Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The Type 1A65/1A65W Electric Heat Thermostat is de­signed for use on all types of electrical heating installa­tions such as cable heat, baseboards, wall insert heaters, etc. Its narrow operating differential and the ability of its fully exposed knob to sense both radiant heat and room air temperature make this control ideal for use on such installations.
Dial Setting: Knob may be set anywhere between 40° and 85°F by simply turning knob so that indicator on knob points to the desired setting.
1A65/1A65W
ELECTRIC-HEAT THERMOSTAT
(Single Pole)
INST ALLA TION INSTRUCTIONS
DESCRIPTION
60
70
50
80
This control is a precision instrument, and should be handled carefully. Rough handling or distorting compo­nents could cause the control to malfunction. Take care
not to push or damage the knob sensing element during installation.
CAUTION
!
To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
Switch Rating: Non-Inductive
22A (2500W) 120 VAC 22A (5000W) 240 VAC 18A (5000W) 277 VAC
If the heating equipment manufacturer has made provi­sions or recommendations for the location of this control, then follow those instructions. If not, the following sugges­tions should be observed.
1. The control should be mounted in the wall, approxi­mately five feet from the floor, as near as possible to the centre of the controlled area.
2. It should be mounted on a partitioning wall, not on an outside wall.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, Fax (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 (905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
PRECAUTIONS
All wiring must conform to local and national electrical codes and ordinances.
WARNING
!
Do not use on circuits exceeding specified volt­ages. Higher voltages will damage control and could cause shock or fire hazard.
Do not use on inductive loads. Inductive (motor) loads will damage control and could cause shock or fire hazard.
SPECIFICATIONS
Temperature Range: 40° to 85°F Differential: 1°F Switch Action: Open on rise Contact Structure: SPST
INSTALLATION
3. It should be mounted as far as possible from undesir­able sources of heat and cold such as:
a. Windows and doors b. Direct rays from sun c. Hot water or cold water pipes d. Adjoining outside walls
PART NO. 37-5427C
9520
WIRING
All wiring must conform to local and national electrical codes and ordinances.
The thermostat may be mounted in any standard 2” x 3” electrical outlet box. For ease of installation use a deep type box.
CAUTION
!
USE WITH COPPER CONDUCTORS ONLY.
1. Make electrical connection to thermostat leads with wire nuts or other local code approved devices. All connections must be tight.
Note: Do not push on this knob because calibration will be changed if knob is bent.
BLACK
BLUE
2. Push the lead wires into the outlet box and mount the thermostat to the outlet box with screws provided.
Take care not to push or damage the knob sens­ing element during installation.
3. Snap on the thermostat cover and turn knob to desired setting.
Thermostat
Mounting Screw
60
70
50
80
LINE
LOAD
Mounting Screw
Cover