagram
UPS
DC Bus
EMERSON
Netw ork Pow er
Liebert FS
Unit #2
Lieber t
UPS
Inverter
EMERSON
Liebert FS
Netw ork Pow er
Unit #N
UPS
Output
Breaker
Lieber t
CRITICAL
AC LOADS
9
DISCONTINUED
PROD U C T
2.0SITE PREPARATION
Site preparation for the Liebert FS is minimal. If a UPS system is already installed, the only requirements are to properly:
• Place the unit in relation to walls, ceiling and other equipment and
• Fasten the unit to the floor.
CAUTION
!
The following sections should be read thoroughly before proceeding with site preparation for
installing the Liebert FS.
NOTE
All drawings referred to in this section are in Appendix D.0 - Installation Drawings.
2.1System Location
Choose a location for the Liebert FS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the Liebert FS
• Air circulation sufficient to expel heat produced by Liebert FS
• Protection against moisture and excessive humidity (not to exceed 95% non-condensing)
• Protection against excessive dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of -4°F to 122°F (-20°C to 50°C)
Site Preparation
2.2Environmental Considerations
Place the system in a clean, dust-free environment. Air must be free to circulate around the cabinet(s). The system pulls air through the front of the Liebert FS and exhausts it out the top for cooling.
If the unit must be located in a dusty environment, Liebert recommends installing an optional air filter, which mounts on the lower inside of the Liebert FS door.
Adequate ventilation, including air conditioning if necessary, must be provided to limit heat accumulation. The ambient temperature for the unit must be from -4°F to 122°F (-20°C to 50°C). Avoid placing the unit in direct sunlight or near other heat sources.
There is a 32°F (0°C) minimum ambient temperature requirement for starting up the unit. Once the
unit has been running for some time, it will keep itself warm enough in ambient temperatures as low as
-4°F (-20°C).
Humidity is not to exceed 95% (non-condensing).
10
DISCONTINUED
PROD U C T
2.3Flooring Requirements
2.3.1Floor Loading
The Liebert FS should be mounted on a finished surface, such as concrete, block, brick or wood. The
floor must be strong enough to support the equipment load and suitable for installation of an anchoring kit with vertical floor loading properly calculated (assume 2,000 PSI or 140 kg/cm
caster wheels; this includes safety factors).
• When installing on a concrete, masonry or stone floor, use the factory-supplied masonry fasteners
(anchors). The fastener manufacturer’s allowable shear load (parallel to floor) for these fasteners
is 2,030 lb. (9 kN) when mounted in normal-weight concrete (2,000 to 3,000 PSI; 140-210 kg/cm
of at least 3 in. (7.6cm) thickness.
• If installing on a floor consisting of a material other than normal-weight concrete as described
above, the mounting should be capable of sustaining a shear load (parallel to floor) of at least
1,500 lb. (6.7 kN) for each of the four mounting points.
• If installing on a raised floor that is less than 2 in. (5cm) thick or constructed of a material not
appropriate for the masonry fasteners provided or lag screw engagement, mount using through
bolts with nuts and large diameter washers as shown in Figure 155.
Full details for mounting the cabinet are found in 4.1 - Cabinet Floor Mounting.
NOTE
The above loads (both the fastener manufacturer load and the minimum mounting load)
include the required safety factors.
Site Preparation
2
contact load at
2
)
2.3.2Floor-Space Occupation
The Liebert FS cabinet requires a floor space of 23" wide by 33" deep (63 x 83cm), resulting in a footprint of 5.7 square feet (0.5m
2
2.3.3Clearances
The Liebert FS installation requires a ceiling height of at least 7 ft. (214cm).
The unit occasionally vents air out of the top. Loose ceiling tiles above the unit may be moved by the
airflow. Ample clearance to access the cable connection at the top of the unit must also be provided.
All system electrical connections are to be routed through the top or side of the cabinet.
A 36" (91cm) clearance is required in the front of the unit for National Electrical Code (NEC) compliance.
Maintenance access to all components is from the front; no side or back access is required for maintenance. Either side of the system cabinet can be placed against walls (assuming minimum distance
from edge of floor). Repair may require access to the rear of the unit. In this unlikely instance, the
unit may need to be rolled out from its installed location (cabinet is on casters).
2.4Electrical Considerations
CAUTION
!
A qualified electrician must perform all electrical connections. The wires (DC power,
grounding, optional status/control and auxiliary power supply) that connect the Liebert FS
system(s) to the UPS system must be provided by the electrical contractor (standard) or by
Liebert as an option. Wire size and installation must comply with all applicable local, regional
and national regulations (e.g., National Electric Code for USA).
).
2.4.1DC Power Connections
Place the Liebert FS as close as practical to the interconnected UPS. The maximum distance allowed
between the UPS and the Liebert FS depends on power levels and the type of DC cables used. Liebert
requires sizing DC cables and placing the Liebert FS for a maximum of no more than 2V loop drop (at
rated power) between the UPS and the Liebert FS.
The Liebert FS is delivered with the standard UPS interconnection kit for connection of the positive
and negative terminals coming from the UPS DC bus or from an external disconnect switch.
For details, see 4.2.2 - DC Power Connections.
11
DISCONTINUED
PROD U C T
2.4.2Status/Control Connections
Site preparation for Status/Control connections vary according to the type of UPS interconnection kit
provided with your Liebert FS.
Liebert recommends making Status/Control connections on the UPS system side.
For details, refer to 4.2.3 - Status/Control Connections.
2.4.3Grounding Connections
A grounding wire must be connected from the Liebert FS to the UPS ground terminal. Identify in
advance the location of the grounding terminal on the UPS system. For further details, see 4.2.2 - DC Power Connections.
2.4.4AC Power Connections
Plan for the availability of a dedicated 110 or 230VAC, 50 or 60Hz circuit with branch circuit protection as a source for AC auxiliary power supply to the Liebert FS. This AC power must be rated for
500VA and must be located either on the output circuit of the UPS system or on another UPS-protected circuit. A qualified electrical contractor should make arrangements for this connection to be
permanent.
Site Preparation
The field-supplied AC wire must comply with all applicable local, regional and national regulations
(e.g., National Electric Code for USA). An 18 AWG (0.82mm
tion.
For details, see 4.2.5 - AC Auxiliary Control Power Supply Connections and Appendix F.0 - Auxiliary Backup AC Power Supply.
2.4.5Remote Monitoring Connections—Optional
If the optional Data Collection Module (DCM) is provided with your Liebert FS system, plan to have
communication cables (local network connection, phone line) installed to support the remote notification and/or monitoring options chosen.
For details, see 4.2.6 - Remote Monitoring Connections—Optional.
2
) cable is recommended for this connec-
12
DISCONTINUED
PROD U C T
3.0UNLOADINGAND UNPACKING
either side)
NOTE
All drawings referred to in this section are in Appendix D.0 - Installation Drawings.
3.1Inspection Before Removal From the Truck
While the Liebert FS shipping package is still on the truck:
• Inspect the equipment and shipping container(s) for any signs of damage or mishandling. Check
also if the shock and tilt gauges (installed for shipping purposes) indicate excessive shock and/or
tilting. If any damage is noted, file a damage claim with the shipping agency within 24 hours and
contact your local sales representative or Liebert at 1-800-LIEBERT to notify them of the damage
claim and the condition of the equipment.
• Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier, your local Liebert representative and Liebert at 1-800-LIEBERT immediately. Please have
the bill of lading available.
CAUTION
!
Do not attempt to install the system if damage is apparent.
3.2Unloading
Figure 8Liebert FS shipping package
Unloading and Unpacking
76"
(1933mm)
Front View
Do not tilt the Liebert FS
more than 15 degrees
from vertical.
The FS as shipped (see Figure 8) can weigh up to 1,462 lb. (663kg). It must be handled with care. It
must be kept upright—pay special attention to the arrows, which indicate the upright position.
45"
(1143mm)
Top View
Side View
24"
(610mm)
(1219mm)
4.4"
(112mm)
Shipping Support
Bands
(on either side)
Metal
Support
Plates
(one on
Shipping Weight:1462 lb. (663kg)
Weight, unit only: 1300 lb (590kg)
48"
14623
13
DISCONTINUED
PROD U C T
3.2.1Handling
The Liebert FS shipping package is designed to be handled using a forklift. Forklift operators must
avoid rough handling when picking up, moving and lowering it.
CAUTION
!
Exhibit care when handling Liebert FS cabinet to avoid equipment damage or injury to
personnel. Failure to do so could throw off the calibration of the mechanical components
contained in the unit and possibly cause permanent damage.
CAUTION
!
The Liebert FS has sensitive electronics and mechanical components that have been
calibrated prior to shipment.
CAUTION
!
Test lift and balance the cabinet before transporting it. Maintain minimum tilt from vertical
at all times—do not exceed 15 degrees of tilt.
CAUTION
!
Sheet metal components and framework may have sharp edges.
3.2.2Unpacking
Unloading and Unpacking
To reduce the possibility of shipping damage, flywheel cabinets are secured to the pallet by two
mounting brackets and two banding straps. These same two mounting brackets are used to mount the
cabinet to the floor.
Packing elements should be removed in this order to ease unpacking:
1. Cut and remove the banding straps (see Figure 8).
CAUTION
!
Use care when removing banding straps and metal mounting brackets. The banding straps
are under tension and may snap violently, causing injury. Always wear proper eye and foot
protection when unpacking or installing the system.
2. Remove hex head bolts holding mounting brackets to pallet as shown in Figure 9.
3. Remove lag bolts holding metal mounting brackets to pallet.
4. Remove mounting brackets from Liebert FS.
Figure 9Removing lag bolts
Lag bolts
securing
Liebert FS to
shipping pallet
14
Metal mounting
bracket bolted to
shipping pallet
DISCONTINUED
PROD U C T
5. Use a forklift to remove the cabinet from the shipping pallet.
To lift the Liebert FS, the forks should be inserted between the caster wheel assemblies (see
Figure 10). Forks must be extended to the full depth of the cabinet—at least 6 ft. (2m) fork
length—to properly support the equipment (see Figure 10). This likely requires fork extenders.
The Liebert FS unit can weigh up to 1,300 lb. (590kg) and must be handled with care.
Figure 10 Lifting the Liebert FS cabinet
Forks must be
extended the
full depth of the
cabinet
6. Unbolt and remove the two metal support plates (one on either side of the pallet).
Figure 11 Removing the metal support plates
Unloading and Unpacking
Metal
support
plate
Caster
(for moving
short
distances)
Leveling
foot (one
on each
corner)
NOTE
Retain the four bolts (1/2" diameter x 1-3/4" long; 12.7mm diameter x 44.5mm long) attaching
the metal support plates to the cabinet. These will be used to attach brackets to the cabinet for
surface mounting.
7. Examine the Liebert FS internally and externally for transit damage. Report any damage to the
shipper, your local Liebert representative and Liebert immediately.
CAUTION
!
Do not attempt to install the system if there is any damage.
8. Check visually for loose connections and unsecured components in the cabinet.
9. You will find the installation manual, operation manual and options manual (if any) enclosed in
the pocket inside the cabinet door (see Figure 12).
10. You will find the serial number and model number plate mounted on the cabinet door pocket or on
the upper right corner of the face of the cabinet frame inside the door (see Figure 12). Record the
model number and serial number in Table 1 - System information.
15
DISCONTINUED
PROD U C T
Unloading and Unpacking
Figure 12 Location of serial and model number plate (cabinet side panel removed and open door)
Serial Number
and Model
Number Plates
3.3Positioning the Liebert FS
3.3.1Moving the Liebert FS
When moving the unit a short distance, the Liebert FS may be rolled on its built-in casters (see
Figure 13) to its location.
Manuals
CAUTION
!
Before moving the Liebert FS across a floor, determine whether the surface will support the
unit’s weight—1,462 lb. (663kg) as shipped; 1,300 lb. (590kg) uncrated.
Figure 13 Liebert FS cabinet caster location
Casters on each corner
(for moving unit short
distances only)
When moving the unit a longer distance or over rough flooring, move the Liebert FS with a forklift or
similar equipment to facilitate the relocation and to reduce vibration of the unit.
CAUTION
!
Ensure that the handling equipment is rated for the weight of the Liebert FS—1,462 lb.
(663kg) as shipped; 1,300 lb. (590kg) uncrated.
3.3.2Storing the Liebert FS for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the temperature
stays within -4°F to 176°F (-20°C to 80°C) and the humidity is no higher than 95% (non-condensing).
16
DISCONTINUED
PROD U C T
4.0INSTALLATION
The Liebert FS system design and safety characteristics allow for a relatively simple and quick installation. The system is designed to be rolled or lifted into place and bolted to the floor using Liebert's
mounting kit, included with the system. The mounting kit in most cases does not require any special
floor preparations (see3.0 - Unloading and Unpacking).
CAUTION
!
The Liebert FS system must be installed in accordance with the instructions and drawings in
this manual.
CAUTION
!
Never attempt to install or power up any unit suspected of damage during shipment.
CAUTION
!
The Initial System Startup must be performed ONLY under the supervision of a
Liebert-certified service technician to ensure proper system operation. Failure to abide by
instructions provided herein may void your warranty.
Contact your local Liebert sales representative or Liebert at 1-800-LIEBERT to arrange for
system startup.
Figure 14 Dimensions, general layout
Installation
Top
Bottom
Control
Panel
71-1/ 8"
(1801mm)
25"
(6 3 6mm)
Front
17
32-1/2"
(828mm)
Right Side
12-100120-09
DISCONTINUED
PROD U C T
Figure 15 Internal layout
Installation
Data
Control
Module
Versatile
Interface
Board
Inductor
Capacitor
Module
Power
Convers ion
Module
Factory-Integrated
Circuit Breaker
Fan
Magnetic
Levitation
Module
71-1/8"
(1807mm)
Flywheel
Module
25"
(636mm)
Front
(door open)
32-1/2"
(828mm)
Right Side
(panel removed )
NOTE
The Liebert FS is designed for front-access-only for installation and maintenance. While the
likelihood of repair is minimal, some repair procedures require side and/or rear access.
Normally, the easiest way to handle this is to disconnect the power and control wiring and roll
the unit out into an open area on its casters. While it is acceptable, under certain
circumstances, to connect the Liebert FS to its companion UPS unit through the sides of the
Liebert FS and UPS cabinets rather than through external conduit, repair access to the Liebert
FS unit will be easier to facilitate if through-cabinet wiring is not installed.
18