Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
AOS_Q OVENS – Service manual
(593802300 - ENG)
1 Programming the default parameters
Switch on the oven (fig. 1).
Just after the switching on, a lamp test will take place (fig 2).
At this point, during the lamp test phase, press the external service buttons (fig.3) till you hear a beep.
1
At this point press the right buttons till you hear a beep (fig. 4).
Press then the left service buttons till the beep (fig. 5).
At this point release the left buttons keeping pressed the middle one (fig. 6) till you hear 2 beeps.
Release the middle button and on the temperature display you will see “PdEF”: the oven will switch off and
on automatically.
Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
AOS_Q OVENS – Service manual
(593802300 - ENG)
2 Advanced programming
The procedure to enter in advanced programming is similar to the procedure for programming the defaults
parameters.
Switch on the oven (fig. 7).
Just after the switching on, a lamp test will take place (fig. 8).
At this point, during the lamp test, press the external service buttons (fig.9) till you hear a beep.
At this point press the right buttons till you hear a beep (fig. 10).
Press then the left service buttons till the beep (fig. 11).
Release the button and on the temperature display you will see “P 1” while on the little display the name of
the parameter will appear (fig. 12).
With the external service buttons it is possible to scroll the list of the parameters.
Pressing the middle button it is possible to see the value of the parameter (fig. 13) and pressing at this
point the external buttons it is possible to modify the value. Press again the middle button returning to the
displaying of the number of the parameter to store the new value.
Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
AOS_Q OVENS – Service manual
(593802300 - ENG)
Switch off the oven to exit from programming.
Fig. 12 Fig. 13
3 By-pass calibration (only for lev. B ovens)
In order to calibrate the by-pass probe on lev. B ovens, follow these steps:
1) Switch on the oven
2) Enter in parameter programming and set parameters cort and OCA1 to 0
3) Exit from programming and switch on again the oven
4) Wait for the end of the pre-heating cycle
5) Select a steam cycle (100 °C)
6) Select continuous time (indication “cont” on time display)
7) Press and hold down the left service buttons and at the same time press the START button (fig. 14);
the oven will give a long beep
8) Release the service buttons and wait for the stabilization of the temperature reading by the by-pass
probe
9) When the temperature has stabilized, press the three service button together in order to memorize the
value (fig. 15); the oven will confirm the storing with a long beep
10) Allow the oven to work for several minutes in steam mode checking the oven cavity temperature, which
should stabilize at the water boiling point. If this reading is greater or less than the correct water boiling
1
point
TPF
FPT, a corrective value can be stored in the parameter OCA1. Pushing the 3 service buttons to store
the bypass temperature, the microprocessor will calculate and store also the value of OCA1.
Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
AOS_Q OVENS – Service manual
(593802300 - ENG)
12) Set the altitude above sea level of the site on parameter SEAL
Fig. 15
Fig. 14
4 Lambda probe calibration (only for lev. A ovens)
The calibration of the lambda probe is necessary for the right working of the oven in case of cycle with set
point under 100 °C. With this procedure we have to find the point of 0% of humidity.
The procedure is done in a way similar to the by-pass calibration. These are the steps:
1) Set an hot air cycle, 150 °C, time over 15 minutes, open flap;
2) Start the cycle pressing together the left and middle service buttons and the START button. The
oven will give a long beep;
3) Wait around 10-15 minutes to dry completely the cavity;
4) Close the flap and wait around 20 seconds to stabilize the humidity inside the cavity;
5) To store the value press together the 3 service buttons. The oven will confirm with a long beep.
6) Stop the cycle with the START button.
This calibration is very important and has to be done with care. If the dry point (0% of humidity) is not
correctly stored, the reading of the relative humidity could be overestimated or underestimated.
5 Cavity offset calibration (only for lev. A ovens)
In order to adjust the offset of the cavity probe, enter in parameter programming and set parameters cort
and OCA1 to 0.
Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
AOS_Q OVENS – Service manual
(593802300 - ENG)
Then run a steam cycle for several minutes and check the cavity temperature, which should stabilize at the
water boiling point. If the stabilized cavity temperature is less or greater than the correct water boiling
2
pointTPF
FPT, a corrective value can be stored in parameter OCA1.
After this, set parameter cort to 1and set parameter SEAL (altitude above sea level).
6 Error codes
Errors can be divided into 2 categories: errors (they stop the appliance) and warnings (they do not stop the
appliance).
6.1 Errors
EE2P: Communication error with the EEPROM
E---: If the controller detects one or more parameters which have values not permitting the minimum
operational requirements, an error code will appear on the display, i.e. “E---” followed by the parameter
number. Enter the programming mode and set the correct value according to the parameter list.
EtUC: Cavity over temperature; cavity temperature exceeded value stored in parameter cot.
EtUB: Boiler over temperature; boiler temperature exceeded value stored in parameter bot.
EFUN: Activation of the thermal protection of the motor. On the little temperature display it will appear “UP”
or “DOWN” according it is the thermal protection of the upper motor (and the motor of 6-10 grid ovens) or
lower motor on 20-grid oven. The thermal protection has an automatic reset but in order to continue with
the cooking process, parameter ALFn has to be reset to 0.
Etc: Tripping out of cavity limiter
Etb: Tripping out of boiler limiter
ESCH: Over temperature on the electronic board; check the cooling fan and the ventilation openings on the
bottom of the control panel.
Ept1: cavity probe in open circuit (only the steam cycle – 100 °C can be selected)
Ept2: boiler probe in open circuit (only hot air cycle can be selected)
Ept3: meat probe in open circuit (only time cooking can be selected)
Ept4: by-pass probe in open circuit (only hot air, regeneration or low temperature steam cycle can be
selected)
Ept8: NTC probe in short or open circuit
ECAD: A/D converters not working
E PM: Communication error with PWM system
E SL: Water level probe error. If the boiler heating elements or burners are on for a tiem over that one
defined in parameter tbon without a water charging phase, this error message is activated. To reset it,
parameter ALFn has to be reset to 0.
burn CAUP: Lockout of cavity burner (gas oven) (the upper one in the 20 grid ovens)
burn CAdo: Lockout of lower cavity burner (gas oven) in 20 1/1 and 2/1 ovens
burn boUP: Lockout of boiler burner (gas oven) (the upper one in 20 2/1 ovens)
burn bodo: Lockout of lower boiler burner (gas oven)
6.2 Warnings
EH2O: Before the starting of the cleaning system and during its working, there are some check points of
the water pressure. If the water pressure is too low this warning message appears on the display. Check
the water pressure (1.5÷2.5 bar), check the correct working of the water pressure switch, check if there are
obstructions on the cleaning water inlet pipe (its inner diameter must be 20 mm).
EFLP: Cavity ventilation flap failure; check the motoreducer or the micro switch that detects the close
position of the flap. If the motoreducer does not close the flap within the time set in parameter FLto, EFLP
error appears.
ECLO: Clock error, it appears if the clock was never adjusted
EPrG: Error in reading the phases of a multiphase recipe
EIND: Error in reading the index of the recipes
EDES: Error in reading the description of a recipe
ERAM: Communication error with the RAM
nFIP: Communication error of recipe display
FILL: Safety level probe of the boiler out of water
PrEH: Preheating phase of the boiler; it indicates the preheating phase of the cavity if the warning message
Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
OPEN: boiler drain activated
COOL: Cavity cooling phase
dEt: low level of detergent
rAI: low level of rinser
rCLN: request for a cleaning cycle (manual or automatic); parameter FCLn is set to a value different from
da 0.
LOAD: end of pre-heating phase of the cavity; if nothing is done, the cavity is maintained at the pre-heating
set-point.
Strt: push START button.
rES: reset procedure of the burners is activated
AOS_Q OVENS – Service manual
(593802300 - ENG)
7 Firmware release
In order to check the version of the firmware, switch on the oven and wait for the lamp test and the end of
the start-up phase (4 lines on the temperature display). When on the temperature display, the actual cavity
temperature appears, pressing the three service buttons together on the display temperature the firmware
version will appear. Pressing again these buttons, the board temperature will be displayed.
8 Working temperatures
While the oven is working, it is possible to see the temperature of the several probes pressing the service
buttons. See the following figures:
Fig. 16
Boiler temperature
“tbol” on the display
Fig. 18
Meat probe temperature
“tPrb” on the display
Fig. 17
By-pass temperature
“tbyp” on the display
Fig. 19
PCB temperature
“tntc” on the display
9 Service utilities
These utilities can be divided in 2 sets: utilities that can be activated with the oven switched on, utilities that
can be activated with the oven in parameter programming
9.1 Utilities that can be activated with oven switched on
With the oven switched on and not in a cooking phase, pressing simultaneously the following buttons it is
possible to activate the detergent, rinser pumps and water valve of the cleaning system:
• Steam cycle, combi cycle, temperature buttons (fig. 20): activation of detergent pump
• Steam cycle, combi cycle, time buttons (fig. 21): activation of rinser pump
• Steam cycle, combi cycle, utility buttons (fig. 22): activation of water valve of the cleaning system
These routines are achievable only on lev. A ovens, i.e. with the parameter dCLn set to 0, closed door and
cavity temperature less than 80 °C and with the oven not blocked with password.
Electrolux Professional S.p.A.
Ovens Platform Customer Support
Technical Training & Service
AOS_Q OVENS – Service manual
(593802300 - ENG)
Fig. 20 Fig. 21 Fig. 22
9.2 Utilities that can be activated in parameter programming
• Pressing the steam cycle and hot air cycle buttons, all the output relays are sequentially activated and
on the time display it will be displayed the activated relay with the message do1, do2, ... (dox=RLx on
the EWD)
o The steam cycle button acts as main switch: if it is released, the test stops.
o Each time the hot air cycle button is pressed, the next relay is activated and remains activated till
the next pressure of the hot air cycle button.
oIf the hot air cycle button is kept pressed, the relays are sequentially activated.
• Pressing the time buttons, the time will be displayed
• Pressing the utility button, on the time display a 4-characters message will be displayed while on the
little display will be shown a number with the following meanings
Big display Meaning of the number on the little display