Read this User’s Manual before working with the 475 Field
Communicator. For personal and system safety, and for
optimum product performance, thoroughly understand the
contents before using or servicing this product.
USING THIS MANUALThe sections in this manual provide the following information on the
475 Field Communicator.
Section 2: Learning the basics contains information on assembly,
components, starting, entering standby, shutting down, settings,
supported PC applications, and maintaining the 475 Field
Communicator.
Section 3: HART functionality contains information on starting and
configuring the HART® Application, working offline, communicating
with HART devices, modifying device parameters, and running
diagnostics.
Section 4: Fieldbus functionality contains information on starting
and configuring the Fieldbus Application, communicating with fieldbus
devices, modifying device parameters, and running diagnostics.
Section 5: Troubleshooting provides solutions to the most common
475 Field Communicator operating problems.
Appendix A: Reference data provides physical, functional, and
performance specifications.
Appendix B: Product certifications contains hazardous location
and international certifications, European directive information, and
approval drawings.
Appendix C: Graphics information contains an overview of the
Graphics functionality and options in the 475 Field Communicator.
www.fieldcommunicator.com
Page 8
8
Introduction
Page 9
475 FIELD COMMUNICATOR
IMPORTANT NOTICE
SECTION 2LEARNINGTHEBASICS
OVERVIEWThis section provides instructions on basic features and functions of
the 475 Field Communicator. It also provides information on assembly,
components, starting, entering standby, shutting down, settings,
applications, and maintaining the 475 Field Communicator. The
functionality described in this section is based on system software
version 3.9.
SAFETY MESSAGESProcedures and instructions in this section may require special
precautions to ensure the safety of the personnel performing the
operation. Information that raises potential safety issues is indicated by
a warning symbol (
performing an operation preceded by this symbo
“Troubleshooting” section for more warning messages.
This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in
accordance with the user’s manual, may cause harmful
interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own
expense.
This device complies with Part 15 of the FCC Rules. Operation is
ject to the following two conditions: (1) this device may not
sub
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
Any modifications made to this device
Emerson Process Management may void the authority granted to
the user by the FCC to operate this equipment.
). Refer to the safety messages before
l. See the
that are not approved by
www.fieldcommunicator.com
This Class A digital apparatus complies with Canadian ICES-003.
Page 10
10
WARNING
Learning the basics
You can install or remove the Lithium Ion (Li-Ion) battery (Power
Module) in a hazardous area environment.You cannot charge the
battery in this environment because the power supply/charger
(00375-0003-0005) is not IS-approved.
475 FIELD
COMMUNICATOR
OVERVIEW
The 475 Field Communicator supports HART and FOUNDATION fieldbus
devices, letting you configure, maintain, or troubleshoot devices. When
using the 475 Field Communicator to communicate with devices,
follow all standards and procedures applicable to the location. Failure
to comply may result in equipment damage and/or personal injury. Be
sure to understand and comply with the sections in this manual.
The 475 Field Communicator includes a color LCD touch screen, a
Li-Ion batte
ry (Power Module), a SH3 processor, memory components,
System Card, and integral communication and measurement circuitry.
The Field Communicator also supports multiple languages. See the
rea
dme file included with the Field Communicator Easy Upgrade Utility
or www.fieldcommunicator.com for more information.
Device interoperability The 475 Field Communicator is designed to operate with a wide range
of HART and F
manufacturer. Device interoperability is achieved through the
Electronic Device Description Language (EDDL) technology supported
by the HART Communication Foundation and Fieldbus Foundation.
Basic testing is performed on all de
manufacturer is asked to certify that they thoroughly tested their
devices with the 475 Field Communicator. If certification is not
received, a warning message displays when you attempt to
communicate with an untested device. New device descriptions are
available from the Field Communicator Easy Upgrade Utility or the
Resource CD or DVD.
OUNDATION fieldbus devices independent of device
vice descriptions. Each device
Page 11
Learning the basics
11
Working in a hazardous
area
Battery and
power supply/charger
A 475 Field Communicator that meets the Intrinsic Safety requirements
(I/S-approved) can be used in Zone 0 (FM), Zone 1, or Zone 2, for
Group IIC, and Class I, Division 1 and Division 2, Groups A, B, C, and
D locations.
An IS-approved 475 Field Communicator may be connected to loops
or segment
Zone 2, for Group IIC; Zone 20, Zone 21, Zone 22, and Class I,
Division 1 and Division 2, Groups A, B, C, and D locations.
IS-approved 475 Field Communicators are ordered with the KL option
have an additional label on the back of the 475 that lists the
and
approvals.
See Appendix B “Product certifications” for more information about IS
approvals and installations.
CAUTION
You can install or remove the Li-Ion battery in a hazardous area
environment. You cannot charge the battery in this environment
because the power supply/charger is not IS-approved.
The 475 Field Communicator is powered by a Li-Ion battery that has a
green, 6-pin connector. The power supply/charger also has a green
connector to match the appropriate connector on the battery. See
Figure 2-1 for the location of the connector.
Prior to using the 475 Field Communicato
supply/charger connected, fully charge the battery.
s that are attached to equipment located in Zone 0, Zone 1,
r without the power
Guidelines and precautions
Understand and follow the guidelines and precautions below before
the battery or power supply/charger.
using
• When transporting a Li-Ion battery, follow all applicable regulations.
• Protect the battery and power supply/charger from moisture, and
respect opera
“Reference data” for more information.
• Do not cover the battery or power supply/charger, subject it to
prolonge
heat-sensitive materials.
• Charge the battery with only the Field Communicator power
supply/ch
other products. Failure to comply may permanently damage your
475 Field Communicator and will void the IS approval and the
warranty.
• Do not open or modify the battery or power supply/charge
are no user-serviceable components or safety elements inside.
Opening or modifying them will void the warranty and could cause
personal harm.
ting and storage temperature limits. See Appendix A
d periods of direct sunlight, or place it upon or next to
arger. The power supply/charger should not be used with
r. There
Page 12
12
Charge Indicator button
Lights illuminated by pressing the Charge
Indicator button
Li-Ion
battery
Green power supply/charger connector (side)
Learning the basics
Checking the remaining charge
To view the remaining charge, press the Charge Indicator button on
the
lower left side of the battery. See Figure 2-1 for the location of this
button. When you press and release the button, the lights above the
but
ton slowly illuminate to display the charge remaining. Each light
represents 20 percent of the charge. The battery is fully charged when
all of the lights are illuminated.
You can also check the remaining charge fr
om the Settings menu on
the Field Communicator Main Menu. See “Power” on page 25 for more
information.
Figure 2-1. Li-Ion battery example
Charging the battery
Prior to first portable use, fully charge the battery. The battery can be
charged
separately or while attached to the 475 Field Communicator.
The 475 Field Communicator is fully operable while the battery is
recharging, and a full charge takes 2-3 hours. An overcharge condition
will not occur if the power supply/charger remains connected.
CAUTION
You can remove and install the Li-Ion battery in a hazardous area
environment. You cannot charge the battery in this environment
because the power supply/charger is not IS-approved.
Page 13
Learning the basics
Power supply/charger
connector
Power supply/charger
Power supply/charger lights
To charge the battery:
1.Plug the power supply/charger into a power outlet.
2.Plug the green power supply/charger connector into the green
connector on
the battery. The flat side of the power supply/charger
connector should face the front of the 475 or the inside of the battery,
if the battery is not attached to the 475. The battery is fully charged
when the light on the power supply/charger is green.
Figure 2-2. Charging the battery connected to the 475 Field
Communicato
r
13
Page 14
14
Learning the basics
Power supply/charger lights
Three lights are on the power supply/charger to indicate the conditions
below. Each light displays a different color.
Table 2-1. Power supply/charger lights
Color Condition
GreenThe battery is fully charged.
Flashing green The battery is nearly fully charged.
YellowThe battery is charging.
Flashing yellowThe power supply/charger is not connected to
the 475 Field Communicator.
Flashing yellow and
The remaining charge in the battery is very low.
red
RedCharging cannot occur. Contact Technical
Support for more information.
Maintaining the battery
To help maintain the performance and life of the Li-Ion battery,
understand and follow the guidelines below:
• Recharge the battery frequently, preferably after each use or at
night. Limit the number of full discharges, if possible.
• Frequent use at high temperatures can reduce performance.
• Use a dry location at or near room temperature when storing the
battery for an extended time. Prolonged storage at higher
temperatures can reduce performance.
• Ensure the remaining charge level is at or near mid-capacity when
storing for an extended time. The remaining charge will slowly drain
during storage. Periodically charge the battery to ensure the
remaining charge does not drain to low levels.
Page 15
Learning the basics
IrDA® interface
(top)
Tab key
Navigation keys
(four arrow keys)
HART and F
OUNDATION fieldbus
communication terminals (top)
Enter key
Function key and
light (for multiple-key
combination
functionality)
Alphanumeric
keypad
Backlight key
Green power
supply/charger
connector on the
battery
(side)
Li-Ion battery (back) and
System Card (internal)
Stylus (in the strap)
Bluetooth®
light
Strap attachment
(side)
Strap attachment (side)
Strap attachment (side)
Touch screen display
Strap attachment
(side)
Power key and light
Charge Indicator button
(side)
Lights illuminated by
pressing the
Charge Indicator button
(side)
15
Figure 2-3. 475 Field Communicator shown with optional rubber boot
Page 16
16
Learning the basics
Using the touch screenThe touch screen and keypad let you select menu items and enter text.
Use the provided stylus or the up and down arrow keys on the keypad
to select a menu item. On the Settings and Field Communicator Main
Menu, tap an icon or press Enter to open the selected icon. On other
menus, double-tap the selected item on the screen or press the right
arrow key on the keypad to open a menu item.
CAUTION
Contact the touch screen with blunt items only, preferably the stylus
included with the 475 Field Communicator. See Figure 2-3 on page 15
for the location of the stylus. Sharp instruments, such as screwdrivers,
can damage
replacement of the entire display assembly, which is possible only at
an authorized service center.
Use the back arrow icon () on the window to return to the previous
menu. Use the close icon (
to end the application.
If the touch screen seems inaccurate, you can recalibrate it. For more
formation, see “Touch Screen” on page 26.
in
the touch screen. Repairing the touch screen requires
) in the upper right corner of the window
NOTE
All instructions in this manual are written for the touch screen.
Use the soft input panel (SIP) keyboard
The SIP keyboard allows for alphanumeric input using the touch
screen
. The SIP keyboard detects when you need to enter characters
and appears automatically as required.
Using the keypadThe following section describes the buttons on the 475 Field
Communicator keypad.
Bluetooth symbol (
The Bluetooth symbol on the keypad is illuminated
Bluetooth is enabled from the Listen for PC window. The 475 Field
Communicator must be licensed for Bluetooth to use this functionality.
Power key
The Power key is used to power on and off the 475 Field
Communicato
r or to put it in standby. You can set the default option,
stand by or shut down, from the Settings menu. See “Power Button” on
page 26 for more information. The green light on the Power key
flashes when you press and hold the Power key to turn on the 475
Field Commun
icator. The light is constant when the 475 is on, and it
slowly blinks when the 475 is in standby.
)
by a blue light when
Page 17
Learning the basics
17
If the Power key is pressed when there is unsent data or a device
method is running, a warning message appears. Tap OK to have the
475 Field Communicator enter standby or shut down, or tap Cancel to
return to the previous window.
The Power key is disabled when the 475 Field Communicator is in
Listen for PC mode or when the ScratchPad application is open.
Arrow navigation keys
Four arrow navigation keys let you move through the menus and icons
in the applications. Press the up and down arrow keys to select a
menu item. On the Settings and Field Communicator Main Menu, tap
an icon or press the Enter key to open the selected menu. On all other
menus, use the right arrow key to open a menu item or the left arrow
key to return to the previous menu.
The blue text near the keys indicates alternate functionality that can be
enabled by pressing the Function key.
Enter key
The Enter key lets you open the selected (highlighted) button on a
window or an icon on the Field Communicator Main Menu or Settings
Menu. For example, if you push the Enter key when the Cancel button
on a window is selected, you will close that window.
Tab key
The Tab key lets you move between selectable controls on a window.
Pressing the Tab key selects the icons from left to right across all of the
rows on the screen.
Alphanumeric keypad
The alphanumeric keypad lets you enter letters, digits, and other
characters, such as punctuation marks. The 475 Field Communicator
automatically determines which text options are available depending
upon the input necessary for the particular field.
To enter text when in alphanumeric mode, press the desired keypad
button in quick repetition to scroll through the options to display the
appropriate letter or number. For example, to type the letter Z, press
the 9 key quickly four times.
The blue text near the keys indicates alternate functionality that can be
enabled by pressing the Function key. The alternate function on the
alphanumeric 5 key (insert) will be activated in future releases of the
475 Field Communicator software.
Page 18
18
Backlight key
The Backlight key lets you adjust the intensity of the touch screen
display. There are four different settings. The intensity impacts the
charge in the battery. Expect a shorter charge life for higher intensities.
See
the backlight after specified periods of inactivity. These timers can help
conserve the battery power.
Function (Fn) key
The Function key lets you enable alternate functionality on select keys.
The Function key does not apply for menus displaying icons.The blue
text near the other keys on the keypad indicate the alternate
functionality. When the Function key is enabled, the orange light in the
left corner of the Function key appears and the FN button on the Soft
Input Panel (SIP), if displayed, is highlighted. Press the Function key
again to disable the functionality and turn off the light.
MemoryTypes
The 475 Field Communicator memory consists of three components:
1.Internal Flash—32MB non-volatile RAM. The Internal Flash memory
stores the operating system and system software. It also stores the
following:
• Up to 25 HART configurations
• HART Event Captures
•FOUNDATION fieldbus statistics
• Text files saved from ScratchPad
2.System Card—an internal 1 GB or higher Secure Digital Card with
non-volatile flash memory. A copy of installable system software
exists on every System Card. The System Card also contains all
HART and F
up to 1,000 HART configurations, depending on the sizes of the files.
3.RAM—32MB used only for program execution.
Learning the basics
“Backlight” on page 24 for information on timers that can turn off
OUNDATION fieldbus device descriptions and can store
Available memory space
To view the available memory in your 475 Field Communicator,
connect to the Field Communicator Easy Upgrade Utility or tap the
Memory icon from the Settings menu. The Field Communicator Main
Menu displays the Settings menu item. See
“Memory” on page 27 for
more information.
Free memory on the System Card
Over time, your System Card may become full and unable to store new
files. To free memory on your System Card, use the Memory
Management feature in the Field Communicator Easy Upgrade Utility.
This lets you filter and select which device descriptions can be
transferred onto your System Card. Device descriptions from selected
manufacturers or protocols are omitted during an upgrade, allowing
more space for other files.
Page 19
Learning the basics
If the selected device descriptions are already on your 475, they are
removed the next time you connect the 475 Field Communicator to the
Easy Upgrade Utility. You are prompted before the files are removed.
See the Easy Upgrade Utility Help for more information.
Accessories Rubber boot
A rubber boot can be purchased to further protect your 475 Field
Communicato
for the straps, and holders for the stylus. An anti-static material is used
to meet the applicable Intrinsic Safety requirements.
19
r. The boot has an additional stand on the back, cut outs
Figure 2-4.
Back of the 475 Field Communicator Rubber Boot
Page 20
20
Learning the basics
Straps
Two straps are available with the 475 Field Communicator. The
magnetic stra
p attaches to the top of the 475 Field Communicator and
lets you hang it from a metal pipe. The strap attachment is located near
the HART and fieldbus terminals on the top of the 475 Field
Communicator.
The side strap lets you attach a strap to the sides or back of the 475
Communicator, making it easy to carry. See Figure 2-5. The side
Field
strap also holds the stylus used with the touch screen.
Figure 2-5. Side Strap Example
Page 21
Learning the basics
Li-Ion battery
System Card partially
inserted into the
System Card socket
Stand
Main unit label
IS label
(KL option)
Battery retaining screws
Connector pins
Strap attachment
Strap attachment
Bluetooth approval label
ASSEMBLY
21
Installing the System Card
and the battery
If you received a 475 Field Communicator with the System Card
already installed, proceed to the " Starting up" section.
1.Place the 475 Field Communicator face down on a level, secure
surfac
e.
2.Remove the protective rubber boot, if attached.
3.With the battery removed, slide the System Card (labeled System
Card),
with the metal card contacts facing up, into the System Card
socket until it clicks. The System Card socket is spring-loaded. See
Figure 2-6 for the location of the System Card socket.
The System Card is not locked into the System Card socket in the
image below
Figure 2-6.
.
Back of the 475 Field Communicator
CAUTION
The System Card must be supplied by the 475 Field Communicator
manufacturer. Failure to comply will void the IS approval.
4.With the 475 Field Communicator still face down, ensure the tops of
the two battery retaining screws are loose and slightly above the top
of the 475.
5.Align the sides of the battery with the 475 and carefully slide it
forward
until it is secure.
6.Carefully hand tighten the two battery retaining screws to secure the
tery. (Do not over tighten, 0.5Nm maximum torque load.)
bat
CAUTION
The connector pins may be damaged if the 475 Field Communicator
and battery are improperly aligned.
Page 22
22
Learning the basics
Removing the battery and
the System Card
STARTING UP AND
SHUTTING DOWN
To remove the battery and System Card:
1.Remove the rubber boot, if attached.
2.Place the 475 Field Communicator face down on a level, secure
surface.
3.Loosen the battery retaining screws until the top of each screw is
slightly above the top of the 475 Field Communicator.
4.Slide the battery off the 475 Field Communicator. Do not pull up the
battery because this could damage the connector pins.
5.Push the System Card into the System Card socket until it clicks to
release it. The System Card socket is spring-loaded.
6.Grasp the System Card with your fingers and slide it straight out of
the 475 Field Communicator.
Prior to using the 475 Field Communicator without the power
supply/charger, fully charge the battery. See
page 12 for more information.
Before operating the 475 Field Communicator, ensure:
• The 475 Field Communicator is not damaged.
• The battery is fully seated.
• All screws are sufficiently tightened.
• The communication terminal recess is free of dirt and debris.
“Charging the battery” on
Starting upPress and hold the Power key on the keypad until the green light on
Figure 2-3 on
The Field Communicator
Main Menu
that key flashes (approximately two seconds). See
page 15 for the location of the Power key.
During startup, the 475 Field Communicator automatically checks for
any system software upgrades available on the internal System Card.
You are notified if an upgrade is on the System Card and ready to be
installed. The Field Communicator Main Menu appears.
The Field Communicator Main Menu is the first menu that appears
after you start the 475 Field Communicator. This menu lets you run the
HART and the Fieldbus Applications, view the Settings menu,
communicate with a PC, and launch ScratchPad or ValveLink™
Mobile. See Section 3 “HART Functionality” and Section 4 “Fieldbus
Functionality” for more information on these applications.
Page 23
Learning the basics
Figure 2-7. Field Communicator Main Menu
23
Entering standbyYou can put the 475 Field Communicator into standby to save power or
to reduce the boot-up time if you are using the 475 Field
Communicator intermittently. Standby turns off the touch screen and
areas within the 475 Field Communicator.
You can put the 475 Field Communicator in standby when the HART
Applica
online with a device when standby is entered, the application main
menu is displayed when the 475 Field Communicator returns from
standby. Otherwise, the 475 Field Communicator displays the last
open window.
To enter standby, press the Power key. From the Power Switch dialog
box, t
close the dialog box and return to the application. You can set the
default option on the Power Switch dialog box. See “Power Button” on
page 26 for more information.The green light on the Power key slowly
flashes when the 475 Field Communicator is in standby. To leave
st
The 475 Field Communicator also enters standby if the standby timer
has expired
tion or the Fieldbus Application is running. If you are working
ap Stand by and tap OK or press the Enter key. Tap Cancel to
andby, press the Power key.
. See “Power” on page 25 for more information.
Shutting down To shut down the 475 Field Communicator, press the Power key. From
the Power Switch dialog box, tap Shut down and tap OK or press the
Enter key. Tap Cancel to close the dialog box and return to the
application. You can set the default option on the Power Switch dialog
box. See “Power Button” on page 26 for more information.
The 475 Field Communicator shuts down if the auto-off timer has
expired
You can also shut down the
simultaneously pressing the Backlight key and the Function key until
the display turns off. The shut down is accomplished in the hardware
(similar to removing the power to a PC using a switch). This is not the
recommended way of shutting off the 475 Field Communicator. Use
this method to shut down and reset the 475 Field Communicator if the
screen appears to lock up and does not respond when you use the
touch screen or keypad.
. See “Power” on page 25 for more information.
475 Field Communicator by
Page 24
24
Learning the basics
SETTINGS You can view and modify the options below for the 475 Field
Communicator from the Settings option on the Field Communicator
Main Menu.
To return to the Field Communicator Main Menu, tap the Back bu
on the screen. Tap the MORE button to view additional items on the
Settings menu.
The About setting lets you view the software revisions in your 475 Field
About
Communicator. If you need to call Technical Support personnel, have
the system software version, Communication and Diagnostic Circuitry
(CDC) version, and the operating system version available.
Tapping RE-IM
and applications on your 475 Field Communicator. The power
supply/charger must be connected when the RE-IMAGE operation is
performed. During the operation, the standby and auto-off timers are
disabled. This operation should only be performed under the direction
of Technical Support personnel.
Tapping RE-FLASH re
System Card. The power supply/charger must be connected when the
RE-FLASH operation is performed. During the operation, the standby
and auto-off timers are disabled. This operation should only be
performed under the direction of Technical Support personnel.
Tap OK t
AGE re-installs the operating system, system software,
-installs the firmware and software from the
o return to the Settings menu.
tton
Backlight
Clock
The Backlight setting lets you adjust the backlight intensity of the
screen. To adjust the backlight, drag the slider left to right.
The Backlight setting also lets you set timers to automatically turn off
backlight after a specified period of inactivity to save battery power.
the
To enable a timer, tap a drop-down list and select the appropriate time
interval. The external power timer applies when the power
supply/charger is connected to the 475 Field Communicator
After you select the appropriate backlight settings, tap OK to
setting for this session only, SET DEFAULT to retain this setting upon
startup, or CANCEL to exit without changes.
The Clock setting lets you set the date, time, and time zone on the 475
Field Communicator. Configure the date by using the drop-down list.
To configure the time, select the appropriate time field and use the
arrows to scroll through values until you find the correct time. Select
the drop-down list to select a time zone. Tap OK to save the changes
and to close the window, or CANCEL to exit without changes.
retain this
Page 25
Learning the basics
25
Contrast
Licenses
The Contrast setting lets you adjust the lightest and darkest areas on
the window. This option applies to only the 375 Field Communicator.
NOTE
Temperature can affect contrast.
The Licenses setting lets you view the enabled and available licenses
for the 475 Field Communicator. A checkmark indicates the license is
enabled. Unlicensed features cannot be accessed. The following
licenses and information are displayed:
• HART - enables your 475 to run the HART Application to
communicate with HAR
T devices.
• Graphics - enables your 475 Field Communicator to display device
formation as images, charts, and graphs.
in
• Easy Upgra
de - enables you to upgrade your 475 Field
Communicator with the latest system software and device
descriptions at your site, without having to send it to a service center.
• Exp Date - displays the expiration date of the Easy Upgra
de license.
The date is listed as year-month-day. N/A appears if the 475 is not
licensed for Easy Upgrade.
• Bluetooth - enables your 475 Field Communicator to communicate
with
supported PC applications, such as the Easy Upgrade Utility,
using Bluetooth.
•F
OUNDATION fieldbus - enables the 475 Field Communicator to run
the Fieldbus Application to communicate with fieldbus devices.
• Device Config Management - enables you to save HART device or
user co
nfigurations to the System Card and to print and store them
using the Easy Upgrade Utility.
The License window also displays the Unit Name and System Card
Serial Number (SN) of th
e 475 Field Communicator. See the Easy
Upgrade Utility Help for more details on assigning a Unit Name. Tap
OK to return to the Settings menu.
Power
The Power setting lets you specify power management options when
the 475 Field Communicator is on battery power. The standby timer
puts the 475 Field Communicator in standby and the auto-off timer
shuts down the 475 Field Communicator after the specified values of
inactivity. To specify values for the standby or auto-off timer, select the
time intervals from the drop-down lists. If set to short intervals, these
timers will save battery power.
The Maximize Power Savings option conserves additional battery
power
by letting the 475 Field Communicator enter standby or shut
down when communicating with a device. To enable Maximize Power
Savings, tap the checkbox. If this option is disabled, the 475 Field
Communicator will not enter standby or shut down when
communicating with a device.
Page 26
26
Power Button
Retrain Battery
Learning the basics
After you select the appropriate power management settings, tap OK
to apply the settings for this session only, SET DEFAULT to retain the
settings upon startup, or CANCEL to exit without changes.
The Power Button setting lets you set the default option for the Power
Switch dialog. The Power Switch dialog appears when you press the
Power key. This option does not let the Field Communicator
automatically shut down or enter stand by when you press the Power
key. You still need to tap OK.
From the Power Button screen, select the S
option and then tap OK to apply the settings for this session only, SET DEFAULT to retain the settings upon startup, or CANCEL to exit
without changes.
The Retrain Battery setting lets you fully discharge the battery so it can
be charged to its full capacity. Perform this operation if you notice a
significant decrease in charge life or performance.
CAUTION
It should not be necessary to perform this operation on a regular basis.
Doing so may damage the Li-Ion battery.
tand by or Shut down
Touch Screen
Ensure the power supply/charger is not connected when this operation
is performed. During the operation, the backlight is set to its brightest
setting to quickly discharge the battery. The backlight, standby, and
auto-off timers are disabled. If you tap CANCEL, the battery stops
discharging and the backlight, standby, and auto-off timers are
re-enabled. The backlight setting is also restored.
After the battery is fully discharged, ma
before using it without the power supply/charger. You can use the 475
Field Communicator while the battery is recharging.
To retrain the battery:
1.Disconnect the power supply/charger, if it is connected to the 475
Field Commun
2.Tap Retrain Battery
3.Wait until the 475 Field Communicator shuts down. It may take up to
severa
remaining when the operation began.
Connect the power supply/charger to the
fully charge the battery.
The Touch Screen setting lets you calibrate the touch screen with the
display. Tap the center of the cross hairs firmly and accurately at each
location on the window. The target continues to move until the touch
screen is aligned. Touch screen alignment is retained upon start up.
l hours to discharge the battery, depending on the charge
icator.
from the Settings menu.
ke sure it is fully recharged
475 Field Communicator and
Page 27
Learning the basics
Event Capture
27
The Event Capture setting lets you create an Event Capture file (.rec),
which is a log of communication, input, and output that occurs between
the 475 Field Communicator and a device (HART only). When working
with Technical Support personnel, you may be asked to create an
Event Capture file to help troubleshoot issues that cannot be easily
isolated or resolved. The Event Capture file can then be transferred to
your PC using the Field Communicator Easy Upgrade Utility and sent
to Technical Support personnel for review.
Tap the option to activate the Event Capture feature. The option is
black when selected.
To delete an existing Event Capture, tap
DELETE EVENT FILE.
NOTE
While Event Capture is enabled, device status and warning messages
do not appear.
To create and send an Event Capture file:
1.Tap Settings from the Field Commu
2.Tap MORE and t
3.Tap T
urn on HART event capture from the Event Capture window
hen tap Event Capture.
nicator Main Menu.
and tap OK.
4.Tap HAR
5.Enter a file name for the Event Capture file and tap OK. The
T from the Field Communicator Main Menu.
file is
saved to a default location.
6.Perform the requested operations to capture the data.
7.Use the Field Communicator Easy Upg
rade Utility to transfer the file
from your 475 Field Communicator to your PC. See the Easy Upgrade Utility Help for more information.
Memory
The Memory setting lets you view available free space in the System
Card, Internal Flash, or RAM. To select the Memory icon, tap MORE
on the Settings screen. If you have less than 10 percent of memory
free, the value is highlighted yellow.
Page 28
28
Learning the basics
CONNECTING TO A
DEVICE
Use the provided lead set and the HART or Fieldbus (if licensed)
Applications to connect and communicate with a device. The
appropriate device description is also required. If the 475 Field
Communicator does not have the HART device description, the device
can be displayed in forward compatibility mode. This mode uses a
generic device description and does not display all device functionality.
Three terminals for the lead set are on the top of the 475 Field
Communicator. Each red terminal is a positive connection for its
protocol, while the black terminal is a common terminal shared by both
protocols. An access door ensures only one pair of terminals is
exposed at any one time. Several markings indicate which pair of
terminals is for which protocol.
See "Section 3 HART functionality" and "Section 4 Fieldbus
functionality" for wiring diagrams and more information. Appendix B
displays diagrams for Intrinsically Safe installations.
PC APPLICATIONSConnect your 475 Field Communicator to a supported PC application,
such as AMS
Communicator Easy Upgrade Utility, to download new system
software, device descriptions, and licenses. You can also transfer
HART configuration files, Event Capture files, and ScratchPad (.txt)
files to a PC.
Suite: Intelligent Device Manager or the Field
AMS Device ManagerThe 475 Field Communicator can connect to AMS Device Manager
(version 6.2 or higher), letting you create, open, edit, or compare
HART device or user configuration files. You may need to connect
using IrDA if Bluetooth is not supported in your version. You can also
transfer configurations between AMS Device Manager and a storage
location in the 475 Field Communicator. Check the AMS Device
Manager Books Online for more information.
Field Communicator Easy
Upgrade Utility
The 475 Field Communicator can connect to the Field Communicator
Easy Upgrade Utility that is available on the Resource CD or DVD. See
the readme file for installation and system requirements. You can
access this file from www.fieldcommunicator.com or the Resource CD
or DVD.
Page 29
Learning the basics
29
The Easy Upgrade Utility lets you do the following:
• Download new system software and device descriptions to upgrade
your 475 Field Communicator at your site.
• Enable new functionality and applications by purchasing and
downloading new application licenses using the Online Licensing
feature.
• Upload Event Capture and ScratchPad files to your PC.
• Upload, download, and print HART device or user configurations
(.hcf files). Uploading configurations to the Easy Upgrade Utility lets
you back up these files.
• Manage the memory in your System Card by specifying which
device descriptions can be downloaded to your System Card.
Limiting the number of device descriptions will free memory on your
System Card.
• Assign a Unit Name to a 475 Field Communicator to uniquely identify
it, which is useful when connecting to a 475 Field Communicator
using Bluetooth.
See the Easy Upgrade Utility Help for more information on these
features.
Connecting the 475 Field
Communicator or System
Card
You can use three connection types to connect a 475 Field
Communicator to the Easy Upgrade Utility: IrDA, Bluetooth (if
licensed), or a supported card reader. The 475 Field Communicator
must be in Listen for PC mode to communicate through IrDA or
Bluetooth. See the AMS Device Manager Books Online for information
on supported connection types.
Certain connection types are required to transfer files or information
between the Field Communicator Easy Upgrade Utility and a 475 Field
Communicator. See
Table 2-2.
Page 30
30
Learning the basics
Table 2-2. Required connection types to transfer files using the Easy Upgrade Utility
File to TransferRequired Connection Type
Device Descriptions*IrDA, Bluetooth, or a Card Reader
Event Capture FilesIrDA or Bluetooth
HART Device or User
IrDA, Bluetooth, or a Card Reader
Configuration Files
LicensesIrDA or Bluetooth
ScratchPad (.txt) FilesIrDA or Bluetooth
System Software*IrDA, Bluetooth, or a Card Reader
Unit NameIrDA or Bluetooth
*Some upgrades may require a card reader.
Listen for PC
The Listen for PC option lets you select IrDA or Bluetooth as the
connection
type to communicate with a PC. To enter Listen for PC
mode, tap the Listen for PC icon from the Field Communicator Main
Menu. IrDA is initially set as the default connection type and is
automatically enabled when you open Listen for PC.
You can change the connection type at an
y time by tapping the
Change Connection Type button and then selectingan option. Tap
OK to use the selected connection type for only the current session.
The default connection type is used the next time you open Listen for
PC. Tap Save as Default to always use the selected connection type
when Listen for PC is opened.
After you select the connection type, the 475 Field Communicator
s for a connection from the PC. When the 475 is connected, a
wait
message appears and the PC name is listed in the Connected PC field
on the Listen for PC window.
NOTE
The Power key, standby timer, and auto-off timer are disabled when
the 475 Field Communicator is in Listen for PC mode.
Bluetooth
The Bluetooth interface (if licensed) lets your 475 Field Communicator
connect to
the Field Communicator Easy Upgrade Utility version 3.0 or
higher to transfer device descriptions, system software, configurations,
Event Captures, application licenses, and ScratchPad (.txt) files.
Check your AMS Device Manager documentation to see if Bluetooth is
supported.
Page 31
Learning the basics
NOTE
The 475 Field Communicator does not communicate with HART or
fieldbus devices using Bluetooth.
To use Bluetooth, you need the following:
• 475 Field Communicator with a Bluetooth license
. To see if your 475
is licensed for Bluetooth, tap the Settings icon from the Field
Communicator Main Menu. Then tap Licenses. A checkmark next to
Bluetooth indicates it is licensed.
• An approved Bluetooth adapter attached to your PC that uses the
Windows Bluetoo
th software and drivers. See the Easy Upgrade
Utility Help and readme file for more information. You can access the
readme file from www.fieldcommunicator.com, the Resource CD or
DVD, or the Field Communicator Easy Upgrade Utility menu in the
Windows Start menu (if the Easy Upgrade Utility has been installed.)
If Bluetooth is not set as the default con
nection type, you need to
enable it on the Listen for PC window. To enable Bluetooth
communication:
1.Tap Liste
2.Tap Change
3.Tap Bluetooth and th
n for PC from the Field Communicator Main Menu.
Connection Type.
en tap OK. You can tap Save as Default to
always use Bluetooth as the connection type.
The Bluetooth symbol on the keypad is illuminated by a blue light (
and a “Waiting for connection” message appears when Bluetooth is
ena
bled. See Figure 2-3 for the location of this light.
The maximum recommended distance between the 475 Field
Communicato
r and PC is 30 feet (10 meters). See the Help in the Easy
Upgrade Utility or AMS Device Manager for more information about
connecting using Bluetooth.
31
)
IrDA
The 475 Field Communicator can communicate
with the Field
Communicator Easy Upgrade Utility and AMS Device Manager using
infrared (IrDA) technology. IrDA is a PC interface supported for the
transfer of device descriptions, software updates, configurations,
Event Captures, application licenses, and ScratchPad files. See Figure
2-3 on page 15 for the location of the IrDA interface on the 475 Field
Communicator. All 475 Field Communicators can use IrDA.
IrDA communication can either be built into the PC, such as a laptop,
rovided through an adapter such as a USB to IrDA adapter. Refer
or p
to your IrDA manual for installation and operating instructions. The
maximum recommended distance between the IrDA and PC is 18
inches.
If you previously set Bluetooth as the default connection type, you
nee
d to enable IrDA.
Page 32
32
Learning the basics
To enable IrDA communication:
1.Tap Listen for PC from the Field Communicator Main Menu.
2.Tap Change Connection Type.
3.Tap IrDA and then tap OK.You can tap Save as Default to always
use IrDA as the connection type.
A “Waiting for connection” message appears when IrDA is enabled.
See AMS Device Manager Books Online or the Easy Upgrade Utility
Help for instructions to connect to those applications using IrDA.
Card reader
The 475 Field Communicator System Card can also communicate with
the Easy Upgrade Utility using a supported Secure Digital card reader.
See the readme file for the supported card readers. You can access
this file from www.fieldcommunicator.com, the Resource CD or DVD,
or the Field Communicator Easy Upgrade Utility menu in the Windows
Start menu (if the Easy Upgrade Utility has been installed.)
CAUTION
Using Windows Explorer and a card reader to manually transfer or
copy files between the System Card and a PC can corrupt the System
Card. This operation should only be performed under the direction of
Technical Support personnel.
The card reader provides faster upload and download speeds than an
IrDA adapter; however, it cannot transfer application licenses, Event
Capture files, or ScratchPad files.
To access the System Card, you need to remove the battery from the
475 Field Communicator. See
“Removing the battery and the System
Card” on page 22 for more information.
See the Easy Upgrade Utility Help for instructions to connect a System
Card and card reader.
Page 33
Learning the basics
33
Upgrading the 475 Field
Communicator
The Field Communicator Easy Upgrade Utility on the Resource CD or
DVD lets you download new system software and device descriptions
to upgrade your 475 Field Communicator at your site. To download
new system software and device descriptions, your 475 Field
Communicator must be licensed for Easy Upgrade.
You can also send your Field Communicator to a Service Center to be
upgraded. For more information, contact your sales representative.
CAUTION
New system software and device descriptions must be downloaded
and transferred to the 475 Field Communicator using the Easy Upgrade Utility. Manually copying files to the System Card using
Windows Explorer will corrupt the System Card.
Downloading new system software and device descriptions
Download the latest system software and device descriptions from the
Internet by using the Update PC functionality in the Easy Upgrade
Utility (version 3.0 or higher). An Internet connection is required to
download the new files. If your site does not have Internet access, a
Resource CD or DVD can provide the latest updates.
Transferring the system software and device descriptions
Use the Easy Upgrade Utility to transfer all the files to a connected 475
Field Communicator. You can use IrDA, Bluetooth, or a card reader to
connect to the Easy Upgrade Utility and transfer the upgrades. Large
or critical upgrades may require a card reader. See the Easy Upgrade
Utility Help for information on connecting and upgrading a 475 Field
Communicator.
The Easy Upgrade Utility also lets you transfer a specific system
software or device description version. Connect a 475 Field
Communicator or System Card and click the More Options button on
the Upgrade window to access the System Software and DDs tabs.
Adding functionality by
enabling licenses
The HART Application, Device Configuration Management, and
Graphics are licensed in all 475 Field Communicators, but other
functionality requires a license. Renew or add licenses anytime at your
site by using the Online Licensing feature in the Field Communicator
Easy Upgrade Utility. Only the Easy Upgrade license needs to be
renewed.
Page 34
34
Learning the basics
Viewing current licenses
To view the current licenses and the Easy Upg
rade expiration date in
your 475 Field Communicator, tap the Settings icon from the Field
Communicator Main Menu. Then tap the Licenses icon.
The Easy Upgrad
e Utility can also display all licensing information from
the Licensing & Registration window or Upgrade window. A 475 Field
Communicator must be connected to view licensing information from
the Upgrade window.
Purchasing and downloading new licenses
You can select and enable new licenses for a 475 Field Communicator
from yo
1.Register your 475 Field Communica
ur site. There are four basic steps to obtain new licenses:
tor by connecting it to the Easy
Upgrade Utility and logging in to the Licensing & Registration
window.
2.Select the licenses to purchase and note the appropriate part
numbers. Y
ou can select licenses for multiple Field Communicators
at one time.
3.Submit a purchase order to your sales representative.You are
ified when your order has been processed and the licenses are
not
available for download.
4.Connect the 475 Field Communicator to the Easy Upg
rade Utility,
and use the Licensing & Registration window to enable the
purchased licenses.
See the Easy Upgrad
e Utility Help for more information on selecting
and enabling licenses.
You can send your 475 Field Communica
tor to a service center to have
a technician enable licenses for you. Contact your sales representative
for more information.
SCRATCHPAD
ScratchPad is a text editor that you can use to create, open, edit, and
save simple text (.txt) documents. ScratchPad supports very basic
formatting. From the Field Communicator Main Menu, tap the
ScratchPad icon to run the application. You can also launch
ScratchPad from within the HART or Fieldbus Application by tapping
the ScratchPad (
) icon in the upper right corner of the window.
You can transfer text files between a PC and the 475 Field
Communicato
NOTE
r using the Field Communicator Easy Upgrade Utility.
The Power key, standby timer, and auto-off timer are disabled when
the ScratchPad application is open.
Page 35
Learning the basics
Creating a new documentFrom the Main Page in ScratchPad, tap NEW. An empty text window
and SIP keyboard appears. See Figure 2-8. You are now ready to
enter text into your new document.
A new document can also be created within ScratchPad by tapping the
New (
) icon in the toolbar or by selecting File | New from the menu.
35
Opening an existing
document
Figure 2-8.
1.From the Main Page in ScratchPad, select the desired file located
under File Name.
2.Tap OP
now ready to edit your document.
You can also open a document by selecting File | Open
bar or by tapping the Open (
Entering text
Using the stylus, tap the desired letters from the SIP keyboard. Using
the
keypad, press the desired keypad button in quick repetitions to
display the appropriate letter or number.
ScratchPad displaying the SIP keyboard
EN. A text window and the SIP keyboard appears. You are
from the menu
) icon in the toolbar.
Selecting text
Drag the stylus over the desired text to highlight or to select all of the
the document tap Edit | Select All.
text in
Cutting text
1.Select the text to be cut.
2.Tap Edit | Cu
You can also cut text by selecting text and tapping the Cut (
the toolbar.
Copying text
1.Select the text to be copied.
2.Tap Edit | Co
You can also copy text by selecting text and
icon in the toolbar.
t.
) icon in
py.
tapping the Copy ()
Page 36
36
Learning the basics
Pasting text
1.Copy the text to be pasted.
2.Tap a location on the screen. This is where the text will be pasted.
3.Tap Edit | Paste.
You can also paste text by copying the text and tapping the Paste (
icon in the toolbar.
Saving a document
1.In your document, tap File | Save.
2.Type the file name in the dialog box if your document is new
.
3.Tap OK.
You can also save a document by tapping the Save (
) icon in the
toolbar.
Saving a copy
To save a copy of the current document under another name:
1.In your document, tap File | Save As...
2.Type the copy file name in the dialog box.
3.Tap OK.
)
Deleting a document
There are three options for deleting a ScratchPad document:
Option 1
1.From the Main Page in ScratchPad, select the file to be deleted.
2.Tap DELETE.
3.A warning appears telling you that the selected file will be
permane
ntly deleted. If you are sure you want to delete this file, tap
Yes.
Option 2
1.To delete from your document, tap Fil
e | Delete.
2.From the Delete File Page, tap the desired file to be deleted.
3.Tap OK.
4.A warning appears telling you that the selected file will be
permane
ntly deleted. If you are sure you want to delete this file, tap
Yes.
5.Tap EXIT when
you are finished deleting files.
Option 3
Delete the .txt file using the Ea
sy Upgrade Utility. See the Easy
Upgrade Utility Help for more information on deleting a User Data file.
Exiting
1.In your document, tap File | Exit.
2.Tap the EX
IT button from the Main Page.
Page 37
Learning the basics
VALVELINK MOBILE
37
ValveLink Mobile lets you configure, calibrate, and troubleshoot Fisher
digital valve controllers (DVC) through an easy-to-use, graphical
interface.To open ValveLink Mobile, tap the ValveLink Mobile icon
from the Field Communicator Main Menu. The Field Communicator
must have a 1 GB or larger System Card and a valid Easy Upgrade
license to open ValveLink Mobile.
Use the leadset to connect to the DVC and run the desired diagnostics
or operations. See the ValveLink Mobile documentation at
www.fieldcommunicator.com for more information about the
functionality.
Upgrades to ValveLink Mobile are included with the Field
Communicator system software updates. Use the Easy Upgrade Utility
to download updates from the Internet to your PC and then transfer
them to your Field Communicator. A card reader may be required.
NOTE
The standby timer and auto-off timer are disabled when ValveLink
Mobile is open.
MAINTENANCEAny maintenance, repair, or replacement of components not listed
below must be performed by specially trained personnel at authorized
service centers. You can perform common maintenance procedures
on the 475 Field Communicator, as described below:
• Cleaning the exterior. Use only a dry, lint-free towel or dampen the
towel with a mild soap and water solution.
• Charging, removing, and replacing the battery.
• Removing and replacing the System Card.
• Removing and replacing the stand.
• Ensuring that all exterior screws are sufficiently tightened.
• Ensuring that the communication terminal recess is free of dirt and
debris (does not require disassembly).
Running a self testThere is no need, nor is it possible, to perform a manual self test with
the 475 Field Communicator. Testing features are done automatically.
A warning message appears if a fault condition is found during these
tests.
CalibratingIt is not necessary or possible to calibrate the 475 Field Communicator.
The 475 Field Communicator is a communication interface that
communicates digitally with HART and F
Voltage measurements made by the 475 Field Communicator are for
use in detection of power or noise on a network, and are for reference
purposes only. NIST standards are not applicable to the 475 Field
Communicator.
OUNDATION fieldbus devices.
Page 38
38
Learning the basics
Page 39
475 FIELD COMMUNICATOR
WARNING
WARNING
SECTION 3HART FUNCTIONALITY
OVERVIEWThis section provides instruction on basic HART functionality in the 475
Field Communicator. It is based on the operation of the HART
Application version 6.1.
SAFETY MESSAGESProcedures and instructions in this section may require special
precautions to ensure the safety of the personnel performing the
operation. Information that raises potential safety issues is indicated by
a warning symbol (
performing an operation preceded by this symbol. Other warning
messages can
manual.
If you choose to ignore all field device status messages, every
message, regardless of severity, is ignored until the specified
number of messages is reached. See
on page 55 for more information.
be found in the “Troubleshooting” section of this
). Refer to the safety messages before
“Ignoring status messages”
Voltage measurements are for reference purposes only. Do not
make critical process control decisions based on these
measurements.
www.fieldcommunicator.com
Page 40
40
BASIC FEATURES AND
FUNCTIONS
HART functionality
HART Application
functionality
The HART Application lets you communicate with and configure HART
devices that are connected to the 475 Field Communicator. You can
also create and edit configurations and run diagnostics.
Using a fast key sequenceA fast key sequence is a sequence of numerical button presses,
corresponding to the menu options that lead you to a given task. See
your device documentation for fast key sequence options.
STARTING THE HART
APPLICATION
To start the HART Application:
1.Press and hold the Power key until the green light on that key blinks
urn on the 475 Field Communicator.
to t
2.Tap
device is connected to the 475 Field Communicato
Application Online menu appears automatically. If a device is not
connected, the HART Application main menu appears after a few
seconds. See Figure 3-1.
To return to the Field Communicator Main Menu, press the left arrow
key on
when prompted if you want to exit the HART Application.
From the HART Application main menu,
Online, Utility, or HART Diagnostics functions. The rest of this
section guides you through the HART Application menus and
functions.
from the Field Communicator Main Menu. If a live HART
r, the HART
the keypad or tap the back arrow on the window. Select Yes
you can choose Offline,
Figure 3-1. HART Application Main Menu
Page 41
HART functionality
41
WORKING WITH OFFLINE
CONFIGURATIONS
Creating a new
configuration
The Offline menu lets you create offline configurations and view and
change configurations stored in the 475 Field Communicator.
There are two types of HART configurations: device configurations and
user configurations. A device configuration is created from a
connected, online HART device. A user configuration is created offline
or transferred to a 475 Field Communicator from another program.
Editing a device configuration within the 475 Field Communicator
changes it to a user configuration.
The concept of partial or standard configurations does not apply to the
475 Field Communicator. All configurations are full configurations.
Creating a new configuration lets you create a user configuration for a
specific device type and revision.
To create a new HART configuration while working offline:
1.From the HART Application main menu, double-tap Offline.
2.Double-tap New Configuration. The manufacturer names of the
installed device descriptions are listed.
3.Double-tap the desired manufacturer to expand the list. The models
available for the manufacturer are listed.
4.Double-tap the desired device model to expand the list. The device
revisions available for the selected device model are listed.
5.Double-tap the desired device revision.
6.If a warning appears, thoroughly read the warning, tap CONT to
accept the warning and proceed, or tap EXIT.
7.Mark (select) the configurable variables you want sent to the device;
unmarked variables are not included when the configuration is
transferred to a device. Double-tap Mark all | OK to have all
variables marked. Double-tap Unmark all | OK to clear the marks
from all variables. If a variable cannot be marked, an error message
appears.
To mark and edit variables individually:
a.Double-tap Edit individually.
b.Scroll through the list of variables and select the variable you want
to mark or edit.
c.To change the value for the selected variable, tap EDIT, change the
value, and tap ENTER. A “*” symbol appears next to the variable
name and the value is highlighted yellow to indicate the change
has not been saved.
To mark the selected variable, tap MARK. A “+” symbol appears
next to the value.
d.Repeat these steps for other variables as necessary and tap EXIT
when you are finished.
8.To save the configuration, double-tap Save as. (The SAVE button
brings you to the Save as menu.)
Page 42
42
HART functionality
a.To change the location where the configuration is saved,
double-tap Location, select an option, and tap ENTER.
b.To specify a name for the configuration, double-tap Name, enter
the name, and tap ENTER.
c.Tap SAVE.
Opening a saved
configuration
A saved configuration lets you edit, copy, send, delete, or rename it.
You can also compare it to other saved configurations.
To open a saved configuration:
1.From the HART Application main menu, double-tap Offline.
2.Double-tap Saved Configuration.
3.Double-tap the storage location where you saved the configuration.
The FILTR button opens a menu that provides both sort and tag filter
options. These options let you customize your view of saved
configurations.
• The Sort option lets you group and display configurations
according to your choice of configuration name, device tag, or
device descriptor.
• The Filter option lets you limit which configurations are displayed
by picking specific characters from the configuration name, device
tag, or device descriptor.
When setting up a filter, you can use two special characters: the
period (.) and the asterisk (*). The period replaces a single
character of any value. The asterisk replaces a string of
characters.
For example, if you want to list all configurations that have a name
of P - 001 to P - 300, enter “P - *” in the filter. If you want to list
configurations with a name that begins P the filter to “P - 0.7”. The period will replace only one character
between the 0 and 7.
The XPAND button lets you view the configuration name, device tag,
manufacturer, device type, device revision, descriptor, and the
configuration type. Tap CMPRS to return to the previous window.
4.Double-tap the desired configuration to open the Saved
Configuration menu.
0 and ends with a 7, set
Editing a saved configuration
The Edit option lets you edit a saved configuration while working
offline.
To edit a saved configuration:
1.Open a saved configuration. See “Opening a saved configuration”.
2.Double-tap Edit from the Saved Configuration menu.
3.If a warning appears, thoroughly read the warning, tap CONT to
accept the warning and proceed, or tap EXIT to end this operation.
4.Mark (select) the configurable variables you want sent to the device;
unmarked variables are not included when the configuration is
transferred to a device. Double-tap Mark all | OK to have all
Page 43
HART functionality
43
variables marked. Double-tap Unmark all | OK to clear the marks
from all variables.
To mark and edit variables individually:
a.Double-tap Edit individually.
b.Scroll through the list of variables and select the variable you want
to mark or edit. To change the value for the selected variable, tap
EDIT, change the value, and tap ENTER. A “*” symbol appears
next to the variable name and the value is highlighted yellow to
indicate the change has not been saved.To mark the selected
variable, tap MARK. A “+” symbol appears next to the value.
c.Repeat these steps for other variables as necessary.
d.Tap Exit.
5.Tap SAVE.
Copying a saved configuration
The Copy to option lets you copy a saved configuration to a new
storage location in the 475 Field Communicator.
To copy a saved configuration:
1.Open a saved configuration. See “Opening a saved configuration” on
page 42.
2.Double-tap Copy to from the Saved Configuration menu.
3.Double-tap Location and select the new storage location to which
you want to save the configuration, and tap ENTER.
4.Double-tap Name, enter the name for the copy of this configuration,
and tap ENTER.
5.Tap SAVE to copy the configuration to a new location.
Sending a saved configuration to a connected device
The Send option lets you send the open configuration to a connected
device. From the Saved Configuration menu, double-tap Send. The
475 Field Communicator sends the configuration to a connected
device that is compatible with the configuration.
Deleting a saved configuration
The Delete option lets you remove saved configurations one at a time.
To delete a configuration from the 475 Field Communicator storage:
1.Open a saved configuration. See “Opening a saved configuration” on
page 42.
2.Double-tap Delete from the Saved Configuration menu.
3.Tap Yes to confirm the deletion. Tap No to cancel.
Page 44
44
HART functionality
Renaming a saved configuration
The Rename option lets you change the name of a saved
configuration.
To rename a saved configuration:
1.Open a saved configuration. See “Opening a saved configuration” on
page 42.
2.Double-tap Rename from the Saved Configuration menu.
3.Double-tap the file you want to rename.
4.Enter the new file name and tap ENTER.
5.Tap SAVE.
Comparing two saved configurations
Any two configurations can be compared. A message appears
indicating if differences exist, but the specific differences are not
displayed.
To compare two saved configurations:
1.Open a saved configuration. See “Opening a saved configuration” on
page 42.
2.Double-tap Compare from the Saved Configuration menu.
3.Double-tap Location and select the storage location containing the
other configuration that will be used in this comparison and tap
ENTER.
4.Double-tap Name to select the desired file to compare.
5.Tap COMP to compare the configurations.
6.Tap OK when you are finished.
Transferring
configurations to a PC
application
You can transfer configurations (.hcf files) from the 475 Field
Communicator to AMS Device Manager or the Field Communicator
Easy Upgrade Utility. After you transfer the configuration, you can
perform different operations depending on the application used.
AMS Device Manager
Use AMS Device Manager to open, edit, compare, and transfer saved
configurations. A Handheld or Field Communicator Interface kit for
AMS Device Manager (version 6.2 or higher) lets you use the 475 Field
Communicator with AMS Device Manager.
If the System Card does not appear as a storage location in AMS
Device Manager, copy the configurations from the System Card into
the Internal Flash in the 475 Field Communicator before connecting to
AMS Device Manager. See
43 for instructions. Then access the Internal Flash location to open,
edit, and save the configurations in AMS Device Manager. See the
AMS Device Manager Books Online for more information on
connecting and transferring configurations.
“Copying a saved configuration” on page
Page 45
HART functionality
HART communication terminal markings
Access door
Communication terminals
WORKING ONLINE WITH
HART DEVICES
Field Communicator Easy Upgrade Utility
Use the Easy Upgra
de Utility to back up, transfer, and print the configurations saved in your 475 Field Communicator. See the Easy
Upgrade Utility Help for more information about connecting and
transferring configurations.
45
Connecting to a HART
device
The 475 Field Communicator can communicate with a device from the
control room, on the bench, or any wiring termination point in the loop.
Connect the 475 Field Communicator with the appropriate connectors
in parallel with the device or load resistor. The HART connectors are
not polarity sensitive.
A minimum of 250 ohms resistance must be present in the HART loop
for
the 475 Field Communicator to function properly. For information
about Intrinsically Safe connections, see Appendix B.
HART communication terminals
Three terminals for the lead set are on the top of the 475 Field
Communicato
r. Each red terminal is a positive connection for its
protocol. The black terminal is a common terminal shared by both
protocols. An access door ensures only one pair of terminals is
exposed at any one time; see Figure 3-2. Several markings indicate
which pair of terminals is for which protocol.
Figure 3-2. HART communication terminals and access door
NOTE
The lead set must be used to communicate with a wired or wireless
device. The 475 Field Communicator cannot communicate wirelessly
with devices.
Page 46
46
HART device
Current
meter
RL≥250Ω
mA
Power supply
+
+
+
+
+
+
-
-
-
-
-
-
Current
meter
mA
Power supply
RL≥250Ω
HART device
+
-
+
+
-+
-
+
-
+-
HART functionality
Wiring diagrams
Figure 3-3 shows how to connect the 475 Field Communicator to a
HART loop.
Figure 3-3. Connecting to a HART loop
Figure 3-4 shows how to connect the 475 Field Communicator directly
to the terminals of a HART device.
Figure 3-4. Connecting directly to a HART device
Figure 3-5 shows how to connect the optional 250 ohm resistor.
Attaching a resistor is necessary if less than 250 ohms resistance is
pre
sent in the HART loop.
Page 47
HART functionality
Optional
250-Ohm load
resistor
HART device
Power
supply
–
+
–
+
Wireless device
Battery
Communication terminals
47
Figure 3-5. Connecting with a 250 Ohm resistor
To temporarily install the optional 250 ohm load resistor:
1.Insert the load resistor into the lead set jacks.
2.Open the loop to allow connection of the resistor in series in the loop.
3.Close the loop using the lead set connectors.
Figure 3-6 shows how to connect the 475 Field Communicator directly
to the communication terminals on
a wireless device.
Figure 3-6. Connecting to a wireless device
Page 48
48
HART functionality
Displaying the connected
HART devices
After the device is connected, tap from the Field Communicator
Main Menu. The HART Application automatically po
lls for connected
devices using the selected polling options. See “Changing the HART
polling options” on page 53 for information on modifying these options.
NOTE
Communication errors, such as a device appearing at multiple
addresses, can occur when polling addresses greater than 15 on a
loop with both HART Universal Revision 5 or earlier and HART
Universal Revision 6 or higher devices.
For many devices, an Online menu similar to Figure 3-7 is the first
menu to appear when connected to a HART device and is the root
menu fo
r the device. This menu displays critical, up-to-date process
information that is continuously updated, including device setup,
primary variable (PV), analog output (AO), PV lower range value
(LRV), and PV upper range value (URV).
Depending on the device description, the first online screen may be a
andard HART menu or a Device Dashboard menu. A Device
st
Dashboard menu displays the same parameters, but they are
organized by task. Options such as Overview, Configure, Service
Tools, and Advanced may appear. See your device documentation for
more information on these menus.
NOTE
Dynamic variables shown while online represent the digital data being
sent from the device.
Figure 3-7. HART Online Menu and Device Dashboard Online Menu
Because the Online menu displays important information, some
submenus display the HOME button to return you to the HART Online
menu.
Page 49
HART functionality
The HART iconA beating HART icon appears at the top of the window when the 475
Field Communicator is communicating with a device. See the table
below for the icons and their meanings.
Table 3-1. HART icons
IconMeaning
49
Saving a device
configuration
The 475 Field Communicator is communicating with
online HART device.
The 475 Field Communicator is communicating with a HART
loop with a device in burst mode.
The 475 Field Communicator is running in shout/deaf mode,
which helps the 475 communicate with a device when it is on
a noisy loop.
The 475 Field Communicator is running in shout/deaf mode
and communicating to a HART loop with a device in burst
mode.
Communication is not occurring. This is common when only
non-dynamic parameters are listed.
When you save a configuration from a connected device, it is saved as
a device configuration. You can save only 25 configurations to the
Internal Flash.
To save the configuration in the connected device:
1.Ensure the 475 Field Communicator is connected to a HART loop or
directly to
2.Tap
menu appears.
3.Tap Save.
the configuration while connected to the device. You may need to
make a change to the configuration or disconnect and then
reconnect to the device to resave.
a.To set the location where the configuration will be saved,
dou
b.To specify a name for the configuration, double-tap Name, enter
the name, and tap ENTER.
4.Tap Save.
Tap YES to overwrite the older version with the new version, or tap
NO to return to the Save as window.
the device and turn on the 475 Field Communicator.
from the Field Communicator Main Menu. A HART Online
The Save button will not appear if you have already saved
ble-tap Location, select an option, and tap ENTER.
If the configuration already exists, a message appears.
a live,
Page 50
50
HART functionality
Displaying Device Setup
options
The Device Setup on the HART Online menu accesses every
configurable parameter for the connected device. Some devices may
not display a Device Setup menu. Check your device documentation
for more information. Double-tap Device setup to view the process
variables, diagnostics and service, basic setup, detailed setup, and
review menus.
Process Variables
The Process Variables menu lists all process variables and their
values. Process variables are continuously updated when this window
is displayed.
Diagnostics and Service
The Diagnostics and Service menu offers device and loop tests as well
as calibration options. The diagnostics and service operations that are
available vary widely from device to device and are defined in the
device description.
The Test device menu lists the status as well as self and master test of
the device. Test device initiates a diagnostic routine at the device and
can report an electronics failure, as well as other failures that can
affect performance.
Loop test is used to set the output of the device at a specified analog
value, and may be used to test the integrity of the loop and the
operation of indicators, recorders, or similar devices in the loop.
Calibration is used to perform such operations as performing a sensor
trim, D/A trim, and scaled D/A trim.
Basic setup
The Basic setup menu provides quick access to a number of
configurable parameters including tag, unit, range values, and
damping.
The options available in the Basic setup menu are the most
fundamental tasks that can be performed with a device. These tasks
are a subset of the options available under the Detailed setup menu.
The Tag identifies a specific device. Changing the unit option affects
the engineering units that are displayed. Changing range values
modifies the analog output scaling. Changing damping affects the
response time of the transmitter and is often used to smooth the output
when there are rapid input variations.
A modified parameter is highlighted yellow and an asterisk appears to
indicate the change has not been sent to the device. Tap Send to
update the device.
Page 51
HART functionality
Figure 3-8. Modified parameter example
Detailed setup
The Detailed setup menu provides access to every editable device
p
arameter and all device functions. The Detailed setup menu varies
widely from one HART device to another. Functions in this menu can
include tasks such as characterization, configuration, and sensor and
output trims.
Review
The Review menu lists all of the static parameters read from the
connected d
evice, including information about the device and sensor
setup and limitations. It also may include information about the
connected device such as tag, materials of construction, and device
software revision.
51
Displaying GraphicsThe HART Application offers graphical views of device data by using
the enhanced Electronic Device Description Language (EDDL)
technology. Device data can be presented as images, charts, and
graphs. These options appear as items in the HART Online menu and
its submenus. The placement of the graphics in the menus varies from
device to device because it is determined by the device manufacturer.
To view the graphical representations, you need a device using an
enh
anced device description. Only devices using an enhanced EDDL
device description offer graphical representations of data. See
Appendix C for more information about the Graphics functionality.
Page 52
52
CONFIGURING THE HART
APPLICATION
Using hot keysSetting up hot key options
The Hot key menu is a user-definable menu that can store shortcuts
for
up to 20 of your most frequently performed tasks. For example, if
you change device tags and damping often, you can add options for
these functions to the Hot key menu for quick access. The Hot key
automatically appears in the toolbar when you are working online. Hot
keys created from generic DDs are not saved.
To add a custom option to the Hot key menu:
1.Connect to a HART device.
2.From the Field Communicator Main Menu, tap
3.From the HART Online Menu or any of the submenus, select the
opt
ion you want to add to the Hot key menu.
4.Tap and hold the Hot key (
shows the new option you are adding.
5.Tap ADD.
6.Tap ALL to add
add the Hot key option for only the device type to which you are
currently connected.
7.If the message “Mark as read only variable on hotkey menu”
app
ears, choose one of the following:
• YES: The
change its value.
You can view and change the value for this variable.
• NO:
8.Respond to the message “Display value of variable on hotkey
menu?” b
• YES: The valu
The Hot Key menu shows the name of the variable but not its
• NO:
value.
9.Tap the EXIT button on
the original menu. The new option is added to the Hot key menu.
the Hot key option for all device types, or tap ONE to
variable for this option is read-only. You can view but not
y choosing one of the following:
e of this variable appears on the Hot key menu.
the Hotkey Configuration window to return to
HART functionality
.
). The Hotkey Configuration window
Using a hot key option
You can access the Hot key menu from any online window.
To use a Hot key option:
1.Connect the 475 Field Communicator to a HART loop or device.
2.From the Field Communicator Main Menu, tap
3.Tap the Hot key (
4.Double-tap the desired option from the Hot key menu.
) from an online menu.
.
Page 53
HART functionality
53
Removing a hot key option
To remove individual Hot key options:
1.Tap and hold the Hot key (
). The Hotkey Configuration window
appears.
2.Tap the menu option you want to remove.
NOTE
Some options are predefined and cannot be removed from the Hot key
menu. These options vary depending on the device type.
3.Tap DEL.
4.When you are done, tap EXIT t
o close the Hotkey Configuration
window.
Removing all hot key options
To remove all Hot key options currently defined:
1.From the HART Application ma
2.Double-tap Configu
3.Double-tap S
torage Cleanup.
4.Double-tap Hotkey
5.Tap YES if
you are sure you want to delete all the items from the Hot
re HART Application.
Menu.
in menu, double-tap Utility.
key menu. Tap NO to return to the Storage Cleanup menu.
Changing the HART
polling options
Use the HART Polling Options to configure your 475 Field Communicator
to automatically search for all or specific connected devices. Most HART
device installations contain one device per loop and the device address is
zero. Refer to your device manual for more information about changing
a device polling address.
To have more than one device per loop, wire the devices in parallel
place into “Multidrop” mode. This mode is enabled by changing
and
the address from zero to any address between 1-63. After the mode is
enabled, the analog output of each device is fixed and no longer
represents any variable.
NOTE
Communication errors, such as a device appearing at multiple
addresses, can occur when polling addresses greater than 15 on a
loop with both HART Universal Revision 5 or earlier and HART
Universal Revision 6 or higher devices.
Page 54
54
HART functionality
To change the polling option:
1.From the HART Application main menu, double-tap Utility.
2.Double-tap Configure HART Application.
3.Double-tap Polling Options. Select one of the following polling
options:
• Poll By Address - Lets you poll for devices at the specified
addresses. Tap Enter and then double-tap Polling Addresses
from the Configure HART Application window to select addresses
to poll. (This option appears only when Poll By Address is
selected.) Select one of the following options from the Polling
Addresses menu:
Table 3-2. Options in the Polling Addresses menu
Polling
Addresses
Recommended Use
0Poll non multi-dropped loops.
0-15Poll HART Universal Revision 5 or earlier devices
on multi-dropped loops.
0-63Poll HART Universal Revision 6 or newer devices
on multi-dropped loops.
63Poll the default address for WirelessHART
adapters.
Custom RangePoll a unique or non-consecutive group of
addresses (example: “0, 5-7, 12”). Use a hyphen
to specify consecutive addresses and/or a comma
to separate numbers or groups of numbers.
• Poll Using Tag - Lets you enter and poll by the tag of the device.
You are prompted to enter a tag when the HART Application
starts.
• Poll Using Long Tag - Lets you enter and poll by the long tag of
the device. (Only supported in HART Universal Revision 6 or
higher devices.) You are prompted to enter a tag when the HART
Application starts.
• Poll Using Unique ID - Lets you poll using the device’s unique ID.
For HART Universal Revision 7 devices, the unique ID is the
expanded device type, a hyphen, and the device ID. For HART
Universal Revision 6 and earlier devices, the unique ID is the
manufacturer ID, the device type, a hyphen, and the device ID.
You are prompted to enter a unique ID when the HART Application
starts.
4.Tap Enter.
Page 55
HART functionality
Ignoring status messagesThe 475 Field Communicator displays status messages from the
connected HART device. The Ignore Status option lets you specify the
number of device status messages that are not displayed, extending
the time between displayed messages. The default is 50 messages
and it is reset to this value after you close the HART Application.
NOTE
If you choose to ignore all device status messages, every message,
regardless of severity, is ignored until the specified number of
messages is reached.
To change the number of ignored status messages:
1.From the HART Application ma
2.Double-tap Configu
3.Double-tap Igno
4.Enter the number of status messages you want ignored before the
next message a
Tap ENTER. All device status messages are ignored until the
5.
quantity specified is reached.
re HART Application.
re Status.
ppears. You can specify a number from 50 to 500.
in menu, double-tap Utility.
55
Displaying the HART short
tag or long tag in a menu
title
The HART Tag menu lets you select the HART short or long tag to
display in the menu title for HART Universal Revision 6 or higher
devices. The short tag can have up to 8 characters, and the long tag
can have up to 32 characters. These tags can be edited at any time. If
the long tag does not fit on the window, an ellipsis is shown at the end
of the tag. Tap and hold the ellipsis to see the full tag name.
The location of these parameters in the Online menu varies from
device to d
To select a HART tag for the menu title:
1.From the HART Application ma
2.Double-tap Configu
3.Double-tap HART T
4.Tap Show Long TShort Tag to display the HART short tag.
5.Tap ENTER.
option you selected until you change the setting.
evice because it is determined by the device manufacturer.
in menu, double-tap Utility.
re HART Application.
ag.
ag to display the HART long tag, or tap Show
The 475 Field Communicator continues to use the
Storage CleanupThe Storage Cleanup menu lets you delete the following items:
• Inte
rnal Flash - Ta p YES to delete all configurations in the Internal
Flash. Tap No to cancel.
• Syste
• Hotkey
m Card - Tap YES to delete all configurations in the System
Card. Tap No to cancel.
Menu - Tap YES to delete all items from the Hot key menu.
Tap No to cancel.
Page 56
56
HART functionality
Viewing available device
descriptions
The Available Device Descriptions menu lets you view all the device
descriptions in the 475 Field Communicator. HART device descriptions
enable the 475 Field Communicator to recognize and configure
specific HART devices. Use the Field Communicator Easy Upgrade
Utility to download or import new device descriptions and then transfer
them to your 475 Field Communicator. See the Easy Upgrade Utility
Help more information.
To view the currently installed HART device descriptions:
1.From the HART Application main menu, double-tap Utility.
2.Double-tap Available Device Descriptions. The manufacturer
names of the installed device descriptions are listed.
3.Double-tap the desired device manufacturer to expand the list. The
models available for the manufacturer are listed.
4.Double-tap the desired device model. The device revisions available
for the selected model are listed. One of the icons below appears
next to each device description to indicate its status.
Table 3-3. Device description icons
IconMeaning
The device description has been tested with the system
software version in the 475 Field Communicator.
The device description has not been formally tested for use
with the system software version in the 475 Field
Communicator. The device description can be used, but you
may experience unexpected results.
The device description is incompatible and cannot be used
with the system software version in the 475 Field
Communicator. You need to transfer a different version of this
device description to the 475 Field Communicator.
Simulating an online
connection to a HART
device
The 475 Field Communicator has a simulation mode that lets you
simulate an online connection to a HART device without actually
connecting to a device. Simulation mode is a training tool that helps
you become familiar with devices before configuring them in a critical
environment. A simulated configuration cannot be saved. Not all
device descriptions have been optimized to run under simulation. The
HART Application will close to the Field Communicator Main Menu if
the device cannot be simulated.
To simulate a connection to a HART device:
1.From the HART Application main menu, double-tap Utility.
2.Double-tap Simulation. The manufacturers with device descriptions
installed in the 475 Field Communicator are listed.
3.Double-tap the desired manufacturer to expand the list. The models
available for the manufacturer are listed.
Page 57
HART functionality
RUNNING HART
DIAGNOSTICS
4.Double-tap the desired model to expand the list. The device
revisions available for the selected model are listed.
5.Double-tap the desired device revision.
to determine the device revision.
6.If a warning appears, thoroughly read the warning, tap CONT to
accept the warning and proceed, or tap EXIT to return to the Utility
menu. (This warning does not appear if your device is tested.) The
Online menu for the simulated device appears.
You can now use the 475 Field Communicator as if it were
connected to
the selected device and perform any online task.
Refer to the device manual
57
DC voltage measurement
(HART terminals)
DISCONNECTING FROM A
HART DEVICE
The HART DC voltage measurement takes a voltage reading at the
HART connector and displays it in the window.
To check the device voltage:
1.From the HART Application ma
Diagnostics.
Double-tap DC Voltage Measurement. The DC voltage
2.
measurement appears.
3.Tap OK
the window, double-tap DC Voltage Measurement from the HART
Diagnostics menu.
CAUTION
Voltage measurements are for reference purposes only. Do not make
critical process control decisions based upon these measurements.
Prior to disconnecting the 475 Field Communicator from a HART
device, check the following items:
• Determine if you want to save a configuration.
• Verify methods, such as calibration or loop test, are complete.
• Resolve any un-sent data to the device.
when you are finished viewing the measurement. To refresh
in menu, double-tap HART
Page 58
58
HART functionality
Page 59
475 FIELD COMMUNICATOR
WARNING
WARNING
WARNING
SECTION 4FIELDBUSFUNCTIONALITY
OVERVIEWThis section provides instruction on basic fieldbus functionality in the
475 Field Communicator. It is based on the operation of the Fieldbus
Application version 6.1.
SAFETY MESSAGESProcedures and instructions in this section may require special
precautions to ensure the safety of the personnel performing the
operation. Information that raises potential safety issues is indicated by
a warning symbol (
performing an operation preceded by this symbol. Other warning
messages can
If a segment is connected to a host system, the changes made
with the 475 Field Communicator may not be recorded in the host
system’s permanent database. Verify the changes in the database.
Otherwise, this could cause unpredictable results and, depending
upon your application, process disruption leading to property
damage, serious injury, or death. Ensure all safety precautions and
work procedures have been followed.
be found in the Troubleshooting section of this manual.
). Refer to the safety messages before
www.fieldcommunicator.com
Changing device parameters could adversely affect the control of
your process. Put the control loop in Manual/Out of Service before
applying changes. Verify the output before returning the control
loop to Auto. Failure to do so could result in property damage,
serious injury, or death. Ensure all safety precautions and work
procedures have been followed.
The 475 Field Communicator draws approximately 12 mA from the
fieldbus segment. Be sure the power supply or barrier on the
fieldbus segment has the capacity to provide this additional
current. If a heavily loaded fieldbus segment is drawing near the
capacity of the segment’s power supply, connecting the 475 Field
Communicator may result in loss of communication.
Page 60
60
BASIC FEATURES AND
FUNCTIONS
Fieldbus functionality
Fieldbus Application
functionality
Link Active Scheduler
(LAS)
The Fieldbus Application lets you communicate with connected
fieldbus devices, modify settings for the application, and run
diagnostics. Your 475 Field Communicator must be licensed for
F
OUNDATION Fieldbus to run this application. See your sales
representative or the Online Licensing feature in the Field
Communicator Easy Upgrade Utility to purchase this license.
All segments have only one Link Active Scheduler (LAS). The LAS
operates as the bus arbiter for the segment. The 475 Field
Communicator is set up to always be the last node to become the LAS
on a segment.
The devices that are capable of becoming the LAS are called link
master devices. All other devices are referred to as basic devices. You
can set a device to be a link master or basic device using the 475 Field
Communicator. See
device” on page 74 for more information.
When a segment first starts up, or upon failure of the existing LAS, the
link master devices on the segment bid to become the LAS. The link
master that wins the bid (the one with the lowest address) begins
operating as the LAS immediately upon completion of the bidding
process. Link masters that do not become the LAS can act as LAS
backups by monitoring the segment for failure of the LAS and then
bidding to become the LAS when a LAS failure is detected.
Although the 475 Field Communicator is capable of becoming the LAS,
it does not maintain the communication schedule and should not be
thought of as a backup LAS.
Only one device can communicate at a time. Permission to
communicate on the bus is controlled by a centralized token passed
between devices by the LAS. Only the device with the token can
communicate. The LAS maintains a list of all devices that need access
to the bus. This list is called the Live Device List; see
connected fieldbus devices” on page 65.
“Setting the device to be a Link Master or Basic
“Displaying the
LAS hierarchyWhen a 475 Field Communicator is connected to a live fieldbus
segment, it joins the fieldbus segment but not as the LAS. This means
the 475 Field Communicator can view and edit device parameters, but
the control of the segment is still handled by the node that is
designated the LAS for the segment. You can also read and write if
there is another LAS. Prior to connecting to a host system, review the
475 Field Communicator Host System Interoperability on
www.fieldcommunicator.com.
Page 61
Fieldbus functionality
61
STARTING THE FIELDBUS
APPLICATION
A general warning message may appear upon starting the Fieldbus
Application when a LAS is detected on the segment. Tap YES to go to
the Live Device List, NO to return to the Field Communicator Main
Menu, or HELP to get more information on the warning.
To start the Fieldbus Application:
1.Press and hold the Power Key until the green light on that key blinks
urn on the 475 Field Communicator.
to t
2.Tap
device is connected to the 475 Field Communicato
Application main menu briefly appears followed by the Live Device
List. Figure 4-1 shows the Fieldbus Application main menu.
If insufficient voltage is detected, a warning message appears. Tap
OK
Figure 4-1. Fieldbus Application Main Menu
from the Field Communicator Main Menu. If a live fieldbus
r, the Fieldbus
to go to the Fieldbus Application main menu.
WORKING ONLINE WITH
FIELDBUS DEVICES
A connection warning message may appear if no communication is
detected. This means that a LAS is not recognized by the 475 Field
Communicator. This typically occurs when connecting to a single
device.
To go back to the Field Communicator Main Menu, tap the back
arro
w button or press the left arrow key on the keypad.
From the Fieldbus Application main menu,
Utility, or Fieldbus Diagnostic functions. The rest of this section
guides you through the Fieldbus Application menus and functions.
The online menus display data for the device to which you are
connected, and they display critical, up-to-date process information,
including the segment Live Device List, Block Lists, Device Dashboard
menus, and parameter information.
NOTE
It is normal for processes to take longer the greater the amount of
scheduled communication. This is influenced by the number of devices
and the control methods in place.
you can choose Online,
Page 62
62
Fieldbus communication terminal markings
Access door
Communication terminals
Fieldbus functionality
Connecting to a fieldbus
device
Connect the 475 Field Communicator by using the lead set with the
appropriate connectors in parallel with the device. Due to
measurement circuitry, the 475 Field Communicator fieldbus
connectors on the communication terminals are polarity sensitive. An
error message appears if the lead set is connected incorrectly.
For information about Intrinsically Safe connections, see Appendix B.
NOTE
Dynamic variables shown while online represent the digital data being
sent from the device.
Digital communication is susceptible to electrical noise; follow proper
wiring instructions.
Fieldbus communication terminals
Three terminals for the lead set are on the top of the 475 Field
Communicato
r. Each red terminal is a positive connection for its
protocol. The black terminal is a common terminal shared by both
protocols. An access door ensures only one pair of terminals is
exposed at any one time; see Figure 4-2. Several markings indicate
which pair of terminals is for which protocol.
Figure 4-2. Fieldbus communicatio
n terminals and access door
Page 63
Fieldbus functionality
T
e
r
m
i
n
a
t
o
r
T
e
r
m
i
n
a
t
o
r
Connection
block
Fieldbus
power
conditioner
24 VDC
power
supply
+
+
++
+
-
-
-
-
-
Bench hook-up
Figure 4-3 illustrates one method of connecting the 475 Field
Communicator on a bench.
For segments that are limited in size, the power conditioner and
termina
tors can be contained in a single wiring block.
Figure 4-3. Bench wiring diagram example
63
Page 64
64
T
e
r
m
i
n
a
t
o
r
T
e
r
m
i
n
a
t
o
r
Fieldbus
power
conditioner
24 VDC
power
supply
Fieldbus
junction
box
Fieldbus
host
control
system
++
+
++
---
-
-
Fieldbus functionality
Field hook-up
Figure 4-4 illustrates one method of connecting the 475 Field
Communicator to a fieldbus segment. The 475 Field Communicator
can be
connected at any convenient place along the bus (segment). In
the field, this is typically done at the device or at the fieldbus junction
box.
Figure 4-4. Field wiring diagram example
CAUTION
The 475 Field Communicator draws approximately 12 mA from the
fieldbus segment. Ensure the power supply or barrier on the fieldbus
segment has the capacity to provide this additional current. If a
fieldbus segment is drawing near the capacity of the segment’s power
supply, connecting the 475 Field Communicator may result in loss of
communication.
Page 65
Fieldbus functionality
65
Displaying the connected
fieldbus devices
To display the connected devices on a fieldbus segment (Live Device
List):
1.Connect the 475 Field Communicator t
2.Turn on the 475 Field Communicator.
3.On the Field Communicator Main Menu, tap
4.On the Fieldbus Application main menu, double-tap Online. T
Fieldbus Live Device List appears and indicates which device or host
is acting as the LAS. The text LAS appears at the top of the window
only when the 475 Field Communicator is the LAS. See Figure 4-5.
If a live fieldbus device is connected to a host acting as the LAS, a
precautionary message
with the tag name and address for the connected device.
If an existing host control system or a device capable of being the
LAS is not
temporary LAS on the segment and produces a warning message.
After reading and following the message instructions, tap OK to
display the Live Device List.
From the Live Device List, a Block List or a Device Dashboard menu
is displayed
To return to the Fieldbus Application Main Menu, press the left arrow
key on
when prompted if you want to go offline.
connected, the 475 Field Communicator acts as a
for a device, depending on the device description.
the keypad or tap the back arrow on the window. Select OK
appears. The Live Device List then appears
o a fieldbus segment.
.
he
Figure 4-5. Live Device List window example
Page 66
66
Fieldbus functionality
Displaying the online
device
Depending on the device description, the first screen displayed may be
the Block List or a Device Dashboard menu. The Block List displays
the block tag, block type, and actual mode of the device blocks in the
connected device. It also lists an Advanced menu with additional menu
options. Consult your device manual or the Fieldbus Foundation for
more information on blocks and their functionality. F
OUNDATION fieldbus
menu trees are on www.fieldcommunicator.com as they become
available.
A Device Dashboard menu displays the same parameters as the Block
List, but they
are organized by task rather than by block. Options such
as Overview, Configure, Service Tools, and Advanced may appear.
The Block List is still accessible from the Advanced option in a device
menu.
The menu items that are displayed vary because they are determined
by the d
evice description. Refer to your device manual or
www.fieldcommunicator.com for menu trees.
To view the Block List or Device Dashboard:
1.From the Fieldbus Application main menu,
double-tap Online.
2.Double-tap a device.
3.The Block List or Device Dashboard menu appears.
NOTE
If the device is commissioned, the following operations are disabled:
modifying the physical device tag, modifying the node address,
scheduling an I/O Block, instantiating or deleting blocks, configuring a
link master device, modifying a block tag.
Figure 4-6. Block List and Device Dashboard example
Block modesThe resource, transducer, and all function blocks in the device have
modes of operation. These modes govern the operation of the block.
Every block supports both automatic (AUTO) and out of service (OOS)
modes. Other types of modes that may also be supported are Cas,
RCas, ROut, IMan and LO.
Page 67
Fieldbus functionality
67
Types of modes
For the procedures described in this manual, it is helpful to understand
the following modes:
AUTO
The functions performed by the block will execute. If the block
has any outputs, these will continue to update. This is typically
the normal operating mode.
MAN
In this mode, the output of the block can be manually overwritten
for testing purposes.
Out of Service (OOS)
The functions performed by the block will not execute. If the
block has any outputs, these will typically not update and the
status of any values passed to other blocks is “BAD”. Before you
make changes to the configuration of the block, change the
mode of the block to OOS. When the changes are complete,
change the mode back to AUTO.
Mode parameters
Mode parameters are used to change the block mode from one state
to another. There are four types of mode parameters: Target, Actual,
Permitted, and Normal.
The Target mode is the mode assigned to a block and is used to
change a block to a desired mode.
The Actual mode is the current mode of the block.
The Permitted mode lists the modes that are allowed for a block.
Setting the Permitted modes prevents unauthorized changes to the
operating mode of a block. To do this, configure the Block:Mode
Permitted parameter to allow only the desired operating modes. It is
recommended to always select OOS as one of the Permitted modes.
The Normal mode is the mode the block should be set to during normal
operation conditions.
Locate mode parameters
In the resource and transducer blocks, the mode parameters are
normally found in the Process menu. In all other function blocks, they
are found in the Common Config menu. The mode parameters are
also included in the All parameter list; see
“Device blocks” on page 69.
You can view and edit the Target mode parameter by tapping the
MODE button in the menus.
Page 68
68
Fieldbus functionality
Change modes
Whenever you need to change the parameters or properties of a block,
you nee
d to change the mode. A warning message may appear if the
mode of any block is included in a list of parameter changes to be sent
to a device.
To change the block mode:
1.Tap the MODE b
utton in the Block Menu or at the bottom of a
screen. See Figure 4-7.
2.If prompted, select a block from the list and tap OK.
3.Remove the checkmark next to the current mode by tapping the
checkbox next to it
. An asterisk (*) symbol appears next to Block
Mode Target and the checkboxes are highlighted yellow to indicate
the change to the Target mode has not been sent to the device. If the
mode checkboxes are read-only, the block may have been set to
allow only one mode.
4.Tap the checkbox next to a mode to select it as the new Target
mode.
5.Tap OK.
6.When the message appears, tap YES to apply and
send the change
to the device, or tap NO to cancel. A Mode Change window showing
the Target mode and Actual mode appears until the Actual mode
changes. If the window does not disappear, the actual mode cannot
be changed due to the current device state. Tap CLOSE to close the
Mode Change window.
Figure 4-7. Device Block Menu and Mode window
Page 69
Fieldbus functionality
Device blocksThe Block Menu is a submenu of the Block List and it displays block
information for the fieldbus device to which you are connected. The
Block Menu is also available from the Advanced option in a Device
Dashboard menu.
Devices that do not support transducer block menus within the device
description have the following selections: All, Process, Status, Other.
If methods are incorporated into the transducer block, they may be
displayed as either Diagnostic Methods or Calibration Methods.
Tap All to display all of the parameters for the desired block. It may
take several minutes to display the parameters. It is recommended that
you use this only if you are unable to find your desired selection
elsewhere.
Displaying the Block Menu
If the device description supports menus, you can display the Block
Menu by performing the following steps:
1.From the Live Device List, double-tap a device to display the Block
List. See
available from the Advanced menu.
2.Double-tap the desired block tag.
3.From the Block Menu, double-tap the desired parameter group.
page 66. For Device Dashboard menus, the Block List is
69
NOTE
The Block mode must be in the appropriate state to accept parameter
changes. Typically, the mode is MAN or OOS.
Displaying parameters
To display the parameters for fieldbus devices:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap the desired block from the Block List or the appropriate
item from a Device Dashboard menu.
4.Double-tap the desired parameter group. The parameters and their
current values appear.
Changing and sending parameter data
Shaded areas in a menu indicate values that cannot be changed. You
can edit only the resource, transducer, and I/O blocks. You can open
and view all other blocks, however, you cannot edit them.
When you modify a parameter value, an asterisk (*) appears and the
value is highlighted yellow to indicate the change has not been sent to
the device.
Page 70
70
Fieldbus functionality
CAUTION
Changing device parameters could adversely affect the control of your
process. Put the control loop in Manual/Out of Service before applying
changes. Verify the output before returning the control loop to Auto.
Failure to do so could result in property damage, serious injury, or
death. Ensure all safety precautions and work procedures have been
followed.
To change the values for parameters:
1.Display the parameters for the device.
2.Double-tap the desired parameter.
3.Change the value for the parameter. (Tap HELP to view a description
he parameter.)
of t
4.Tap OK.
5.Tap SEND t
Repeat these steps for other parameters as necessary.
o commit your changes to the connected device. After
you tap SEND, the modified values are no longer highlighted yellow.
Displaying the status of a block
Different devices have different options associated with them and the
selection
s on these menus vary accordingly. See your device
documentation for more information on supported menu items.
To display device status:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap the desired block.
4.Double-tap St
atus. Status parameters appear.
Running methods
Different devices have different methods associated with them, and the
selection
s on these menus vary accordingly. See your device
documentation for more information on supported menu items.
To run methods:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap the desired block (typically, methods are run in the
sducer block).
tran
4.Double-tap a menu containing meth
ods. The menu option will vary
for each device.
5.Double-tap the type of method you want to run, for example,
ration or diagnostic. Follow the prompts on the windows to run
calib
the method.
Page 71
Fieldbus functionality
71
Displaying device information
NOTE
The physical device tag and address of a device are read-only when
the device is commissioned or, at a minimum, any of the following
hosts/linking devices are detected on the segment: Rosemount 3420,
DeltaV, Ovation, Allen-Bradley FFLD and FFLDC, Honeywell Experion
PKS, Yokogawa Stardom or CENTUM, Softing FG-100/HSE, or SMAR
DF62. To change the device tag or address, use the host system or
remove the device from the segment and connect it directly to the 475
Field Communicator.
To display the Physical Device Tag, Device Address, Device ID, and
the Device Revision:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap Advanced.
4.Double-tap Detail.
5.Double-tap one of the following options:
• Physical Device Tag designates a device’s identity in the system.
• Address is the data link layer node address of the device. The host
control system has the ability to assign an address to a device when
it is connected to a segment. When assigning device addresses,
follow the guidelines below:
• Valid device addresses for fieldbus devices are 20 through 247
with the exception of the addresses between V(FUN) and
V(FUN) + V(NUN)-1 parameters as defined for the 475; see
“Changing the fieldbus polling addresses” on page 75. These
parameters are available in the Polling menu.
• Addresses between 16 and 19 are usually reserved for host
systems. A device should not be assigned in this address
range.
• Addresses below 16 are not available.
• Addresses between 248 and 251 are temporary addresses.
Devices without a tag or address appear on the segment at
these addresses.
• Addresses in the range 252 to 255 are reserved for visitors,
such as the 475 Field Communicator.
• Device ID is the unique number identifier for each device. It is set by
the device manufacturer and cannot be changed.
• Device Revision is the manufacturer revision number. It is used by
an interface device to locate the device description and cannot be
changed.
Page 72
72
Fieldbus functionality
6.Select Yes or No when you are asked if the device is commissioned.
You cannot change the physical device tag or address if the device is
commissioned.
7.Using the SIP keyboard, enter the new information. When you
modify a parameter value, an asterisk (*) appears and the value is
highlighted yellow to indicate the change has not been sent to the
device.
8.Tap OK.
9.Tap SEND to send the changes to the device. A window appears
until the changes are made.
10.Tap YES, if prompted.
Displaying network settings
To view the network parameters for the device or segment:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap Advanced.
4.Double-tap Network Management.
5.Double-tap the desired label to view the values.
Tap the SAVE button to save this as a text file. Connect your 475 Field
Communicator to the Field Communicator Easy Upgrade Utility to
transfer this file to a PC. The file appears in the User Data tab.
Changing the I/O block schedule
Changing the I/O Block Schedule is typically done on the bench (not
connected to a control system) when you want to execute an I/O block
to verify that the outputs of the block are computed correctly.
NOTE
You cannot schedule I/O blocks when the device is commissioned or,
at a minimum, any of the following hosts/linking devices are detected
on the segment: Rosemount 3420, DeltaV, Ovation, Allen-Bradley
FFLD and FFLDC, Honeywell Experion PKS, Yokogawa Stardom or
CENTUM, Softing FG-100/HSE, or SMAR DF62. To schedule I/O
blocks, use the host system or remove the device from the segment
and connect it directly to the 475 Field Communicator.
To change the schedule:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap Advanced.
4.Double-tap Schedule.
5.Select Yes or No when you are asked if the device is commissioned.
You cannot schedule blocks if the device is commissioned.
6.Select the appropriate MacroCycle from the drop-down list.
Page 73
Fieldbus functionality
73
7.Tap the appropriate checkboxes next to the I/O blocks.
8.Tap OK. This schedules the blocks and sets the block mode to Auto.
9.After reading the note, tap OK to acknowledge that the I/O blocks
were successfully scheduled.
Instantiating blocks
The Instantiate Block menu lets you add function and transducer
blocks to a connected device. This menu item appears only if the
fieldbus device contains instantiable block types. After a block has
been instantiated, the view displays the new block. The Actual mode of
the new instantiated block is set to OOS.
NOTE
You cannot instantiate or delete blocks when, at a minimum, any of the
following hosts/linking devices are detected on the segment:
Rosemount 3420, DeltaV, Ovation, Allen-Bradley FFLD and FFLDC,
Honeywell Experion PKS, Yokogawa Stardom or CENTUM, Softing
FG-100/HSE, or SMAR DF62. To instantiate or delete blocks, use the
host system or remove the device from the segment and connect it
directly to the 475 Field Communicator.
To instantiate a block:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap Advanced.
4.Double-tap Instantiate Block.
5.Select Yes or No when you are asked if the device is commissioned.
You cannot instantiate blocks if the device is commissioned.
6.Tap the type of block that you want to add to the device.
7.Tap OK to add the block to the device. Tap CANCEL to exit the
window without adding a block.
8.When the warning message appears, tap YES to instantiate the
block, or NO to cancel the operation.
Deleting instantiated blocks
The Delete Block menu lets you delete instantiated blocks from a
fieldbus device; you cannot delete permanent blocks. You can delete
only one instantiated block at a time, and the Actual mode in the
device must be set to OOS. If the Delete Block menu item is selected
and no blocks have been instantiated in the device, an error message
appears. After a block has been deleted, the window is refreshed and it
does not display the deleted block.
To delete an instantiated block:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap Advanced.
Page 74
74
Fieldbus functionality
4.Double-tap Delete Block.
5.Select Yes or No when you are asked if the device is commissioned.
You cannot delete blocks if the device is commissioned.
6.Tap the block that you want to delete from the device.
7.Tap OK.
8.When the warning message appears, tap YES to delete the block, or
NO to cancel the operation.
NOTE
Some devices restart after a block is instantiated or deleted, causing a
loss in communication between the 475 Field Communicator and the
device. After the device and 475 Field Communicator resume
communication, the Live Device List appears.
Setting the device to be a Link Master or Basic device
If a device is capable of becoming a Link Active Scheduler (LAS), the
Link Master Configuration menu option is displayed in the Advanced
menu. The screen shows the current operating class in the drop down
box and lets you select the new operating class. Select Link Master if
you want the device to attempt to be the LAS, or select Basic if you
want to prevent the device from becoming the LAS.
Setting the device as a link master does not set the device as the LAS.
The link master device must follow the fieldbus process to become the
LAS if other link master devices are on the segment.
After you set the option, the device resets and the Field Communicator
temporarily loses communication with the device.
NOTE
You cannot change the device to be a link master or basic device
when, at a minimum, any of the following hosts/linking devices are
detected on the segment: Rosemount 3420, DeltaV, Ovation,
Allen-Bradley FFLD and FFLDC, Honeywell Experion PKS, Yokogawa
Stardom or CENTUM, Softing FG-100/HSE, or SMAR DF62. To
change the device to be a Link Master or Basic device, use the host
system or remove the device from the segment and connect it directly
to the 475 Field Communicator.
Page 75
Fieldbus functionality
To set a device to be a link master or basic device:
1.Display the Live Device List; see page 65.
2.Double-tap a device.
3.Double-tap Advanced.
4.Double-tap Link Master Configuration.
5.Select Yes or No when you are asked if the device is commissioned.
You cannot change the operating class if the device is
commissioned.
6.Select the Basic or Link Master option from the drop down box.
7.Tap OK.
8.Tap OK when prompted that the device will restart. The Live Device
List appears.
9.Wait until the device reappears on the screen.
75
Displaying GraphicsThe Fieldbus Application offers graphical views of device data by using
the enhanced Electronic Device Description Language (EDDL)
technology. Device data can be presented as images, charts, and
graphs. These options appear as items in the Online menu and its
submenus. The placement of the Graphics options in the menus varies
from device to device because it is determined by the device
manufacturer.
To view the graphical representations, you need a device using an
enhanced device description. Only devices using an enhanced EDDL
device description offer graphical representations of data. See
Appendix C for more information about the Graphics functionality.
CONFIGURING THE
FIELDBUS APPLICATION
Changing the fieldbus
polling addresses
Polling is a method of determining which devices are present on a
network. The V(FUN) is the first unpolled node address. V(NUN) is the
number of unpolled node addresses. The addresses between V(FUN)
and V(FUN)+V(NUN)-1 are not polled. The default value for V(FUN) is
200 and the default value for V(NUN) is zero. Narrowing the range of
devices being polled provides a quicker Live Device List refresh.
The DeltaV System Polling checkbox instructs the 475 Field
Communicator to use the same polling scheme as DeltaV. The V(FUN)
and V(NUN) options are read-only when the checkbox is selected.
To change the polling addresses:
1.From the Fieldbus Application main menu, double-tap Utility.
2.Double-tap Polling.
3.Enter values in the V(FUN) and V(NUN) fields and tap OK.
Page 76
76
Fieldbus functionality
Changing the Slot TimeSelect the default Slot Time of 8 to allow the devices to be seen on the
475 Field Communicator Live Device List. From the Fieldbus
Application Utility main menu, double-tap Utility and then double-tap
Link Settings to access the Slot Time menu. It may be necessary to
change the Slot Time to 16 to view older devices on the 475 Field
Communicator Live Device List.
Viewingavailable device
descriptions
The Available Device Description List menu lets you view all the device
descriptions in the 475 Field Communicator. Fieldbus device
descriptions enable the 475 Field Communicator to recognize and
configure fieldbus devices. Use the Field Communicator Easy Upgrade
Utility to download or import new device descriptions and then transfer
them to your 475 Field Communicator. See the Easy Upgrade Utility
Help for more information.
To view the fieldbus device descriptions installed in the 475 Field
Communicator:
1.From the Fieldbus Application main menu, double-tap Utility.
2.Double-tap Available Device Description List. The manufacturer
names of the installed device descriptions are listed.
3.Double-tap the desired device manufacturer to expand the list. The
models available for the manufacturer are listed.
4.Double-tap the desired device model. The device revisions available
for the selected model are listed. One of the following icons appears
next to each device description to indicate its status.
Table 4-1. Device description icons
IconMeaning
A tested device description can be used with the system
software version in the 475 Field Communicator.
An untested device description has not been formally tested
for use with the system software version in the 475 Field
Communicator. The device description can be used, but you
may experience unexpected results.
An incompatible device description cannot be used with the
system software version in the 475 Field Communicator. You
need to transfer a different version of this device description to
the 475 Field Communicator.
Page 77
Fieldbus functionality
77
RUNNING FIELDBUS
DIAGNOSTICS
The Fieldbus Diagnostics menu lets you run diagnostics to
troubleshoot fieldbus networks and devices. You can check the DC
voltage, the noise level at low frequencies, and the signal level and
communication status. The selected tests are automatically repeated
and the test results are updated in the Diagnostics Results window.
To view the values associated with the status indicators or the possible
causes of the values, run the diagnostic test, highlight the test on the
Diagnostics Results window, and tap HELP.
DC voltage measurementThe DC voltage test displays the amount of DC voltage on a segment.
The word Limit appears if the DC voltage measurement is out of the
-37 V to 37 V range. If the DC voltage is out of this range, there may be
a faulty terminator, wiring problem, or power supply problem.
This test displays the measurement value, measurement unit, and one
of the status indicators listed below.
OK- The value is within the acceptable range.
High - The value is greater than 32 V.
Low - The value is less than 9 V.
Error - There is an error in the measurement or within the 475 Field
Communicator.
Noise level measurementThe noise level test displays the amount of noise on the segment. The
word Limit appears if the noise level measurement is greater than 1.0
V. If the low frequency noise is too high, the power supply or power
conditioner may be faulty.
This test displays the measurement value, measurement unit, and one
of the status indicators listed below.
OK- The value is within the acceptable range.
High - The value is greater than 75mv from peak to peak.
Error - There is an error in the measurement or within the 475 Field
Communicator.
Signal level measurementThe signal level test determines if a 475 Field Communicator can
receive signals from devices on a segment. To measure the fieldbus
signal level, make sure a LAS is on the segment. Up to 16 different
nodes are checked. The word Limit appears if the signal level value is
greater than 1.3 V. The word Lowappears if the signal level value is
less than 100 mV.
Page 78
78
Fieldbus functionality
This test displays the node address, measurement value,
measurement unit, and one of the status indicators listed below.
- All signal responses from the device were received by the 475
Field Communicator.
! - One or more signal responses from the device was not received
by the 475 Field Communicator. This may be caused by noise on
the segment.
X - No signal responses from the device were received by the 475
Field Communicator. This may be caused by noise on the
segment.
Error - The measurement value is less than 75 mV or there is an
error within the 475 Field Communicator.
Figure 4-8. Fieldbus diagnostics window examples
DISCONNECTING FROM A
FIELDBUS DEVICE
Prior to disconnecting or turning off the 475 Field Communicator,
check the following items:
• Verify methods are complete.
• Resolve any un-sent data to the device.
Page 79
475 FIELD COMMUNICATOR
SECTION 5TROUBLESHOOTING
OVERVIEWThis section provides basic troubleshooting techniques for the 475
Field Communicator.
Below are methods for troubleshooting networks that are experiencing
problems communicating between a device and the 475 Field
Communicator.
Troubleshooting
suggestions
Answer the questions below and use the tables in this section before
calling Technical Support personnel.
• Does the control system have HART or fieldbus communication
capabilities?
• Is it configured to communicate HART or fieldbus?
• Is it reporting communication problems? If not, stop communications
on the control system and re-test communication with the 475 Field
Communicator.
• Is there a barrier installed?
• Is the barrier capable of passing along the signal?
General troubleshooting information for the system software
If the 475 Field Communicator screen does not respond or it appears
to lock up, you may need to restart and reset the 475 Field
Communicator by doing the following.
1.Simultaneously press the Fn and Backlight keys to shut down the
Field Communicator. The green light on the Power key should turn
off.
2.Power on the Field Communicator by pressing and holding the
Power key.
www.fieldcommunicator.com
Page 80
80
Troubleshooting
HART loops
Verify the HART loop current and voltage on the device. Almost all
devices need at least 4 mA and 12V DC to operate properly.
If there are multiple devices on a multidrop loop, set the 475 Field
Communicator to Poll by Address. See
“Changing the HART polling
options” on page 53 for more information on polling options.
Inspection of the loop wiring can often reveal problems. The shield is
normally grounded at one end only, which is usually the control
system.
Verify the loop has a minimum of 250 ohms resistance. If there is not
an external resistor, then, normally, the total resistance is the
resistance of the process-indicating device monitoring the loop. Check
the manuals for the process-indicating device to determine its loop
resistance. If the resistance of the process-indicating device is
unknown, it can be determined by knowing the current flow in the loop
and the voltage across the process-indicating device.
The resistance can be calculated using the formula, Resistance =
Voltage / Current. The 475 Field Communicator can be used to
measure the voltage; see
“DC voltage measurement (HART
terminals)” on page 57.
Sample values
Loop Current Flow Minimum voltage for 250 ohms.
4 mA 1 Volt
8 mA 2 Volts
12 mA 3 Volts
16 mA 4 Volts
20 mA 5 Volts
If the voltage across the process-indicating device is greater than the
value listed for a given current flow, the device has at least 250 ohms
of internal resistance. If the voltage is less than the value listed in the
table for the given current flow, more resistance needs to be added to
the loop.
If an oscilloscope is available, use it to look for noise on the loop. Use
a scope with differential mode capability or a battery powered/isolated
scope to avoid grounding one side of the loop. Noise with a frequency
of 500 Hz to 10,000 Hz is of particular interest, as this represents
frequencies near the HART frequencies of 1200 and 2200 Hz.
Page 81
Troubleshooting
81
Table 5-1. Troubleshooting table for the HART protocol
SymptomPossible causesSolution
Intermittent
communication
No communication
with device.
Cannot connect to a
HART device.
Control system is
communicating
HART, but the Field
Communicator is
not communicating
properly.
Insufficient loop current
and voltage at the
device terminals.
Verify there is at least 4
mA and 12V DC at the
device terminals; see
“DC voltage
measurement (HART
terminals)” on page 57.
Noise on the field loop.
Noise or signal distortion
from the control system,
i.e., noise from the
power supply powering
the devices or front end
analog circuitry inside
the control system may
be distorting the HART
signal.
Poor wiring.Check wiring
terminations and
exposed signal wire for
damage.
Insufficient loop
resistance at the HART
frequencies.
Add an additional 250
ohm resistor in series in
the loop. Place the
leads across the resistor
and verify if
communication has
been restored.
Insufficient loop current
and voltage at the
device terminals.
Verify that there is at
least 4 mA and 12V DC
at the device terminals;
“DC voltage
measurement (HART
terminals)” on page 57.
Device may be set to a
HART address other
than zero (multidrop
mode).
Change Polling mode to
Poll by Address. See
“Changing the HART
polling options” on
page 53.
The polling address or
tag may not match the
device.
Check the Polling
Options to ensure the
proper polling type is
selected.
HART communication is
being prevented by the
control system.
Stop HART
communications on the
control system and
verify if communication
between the devices
and the 475 is restored.
Page 82
82
Troubleshooting
A HART device
appears at the
multiple addresses.
More than one Field
Communicator or other
Secondary Master may
be attached to the
control loop.
The incorrect polling
addresses may be used.
HART Universal
Revision 5 (or earlier), 6,
and 7 devices are on the
same loop
Ensure there is only one
Primary Master and one
Secondary Master on
the control loop.
Change the addresses
being polled. See
“Changing the HART
polling options” on
page 53.
Put HART Universal
Revision 5 or earlier
devices on a separate
loop from HART
Universal Revision 6 or
7 devices.
Page 83
Troubleshooting
83
Table 5-2. Troubleshooting table for the fieldbus protocol
SymptomPossible causesSolution
No
communication
with device.
Connected to a
segment in a
bench
configuration and
the Live Device
List remains
blank (even the
Field
Communicator
does not appear).
Unable to change
the address of a
device.
The Field
Communicator
does not remain
the LAS on a
segment.
The Field
Communicator is
connected to a
segment with DeltaV
and the device on
the same segment is
being commissioned
using DeltaV.
This issue is caused
by the speed at
which certain
LAS-enabled
devices are
attempting to run the
segment.
The Field
Communicator is
unable to change the
address of a device
that is currently the
LAS.
A host takes over as
the LAS.
A backup LAS takes
over as the LAS. The
lower the address
and Slot Time of the
device, the more
likely this will occur.
The Field Communicator is
unable to communicate with
this device until you go
offline and then back online.
Establish communication by
putting the Field
Communicator on the
segment first and then
adding one or more devices.
By putting the Field
Communicator on first, it will
remain the LAS and control
the communication.
Establish communication by
putting the Field
Communicator on the
segment first and then
adding one or more devices.
By putting the Field
Communicator on first, it will
remain the LAS and allow
the address change.
When a host is established
on a segment, it will take
over as the LAS. No action
is required.
See “Changing the Slot
Time” on page 76.
Page 84
84
Troubleshooting
ERROR AND STATUS
MESSAGES
Table 5-3. Field Communicator error messages
General error messagesDescription
License file check failed - error code
x. Please contact service center to
License file check failed during
power- up.
resolve this problem.
Press OK to turn off. (Where x
indicates the test that failed.)
Warning: System incompatibility
detected - error code x. Start Listen
For PC and use the Easy Upgrade
Hardware version or operating
system in your Field
Communicator is not compatible.
Utility to resolve this, turn off your
Field Communicator and contact
service center to resolve this.
(Where x is an error code indicating
what the incompatibility detected
was or related errors.)
Installation file is corrupt - error code
The installation is corrupt.
x. Please call service center to
resolve this problem. Press OK to
turn off.
This Field Communicator is not
licensed for F
OUNDATION Fieldbus.
Your 475 Field Communicator is
not licensed for FOUNDATION
fieldbus functionality. Contact your
sales representative for
information about adding this
functionality.
The Field Communicator is not
licensed for Bluetooth
communication.
Your 475 Field Communicator is
not licensed and does not have
the necessary hardware for
Bluetooth communication.Contact
your sales representative for
information about this functionality.
The Field Communicator does not
detect a System Card. Please make
sure your System Card is properly
installed in its slot. Press OK to turn
off.
The System Card is improperly
installed in the System Card
socket or the System Card is
missing. The System Card socket
is spring-loaded. Ensure that when
you insert the System Card into
the socket, you hear a click.
Also ensure the System Card has
the metal card contacts facing up
when you insert the card. See
“Installing the System Card and
the battery” on page 21. The
System Card may be damaged if
inserted improperly.
Page 85
Troubleshooting
Table 5-4. HART Application error messages
HART error messagesDescription
Hart Application Error... “registry
failure”...Reinstall System Files...See
User's Manual for details.
A registry setting in the 475 is
corrupted. From the Field
Communicator Main Menu, do the
following:
1. Tap Settings.
2. Tap About.
3. Double-tap RE-FLASH.
4. Tap Yes to proceed.
Voltage detected on FF connectors.
Check your connectors and press
OK.
Insert the lead set connectors into
the HART communication
terminals on the top of the 475.
The access door shows which
protocols terminals are exposed.
CDC Error...“failure while switching
to HART”...Reinstall System
Files...See User’s Manual for details.
The HART Application fails to put
the CDC in HART mode for talking
to a HART device. From the Field
Communicator Main Menu, do the
following:
1. Tap Settings.
2. Tap About.
3. Double-tap RE-FLASH.
4. Tap Yes to proceed.
DD Error…"tokenizer
mismatch"…DD version
<manufacturer name, device name,
dev. rev. #, and
DD rev. #>; HART application
<version x.y>; HART app version
x.y...Reinstall DD…See
Programming Interface for details.
The version of the tokenizer used
to tokenize the device description
is not what the HART Application
expects and the device description
is incompatible with the installed
HART Application version.
Upgrade the system software and
device descriptions in the Field
Communicator using the Field
Communicator Easy Upgrade
Utility.
DD Error…"linker mismatch"...DD
version x.y; HART app version
x.y...Reinstall DD…See
Programming Interface for details.
name, device name, dev. rev. #, and
DD rev. #>…you may experience
unexpected or inappropriate
results…See Programming Interface
for details on DD updates…Do you
want to accept these risks and
proceed?
DD Error…"tested-to sequence
mismatch"…DD version
<manufacturer name, device name,
dev. rev. #, and
DD rev. #>; HART application
<version x.y>; HART app version
x.y…See Programming Utility for
solution.
DD Error…"developed-to
mismatch"...DD version
<manufacturer name, device name,
dev. rev. #, and
DD rev. #>; HART application
<version x.y>; HART app version
x.y...See Programming Utility for
details
Device Description Error...'Device
Description header file
corrupted'...To repair, reinstall the
Device Descriptions for %s %s dev
rev %d DD rev %d...see
Programming Utility for
details...Press FWDCOM to attempt
to load an earlier Device
Description."
Communication Error…See User's
Manual for solution.
The device description was not
tested and verified with the
installed version of the HART
Application. Obtain a newer
version of the device description
using the Field Communicator
Easy Upgrade Utility.
The DD was tested with a previous
version, but not with this version of
the HART Application. Obtain a
newer version of the device
description using the Field
Communicator Easy Upgrade
Utility.
The DD was developed using a
later HART Application revision.
Upgrade the system software and
device descriptions using the Field
Communicator Easy Upgrade
Utility.
There is a checksum error in the
device description header file.
Obtain a newer version of the
device description using the Field
Communicator Easy Upgrade
Utility.
Check the wiring to the device.
Page 87
Troubleshooting
87
Forward Compatibility Blocked…The
Device Description for x Device Rev
x dd Rev x cannot be used in forward
compatibility mode…x… Press OK
to load the Generic Device
Description.
Device Description Not
Installed…The Device Description
for device type x device rev x is not
installed on the System Card…See
Programming Interface for details on
Device Description updates…Do you
wish to proceed in forward
compatibility mode?
Do you want to ignore this message
while communicating with this
device?
The HART Application attempts to
use a device description to run in
forward compatibility mode and
cannot. A generic device
description will be used.
The device description for the
connected device is not in the 475
Field Communicator. If you have
the Easy Upgrade option, you can
add device descriptions to your
475 Field Communicator from the
Field Communicator Easy
Upgrade Utility.
The HART Application lets you
ignore some response code
warning messages, such as
Update Failure, while
communicating with a device. The
next time you communicate with
the device, this message will
appear.
Page 88
88
Table 5-5. Fieldbus Application error messages
Fieldbus error messagesDescription
Connection Error - Voltage Detected
on HART connectors. Please check
your connectors. Press OK to retry
connecting to the segment. Press
CANCEL to end the Fieldbus
Insert the lead set connectors into
the fieldbus communication
terminals on the top of the 475.
The access door shows which
protocols terminals are exposed.
Application.
Connection error - Polarity reversed
on the fieldbus segment connection.
Please reverse connectors. Press
OK to recheck polarity.
The lead set connectors attached
to the 475 Field Communicator
need to be reversed (rotated) and
reconnected to the 475. The
fieldbus terminals are polarity
sensitive.
DDP Error 1: Unable to load DD.
Press OK to return to Block List.
Using the Field Communicator
Easy Upgrade Utility, check to see
if this device description is
available to load into your 475
Field Communicator. If not,
contact the device manufacturer.
There has been a loss of
communication with one or more
Check connection to fieldbus
devices.
devices on the segment. Press OK
to return to the Fieldbus Live Device
List.
The Field Communicator has been
disconnected from the segment.
Press RETRY to attempt to
reconnect to the segment. Press
Verify that the 475 Field
Communicator lead set is still
securely connected to the FF
Segment and tap RETRY.
CANCEL to return to the Fieldbus
Application main menu. Press EXIT
to exit the Fieldbus Application.
SM ERROR: FAILED RESPONDER
IDENTIFY
There is a problem sustaining
communications with the device.
Contact 475 Field Communicator
Technical Support personnel.
FFLIB: Incompatible DD Static
Description
The device description (DD) does
not match the actual device.
Use the Field Communicator Easy
Upgrade Utility to see if a new DD
is available for that device.
Contact 475 Field Communicator
Technical Support personnel. See
http://www.fieldcommunicator.com
.
Device Upload aborted. Press OK to
return to the Fieldbus Live Device
List.
Communication with a device has
timed out. This should normally
not happen, unless a host was
selected. Contact 475 Field
Communicator Technical Support
personnel.
Troubleshooting
Page 89
Troubleshooting
89
Function Block Service Error:
Parameter Check
Function Block Service Error:
Exceeds Parameter Limits
Function Block Service Error: Wrong
Mode For Request
SM ERROR: REMOTE ERROR
INVALID STATE
FF Library System Management
Error. SM Set Address Failed.SM
Error SM ERROR: Failed.
RESPONDER IDENTIFY
or
Fieldbus Library error code -49
FBLIB: Address outside of range set
in Field Communicator.
The parameter value being
entered is invalid for this device.
Check with the device supplier.
Make sure the value entered is
valid for that specific device
parameter.
The parameter value being
entered is outside the range of
valid values for the device
parameter. Check with the device
supplier. Make sure the value
entered is in the correct range for
that device parameter.
The block is in the wrong mode to
accept the parameter change
being requested. See “Change
modes” on page 68 for information
on how to change block modes.
An attempt to change the address
of the device serving as the LAS
on the segment is being made.
Changing the device address of
the LAS is not recommended.
These messages typically occur
when there is an error changing a
device address.
Possible solutions:
1.Make sure the 475 Field
Communicator is the LAS. Some
LASs may not let you change the
device address.
2. Make sure the address is not
already used by another device.
3. Make sure the polling range is
set to poll the device address.
Page 90
90
Troubleshooting
INFORMATION FOR
TECHNICAL SUPPORT
Before you call Technical Support personnel, have a detailed
description of the issue, including the information below (if applicable).
Have the User’s Manual for the device available.
• 475 Field Communicator system software revision.
• What is the serial number of the 475 Field Communicator having the
communication issue? This is located on the label on back of the
Field Communicator. The battery also has a serial number, but this
does not apply to the Field Communicator unit.
• Manufacturer and model of control system.
• Does the control system support HART or fieldbus communications?
• Device manufacturer name (or ID) and model revision of device (as
displayed on the 475 Field Communicator, exact spelling if possible.)
• What task is being performed when the communication problem
occurs?
• Can AMS Device Manager or another Field Communicator talk to
the device?
• Are you having communication problems with multiple devices?
• Are there any error messages displayed when attempting to
communicate with a device (e.g., device not found)?
• Does communication work when certain devices or processes are
not running?
• What is the total cable length run from the termination panel to the
device?
• What is the loop impedance in the HART device loop? (resistance
value)
• If a HART multiplexer is being used, what is the manufacturer and
model?
• Is the device in burst mode?
• Is the device address set to "0"?
• Is there more than one device on the loop?
• Is there another master (primary or secondary) on the loop? (i.e.,
control system, multiplexer, etc.)
Contacting Technical Support personnel
Contact your supplier or go to http://www.fieldcommunicator.com for
Technical Support contact information.
Page 91
APPENDIX AREFERENCEDATA
PROCESSOR AND
MEMORY SPECIFICATIONS
475 FIELD COMMUNICATOR
Microprocessor80 MHz, max 133 MHz Hitachi
®
SH3
MemoryInternal Flash
32 MB
System Card
1 GB Secure Digital card or higher
RAM
32 MB
PHYSICAL
SPECIFICATIONS
WeightApproximately 1.65 lb (750 grams) includes battery
Display3.5” diagonal, 1/4 VGA (240 by 320 pixels) color touch screen
Hard-coated surface
Dimensions approximately 2.81” x 2.11” (71.5 mm x 53.6 mm)
KeypadThe keypad consists of the following:
• A Power key to turn on and off the 475 or to put it in standby
• A Backlight key to adjust the intensity of the light on the screen
• Four navigation (arrow) keys to select, open, and back out of menu
items
• An Enter key to open menu items from the Field Communicator Main
Menu or Settings menu, and select any highlighted button
• A Tab key to move between buttons or fields on a window
• A Function key that enables alternate functionality indicated by the
blue text near the keys
• Alphanumeric keys for entering data
www.fieldcommunicator.com
Page 92
92
USAGE SPECIFICATIONS
Temperature limits+14°F to +122°F (-10°C to +50°C)
0% to 95%RH (non-condensing) for +32°F to +122°F (0°C to +50°C)
Storage with batteries -4°F to 131°F (-20°C to +55°C) for less than 1 month
Storage without batteries-4°F to +140°F (-20°C to +60°C)
Enclosure ratingIP51 (front)
ShockPasses the 1-meter drop test onto concrete
General guidelines• Only use new, original parts.
• Do not recharge the battery in hazardous areas.
• Have repairs done by only qualified personnel.
• Charge or power using only the Field Communicator power
supply/charger.
CONNECTION
SPECIFICATIONS
HART and fieldbus
communication terminals
Three 4mm banana plugs (one common terminal to both HART and
F
OUNDATION fieldbus.)
Connection typesIrDA port
± 15 degrees recommended maximum angle between the 475
interface and adapter or PC.
18 in. recommended maximum distance between the 475 interface
and adapter or PC.
Bluetooth interface
The Bluetooth Interface is a licensed option for the 475 Field
Communicator. If your 475 is not licensed for Bluetooth, it does not
have a Bluetooth radio.To use Bluetooth you need an approved
adapter using the Windows Bluetooth software and drivers (stack)
included with Windows XP Professional Service Pack 2 or 3, Windows
Vista Business Service Pack 1, or Windows 7 Professional. The
adapter should be plug-and-play if no other Bluetooth software or
drivers were installed on your PC. The Easy Upgrade Utility cannot
communicate with an adapter using third-party drivers. See
www.fieldcommunicator.com or the readme file for more information.
30 feet (10 meters) recommended maximum distance between the
475 and a Bluetooth adapter attached to a PC.
Page 93
Card reader
Only supported card readers can be used with the System Card.
Unsupported card readers may corrupt files. See the readme file on
your Resource CD or DVD or www.fieldcommunicator.com for the list
of supported card readers.
The card reader can be used only with the Field Communicator Easy Upgrade Utility.
93
BATTERY
SPECIFICATIONS
Battery typeTwo rechargeable Li-Ion cells, not serviceable
ConnectionGreen six-pin mini din (female) jack on the side of the battery
Charge+50°F to +104°F (10°C to +40°C)
Guidelines for the Li-Ion battery (Power Module)
• Do not recharge the battery in hazardous areas. The power
supply/charger is not IS-approved.
• Charge or power using only the Field Communicator power
supply/charger.
• Recharge the battery frequently, preferably after each use. Limit full
discharges, if possible.
LightsFive lights (LEDs) on the side of the battery indicate the remaining
level of battery charge. When you press and release the Charge
Indicator button below these lights, the lights slowly illuminate. Each
light indicates 20 percent of remaining charge, and the battery is fully
charged when all of the lights are illuminated. See
page 2-12 for the location of the Charge Indicator button.
Figure 2-1 on
Operating time10 or more hours when the backlight is to highest setting
20 or more hours when the backlight is off
80 or more hours when using standby
Storage-4°F to +131°F (-20°C to +55°C) less than one month
Storage Guidelines for the Li-Ion Battery
• Use a location at room temperature or cooler. Prolonged storage at
higher temperatures can permanently reduce the charge capacity
and performance.
• Ensure the remaining charge is at or near mid-capacity. The charge
will slowly drain during storage. Periodically recharge the battery
during storage to ensure it does not drain to low levels.
Page 94
94
POWER
SUPPLY/CHARGER
SPECIFICATIONS
ConnectionGreen six-pin mini din (male) plug
LightsThe power supply/charger has three colored lights that indicate the
conditions below. Each light displays a different color.
Color Condition
GreenThe battery is fully charged.
Flashing green The battery is nearly fully charged.
YellowThe battery is charging.
Flashing yellowThe power supply/charger is not connected
to the 475 Field Communicator.
Flashing yellow and
red
RedCharging cannot occur. Contact Technical
The remaining charge in the battery is low.
Support for more information.
Voltag e100-240 VAC, 50/60Hz,
US/UK/EU connection types included
Technical data
Input voltage100 - 240 VAC ±10%
Input current750 mA max.
Standby current20 mA max.
Input fuse typeTES 2A 250 V Timelag
Output voltage 10 - 8.3 V
Output current 11000 mA max.
Output voltage 20 - 9.0 V
Output current 21400 mA max.
Output power rating20 W
Operating temperature0°C - +40°C
Storage temperature-20°C -+80°C
Measurements [L x B x H]112 mm x 51.5 mm x 29.5 mm
Total Mass240 g.
AltitudeUp to 2000m
Pollution Degree2
Installation Category2
IEC Protection ClassDouble Insulation
Page 95
ORDER INFORMATION
95
Model
Product Description
475Field Communicator (Note 1)
Code
Communication Protocol
HHART
FHART and FOUNDATION fieldbus (Note 2)
Code
Battery Type
PRechargeable Li-ion Power Module
Code
Power Supply/Charger
1Power Supply/Charger Li-ion/NiMH US/UK/EU
connection types included (Note 3)
9Not Included (Note 4)
Code
Language
EEnglish
DGerman
JJapanese
RRussian
CChinese
FFrench
PPortuguese
Code
Product Certifications
KLATEX, FM, CSA and IECEx Intrinsically Safe
(includes FISCO as applicable)
NANo Approval
Code
Easy Upgrade
UEasy Upgrade Option (Note 5)
9Not Included
Code
Included Options
Graphics (Included at no charge) (Note 6)
GMDevice Configuration Management (Included at no
charge)
(Note 7)
CodeBluetooth
TBluetooth Communications (Note 8)
9No Bluetooth Communication (Note 8)
CodeOptions
Spare Battery
ASpare Rechargeable Li-ion Power Module (Note 9)
Enclosures
SProtective Rubber Boot with Stand
Typical HART Model Number: 475 H P 1 E KL U GMT
Typical HART/Fieldbus Model Number: 475 F P 1 E KL U GMT
(1) Base Model 475 includes Field Communicator unit with color LCD display, System Card,
Leadset with connectors, Carrying Case, Getting Started Guide, 475 Resource CD or
DVD, stylus and straps.
(2) This option requires that the Easy Upgrade option (code U) is specified.
(3) To obtain an Australian Power Cord, order part number 00375-0003-0003.
(4) This option should only be considered if the user already has a 375 or 475 Power
Supply/Charger. If it is a 375 Power Supply/Charger, it must be the Li-Ion/NiMH version.
Page 96
96
(5) The Easy Upgrade feature allows the user to add new System Application software and
device descriptions (DDs) to the 475 for a period of 3 years. To upgrade without this
feature, the System Card would have to be sent to a Service Center.
(6) The Graphics Option enables a user to access enhanced graphical features when using
the HART or FOUNDATION fieldbus application.
(7) Device Configuration Management provides the capability to store up to 1000
configurations and print them using the Easy Upgrade Utility.
(8) Bluetooth enables communication to a PC via the Bluetooth protocol. See list of countries
with Bluetooth approval at www.fieldcommunicator.com.
(9) A fully charged Li-Ion Power Module is capable of delivering power for 40 hours of typical
field use. If requirements exceed this specification, a spare Power Module (code A) should
be specified.
Page 97
SPARE PARTS LIST
97
Description
Part Number
Ruggedized 250 Ohm Load Resistor00275-0096-0001
Rechargeable Li-Ion Power Module00475-0002-0022
Power Supply/Charger (Li-Ion/NiMH) US/UK/EU
00475-0003-0022
connection types included
Power Supply/Charger Standard cord set
00375-0003-0002
(US/UK/EU cords)
Australian (AU cord) for Power Supply/Charger 00375-0003-0003
Lead Set with connectors 00375-0004-0001
Hand Strap (pack of 2)00475-0005-0002
Carrying Case (with spare Hand Strap and Stylus) 00475-0005-0003
Magnetic Hanger 00475-0005-0004
Protective Rubber Boot with stand (Boot available to
00475-0005-0005
ship Dec. 09)
Stylus (pack of 2)00475-0006-0001
IrDA to USB Adapter (Note 1)00375-0015-0002
System Card (SD) Reader (with USB interface)
00375-0018-0022
(Note 2)
Bluetooth Adapter (Note 1)00475-0018-0023
Stand00475-0044-0001
Field Accessory Kit (Note 7)00475-0019-FK01
Shop Accessory Kit (Bluetooth) (Note 8)00475-0019-SK01
Shop Accessory Kit (Non-Bluetooth) (Note 8)00475-0019-SK02
Getting Started Guide00475-0045-3001
Resource CD00475-0049-0001
Resource DVD (Note 9)00475-0049-DVD1
Technical Training CD00475-0050-TRN1
Online Licensing (Note 4)
FOUNDATION fieldbus license via Web00375-0142-0002
Easy Upgrade (New) license via Web (Note 3)00375-0142-0003
Easy Upgrade (Renew) license via Web (Notes 3
00375-0142-2003
and 5)
AMS Device Manager Handheld Interface Kit
(Note 6)
AMS Suite: Intelligent Device Manager
AW7005HC00025
Field Communicator Interface Kit (25 tags)
AMS Suite:Intelligent Device Manager
AW7005HC20000
Field Communicator Interface Kit (100 tags and
above)
(1) Can be used to support communication between the 375/475 and the Easy Upgrade
Programming Utility or AMS Device Manager (with Handheld Communicator Interface Kit).
Either IrDA or Bluetooth Communication is required to register the 375/475 or use the
Online Licensing system.
(2) The System Card (SD) Reader allows a user the ability to upgrade a System Card much
faster than they can when using IrDA or Bluetooth. Due to the file size constraints, major
upgrades require the use of a card reader.
(3) The Easy Upgrade feature allows the user to add System Application Software and device
descriptions (DDs) to the 475 for a period of 3 years. To upgrade without this feature, the
System Card would have to be sent to a Service Center (fee would apply).
Page 98
98
(4) These parts support license upgrades of System Cards in the field through the use of the
Field Communicator Online Licensing system. The capability is available to end users and
may also be performed by an agent on the user’s behalf. It is at the agent’s discretion if an
additional fee should apply. Any order must be accompanied by the System Card S/N.
Instant notification of when the licenses are available for download are sent to emails
provided at time of order. For further details, see the Online Licensing procedure at
www.fieldcommunicator.com.
(5) The ReNew option is available on System Cards where the Easy Upgrade license has
been expired for less than 90 days. Date of expiration can be obtained by interfacing the
475 with v3.0 (or higher) of the Easy Upgrade Programming Utility.
(6)Requires AMS Device Manager (version 6.2 or higher). Both AMS Device Manager and the
Handheld Communicator Interface kit are available for sale through select channels only.
See www.assetweb.com for further details.
(8) Contains Field Accessory Kit plus System Card Reader, Bluetooth Adapter , and Resource
CD and DVD. Non-Bluetooth model substitutes IrDA to USB adapter for Bluetooth
adapter.
(9) Same content as Resource CD, but also includes localized versions for English, German,
Russian, Chinese, and Japanese.
Page 99
475 FIELD COMMUNICATOR
APPENDIX BPRODUCTCERTIFICATIONS
OVERVIEWAll 475 Field Communicators come with the main unit label (see
Figure B-1). Intrinsically Safe (KL option) 475 Field Communicators
also have an additional label opposite the main unit label on the back
of the Field Communicator. If the 475 Field Communicator does not
contain this label (NA option), then it is considered non-IS approved.
The Declaration of Conformity and other approval information are
available on www.fieldcommunicator.com.
The Federal Communications Commission (FCC), Industry Canada
(IC), Telecommunications Regulatory Authority (TRA), and Radio and
Telecommunications Terminal Equipment (R&TTE) approvals apply to
only 475 Field Communicators licensed for Bluetooth. A labels appears
on the back of the Field Communicator if it is licensed for Bluetooth.
APPROVED
MANUFACTURING
R. STAHL HMI Systems GmbH —Cologne, Germany
LOCATIONS
FCCThis equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the
user’s manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Any modifications made to this device that are not approved by
Emerson Process Management may void the authority granted to the
user by the FCC to operate this equipment.
ICThis Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme
NMB-003 du Canada.
www.fieldcommunicator.com
Page 100
100
TELECOMMUNICATIONS
OMAN - TRA TRA/TA-R/0089/11 D080273
REGULATORY
AUTHORITY
EUROPEAN DIRECTIVE
INFORMATION - CE
COMPLIANCE
R&TTE (1999/5/EC)
Electro Magnetic
Compatibility
This equipment is in conformity with the Radio and
Telecommunications Terminal Equipment (R&TTE) Directive
1999/5/EC, ETSI EN 300328 V1.81:2012-06, and IEC 62209-2:2007
standards.
Tested to the EN 61326-1:2006 and ETSI EN 301489-17:2002-08
specification.
(2004/108/EC)
Low Voltage (2006/95/EC)Tested to the EN 61010-1:2001 specification.
ATEX Directive (94/9/EC)
See “European Certifications” for more information.
(KL option only)
HAZARDOUS LOCATIONS
CERTIFICATIONS
(KL
The Intrinsic Safety approvals listed in this section include compliance
with the FISCO requirements.
OPTION ONLY)
European CertificationsATEX Intrinsic Safety (KL option only)
This equipment complies with the ATEX Directive (94/9/EC).
Specific ATEX Directive Information is located within this section and in
the
475 Field Communicator Getting Started Guide.
Applicable standards EN 60079-0:2012, EN 60079-11:2012, and EN
79-26:2007.
600
Certification No.: BVS 09 ATEX E 022
II 2 G (1 GD) Ex ia [ia Ga] [ia Da IIIC] IIC T4 Gb (-10°C ≤ Ta ≤
+50°C)
0158
HART Intrinsically Safe Electrical Parameters
Input Parameters
U
i
I
i
P
i
L
i
C
i
= 30 Volt DC
= 200 mA
= 1.0 Watt
= 0
= 0
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.