25. Spare parts .......................................................................................................Page 26
Edition 08 17.11.2004 / Bak Page 2/26
Emergency power lamp
Dr. Mach
Lamps and Engineering
1. Instructions for use / operating Instructions
for sealed lead - acid batteries
1. Identification, operating data
Type of battery: BTX 12-24
Block voltage: 12 V Length 166 mm
Number of blocks: 2 Width: 175 mm
Number of cells: 12 Height 125 mm Assembly date: 12-2002
Nominal voltage UN 24 V Capacity* C
Block weight: 9.2 kg Capacity* C
Electrolyte density 1.3 kg/l Capacity* C
Nominal temperature 20
Ideal room temperature20
0
C Capacity* C
0
C Torque on installation.: 4.5 Nm
(1.8 V/cell): 26 Ah#
20
(1.8 V/cell): 24 Ah
10
(1.75 V/cell): 20 Ah Commissioning date:
3
(1.75 V/cell): 16 Ah
1
Antimony content: <<1 % Torque in service: 3.6 Nm
Service interval: see 7.2 Ventilation calculation: DIN/EN 50272-
# = Reference capacity (nominal capacity) according to DIN/EN 60896-1 (x V/cell) = Voltage at end of discharge
2. Safety instructions
2.1 Maintenance free / pressure relief valves
The sealed battery blocks require no maintenance. Topping up with water is not allowed. Pressure relief valves are used
as stoppers. Opening them results in the destruction of the battery.
However, the battery requires regular inspection and maintenance (see Section 7).
2.2 Prohibitions, requirements and disposal instructions
1
2
3
4
5
Delivery date: 12-2002
Assembled by:
Commissioned by:
CE-characteristic by:
6
7
PERL emergency current
PERL emer-
gency current
* = for 25
8
0
C
i
1 Observe the Instructions for Use.
2. When working on batteries wear protective glasses and clothing as
specified in the Accident Prevention Instructions and DIN/EN
50272-2 (VDE 0510).
3. Smoking is forbidden, no naked flames, embers or sparks are
allowed in the vicinity of the battery.
4. There is a danger of explosion and fire so avoid short circuits. Metal
parts of the poles are always live, therefore do not put tools or other
items on the battery.
5. The electrolyte, sulphuric acid, is very corrosive. There is no possibility of contact with the electrolyte unless the battery is damaged
If the casing is defective the electrolyte retained in the
fleece behaves like liquid electrolyte.
6. Any droplets of acid that gets into the eye or on the skin
must be rinsed out or washed off immediately with a
copious supply of water. Then get to a doctor without
delay. If clothing is polluted wash it immediately with
water.
7. Block batteries are heavy. Take care to put them on a
safe base. Only use suitable transport equipment.
8. Old batteries with this sign can be recycled and must be
put through the recycling process. Old batteries, which
are not put through the recycling process should be disposed of in accordance with all the regulations as special waste products.
Pb
3. Storage
All battery blocks are delivered in the charged condition. If they are not to be put into service immediately but are to be put in store
for a long time they should be stored in a dry, clean and frost free place. Sealed lead acid batteries are best given a trickle charge
when stored. If this is not the case, they must be given an equalisation charge (see Section 6.1.4) at the latest when they sink to
12.5 V open circuit voltage, or every 6 months depending on which occurs first.
4. Commissioning
The ideal operating temperature is 200C. Higher temperatures shorten the life of the battery, lower temperatures reduce
the available capacity. The battery blocks must be so set up, that within the same blocks temperature differences of >3
occur. Before commissioning, the batteries should be examined for damage, correct pole connection, solid fit of the connectors (for
torques see table above) and secure contacts. If necessary, pole covers should be fitted. After the charging device and loads are
switched off the correct poles of the battery should be connected to the d.c. supply. Switch on the charging device and charge the
battery as specified in Section 6.1.
The regulations in DIN/VDE 0107, DIN/VDE 0108, DIN/EN 50272-2 (VDE 0510-2) or DIN/VDE 0510-7 as well as IEC 896-2
(DIN/EN 60896-2) should be observed if necessary.
0
C cannot
Edition 08 17.11.2004 / Bak Page 3/26
Emergency power lamp
Dr. Mach
Lamps and Engineering
5. Operation
The regulations of DIN/VDE 0107, DIN/VDE 0108, DIN/EN 50272-2 (VDE 0510-2) or DIN/VDE 0510-7 as well as IEC 896-2
(DIN/EN 60896-2) should be observed when operating static sealed batteries.
6 Charging, discharging
6.1 Charging
Any of the charging procedures with their limits as specified in DIN 41773 (IU-characteristic), DIN 41774 (W-characteristic) or DIN
41776 (I-characteristic) can be used. Depending on the equipment the batteries in this equipment are charged with the IUcharacteristic.
6.1.1 Maintaining the full load condition (maintenance charge)
Equipment with the properties specified in DIN 41773 (IU-characteristic) should be used. The equipment should be so set up, that
the cell voltage
higher or lower environmental temperature, the charging voltage must be adjusted to:
= 2.3 V/cell (permissible deviation: 1%). If the battery temperature is continuously higher or lower due to
(20°C)
Charging voltage
Charging voltage
Example
predominately at 30°C, Charging voltage = 2.3V/cell - 0.040 V/cell = 2.260 V/cell.
: Temperature lies predominately at 15°C, charging voltage = 2.3 V/cell + 0.02V/cell = 2.320 V/cell. Temperature lies
(more than 20°C)
(less than 20°C)
= 2.3 V/cell - 0.004 V • ∆T (∆T = Temperature difference above 20°C)
= 2.3V/cell + 0.004 V • ∆T (∆T = Temperature difference below 20°C)
6.2 Discharging
The correct discharging currents are obtained from the capacities as specified in I
more than the correct capacity can be taken out. In order to avoid a deep discharge and consequent destruction of the battery, it
must be disconnected from the loads before reaching the discharge finishing voltage that is dependent on the bridging time.
Guide values are:
Bridging time Discharge finishing voltage Bridging time Discharge finishing voltage
> 3 h 1,80 V/cell 20 min. – 1 h 1,67 V/cell
1-3 h 1,75 V/cell < 20 min. 1,60 V/cell
The connection of the loads should only be done after the power supply has been restored. After discharge, even partial dis-charge, the battery should immediately be charged.
= Ct/t. Unless other data is available, not
(Disch..)
7. Battery maintenance, inspection of the battery equipment
7.1 Battery maintenance
The battery should be kept clean and dry in order to prevent leakage currents. The cleaning of the battery should be done in
accordance with the ZVEI-leaflet “Cleaning of batteries“. Plastic parts of the battery may only be cleaned with clean water.
7.2 Inspection of battery equipment
It is recommended that every 3 months the following work should be done and documented:
• Visual inspection of the battery regarding cleanliness, damaged battery blocks and loose contacts
• Measurement of charge maintaining voltage of the battery and the individual battery blocks
• Measurement of the surface temperature of the battery blocks
• Measurement of the temperature in the battery room.
The following work should be carried out and documented at least every 12 months (guarantee condition):
• All connections should be tightened to the recommended values (see table under Item 1) by a torque spanner,
• The tests for 6 months should be repeated
• If possible, measure the voltage of the battery and the individual battery blocks with the charging device switched off.
Only in collaboration with the System Manufacturer or someone authorised by him:
• Record the battery block voltages during the discharge of the battery (capacity test).
When tests are carried out they should be done as specified in IEC 896-2 (DIN/EN 60896-2). Instructions specified in DIN/VDE
0107 and DIN/VDE 0108 should also be observed.
8. Guarantee
Guarantee claims are only accepted if the maintenance and servicing work have been properly carried out. For guarantee claims
at least the following data/documents must be provided: the reason for the complaint, contract number and the last two maintenance reports. Defective battery blocks must be sent back for defect analysis carriage paid.
If the Instructions for Use are not followed, e.g. if the room temperature is too high, the batteries are left discharged for a
long time or stored in unsuitable conditions, trickle charged at the wrong voltage or the service intervals and instructions
are not observed, the guarantee becomes invalid.
Edition 08 17.11.2004 / Bak Page 4/26
Emergency power lamp
Dr. Mach
Lamps and Engineering
Extent of supply:
• Emergency power unit
• Allan key / DIN 911 –5 long –3 and –10
• Spring arm / central spring arm
• Lamp Mach 380 / Mach M3 / Trigenflex /
Triaflex
• Pre-mounted stand tube
• Two long feet with brakes
• Two short feet without brakes
• 1x cable binder 2,7mm
• Spare parts: 1x fuse 6x35, 10A secondary,
and 2x battery fuse 5x20, 1,6A
These installation instructions must be kept in a safe place together with the relevant operating
instructions for the light, so they can be consulted whenever necessary.
2. General instructions
All Dr. Mach emergency lighting systems are supplied with all parts necessary for installation and connection.
The supporting pole is divided into two parts.
The battery box is supplied with a connecting cable and earthed plug.
The plugs used must be installed in accordance with the requirements of IEC or VDE 0107.
A check should be made to ensure that there is a standard electric socket within the working area of the
light.
The light must be kept continuously connected to the mains, as otherwise it will not be permanently available.
Maintenance of the supporting pole and any special installation work on the sliding contacts can
only be carried out by us or by our appointed technicians.
The manufacturer only guarantees the safety of the light if repairs and alterations have been carried out by him or by a technician who adheres to the safety regulations.
The manufacturer shall have no legal liability for injury to persons or damage to property if the
light is operated wrongly or in any other way or used for any other purpose than that for which it
was designed.
Edition 08 17.11.2004 / Bak Page 5/26
Emergency power lamp
Dr. Mach
Lamps and Engineering
3. Wiring diagram
4. Controls
H1
H2
Q1
S1
Edition 08 17.11.2004 / Bak Page 6/26
H5 H4 H3
Emergency power lamp
5. Key to the wiring diagram
A 1 Charge regulator
A 2 Electronic control module
A 3 Output level for charge regulator
F 1 Mains fuse
F 2 Mains fuse
F 3 Battery fuse
H 1 LED green to show mains operation
H 2 LED yellow to show battery operation
H 3 LED green to show battery fully charged
H 4 LED yellow to show battery charged 80% to 20%
H 5 LED red to show battery discharged
Dr. Mach
Lamps and Engineering
S 1 Acknowledgement button
Q 1 ON/OFF switch for testing
T 1 Transformer
V 1 Rectifier
K 1 Switchover protector
Edition 08 17.11.2004 / Bak Page 7/26
Emergency power lamp
6. Mounting the stand tube and the battery box
L
K
L
to the stand foot
Loosen two screws 1 before mounting each foot.
Then insert the four feet and fix them with the
screws (do not tighten!)
For mounting the stand foot proceed as described
in the enclosed figures and drawings.
K
L = long feet
S = short feet
1
Attention!
After fixing the feet, tighten all sixteen screws
uniformly!
Dr. Mach
Lamps and Engineering
Push together both tubes as shown in the photography.
Connecting the battery box
After mounting the stand foot put the battery box on
the stand foot. Use the pad included in the scope of
supply.
Remark:
Because of the high weight of the battery box it
is recommended that this work is carried out by
two persons to avoid damage.
Edition 08 17.11.2004 / Bak Page 8/26
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.