Eaton LK8-NO, LK8-LRC, LK8-MRC, LK8-TPRC Installation Manual

Installation Instructions
LiteKeeper® 8
Model# LK8-NO Model# LK8-LRC Model# LK8-MRC Model# LK8-TPRC
INS #
General Information
Getting Started
1. Do not discard these installation instructions. Please keep for future reference and operation information.
2. The relay cards are protected by shrink-wrap. Leave shrink-wrap in place until all drilling and metal work is complete to protect against metal shards getting into component circuitry.
3. Always disconnect all power before wiring.
4. Use only as intended and at the listed voltage.
5. All installation service must be performed by qualified personnel or service technicians.
6. Install in accordance with National Electrical Code and any other codes that may apply.
7. High Voltage is present inside the lighting enclosure. Use extreme caution when performing maintenance on this equipment. Failure to follow this warning and proper safety procedures could result in severe injury or death and/or damage to the equipment.
8. Document all wiring that is terminated to the relays so that the lighting control equipment can be properly configured and programmed for operation.
9. It is recommended that all low voltage wiring be done with power removed to the logic board to protect components from potential shorts during the wiring process.
Mounting in the Enclosure
1. Choose a dry location convenient to the circuit breaker panel.
2. Mount the panel on a firm surface using pre-drilled holes.
3. Connect the enclosure to the circuit breaker panel using conduit into the punch holes provided.
4. Remove all cuttings and dirt before removing shrink-wrap from the relays.
ote:N Make certain that high voltage and low voltage
wiring enters the enclosure separately. High Voltage wiring should be brought into the top or bottom of the enclosure. Low Voltage wire should enter in the low voltage wiring compartment on the left side of the enclosure.
Failure to separate high voltage from low voltage wiring may cause interference with logic board function.
ON
C
+24
H 1
LITEKEEPER
OFF
12:OO O1/O1/95
ON
C H
+24
1
OFF
3
5
1
7
RELAY
ON
C
+24
H 1
OFF
ON
C
+24
H 1
OFF
ON
C
+24
H 1
OFF
ON
C H
+24
1
OFF
ON
C H
+24
1
OFF
ON
C
+24H
8
OFF
+24 VDC
DC GND
Low Voltage Wiring Compartment
2
1
3A
OUTPUTS
6
2
8
4
TB1TB1
4
7
5
6
9C
8
0* #D
B
High Voltage Wiring Compartment
Low and High Voltage
Wiring the Transformer
Wiring the Transformer
The transformer is multi-tapped and voltages are color-coded. The transformer is available in 120/277 VAC and 120/347 VAC models. It is recommended that a dedicated branch circuit with circuit protection be provided for the transformer.
1. Connect neutral wire to the wire with the appropriate color-coding for the voltage being used: White/ Black=120 VAC, White/Orange=277 VAC, Brown=347 VAC.
2. Connect the solid black wire to the dedicated branch circuit that is powering the transformer.
System Power Supply
Line Voltage = Black Neutral:
120VAC = white/black 277VAC = white/orange 347VAC = brown
Ground = green
Transformer Wiring Information
Standard Relay Card Notes
1. The Standard Relay Card is rated for single-pole load use only. Connection of 2 pole circuits/loads to the Standard Relay Card will void the equipment warranty and may result in severe injury or death, and/or damage to the equipment.
2. Relay ratings are 120 or 277 volt, 20 amp maximum.
3. Relay terminal blocks have a maximum limit of 10AWG wire.
Standard Relay Card Wiring
The standard relay is a simple contact closure, breaking the line and load wires of a normal circuit. To wire the relay into the control circuit:
1. Connect a 120 or 277 volt, 20 amp max, de-energized branch circuit breaker to the relay terminal block.
2. Connect the load wiring to the output terminal block.
ote:N Terminal blocks are not polarity sensitive although it
is recommended that line and load be brought into terminal blocks in the same manner for consistency.
3. Tighten down relay terminal screws. Manufacturer’s recommended torque rating is 7 lbs-in. (0.59 lbs-foot) (0.8 Nm).
4. Document relay to circuit information for future reference.
Relay Wiring
Wire: 10 AWG Max.
Relay Rating: 20amps, 277V
Connecting Relay Loads
The relay cards will be pre-mounted by the manufacturer in the enclosure per the order specifications. There are currently four available relay types for the enclosure. This includes the Standard Relay Card, the Modular Relay Card, the Latching Relay Card and the Two Pole Relay Card. If a Modular Relay Card or Two Pole Relay Card is ordered, a deeper enclosure will be provided to allow for clearance of the transformer with the larger relay types. Refer to the specific section for your relay card type that you are wiring. For all relay types:
1. Verify that all wire cuttings are removed from the enclosure.
2. Take the protective shrink-wrap off of the relay cards AFTER the wire cuttings are removed from the enclosure.
3. Test branch circuits for short circuits prior to landing wiring on relays.
ote:N Neutrals terminate within the adjoining lighting panel.
From Branch Circuit
To Lighting Load
54-015030 54-015030
Standard Relay Card Wiring
TB8
TB6
TB4
TB2
Latching Relay Card Notes
1. The Latching Relay Card is rated for single-pole load use only. Connection of 2 pole circuits/loads to the Latching Relay Card will void the equipment warranty and may result in severe injury or death, and/or damage to the equipment.
2. Relay ratings are 120/277/347 volt, 20 amp maximum.
3. Relay terminal blocks have a maximum limit of 6AWG wire.
2
LiteKeeper® 8
Connecting Relay Loads
Latching Relay Card Wiring
The latching relay is a simple closure, breaking the line and load wires of a normal circuit. To wire the relay into the control circuit:
1. Connect a 120, 277 or 347 volt, 20 amp maximum, de-energized branch circuit breaker to the relay terminal block.
2. Connect the load wiring to the output terminal block.
ote:N Terminal blocks are not polarity sensitive although it
is recommended that line and load be brought into terminal blocks in the same manner for consistency.
3. Tighten down relay terminal screws. Manufacturer’s recommended torque rating is 18 lb-in. (1.475 foot-lbs) (2.0 Nm).
4. Document relay to circuit information for future reference.
U2 U3
RP1
RN1
LED 1
Relay Wiring
Wire: 6 AWG Max.
Relay Rating: 20amps, 347V
K8
K6
U1
RP2
Q1
Q2
SR1
K4
K2
TB8
MOV8
TB6
MOV6
TB4
MOV4
MOV2
TB2
Latching Relay Card Wiring
From Branch Circuit
To Lighting Load
Modular Relay Card Notes
The Modular Relay Card provides flexible options for relay control. It is designed to allow modular relay control by allowing you to install a variety of relay module types on the same relay card. Current available relay module types include a Two Pole Relay Module (TPRM) Normally Open, the Latching Relay Module (LRM) and the Standard Relay Module (SRM).
LRM
TB1
Line
MOV1
Load
Modular Relay Card Wiring Diagram
K1
Relay Rating: 20Amps 120/277/347 VAC Wire: 6 AWG max.
R4
R4
TB1
K1
MOV1
U1
RP1
TB1
K1
MOV1
U1
RP1
SRM
TPRM
Line 1
Load 1 Line 2
Load 2
Relay Rating: 20Amps 208/240/480 VAC Wire: 6 AWG max.
Relay Rating: 20Amps 120/277 VAC Wire: 10 AWG max.
Line Load
Modular Relay Card
Standard Relay Module
1. The Standard Relay Module is rated for single-pole load use only. Connection of 2 pole circuits/loads to the Standard Relay Module will void the equipment warranty and may result in severe injury or death, and/ or damage to the equipment.
2. Relay ratings are 120 or 277 volt, 20 amp maximum.
3. Relay terminal blocks have a maximum limit of 10AWG wire.
4. The SRM contains an LED indicator that will be lit when the relay is commanded by the control panel to be in the closed position.
Relay Status Indicator LED
Wiring Terminal Block
LiteKeeper® 8
SRM
Relay Slot Pin Connector: Please note relay number location for programming purposes.
Standard Relay Module (Modular Relay Card)
3
Connecting Relay Loads
Standard Relay Module Wiring
The standard relay is a simple contact closure, breaking the line and load wires of a normal circuit. To wire the relay into the control circuit:
1. Connect a 120 or 277 volt, 20 amp max, de-energized branch circuit breaker to the relay terminal block.
2. Connect the load wiring to the output terminal block.
ote:N Terminal blocks are not polarity sensitive although it
is recommended that line and load be brought into terminal blocks in the same manner for consistency.
3. Tighten down relay terminal screws. Manufacturer’s recommended torque rating is 7 lbs-in. (0.59 lbs-foot) (0.8 Nm).
4. Document relay to circuit information for future reference.
Wiring Terminal Block
PCI 2003
C
TB1
Relay Status Indicator LED
RP1
MOV1
Relay Slot Pin Connector: Please note relay number location for programming purposes.
Latching Relay Module
U1
K1
R4
J1
Latching Relay Module
1. The Latching Relay Module is rated for single-pole load use only. Connection of 2 pole circuits/loads to the Latching Relay Module will void the equipment warranty and may result in severe injury or death, and/or damage to the equipment.
2. Relay ratings are 120/ 277/347 volt, 20 amp maximum.
3. Relay terminal blocks have a maximum limit of 6AWG wire.
4. During initial power-up, the relay on the Latching Relay Module will remain in its current latched state for a period of 30 seconds. After 30 seconds, the relay will assume its programmed state.
5. During a power outage, the LRM relay will remain in the state it was in prior to the power outage. Once power returns, the relay will stay in its state for 30 seconds then assume its programmed state.
6. There is a manual switch on each relay that indicates relay status and allows for a temporary override of the lighting load. If the switch is moved towards the center of the Modular Relay Card, the relay is ON. If the relay switch is moved towards the outside of the relay card, the relay is OFF. If this switch is used to override lighting, the relay will stay in the overridden state until the next command to that relay is given by the logic board.
Latching Relay Module Wiring
The latching relay is a simple closure, breaking the line and load wires of a normal circuit. To wire the relay into the control circuit:
1. Connect a 120, 277 or 347 volt, 20 amp maximum, de-energized branch circuit breaker to the relay terminal block.
2. Connect the load wiring to the output terminal block.
ote:N Terminal blocks are not polarity sensitive although it
is recommended that line and load be brought into terminal blocks in the same manner for consistency.
3. Tighten down relay terminal screws. Manufacturer’s recommended torque rating is 18lb-in. (1.475 foot-lbs) (2.0 Nm).
4. Document relay to circuit information for future reference.
Two Pole Relay Module
1. Two Pole Relay ratings are 208/240/480 volt, 20 amp maximum.
2. Relay terminal blocks have a maximum limit of 6 AWG wire.
3. Two Pole Relays take up two relay slots in the enclosure.
4. Two Pole Relays come in a normally open configuration.
5. There is an LED that will light up when the relay is commanded to be in the closed position.
4
LiteKeeper® 8
Connecting Relay Loads
6. To program the controller to control a Two Pole Relay Module, apply programming to the relay number where the relay pin connector is attached to the MRC.
Wiring Terminal Block
Line 1
Load 1
Line 2
Load 1
Relay Slot Pin Connector: Please note relay number location for programming purposes.
Two Pole Relay Module
Relay Status Indicator LED
TPRM
Two Pole Relay Module Wiring
1. Connect one de-energized branch circuit breaker to one of the relay terminal blocks
2. Connect the load side to the output terminal block position of this same terminal block. Note: terminal blocks are not polarity sensitive although it is recommended that line and load be brought into terminal blocks in the same manner for consistency.
3. Connect the other de-energized branch circuit breaker to the other relay terminal block on the module.
4. Connect the second load wire to the second terminal block.
5. Tighten down relay terminal screws. Manufacturer’s recommended torque rating is 18lbs-in. (1.475 foot-lbs) (2.0 Nm).
6. Document relay to circuit information for future reference.
Two Pole Relay Card Notes
The Two Pole Relay Card(s) is installed at the factory in the Lighting Controller specified.
The Two Pole Relay Card relays are shipped separately and are installed in the field. The relays that are available are Two Pole Relays rated at 120V/208V or 277V/480V. A Single Pole Relay is also available, rated at 347V. All relays are rated to 20 Amps. The following information describes the installation of the relays onto the Two Pole Relay Card.
Each Two Pole Relay Card has eight mounting clips for the placement of the relays. The Two Pole Relay Card will hold eight 208V two pole relays, one in each mounting clip. The 480V Two Pole Relay Card uses two mounting clips, thus only four relays will fit per card. The Two Pole Relay Card will hold eight 347 Single Pole Relays, one in each mounting clip.
1. Position the relay so that the input coil faces the center of the Two Pole Relay Card and the output contacts face outwards toward the enclosure walls.
2. Place the input coil side in first then press down with an even motion and snap the relay into place. (To remove the relay, press down on the metal release bar and pull the relay out).
3. The coil control wires (blue and red) and a connector are supplied already attached to the relay. Simply plug this connector into the Two Pole Relay Card. The relay number slot that this connector is plugged into will be the relay that will need to be programmed in the controller for proper function. Wire as indicated in the diagram following.
Two Pole Relay Card
with Four 208V Two Pole Relays.
Mounting Clip
Output Contact Terminals
ON ON
ON
Load 2 (Out)
Line 2 (In) Line 1 (In)
Load 1 (Out)
Mounting Clip
Output Contact Terminals
Load 2 (Out) Line 1 (In)
Mounting Clip
Output Contact Terminals
Line 1 (In)
Load 1 (Out)
Line 2 (In)
Load 2 (Out)
ON
ON
Input Coil with Connector
Two Pole Relay Card
with Four 347V Single Pole Relays
ON
ON
Two Pole Relay Card
with Two 480V Two Pole Relays
ON
ON ON
Input Coil with Connector
Input Coil with Connector
LiteKeeper® 8
Two Pole Relay Card Wiring
5
Connecting Low Voltage Inputs
Connecting Low Voltage Inputs
The LiteKeeper 8® logic board can support up to 64 switch inputs. Of these 64 inputs, 8 of them may be dry contact closure inputs that are connected to the terminal blocks on the left side of the LiteKeeper® Logic Board. Digital switch inputs may also be used on the LiteKeeper®. If no contact input type switches are being used, the full 64 switch inputs may consist of digital switches. If a combination of contact input switches and digital switches are being used, the combined total cannot exceed 64 inputs.
Regardless of input type used, it is recommended that all input wiring be done prior to applying power to the logic board. Please verify that there are no shorts to AC Ground prior to connection of input devices.
Regardless of input type, the following notes apply.
1. All low voltage wiring is Class 2 wiring.
2. All low voltage wiring must enter the cabinet into the low voltage section of the enclosure. Low Voltage wiring can be brought into the enclosure from the left side of the enclosure. Failure to separate high voltage from low voltage wiring may cause interference with logic board function.
3. All low voltage wiring must be run in separate conduit from line-voltage wiring.
4. Test all low voltage wiring for shorts to AC ground before connection to the relay panel.
5. When powering peripheral devices such as motion sensors and photocells from the LiteKeeper® panel, there may be a limitation on the number of sensors that can be supported. This is also true if digital switches are used with the system. See the recommendations below or contact Eaton’s Cooper Controls Business for further information.
6. It is recommended that power be removed from the logic board when doing initial switch input wiring.
Contact Input Switch Wiring
This section describes the wiring for dry contact closure devices. There are eight switch input wiring terminals on the left side of the LiteKeeper-8® to allow for wiring of the dry contact closure devices.
1. Use 18AWG twisted, unshielded wire for all low voltage dry contact closure device wiring.
2. Maximum length for dry contact closure device wiring is 1000 feet.
3. Please see wiring detail below for details on connections of different devices to the LiteKeeper 8® system.
C H 1
Momentary
C H 2
C
Toggle
H 3
C H 4
C H
Maintained
LiteKeeper-8® Low Voltage Switch Wiring
5
ON +24VDC OFF ON +24VDC OFF
ON +24VDC OFF
ON +24VDC OFF
ON +24VDC OFF
Contact Input Photosensor and Greengate Sensor Notes
It is possible to use a contact input photosensor and Greengate motion sensors in conjunction with the lighting control system. The LiteKeeper 8® is capable of powering a number of these devices. Please refer to the chart below for details on how many devices the transformer can support.
Greengate
PIR Sensor
40 16 20 20 4
Greengate
Dual-Technology
Sensor
Greengate Ultrasonic
Sensor
Please contact technical support if it is necessary to power additional sensors beyond the numbers listed above. These figures do not account for additional devices such as digital switches being used. If using a combination of devices, please contact technical support for exact limits on how the number of devices the logic panel can power.
PPS5
Black
Black
Black
REM PWR DC GND (Black Wire)
Photocell and Motion Sensor Wiring
ON (White Wire)
+24VDC (Red Wire)
PPS4
ON (Blue Wire)
+24VDC (Red Wire)
Yellow & White wires not used
ON (Blue Wire)
+24VDC (Red Wire)
PPS-4 Indoor
Photosensor
ON
C
+24
H
1
OFF ON
C
+24
H
OFF
2
ON
C
+24
H
OFF
3
ON
C
+24
H
OFF
4 C
ON
H
+24
5
OFF
C
ON
H
+24
6
OFF
C
ON
H
+24
7
OFF ON
C
+24
H
OFF
8
+24VDC GND
PPS-5
Outdoor
Photosensor
Contact Input
Photosensor
Typical Greengate
Motion Sensor
Wiring
6
LiteKeeper® 8
Digital Switch Wiring
Digital Switch Wiring
Each LiteKeeper 8® unit is capable of supporting the Greengate Digital Switch (GDS) station. The GDS do not wire directly to the LiteKeeper 8® logic board, but are wired using a CAN Bus network that connects to the LiteKeeper 8® through a gateway called the GDS-I. GDS stations are wired using the Eaton’s Cooper Controls LCCP or LCCNP cable, or Belden 1502P or 1502R equivallents.
For best network performance, one of the suggested cables should be used. If the specified cable is not used and communications problems occur that require troubleshooting assistance, additional charges for support may be assessed.
Digital Switch devices should be networked together in a daisy chain configuration. No T-Taps/Stars should be used. The GDS-I device should reside somewhere within the daisy chain switch network. Total daisy chain network length should not exceed 1000 feet.
The following instructions describe the GDS-I device connection to the LiteKeeper 8®. Please refer to the Greengate Digital Switch installation instructions for information on wiring the Digital Switch Network to the Digital Switch Gateway.
1. Mount the GDS-I next to the LiteKeeper®-8 panel. A six foot phone style cable has been provided for connection to the LiteKeeper-8® panel.
2. Run a length of the Digital Switch LC or Belden cabling from the GDS-I location to the low voltage section of the LiteKeeper 8®.
3. Connect the RED wire in the cable to the +V terminal on the back of the GDS-I and to the LiteKeeper 8® at one of the switch input +24 VDC terminals.
4. Connect the BLACK wire in the cable to the GND terminal on the back of the GDS-I and to the LiteKeeper 8® remote power connector GND terminal.
5. Tape back or cap the blue and white wires and shield wire for the cable. They will not be used for connection between the GDS-I and lighting controller.
6. Locate the 6 foot phone style cable included in the GDS-I box. Run this from the GDS-I into the low voltage section of the LiteKeeper 8® enclosure plugging the end with 9 pin head into the GDS-I. Plug the end the RJ11 phone style plug into the LiteKeeper 8®.
7. It is recommended that power be removed from the logic board when doing initial switch input wiring.
Panel must be Set
to Communicate to
the GDS Switch BUS
Through Menu Option 8
Communication Cable
GDS-I
Red Wire From
GDS-1 +24 to
LK +24
Black Wire From GDS-1
0V to LK GND
Cabling is Cooper LC Cable,
Belden 1502R, or Belden 1502P
GDS-I Wiring
Applying Power
1. Once the wiring is complete, make certain that the enclosure is clean of any wire clippings and that no fragments are lodged in the relay circuit boards.
2. Ensure that there are no loose wires or exposed wires that could short to other wires or components.
3. Power-up the unit from the circuit breaker.
4. Once power is applied to the unit, lighting loads may be operated via the ALL ON/ AUTO/ ALL OFF switch as necessary.
Manually Controlling Relays
The relays in the enclosure may be controlled before the logic board is programmed by using the on-board, ALL OFF, AUTO, ALL ON switch. In the ALL ON position the relay coils will be energized. In the ALL OFF position, the relay coils will be de-energized. The middle, AUTO, position allows the relays to be controlled by the individual relay switches or from the logic controller.
LiteKeeper® 8
System Reset and Clear Commands
Under certain circumstances, you may want to reset the LiteKeeper 8®. There are two different types of reset commands available in the LiteKeeper 8® system: a soft reset command and a clear reset command.
7
Programming the LiteKeeper-8®
Soft Reset Command: The Soft Reset Command reboots the
microprocessor. It will not cause loss of panel programming. To perform a Soft Reset Command, insert a slim object through the hole in the black casing located in the bottom section of the logic panel. Press in and then immediately release the reset button under this point. The display will go blank then read “Initializing”
Clear Settings Command: A clear settings command is
used to remove all programming from a LiteKeeper 8® unit. It should be done before programming to the unit for the first time or when asked to by a Technical Support representative. Please use caution with this command! When performing a Clear command, all relay loads will turn OFF. Use the ALL ON override switch to keep lighting ON if necessary.
To Perform a Clear Command: Reset the panel, using the
Reset Button. Wait for the screen to initialize. Hit the key sequence “A, B, C, D, *.” The display will read “Initializing” again. The unit is now cleared to factory default programming.
Programming the LiteKeeper-8
The LiteKeeper 8® is programmed either through the keypad onboard interface or through the optional Keeper Enterprise Software. Please refer to programming guide that came with the unit to program via the keypad or to your Keeper Enterprise Manual for programming details. It is recommended that a Clear Settings command be performed on the controller before the first programming is done to clear any test data that may be left in the controller from factory testing.
®
Repair Information
If a repair becomes necessary on your LiteKeeper 8® unit, please refer all service to Greengate technical support line at 1-800-553-3879.
Display
ON
C
+24
H 1
OFF
ON
Status LEDs
Physical Override
Reset Switch
RS-232 Port or Digita Switch Port
C H
+24
1
OFF
ON
C H
+24
1
OFF
ON
TB1TB1
C H
+24
1
OFF
ON
C H
+24
1
OFF
ON
C
+24
H 1
OFF
ON
C H
+24
1
OFF
ON
C H
+24
8
OFF
+24 VDC
DC GND
Low Voltage Wiring Compartment
Keyboard
LIGHTING CONTROL
12:OO O1/O1/0 8
3
5
1
7
RELAY
2
1
3A
OUTPUTS
2
8
6
4
B
5
4
6
9C
8
7
0* #D
Switch Inputs
Item Reference Drawing
System Ground
Output Relays
Multi-Tapped Transformer
High Voltage Wiring Compartment
8
LiteKeeper® 8
Loading...
+ 16 hidden pages