Duke SIIM User Manual

SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL SIIM
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model SIIM, Type I, UL Listed, and in compliance with NFPA Bulletin 96. Ventilator shall be high velocity, low volume, wash type and have a nominal 95% grease extraction efficiency certied by an independent testing laboratory.
Canopy, constructed of 18-gauge stainless steel (where exposed) with bottom perimeter edges gutterless. Weld extraction chamber, plenum, and external seams and joints to form a liquid-tight construction. Polish stainless steel to a #3 nish.
Exhaust plenum Extraction Chamber to be dual inlet, same material as canopy, full length of section at the back. Furnish water wash manifold consisting of a series of brass spray nozzles installed within chamber. Manifold to be positioned within plenum area out of air-stream to minimize nozzle clogging. Bottom of exhaust plenum to be formed into a pitched trough to allow laminar ow, during wash cycle, to drain pipe connection.
Water Wash System to serve the dual purpose of daily cleaning and re control. The wash cycle shall be initiated when the stop/wash button on the control cabinet (required with each hood system) is depressed. Internal cleaning will be achieved by means of 110˚ - 160˚F water mixed automatically with injected detergent. In the event the re control system is activated, the system shall supply a continuous re quenching spray. Fire quenching spray shall continue to operate until the reset button is pushed. Pressing the start button will restart the fan system.
Install hinged, motorized Fire Damper full length at air inlet of ventilator. Damper opens when ventilator is in normal operation, acting as an extracting baffle, and closes when ventilator is turned off to allow thorough cleansing of extraction chamber interior. Damper automatically closes, sealing interior of ventilator from re when thermostat senses 325˚F.
Furnish Duct Collar, fully welded, complete with re detection thermostat, in top of canopy within exhaust plenum area. Duct collar size based on an average 1800 F.P.M. air velocity.
Integral Make-Up Air furnished at front of ventilator shall be SOUTHERN ENGINEERING proprietary “Short Cycle” design. Outside shell constructed of 18-gauge stainless steel integrated with canopy. Lower inside wall of chamber constructed of perforated 18-gauge stainless steel forming a continuous make-up air diffuser. Diffuser to lift out using handles provided for easy access to chamber. Make-up air chamber tted with an interior diffuser baffle designed to provide even air distribution across the perforated surface. Top of chamber to be tted with a properly sized rectangular duct collar. make-up air duct collar provided with NFPA 96 damper and sized to permit up to 60% supply air.
Furnish UL listed, NSF listed, vapor proof incandescent Light Fixtures installed on 3’ to 4’ centers. ­Fixtures to be completely inter-wired to a junction box and left ready for nal connection to power source. Field connections, light switch and bulbs by applicable trades.
Furnish Rod Hanger Brackets at front and center to suspend canopy from ceiling.
Canopy shall be UL Listed and NSF approved. Equipment b
uilt in an ISO 9001:2000 approved
manufacturing facility.
2305 N. Broadway St. Louis, MO 63012 Phone 314-231-1130
BY
www.dukemfg.com
"Your Solutions Partner"
Fax314-231-5074
6/07
Exhaust Requirements Make-up Air Requirements
CFM ________________ SP (“w.g.) _____________ CFM ________________ SP (“w.g.) ________
Duct Collar ________ “x ______________” Duct Collar ________ “x _________”
Fire Protection Lighting Fixture (UL listed)
(Submit cooking equipment plan showing make  Globe incandescent (100W)
and model on equipment.) Recessed incandescent (150W
 Ansul Wet #R-102  Recessed fluorescent  Other ___________________________________  Light switch  Internal Piping Only NOTE: Incandescent lights are located Complete System on approx. 4’ centers. Fluorescent  By Others xtures are 3’ (50W) and 4’ (64W)
NOTE: Fuel shut-off devices by others (unless specied
Optional Accessories
otherwise). Enclosure paneling (Finished ceiling higher than 9’0”)
Continuous Cold Water Mist
Design Option
VC-1C S/S Control Cabinet with push button controls VC-1M S/S Control Cabinet with programmable Mode Commander Microprocessor
Shipping Wt. 165 lbs./Linear Ft.
COMMENTS/NOTES: ____________________________________________________________________
N.F.P.A. #96 SUPPLY DAMPERS
3/8" DIA. G.I. ROD HANGERS
FURNISHED BY OTHERS
FINISHED S.S. PANELING
DIFFUSER BAFFLES
1/2" INSULATION ON INTERIOR
18 GA. S.S. PERF. PANELING
WITH LIFT OFF HANDLES
FOR EASY REMOVAL
2'-6"
6'-6" A.F.F.
'- "
2'-0" 9"
9"
VENTILATOR DRAIN
(FLOURESCENT LIGHTS OPTIONAL)
" "5"
T-STATS
4"
'- "
(60"-72" STD.)
INCANDESCENT LIGHTS
BULBS NOT INCLUDED
Loading...
+ 2 hidden pages