Emerson 1F78-151, 1F78-144 User Manual

W905
Clip for
Hydronic
System
W904
Clip for
W905
W904
ELEC GAS
Electric/Gas
Switch
W RH B RC
G O Y
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Cool only, 3-wire, single transformer systems
Cooling System
Fan
Relay
RCOB
JUMPER
WIRE
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Heat only, 3-wire, single transformer systems
TRANSFORMER
Heating System
Fan
Relay
Y
RC
JUMPER
WIRE
For 2-wire Heat only attach to RH and W
NOTE
OB
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Heat/cool, 4-wire, single transformer systems
TRANSFORMER
Heating System
Fan
Relay
Cooling System
RC
JUMPER
WIRE
RED jumper wire (provided
with thermostat) must be connected between thermo­stat's RH and RC terminals for proper thermostat oper­ation with this system.
NOTE
OB
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Heat/cool, 5-wire, two-transformer systems
HEATING TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
24 VAC
120 VAC
Hot
Neutral
COOLING TRANSFORMER
OB
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Heat pump with cool active reversing valve
TRANSFORMER
Reversing
Valve*
RCOB
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the system switch is in the COOL position
Fan
Relay
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Heat pump with heat active reversing valve
TRANSFORMER
Reversing
Valve*
RCOB
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the system switch is in the HEAT position
Fan
Relay
1F78-144 1F78-151
CONFIGURATION AND
TYPICAL WIRING DIAGRAMS
CONFIGURATION
TYPICAL WIRING DIAGRAMS