Emerson 47D40-801 Installation Manual

47D40-801
WARNING
!
Demand Defrost Control
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
The 47D40-801 control is a microprocessor-based demand defrost controller intended for Rheem heat pump systems. This controller uses basic differential temperature means to detect degradation of system performance due to ice build-up on the outdoor coil. The controller uses “self-calibrating” prin­ciples to calibrate to the heat pump system. The defrosting is performed by reversing the refrigerant direction of flow.
The 47D40-801 is meant to replace the following controllers in Rheem heat pump systems:
47-21517-16 47-21517-17 47-21517-18 47-21517-23 47-21517-24 47-21517-11 47-21517-14 47-21517-13
47-21517-82 47-21517-88 47-102685-01 47-102685-03 47-102684-01 47-102684-03 47-102684-83
DDL-013102-1RH DDL-017002-2RH DDL-017102-1RH DDL-017702-1RH DDL-117702-3RH DDL-013002-0RH DDL-013002-1RH
47D40-801
PRECAUTIONS
CAUTION
• This control is intended only for Rheem heat pump systems.
• Replace 47D40-801 control as a unit - no user service­able parts.
If in doubt about whether your wiring is millivolt, line or low voltage, have it inspected by a qualified heating and air conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
CONTENTS
Description ................................................................ 1
Precautions .............................................................. 1
Specifications ........................................................... 2
Operation .................................................................. 2
Installation ................................................................ 3
• To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
• This control is not intended for use in locations where it may come in direct contact with water. Suitable protections must be provided to shield the control from exposure to water (dripping, spraying, rain, etc.)
• Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper or loss of heat pump operation and/or shock hazard.
• Following installation or replacement, follow appliance manufacturer’s recommended installation/service
instructions to insure proper operation.
• Do not use on circuits exceeding specied voltage. Higher voltage will damage control and could cause shock or re hazard.
!
white-rodgers.com
emersonclimate.com
PART NO. 37-7200B
Replaces 37-7200A
1536
SPECIFICATIONS
Electrical Ratings [@ 77o F (25o C)]:
Rated Voltage ..................................... 24 VAC
Rated Voltage Range ............................... 18-30 VAC
Max. Power Consumption @ 24 VAC .................. 4.08 VA
Nominal Frequency................................. 50/60 Hz
Relay Load Ratings:
Compressor Contactor Relay ...................... 20 VA in rush, 6 VA holding
Fan Relay ...................................... 1/2 HP @ 240, 1/4 HP @ 120 VAC
Reversing Valve Relay (RV) ........................ 24 VA
Auxiliary Heat Relay (D)........................... 1 Amp. 0.6 P.F.
Operating Temperature Range ........................ -40o to 150o F (-40o to 65o C)
Humidity Range ................................... 5% to 95% relative humidity
(non-condensing)
Timing Specications @ 60Hz*
Nom Units
Defrost Lockout Time 34 Mins. Maximum Defrost Time 14 Mins. Transient Delay 2 Mins. Maximum Frosting Time 6 Hrs. Short Cycle Lockout Time 5 Mins. Noise Abatement Time 5 Sec.
*50Hz Timings are 20% longer.
The control is recognized by UL as an incorporated electronics control per UL 60730-1A. This control does not perform any safety/protective functions. This device is automatic, type 1 action, incorporated control.
OPERATION
Each controller has 24 VAC input and B, Y, and D terminals for connection to a standard thermostat. The controller has pins for connection of two temperature sensors to measure ambient and coil temperature. Controlled outputs are outdoor fan, reversing valve, and compressor contactor.
The controller has a LED to indicate system operation status.
Option Switch
Switch labeled SW1 is used to select the defrost mode termination temperature of outdoor coil. Defrost mode is terminated when the coil temperature exceeds the selected termination temperature. Temperature options for SW1 switch settings are:
B A
On Off 50o F
B A
Off On 60o F
B A
On On 70o F (default)
B A
Off Off 80o F
B A
Test Pins
The connector labeled TEST can be used to change operation mode in the field. Momentarily short the test pins to force the system into the defrost mode. Momentarily short the test pins again to terminate the defrost mode. To avoid unnecessary system mode transition, do not use the test pins frequently.
Short Cycle Protection
The control includes protection against short cycling the compressor. At power-up, and each time the Y input is interrupted, the control will enter a 5-minute short cycle lockout period. During this lockout, the control will not energize the compressor contactor, even if a call for heating or cooling is received on the Y input. The control will resume normal operation when the lockout period expires.
Noise Abatement
When the reversing valve is switched during an active call for heating or cooling, such as when entering or leaving a defrost cycle, the control will de-energize the compressor contactor for 5 seconds in order to reduce compressor noise.
Diagnostic Features
The control continuously monitors system operation. If a fault occurs, the red LED on the control will flash a diagnostic code, if more than one fault occurs, only the code with the higher priority will flash. The flash time is to be 0.5 seconds on and 0.5 seconds off followed by 2 seconds off. The table shows the diagnostic codes:
LED Fault Indication Display Priority
ON Normal 0
1 Flash Defrost mode 1
2 Flashes Coil sensor fault 3
3 Flashes Ambient sensor fault 2
2
Loading...
+ 2 hidden pages