Emerson 48330 User Manual

ACTURA Flex 48330 Power System User Manual
Version: V1.0 Revision date: May 20, 2005 BOM: 31011084
Copyright © 2005 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to
change without notice.
Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District
518057, Shenzhen China Homepage: www.emersonnetworkpower.com.cn E-mail: support@emersonnetwork.com.cn
Safety Precautions
To avoid accident, read the safety precautions very carefully before operation. The "Caution, Notice, Warning, Danger" in this manual do not represent all the safety points to be observed. Therefore, the installation and operation personnel must be strictly trained and master the correct operations and all the safety points before actual operation.
When operating Emerson products, the safety rules in the industry, the general safety precautions and special safety instructions must be strictly observed.
Electrical Safety
1. Hazardous voltage Some components of the power system carry hazardous voltage in operation,
direct contact or indirect contact through moist objects with these components will result in fatal injury.
Safety rules in the industry must be observed when installing the power system. The installation personnel must be licensed to operate high voltage and AC power.
In operation, be sure to remove conductive objects, such as watch, bracelet, ring, and so on.
When water or moisture is found on the cabinet, turn off the power immediately. In moist environment, take precautions to keep moisture out of the power system.
"Prohibit" warning label must be attached to the switches and buttons which are not permitted to be operated on during installation.
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance with the local codes and regulations. Only those who are licensed to operate high voltage and AC power can perform high voltage operations.
2. Tools In high voltage and AC operation, special tools must be used. No common or
homemade tools should be used.
3. Thunderstorm Never operate on high voltage, AC, iron tower or mast on a day with
thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well-earthed in time to avoid damage by lightning strikes.
4. ESD The static electricity generated by the human body will damage the static
sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive elements. The other end of the ESD wrist strap must be well earthed.
5 Short-circuit During operation, never short the positive and negative terminals of the MFU
of the system or the non-earthing terminal and the earth. The power system is a constant voltage DC power equipment, short circuit will result in equipment burning and endanger human safety.
Check carefully the polarity of the cable and connection terminal when performing DC live operations.
Never wear a watch, bracelet, ring, or other conductive objects during operation.
Insulated tools must be used.
Battery
Before any operation on battery, read very carefully the safety precautions for battery transportation and the correct battery connection method.
Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent battery short circuit and overflow of electrolyte. The overflow of electrolyte will pose potential threat to the equipment, it will erode the metal objects and PCBs, thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points: Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist. Use special insulated tools. Wear an eye protection device, and take preventive measures. Wear rubber gloves and apron to guard against electrolyte overflow. In battery transportation, the electrode of the battery should always be kept
facing upward. Never put the battery upside down or slanted.
Special Safe Requirements of This Equipment
The equipment has multi power inputs; The equipment shall be installed on cement ground.
Others
1 Safety requirement Please use the same model fuse to replace the fuse in the DC Power System.
2. Sharp object When moving equipment by hand, wear protective gloves to avoid injury by
sharp object.
3. Cable connection Please verify the compliance of the cable and cable label with the actual
installation prior to cable connection.
4. Binding the signal cables The signal cables should be installed separately far away from heavy current
and high voltage cables, with distance at least 150mm.
Contents
Chapter 1 System Description................................................................................................1
1.1 Abbreviation..............................................................................................................1
1.2 Introduction...............................................................................................................1
1.3 Features....................................................................................................................1
1.4 Sy
1.5 Components..............................................................................................................4
Chapter 2 Installation...........................................................................................................12
2.1 Installation Preparation ...........................................................................................12
2.2 Installation Procedures............................................................................................15
2.3 External Electrical Connection
2.4 Battery Installation And Cabling
2.5 Parallel Connection Of Cabinets.............................................................................29
stem Configuration................................................................................................2
1.5.1 Rectif
1.5.2 Rectif
1.5.3 SCU................................................................................................................7
1.5.4 Multi-Function Unit (MFU)...............................................................................9
1.5.5 Battery Connection Unit (BCU).....................................................................10
1.5.6 Sy
2.1.1 Env
2.1.2 Power Supply................................................................................................12
2.1.3 Si
2.1.4 Tools & Material............................................................................................13
2.1.5 Unpacking.....................................................................................................14
2.2.1 Cabinet Installati
2.3.1 Connection Of Inpu
2.3.2 Connection Of Load Cables..........................................................................20
2.3.3 Connection
2.3.4 Layout Of Connector Board S6415X2...........................................................22
2.3.5 Interface Definition Of Connector Board S6415X2........................................23
2.3.6 Connection
2.3.7 Connection With MODEM.............................................................................24
2.3.8 Connection
2.4.1 Battery Installation ........................................................................................25
2.4.2 Battery Cable Connection.............................................................................26
ier Shelf..................................................................................................4
ier...........................................................................................................6
stem Cabinet.............................................................................................11
ironmental Conditions.............................................................................12
te Survey
...................................................................................................13
on .......................................................................................15
Interface .................................................................17
t Cables..........................................................................17
Of Communication Cables.........................................................21
Of Temperature Sensor Cables.................................................24
With Dry Contacts......................................................................25
..............................................................................25
Chapter 3
3.1 Checki
3.2 Startup Process
3.3 Parameters Configuration.......................................................................................31
Startup.................................................................................................................30
ng Before Startup.........................................................................................30
......................................................................................................31
Chapter 4 Testing.................................................................................................................32
4.1 Testing MFU ...........................................................................................................32
4.2 Testing Rectifier......................................................................................................32
4.3 Testing SCU............................................................................................................32
4.4 Battery
4.5 BCU Te
Breaker Test...............................................................................................33
st ................................................................................................................33
4.6 Load Breaker Test ..................................................................................................33
Chapter 5 Operating SC
U....................................................................................................34
5.1 Operation Panel......................................................................................................34
5.2 Operation Procedures.............................................................................................35
5.3 Query
5.3.1 First Page Of System Informatio
ing System Status .........................................................................................36
n.................................................................36
5.3.2 Other System Information Screen.................................................................37
5.4 Querying Rectifier Status........................................................................................39
5.5 Querying Alarms And Setting Alarm Plans
..............................................................40
5.5.1 Querying Active Alarm..................................................................................40
5.5.2 Query Alarm History
......................................................................................41
5.5.3 Alarm Type Table..........................................................................................43
5.5.4 Changing Audible/Visual Alarm And Alarm Call Back Pl
an...........................46
5.5.5 Changing Alarm Types Of Dry Contacts.......................................................46
5.5.6 Setting Alarm Type For Dry
Contacts ...........................................................46
5.5.7 Set the Alarm Names Through PLC Function...............................................48
5.6 Maintenance ...........................................................................................................51
5.7 Setting System Parameters ....................................................................................53
5.7.1 Parameter Setting
Method............................................................................53
5.7.2 Batt. Selection...............................................................................................55
5.7.3 LVD
Parameter Description..........................................................................56
5.7.4 Charging Management Parameters..............................................................57
5.7.5 Bat
tery Test Parameters...............................................................................60
5.7.6 Temperature Compensation Coefficient Parameters....................................62
5.7.7 AC Se
ttings...................................................................................................63
5.7.8 DC Setting ....................................................................................................64
5.7.9 Rect Settings ................................................................................................65
5.7.10 Sy
stem Settings..........................................................................................66
5.7.11 Alarm Settings.............................................................................................70
Chapter
6 Routine Maintenance...........................................................................................72
6.1 Mainte
nance Of Rectifier.........................................................................................72
6.2 Maintenance Of SCU..............................................................................................72
6.3 Mainte
nance Of MFU..............................................................................................72
6.4 Cover Plates ...........................................................................................................73
6.5 Battery Maint
6.5.1 Stora
enance...............................................................................................73
ge And Supplementary.........................................................................73
6.5.2 Daily Inspection.............................................................................................73
6.5.3 Replacement.................................................................................................74
Chapter 7 Troubleshooting...................................................................................................75
7.1 Troubleshooting Rectifier........................................................................................75
7.2 Mains Failure ..........................................................................................................76
7.3 Disastrous Accidents ..............................................................................................76
Appendix 1 System Technical Parameters ..........................................................................77
Appendi
x 2 Engineering Design Diagram ............................................................................79
Appendi
x 2.1 Engineering Design Diagram For 2000mm%600mm%600mm Cabinet Appendix 2.2 Engineering Design Diagram For 2000mm%600mm%400mm Cabinet
Appendix 2.3 Engineering Design Diagram For 700mm%600mm%400mm Cabinet....81
Appendi
x 2.4 System Input And Output Connecto
Appendix 3 System Circ
uit Diagram.....................................................................................82
r Specs............................................81
Appendix 3.1 System Electric Schematic Diagram.......................................................82
Appendix 3.2 System Wiring Diagram
..........................................................................83
Appendix 3.3 MFU Electric Wiring Diagram..................................................................84
Appendix 3.4 BCU Electric Wiring Diagram..................................................................85
Appendi
x 4 Glossary............................................................................................................86
..79 ..80
Table List
Table 1-1 Configurations of Actura Flex 48330 Power System..............................................3
Table 1-2 Dimensions of rectifier shelf...................................................................................5
1-3 Function of indicators.............................................................................................7
Table
Table 1-4 Authority and default password..............................................................................9
Table 1-5 Configuration of MFU...........................................................................................10
Table 1-6 BCU configuration................................................................................................11
2-1 Environmental conditions in power room .............................................................12
Table
Table 2-2 AC input modes ...................................................................................................17
Table 2-3 Configuration number of load MCBs and battery MCBs.......................................20
Table 2-4 Interface definition of connector board S6415X2.................................................23
3-1 System checklist before startup...........................................................................30
Table
Table 5-1 Functions of LED indicators.................................................................................34
Table 5-2 Functions of SCU keys.........................................................................................34
Table 5-3 Alarm type table
Table 5-4 Changing audible/visual alarm and alarm call back plan......................................46
Table 5-5 Optional alarm types............................................................................................47
Table 5-6 Logic matrix used for configuring 8 dry contacts..................................................49
Table 5-7 Example of PLC setting........................................................................................49
Table 5-8 PLC SN and Alarm...............................................................................................49
5-9 Password levels and authorities...........................................................................54
Table Table 5-10
Table 5-11 Value description of the LVD parameters...........................................................57
Table
Table 5-13 Value description of the battery test parameters................................................61
Table 5-14 Value description of temperature compensation coefficient...............................62
Table 5-15 Value description of AC se Table 5-16 Value description of DC se
Table 5-17 Value description of rectifier settings..................................................................65
Value description of the basic battery parameters .............................................56
5-12 Charging management parameter value description..........................................59
...................................................................................................43
ttings........................................................................63
ttings........................................................................64
Table 5-18 Value description of system settings
Table 5-19 Relationship between system model and system type.......................................70
Table 5-20 Value description of alarm settings ....................................................................71
Table 7-1 Troubleshooting ...................................................................................................75
..................................................................68
Figure List
Figure 1-1 Outline .................................................................................................................. 2
Figure 1-2 Rectifier shelf outline.............................................................................................
Figure 1-3 Rectifier shelf with rectifiers and CU.....................................................................4
Figure 1-4 Dimensions...........................................................................................................6
Figure 1-5 Outline of SCU......................................................................................................7
Figure 1-6 Outline and components of MFU..........................................................................9
Figure 1-7
Figure 2-1 Installation dimensions of the cabinet base ........................................................15
Figure 2-2 Installing expansive pipe.....................................................................................16
Figure 2-3 Fixing cabinet with Tap.......................................................................................16
Figure
Figure 2-5 Connection of input terminals .............................................................................18
Figure 2-6 Top cover............................................................................................................18
Figure 2-7 Connection of 3-phase AC power input ..............................................................18
Figure 2-8
Figure 2-9 Connection of dual-phase AC power input..........................................................19
Figure 2-10 Connection of load cables.................................................................................20
Figure 2-11 Cable connection to MCB
Outline of battery connection unit (BCU).............................................................10
2-4 Cable mounted with H terminal...........................................................................17
Connection of single-phase AC power input.......................................................19
.................................................................................20
4
Figure 2-12 Connector board in rectifier shelf......................................................................21
Figure 2-13 Layout of connector board S6415X2.................................................................22
Figure 2-14 Input/output interfaces of TD-5648DC MODEM................................................24
Figure 2-15
Figure 2-16 Connection of battery cables. ...........................................................................27
Figure 2-17 Positive and negative battery cables in each level............................................27
Figure 2-18 Negative battery cables connection in BCU......................................................28
Figure 2-19 Parallel connection of DC power system cabinet with battery cabinet..............29
Figure Figure
Figure 5-3 Schematic diagram of the test function...............................................................61
Figure
Cabinet with four battery strings ins
5-1 SCU Front Panel.................................................................................................34
5-2 BC/FC switchover diagram.................................................................................59
5-4 System model description...................................................................................69
talled .........................................................26
Chapter 1 System Description
1.1 Abbreviation
AC Alternate Current DC Direct Current SCU Standard Controller Unit BCU Battery Connection Unit CSU Central Supervision Unit HVSD High Voltage Shutdown MCB Miniature Circuit Breaker
Chapter 1 System Description 1
APFC Active Power Factor Correction MFU Multi-Function Unit
1.2 Introduction
The ACTURA Flex 48330 Power system consists of 50A rectifiers, Control Unit, Multi-Function Unit (MFU), rectifier shelf and BCU (optional).
The product is used in base station, small exchange station, satellite communication, data communication, and so on, with a strong adaptability to power network fluctuation.
This system is used as a power supply for telecom equipment with system nominal voltage of -48V and positive terminal earthed.
1.3 Features
The DC power system is easy-to-operate, easy-to-install and easy-to-maintain. Its main features are:
Rectifier uses APFC technology and therefore its PF is up to 0.99; Wide AC input voltage range of 85~290V; Rectifier efficiency is at least 90%; Extra low EMI of rectifier and excellent EMC performance;
ACTURA Flex 48330 Power System User Manual
2 Chapter 1 System Description
High power density of rectifier; Rectifier has damage-free hot plugging/unplugging function, the replacement
time is less than 1min;
Rectifier has two kinds of over-voltage protection methods; Perfect battery management with BLVD function; Up to 200 PCS of historical alarms can be stored in SCU; Provide RS232, Modem and dry contacts communication interfaces;
1.4 System Configuration
The outline of the DC Power System is illustrated in Figure 1-1:
Multi-function unit
Rectifier Connector Board
Control unit
Rectifier shelf Rectifier cover Battery connection unit
Battery shelf
Door
Figure 1-1 Outline
There are three kinds of DC Power Systems, and their detail configurations are as shown in Table 1-1:
ACTURA Flex 48330 Power System User Manual
Chapter 1 System Description 3
Table 1-1 Configurations of Actura Flex 48330 Power System
Configuration
Cabinet dimension
2.0 % 0.6 % 0.6 m3 2.0 % 0.6 % 0.4 m3 0.7 % 0.6 % 0.4 m3
3P+N/380V AC input with SPD 3P+N/380V AC input without SPD 1P+N/220V AC input with SPD 1P+N/220V AC input without SPD
AC distribution
DC distribution Up to 28 13mm-wide MCB, or 20 18mm-wide MCB Rectifier Up to 5 rectifiers Control unit 1 SCU BCU 1 BCU with up to 5 battery circuit breakers
Battery
Dimensions (H×W ×D) mm
L1+L2/220V AC input with SPD L1+L2/220V AC input without SPD 3P/220V AC input with SPD 3P/220V AC input without SPD 5 2P AC input MCBs Individual AC cables with just terminals
Telion 12V 165Ah FT: 16 Blocks
Hawker 12V 155Ah FT: 16 Blocks
Hawker 12V 105Ah FT: 20 Blocks
Hawker 12V 105Ah FT and 6U space:
16 Blocks
2000×600×600 2000×600×400 700×600×400
Hawker 12V82F: 16 Blocks Hawker SBSC11 and
3U space: 16 Blocks EB4: 20 Blocks Hawker 12V82F( no
BCU): 20 Blocks
No battery
ACTURA Flex 48330 Power System User Manual
4 Chapter 1 System Description
1.5 Components
1.5.1 Rectifier Shelf
Outline
The outline of the Rectifier Shelf is illustrated in Figure 1-2:
Chassis
Terminal connecting 50A Rectifier
Connector Board
Ear Bracket
(a) Actual appearance (front view)
Bus Bar
Back Board
(b) Actual appearance (rear view)
Figure 1-2 Rectifier shelf outline
The shelf can accommodate 5 rectifiers and a control unit as shown in Figure 1-3. The user can mount the rectifier shelf into cabinets with widths of 600mm and depths of 400mm. The rectifier shelf has a height of 3U (132.5mm).
Figure 1-3 Rectifier shelf with rectifiers and CU
ACTURA Flex 48330 Power System User Manual
Chapter 1 System Description 5
The Dimension of Rectifier Shelf are given in Table 1-2
Table 1-2 Dimensions of rectifier shelf
Manufacture type W(mm) ×D(mm) ×H(mm) Note
PSS485023/C 584.2×327×132.5 23’’ with controller
Backboard
The backboard has the functions below:
DC power source feed for controller and the connector board. DC input filter and input fuse. All the ingoing and outgoing signals of the controller
The backboard also contains system internal connectors below:
10 Distribution unit fuses alarm signal measurement input 4 battery fuse alarm signal measurement input 2 battery current shunt measurement inputs 1 load Current shunt measurement input System bus-bar DC Voltage measurement input Three-phase from two mains AC Voltage measurement inputs CAN communication between rectifiers and controller AC alarm module signals System fault indicator drivers LLVD & BLVD mono contactor driver outputs The entire signal outgoing to the connector board
Connector board
Connector board is a user interface board and has the functions below:
8-channel relay outputs 8-channel digital inputs One power source feed terminal (for digital inputs) 2-channel temperature sensor inputs 2-channel RS232 parallel connection outputs LLVD & BLVD bistable contactor driver circuits and outputs
ACTURA Flex 48330 Power System User Manual
6 Chapter 1 System Description
One Ethernet output One RS485 output One console output for ECU debug The connector board can be hot plug and has enough space for
accommodating all the interface cables.
The connector board should space the hollow to the SCU convection for air
flowing
The connector board is mounted in the room 1U×2U at the top of the SCU. The shelf has a 1U×2U panel for the connector board. One RS232 and Ethernet ports are located at the front of the connector board. The shelf has two rails for supporting the connector board
1.5.2 Rectifier
Outline
The appearance and dimensions (unit: mm) of the rectifier are illustrated in the following figure.
Figure 1-4 Dimensions
Weight: 3.5kg Dimensions (H × W % D): 124.3mm % 84mm % 287mm The functions of the indicators in front panel are listed in Table 1-3.
ACTURA Flex 48330 Power System User Manual
1.5.3 SCU
LED Normal Abnormal Cause of abnormality
Power indicator (green) ON
Protection indicator (yellow)
Alarm indicator (red) OFF
OFF
Outline
Chapter 1 System Description 7
Table 1-3 Function of indicators
OFF No AC Mains Supply Blinking Rectifier is under control by SCU
ON Blinking Communication of rectifier with SCU failure
ON Output Over-voltage Blinking Fan Failure
AC input over/under voltage, PFC over/under voltage and over temperature
Figure 1-5 Outline of SCU
Dimension (H % W % D):132mm % 85mm % 287mm Weight: 0.76kg
Multi-Communication mode
SCU communicates with MC (Main Computer) through the RS232/MODEM communication port and 8 groups of alarm dry contacts on the Signal Junction Board.
SCU supports both China Telecom Communication Protocol and EEM Protocol. Make sure that the baud rates for receiving and transmitting are set to be consistent when using SCU.
1. Communication through RS232 RS232 communication mode is mainly used for short-distance point-to-point
communication. The communication distance shall be less than 15m. If SCU communicates with MC through RS232, just connect SCU RS232 port to the RS232 port of MC.
2. Communication through MODEM or ES-MOD
ACTURA Flex 48330 Power System User Manual
8 Chapter 1 System Description
When SCU communicates with MC through MODEM or ES-MOD, it uses PSTN to realize long-distance monitoring. Power supply cables and communication cables shall be prepared for the communication through MODEM.
3. Dry Contacts Output SCU has 8 dry-contact outputs. Every dry-contact output has NC (normally closed)
and NO (normally-open) contacts. Every dry-contact output shall be configured before the alarm event occurs. Different dry-contact output can trigger different alarms. Once the alarm event occurs, the dry-contact will close or open to generate the alarm.
If the user has other intelligent equipment to be monitored by SCU, the user can connect the dry contacts to the interface of the intelligent equipment, and control the intelligent equipment through these dry contacts.
Capacity of dry contacts: 2A@30Vdc; 05A@125Vac; Maximum power dissipation: 60W
Functions fulfilled by SCU and MC
In RS232 and MODEM communication modes, the MC can fulfill the following functions through SCU:
1. Remote acquisition of analog and digital values: MC can acquire the real-time analog and digital values of DC Power System through SCU;
2. Remote control functions: MC can shut down the rectifiers, change the boost charge status to float charge status (or in reverse), silence the alarm and stop/start the battery test through SCU.
Alarm category settings for dry contact output
1. Through setting the parameter of “Relate Relay”, the user can configure the alarm category for every dry-contact output. Every dry-contact output has been configured to correspond to an alarm category before SCU is delivered to customer.
2. SCU has PLC functions in the alarm management. The PLC is to realize simple logic operation, i.e. the "And", "Or" and "Not" operations. The PLC inputs are all the possible alarm signals, and the PLC outputs can be used to select one of the 8 dry contacts. The alarm categories can be configured flexibly for every dry-contact output through MC. The PLC settings for every dry-contact have three alarm inputs, and two relation flag. The SN of three alarm categories and the mutual logic relationships need to be configured.
PLC can be set to “Disabled”. If PLC functions and alarm co-relation are enabled at the same time, the dry contact will act to activate an alarm when any alarm event occurs.
ACTURA Flex 48330 Power System User Manual
Chapter 1 System Description 9
Password protection for important operations
The users must input the correct password before they conduct “Maintenance” and “Settings” operations. The password has 3 levels: user, operator or administrator. The authorities of the 3 levels are the same while conducting “Maintenance”, but different in conducting “Settings”. The operator can see 3 more pages than the user, which are “resetting system”, “resetting password” and “modifying system type”. The administrator can see 2 more pages than the operator, which are “modifying password of all levels” and “controlling alarm sound volume”. In addition, the administrator can browse the rectifier parameter serial No., software version and the setting of internal switches. See the following table:
Table 1-4 Authority and default password
Level Authority Default password
User Configuration of general parameters 123456 Operator
Administrator
User’s authority, plus resetting system, resetting password and modifying system type. Operator’s authority, plus modifying password of all levels, controling alarm sound volume, browsing system parameters that can be set only through the host
654321
640275
1.5.4 Multi-Function Unit (MFU)
Outline and components
The outline and the components of the MFU are illustrated in the following figure.
Bypass bar
BLVD contactor
Battery MCB
Battery -48V bus
Load MCB
OV DC bus
LLVD contactor
Shunt
Prior load bus
PE bus
SPD
AC input terminals
Rectifier AC input MCB
Low prior load bus
Figure 1-6 Outline and components of MFU
ACTURA Flex 48330 Power System User Manual
10 Chapter 1 System Description
Table 1-5 Configuration of MFU
No. Component Description
1 SPD 2 AC input terminals Rating Current 150A 3 Rectifier AC input MCB Rating Current 25A 4 BLVD contactor 200A or 400A optional 5 LLVD contacto r 200A or 400A optional 6 Shunt 300A/75mV 7 Battery MCB 100A MCB (up to 5 battery MCBs can be selected to configure) 8 Load MCB Selected according to user’s requirement
The user can mount the distribution unit into cabinets with widths of 600mm and depths of 400mm and 600mm. It has a height of 4.5U (200mm).
1.5.5 Battery Connection Unit (BCU)
Outline
Norminal Dischage Current(8/20μS) 20kA; Ue=385V
The outline of the Battery Connection Unit (BCU) is illustrated in Figure1-7.
Enclosure
Battery MCB
-48V DC Bus
Figure 1-7 Outline of battery connection unit (BCU)
Physical size
Battery Connection Unit (BCU) can be installed in cabinets with widths of 600mm and depths of 400mm and 600mm. BCU has a maximum height of 1.5U (67mm).
BCU contains 2 to 5 circuit breakers, each with ratings of 100A and 200A.
Alarm output
The BCU will generate an alarm if a battery circuit breaker is off. This alarm shall be possible to connect to the connector board for display in the Controller. It shall be possible to combine the alarms from 2 BCUs to generate a single alarm in the controller. It shall also be possible to combine the alarm from the BCU with an
ACTURA Flex 48330 Power System User Manual
alarm generated from battery circuit breakers that are switched off in the BCU (for example when using a BCU in an extension battery cabinet and battery circuit breakers in the BCU in a main cabinet).
BCU configuration
The BCU configuration is as shown in Table 1-6:
Item Function unit Amount
Battery connection unit
1.5.6 System Cabinet
There are three kinds of cabinets. Their dimensions are 2.0m % 0.6m % 0.6m, 2.0m % 0.6m % 0.4m and 0.7m % 0.6m % 0.4m respectively.
Chapter 1 System Description 11
Table 1-6 BCU configuration
100A CB for battery input 2/3/4/5 200A CB for battery input 2/3/4/5
2.0m % 0.6m % 0.6m cabinet
This cabinet is installed with 1 % MFU, 1 % Rectifier Sub-rack, 1 % BCU and the following combination of units:
16 Blocks of Telion 12V 165Ah FT batteries or 16 % Hawker 12V 155Ah FT
batteries
20 Blocks of Hawker 12V 105Ah FT batteries 16 Blocks of Telion 12V 100Ah FT batteries (20 blocks is preferred, if possible) 16 Blocks of Hawker 12V 105Ah Ft batteries and 6U of unspecified equipment
(such as DC/DC converters or similar)
2.0m % 0.6m % 0.4m cabinet
This cabinet accommodates 1 % MFU,1 % Rectifier Sub-rack, 1 % BCU and the following combination of units:
16 Blocks of Hawker 12V82F batteries or 16 Blocks of Hawker SBSC11 and
3U available for additional equipment such as DC/DC converters 20 Blocks of EB4 batteries 20 blocks of Hawker 12V82F batteries (20 blocks and BCU is preferred, if possible)
0.7m % 0.6m % 0.4m cabinet
This cabinet accommodates 1 % MFU, 1 % Rectifier Sub-racks and 1 % BCU. There shall be 3U available for the mounting of additional equipment such as DC/DC converters. The cabinet should not be installed any battery.
ACTURA Flex 48330 Power System User Manual
12 Chapter 2 Installation
Chapter 2 Installation
2.1 Installation Preparation
2.1.1 Environmental Conditions
Make sure the following environmental conditions are satisfied when selecting the installation site:
Table 2-1 Environmental conditions in power room
Environmental conditions Recommended range
Ambient temperature
Humidity 90%RH, non-condensing Dust Sunlight No direct sunlight Corrosives No pollutants, such as salt, acid, and smoke, etc. Shake Insects, pests, and termites None Mildew None Moisture Water proof Fire protection No flammable on the top/bottom of the cabient.
The DC Power system will be damaged if dust or sand accumulates in it. The following measures are recommended for dusty environment:
-5~50°C (If ambient temperature > 45°C, for the cabinet with 400mm depth, it should demount the front door of cabinet to ensure the normal operation of the system.)
3
1mg/m
1.5m/s
2
1.The system should be installed in an airtight and air-conditioned power room. The air-conditioner filter should be well serviced without being obstructed. To reduce the dust in the power room, un-attendance in the power room is recommended.
2.The air filter should be cleaned periodically.
3.The product should be installed on a cement ground.
2.1.2 Power Supply
AC power supply for communication uses AC mains as its main power source. Backup batteries and generator should be configured according to the actual power supply situation. The AC power supply system composed of AC mains and generator should adopt centralized power supply mode to supply power, while low
ACTURA Flex 48330 Power System User Manual
voltage AC power supply system should adopt three-phase five-line or single-phase three-line modes.
The AC power cable should adopt copper core cable, and the cable section should suit the load. It is recommended that the power cable outside the power room be buried directly under the ground or by means of cable pipe. Power cable should be wired separately from signal line.
The AC mains voltage shall be within the range of the voltage input range of rectifiers.
The DC power system has a circuit breaker that can cut the AC mains power to it.
2.1.3 Site Survey
The power room must be surveyed prior to installation, which should be focused on:
1. Checking the wiring device, including cable chute, wiring rack, floor, wiring holes.
Chapter 2 Installation 13
2. Checking the environmental conditions, including temperature, humidity, dust.
3. Checking the conditions for implementing the installation, including power supply and lighting.
2.1.4 Tools & Material
1. Tools required for power equipment installation include electric drill, wire cutter, wire presser, various wrenches, screwdriver, electrician knife, and steel saw. The tools must be insulated and antistatic handled before they are used.
2. Power cables for electrical connection include AC cables, DC load cables, battery cables, earth cables, earth bar and lighting connection cables. Their design specifications should be in accordance with relevant specifications in the electrical industry and the materials should be purchased according to the design material list.
AC cables: this system uses 3-phase or single-phase AC power. Copper-core flame-retardant PVC insulated cable and PVC sleeve soft cable, such as NH-BVR, are recommended for the AC cables, whose sectional area should suit the load. When the wiring distance is less than 30 meters, take 2.5A/mm current density to calculate the sectional area of the AC cables.
2
of economical
The sectional area of the DC load cables and battery cables should be calculated using the following formula:
A=ΣI×L/KU
ACTURA Flex 48330 Power System User Manual
14 Chapter 2 Installation
In this formula: A is the sectional area of the lead (mm2), ΣI is the total current (A) flowing through the lead, L is the length (m) of the lead loop, U is the permitted voltage drop on the lead, while K is the conductivity. Kcopper=57. For safety, the
voltage drop on the cables connecting battery and load cannot exceed 3.2V. The sectional area of the lightning protection earth cable should not be less than
2
6mm
, and that of the DC operation earth cable, usually between 35-50mm2, is determined by user. Take the greatest sectional area among the above 3 earth cables as that of the cable connecting the user earth bar.
3. Purchase materials according to the materials list and inspect the materials, for example, check the heat durability, moisture resistance, flame resistance, and voltage resistance of the cable.
4. The auxiliary materials for power supply installation include expansive bolts, binding strips, and insulating tape.
2.1.5 Unpacking
To ensure smooth installation, the power equipment must be carefully inspected when it is unpacked.
The equipment unpacking and inspection are allowed only after it arrives the installation site. The inspection is co-accomplished by the user representative and representative from Emerson Network Power Co., Ltd.
When inspecting the equipment, first open the packing case with packing list put in it, take out the packing list, and conduct inspection against the packing label, including the customer name, customer address, machine No., total amount, case No., contract No., etc.
Unpacking and inspection: after opening the packing case, check the goods one by one according to the goods list on the packing label. The checking should include:
1. The number and serial number marked on the packing cases according to the actual number of the packing cases.
2. The correctness of the equipment packing according to the packing list.
3. The number and model of the accessories according to the accessory list.
4. The completeness of the equipment set according to the system configuration.
5. The condition of the goods through visual inspection. For example, check if the cabinet is damaged, if the cabinet has regained moisture; shake gently the rectifiers and monitoring module to see if the parts and connections have been loosened during delivery.
ACTURA Flex 48330 Power System User Manual
2.2 Installation Procedures
2.2.1 Cabinet Installation
Installation on the floor
Step 1: mark the position where the power system is to be installed. Determine the installation position of the power supply cabinet in the power room
according to the installation chart. Based on the mechanical specifications (see Fig. 2-1) of the installation holes of the power supply cabinet, determine the accurate position of the center points of the installation holes on the floor, and mark them with a pencil or oil pen.
Chapter 2 Installation 15
(Applicable to the cabinet with 600mm depth)
(Applicable to the cabinet with 600mm depth)
Figure 2-1 Installation dimensions of the cabinet base
Step 2: drill reserve holes. The expansive pipes delivered with the power system are M10%55mm, therefore,
use electric drill with drill bit Φ12 and depth 70mm to drill holes at the center points of the installation holes marked on the ground. To avoid being off-center, be careful
ACTURA Flex 48330 Power System User Manual
16 Chapter 2 Installation
not to shake the drill, and try to keep as vertical as possible to the ground, as shown in Figure 2-2.
Step 3: install expansive pipes. Clean the dust, and insert the expansive pipe into the reserve hole, knock it down
gently using a hammer until the top of the expansive pipe is level with the ground, as shown in Figure 2-2.
Power cabinet
1) Drill vertically
Expansive pipe
2) Clean the dust 4) Tighten the bolt
3) Knock it into place
Figure 2-2 Installing expansive pipe
Step 4: place cabinet in position Move the cabinet to the installation position aligning the installation holes of the
cabinet to the expansive pipe on the ground. Step 5: fix the cabinet After the cabinet is in position, make some horizontal and vertical adjustments.
Insert some iron pieces under the lower edge and corner of the cabinet to adjust the vertical obliquity of the cabinet within 5 degrees. Finally, screw down the tap bolt with plain washer and spring washer into the expansive pipe, and tighten it with wrench. The cabinet fixation is illustrated in Figure 2-3.
Tap bolt
Spring washer
Cabinet base Ground
Expansive pipe
Figure 2-3 Fixing cabinet with Tap
ACTURA Flex 48330 Power System User Manual
Plain washer
2.3 External Electrical Connection Interface
2.3.1 Connection Of Input Cables
The AC input terminals, SPD, rectifier AC input switch, PE bus and PE terminals are illustrated in Figure 1-6. SPD is just adjacent to the AC input terminals and has been connected in before delivery. PE bus is at the top of the MFU and is connected to the DC Power Cabinet through screws. PE bus is connected PE terminal through a cable.
Connection requirements
The AC mains is connected to the AC input terminals directly. There are 6 AC input modes as shown in Table 2-2:
Table 2-2 AC input modes
Item Function unit Amount
3P+N/380V AC input 1P+N /220V AC input
AC distribution
L1+L2/220V AC input 3P/220V AC input Terminals only - for individual rectifier AC feeds 2P MCB only - for individual rectifier AC feeds
Chapter 2 Installation 17
Connection method
Strip the insulation layer of one end of the AC input cable, and then mounted the cable end with an H terminal.
The cable mounted with an H terminal is shown in Figure 2-4.
H Terminal
AC Input Cable
Figure 2-4 Cable mounted with H terminal
After attaching the H terminal to the AC input cable, connect the AC input cable to the AC input terminals as shown in Figure 2-5:
ACTURA Flex 48330 Power System User Manual
18 Chapter 2 Installation
A
A
A
C input terminals
Figure 2-5 Connection of input terminals
The AC input cable is fed to the system through the top cover of the cabinet, as shown in Figure 2-6:
C input cable
Cable bracket
Top cover
Figure 2-6 Top cover
There is a cable bracket on the top cover. The input cables are bound to the cable bracket with a cable tie.
Different cable connection modes
There are 4 AC input terminals. For 3-phase AC power input, just connect the AC input cables as shown in Figure 2-7:
L1 L2 L3 N
C input terminals
Figure 2-7 Connection of 3-phase AC power input
ACTURA Flex 48330 Power System User Manual
Chapter 2 Installation 19
For single-phase AC power input, connect the AC input cables as in Figure 2-8:
L
N
AC Input Terminals
Figure 2-8 Connection of single-phase AC power input
If the AC input is single phase, the second and fourth terminals are not connected. For dual-phase AC power input, connect the AC input cables as in Figure 2-9:
L1
L2
AC Input Terminals
Figure 2-9 Connection of dual-phase AC power input
If the AC input is dual-phase, the second and fourth terminals are not connected. The yellow, green, red, and light blue AC cables correspond respectively to the AC
phase L1, L2, L3 and neutral lines. If the cables are the same color, they should be identified with labels.
The AC cables should be laid separately from the DC cables. No splice, damage, or scratch on the cables is permitted. The rectifier AC input cables have already been connected in factory.
Note
1.To insure AC input cable has enough bearing current capability, the section area of the AC input cable for 3-phase AC power input should not be less than 10mm AC power input and dual-phase AC power, it should not be less than 25mm area of input earth line should not be less than 35mm
2
.
2. The external AC input MCB of cabinet must be sure to disconnect all the AC input lines (including live lines, zero line), but input earth line can not be disconnected by any breaking device. It is recommended that the rated current of the AC input MCB is not less than 125A.
2
; and for single-phase
2
. The section
ACTURA Flex 48330 Power System User Manual
Loading...
+ 67 hidden pages