Eemax AP032208, AP032208 EE, AP032208 S, AP036208, AP036208 EE User Manual

...
0 (0)

SpecAdvantage

Specifications

For Commercial and Industrial Applications

Tankless Electric Water Heater

 

 

 

 

 

Applications

Designed for low duty cycle applications where precise temperature controls and low pressure drop are required

Performance Features

Designed for commercial and industrial applications

Capable of high volume and high temperature applications at low duty cycle

Fully modulating - Predictive control algorithm and diverse safety features ensures precise temperature control

T&P not required per UL499 (check local codes)

Thermo-Optical Sensor for infrared element monitoring

Field programmable, updatable firmware, and adjustable

Optional Features (NEMA cabinet required)

N4 (powder coated steel), N4X (304SS) N4X6 (316SS) enclosures

Free standing legs

Freeze protection for harsh climate, up to -30°F

Non-fused or fused electrical disconnect

GFCI

Explosion proof – C1D2 Compliant, local certification required. Class Z purge and pressurization system provided with pressure switch for alarm controls. For classification other than C1D2 please contact the factory to discuss options.

Siren and beacon - audible and visual alarm (C1D2 compliant when paired with explosion proof package)

Product Specifications

Min. Operating Pressure:

35 PSI

Max. Operating Pressure:

150 PSI

Optimum Operating Pressure:

60-90 PSI

U.S. Patent #'s: US20140023354 and US20140178057

Installation Requirements

Properly sized water hammer arrestor

Minimum 35 PSI dynamic pressure at inlet

Sediment filter installed on inlet

Special Design Service

Inquiries for units for unique applications are welcome. Call our Technical Service department at 1-800-543-6163.

Custom orders non-refundable

 

Assembled

*The wetted surface of this product

 

 

 

 

 

 

 

 

contacted by water contains less than

 

 

 

 

0.25% lead and meets NSF/ANSI 372

In USA

Suggested Specification

Tankless water heater shall be an Eemax SpecAdvantage model number AP_________________________.

Optional factory installation in a ____(N4/N4X/N4X6) enclosure. Enclosure to be fitted with the following features:

_____ FP

Freeze protection (-30°F)

_____ EDS

Non-fused disconnect

_____ FDS

Fused disconnect

_____ EP

Explosion proof (C1D2 compliant)

_____ GFCI

True RMS GFCI with digital display and reset

_____ SK

24" legs for free standing applications

_____ RD

Remote display

_____ SB

Siren and Beacon

_____ DC

Dry contact

_____ ES

Emergency stop - push button

Tankless water heater must have water connections on the bottom, and be constructed with NSF 61 listed materials. Direct heating element to be non-ferrous, cartridge style, designed for field replacement. Tankless water heater to utilize a dual PID algorithm, actively managing power application to real-time system demand. Integrated flow meter capable of volumes in excess of 30 GPM drives predictive control algorithm. Water heater must be protected by redundant safeties. Redundant safeties to include thermo mechanical safety switches, infrared element monitoring via thermo optical sensors, and dual temperature monitoring via primary control board. Tankless water heater user interface must have the following capabilities:

Selectable display including Celsius/Fahrenheit, inlet temperature, outlet temperature, flow rate, and setpoint temperature.

Capable of displaying flow rate in gallons per minute or liters per minute.

Diagnostic features to include error and fault code display.

Control board must maintain error/fault history of 9 events.

Capable of factory coded temperature setting (max. and min.)

Capable of firmware upgrades via USB port

Capable of BMS integration - contact factory

Compliant with ANSI Z358.1 tepid water without additional mixing or purge features (inlet temperatures must not exceed 100°F when selecting an EE or EFD option)

Information and product specifications contained in this document are subject to change without notice. REV 2020-01

9

Eemax AP032208, AP032208 EE, AP032208 S, AP036208, AP036208 EE User Manual

SpecAdvantage

Specifications

For Commercial and Industrial Applications

Tankless Electric Water Heater

 

Suffix Definitions

SSanitation. Shipped at 180°F with temp range of 100°F-190°F max.

EEEmergency Eyewash. Max. outlet temperature 90°F. Conforms to ANSI Z3581.1 tepid water without additional mixing valve. Shipped with display "Locked."

EFD

Emergency Eye, Face &

 

Drench. Max. outlet temperature

 

90°F. Conforms to ANSI Z3581.1

 

tepid water without additional

 

mixing valve. Shipped with display

 

"Locked."

Note: Models with an EE or EFD suffix are not to be fed to a thermostatic mixing valve. If a thermostatic mixing valve is required, heater of non EE or

EFD must be specified.

Note: Models without a suffix are set to a maximum temperature of 140°F if the turn on is greater than 1.5 GPM. Models with a 1.0 or 1.5 GPM turn on are limited to 120°F.

PHD Pressure Drop 63-150 kW

Flow Rate (GPM)

Delta PSI

 

 

2

0

 

 

3

0

 

 

4

0

 

 

6

0

 

 

8

1

 

 

11

3

 

 

12

4

 

 

15

6

 

 

18

8

 

 

20

10

 

 

22

13

 

 

24

14

 

 

27

17

 

 

30

22

 

 

33

26

 

 

35

30

 

 

37

34

 

 

40

43

 

 

 

 

 

 

AMPS

 

RECOMMENDED

 

 

 

TEMPERATURE RISE °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TURN ON

3.0

4.0

5.0

6.0

20.0

23.0

26.0

30.0

 

 

 

 

PER

WIRE SIZE

 

MODEL NUMBER

kW

BTU/H

PHASE

(GPM)

(75° C/CU)

GPM

GPM

GPM

GPM

GPM

GPM

GPM

GPM

 

VOLTS 208 Three Phase Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

AP032208

32

109,189

89

1.0*

3 AWG

73°

55°

44°

36°

11°

10°

 

AP032208 EE

32

109,189

89

1.0

3 AWG

55°

44°

36°

11°

10°

 

AP032208 S

32

109,189

89

2.5**

3 AWG

73°

55°

44°

36°

11°

10°

 

AP036208

36

122,837

100

1.0*

3 AWG

82°

61°

49°

41°

12°

11°

 

AP036208 EE

36

122,837

100

1.0

3 AWG

49°

41°

12°

11°

 

AP036208 S

36

122,837

100

2.5**

3 AWG

82°

61°

49°

41°

12°

11°

 

AP041208

41

143,310

113

1.0*

2 AWG

93°

70°

56°

47°

14°

12°

11°

 

AP041208 EFD

41

143,310

113

1.0

2 AWG

56°

47°

14°

12°

11°

 

AP041208 S

41

143,310

113

2.5**

2 AWG

93°

70°

56°

47°

14°

12°

11°

 

AP054208

54

184,256

150

1.5*

1/0 AWG

92°

74°

61°

18°

16°

14°

12°

 

AP054208 EFD

54

184,256

150

1.5

1/0 AWG

18°

16°

14°

12°

 

AP054208 S

54

184,256

150

6.0**

1/0 AWG

123°

92°

74°

61°

18°

16°

14°

12°

 

AP064208

64

218,377

178

2.5

3/0 AWG

109°

87°

73°

22°

19°

17°

15°

 

AP064208 EFD

64

218,377

178

2.5

3/0 AWG

22°

19°

17°

15°

 

AP064208 S

64

218,377

178

6.0**

3/0 AWG

146°

109°

87°

73°

22°

19°

17°

15°

 

VOLTS 480 Three Phase Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

AP036480

36

122,837

43

1.0*

8 AWG

82°

61°

49°

41°

12°

11°

 

AP036480 EE

36

122,837

43

1.0

8 AWG

49°

41°

12°

11°

 

AP036480 S

36

122,837

43

2.5**

8 AWG

82°

61°

49°

41°

12°

11°

 

AP039480

39

133,074

47

1.0*

8 AWG

89°

67°

53°

44°

13°

12°

10°

 

AP039480 EE

39

133,074

47

1.0

8 AWG

53°

44°

13°

12°

10°

 

AP039480 S

39

133,074

47

2.5**

8 AWG

89°

67°

53°

44°

13°

12°

10°

 

AP048480

48

163,783

58

1.0*

6 AWG

109°

82°

66°

55°

16°

14°

13°

11°

 

AP048480 EFD

48

163,783

58

1.0

6 AWG

55°

16°

14°

13°

11°

 

AP048480 S

48

163,783

58

2.5**

6 AWG

109°

82°

66°

55°

16°

14°

13°

11°

 

AP054480

54

184,256

65

1.5*

6 AWG

92°

74°

61°

18°

16°

14°

12°

 

AP054480 EFD

54

184,256

65

1.5

6 AWG

18°

16°

14°

12°

 

AP054480 S

54

184,256

65

2.5**

6 AWG

123°

92°

74°

61°

18°

16°

14°

12°

 

AP063480

63

214,965

76

2.5

4 AWG

108°

86°

72°

22°

19°

17°

14°

 

AP063480 EFD

63

214,956

76

2.5

4 AWG

22°

19°

17°

14°

 

AP063480 S

63

214,965

76

6.0**

4 AWG

143°

108°

86°

72°

22°

19°

17°

14°

 

AP072480

72

245,674

87

2.5

3 AWG

98°

82°

25°

21°

19°

16°

 

AP072480 EFD

72

245,674

87

2.5

3 AWG

25°

21°

19°

16°

 

AP072480 S

72

245,674

87

6.0**

3 AWG

123°

98°

82°

25°

21°

19°

16°

 

AP096480

96

327,566

116

2.5

1 AWG

109°

33°

29°

25°

22°

 

AP096480 EFD

96

327,566

116

2.5

1 AWG

33°

29°

25°

22°

 

AP096480 S

96

327,566

116

6.0**

1 AWG

131°

109°

33°

29°

25°

22°

 

AP108480

108

368,511

130

2.5

1 AWG

37°

32°

28°

25°

 

AP108480 EFD

108

368,511

130

2.5

1 AWG

37°

32°

28°

25°

 

AP108480 S

108

368,511

130

6.0**

1 AWG

148°

123°

37°

32°

28°

25°

 

AP126480

126

429,930

151

2.5

2/0 AWG

43°

37°

33°

29°

 

AP126480 EFD

126

429,930

151

2.5

2/0 AWG

43°

37°

33°

29°

 

AP126480 S

126

429,930

151

6.0**

2/0 AWG

143°

43°

37°

33°

29°

C

AP144480

144

491,348

173

2.5

2/0 AWG

49°

43°

38°

33°

C

AP144480 EFD

144

491,348

173

2.5

2/0 AWG

49°

43°

38°

33°

C

AP144480 S

144

491,348

173

6.0**

2/0 AWG

49°

43°

38°

33°

 

VOLTS 600 Three Phase Delta

 

 

 

 

 

 

 

 

 

 

 

 

C

AP061600 EFD

61

208,141

59

2.5

6 AWG

21°

18°

16°

14°

C

AP071600 EFD

71

242,262

68

2.5

4 AWG

24°

21°

19°

16°

C

AP102600 EFD

102

348,038

98

2.5

3 AWG

35°

30°

27°

23°

C

AP130600 EFD

130

443,578

125

2.5

1 AWG

44°

39°

34°

30°

C

AP150600 EFD

150

511,821

144

2.5

1/0 AWG

51°

45°

39°

34°

* Units with a 1.0 or 1.5 GPM turn-on are limited to 120°F only. Contact Eemax support for applications above 120°F.

† Temperature electronically limited to factory preset temperature.

"C" indicates evaluation and compliance to either Underwriters Laboratories (UL) or Intertek (ETL) under CAN/CSA-C22.2 No. 64/No. 88. ** Contact Eemax for applications requiring lower turn on.

Electrical configuration and requirements

All Eemax three phase units are custom made to order and as such, are non-returnable and non-refundable. Check your electrical supply,

making sure all criteria for operating your Eemax water heater are met.

L1

Eemax 600V,480V and 208VThree Phase Units Delta Configuration

 

Requires: 3 Lives and 1 Ground (earth)

L2

 

 

L3

10

Information and product specifications contained in this document are subject to change without notice. REV 2020-01

Loading...
+ 2 hidden pages