Desa VSGF33NRB, VSGF33PRB, EFS33PRB, EFS33NRB User Manual

UNVENTED (VENT-FREE) GAS FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Shown with optional cabinet mantel, hearth base and trim accessories.
EFS33PRB, EFS33NRB, VSGF33PRB AND VSGF33NRB
REMOTE-READY FIREPLACE SYSTEM
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service, or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety Information ............................................... 3
Product Identification .......................................... 4
Local Codes ........................................................ 5
Unpacking ........................................................... 5
Product Features ................................................ 5
Air For Combustion and Ventilation ....................5
Installation ........................................................... 8
Operating Fireplace .......................................... 17
Inspecting Burners ............................................ 20
Cleaning and Maintenance ...............................21
2
www.desatech.com 113132-01A
Wiring Diagram .................................................22
Specifications .................................................... 22
Troubleshooting ................................................23
Replacement Parts ........................................... 27
Service Hints ..................................................... 27
T echnical Service.............................................. 27
Illustrated Parts Breakdown and Parts List ....... 28
Accessories.......................................................32
Warranty Information.......................... Back Cover
SAFETY INFORMATION
WARNING: This product con­tains and/or generates chemicals known to the State of California to cause cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this heater. Im­proper use of this heater can cause serious injury or death from burns, fire, explosion, elec­trical shock, and carbon mon­oxide poisoning.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furni­ture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of car-
bon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/
LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn­ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this heater.
Fireplace front and screen be­come very hot when running fire­place. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fire­place will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil­dren when they are in the room with fireplace. When using the optional hand-held remote ac­cessory, keep selector switch in the OFF position to prevent chil­dren from turning on burners with remote.
You must operate this fireplace with the fireplace screen and hood in place. Make sure fire­place screen and hood are in place before running heater.
Keep the appliance area clear and free from combustible ma­terials, gasoline, and other flam­mable vapors and liquids.
113132-01A 3
www.desatech.com
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appli­ance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in­side any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bed­room or bathroom.
5. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, pages 21 and 22.
8. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9. This fireplace needs fresh air ventilation to run properly. This fireplace has an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if enough fresh air is not available. See Air for Combustion and Ventilation, pages 5 through 7. If fireplace keeps shutting off, see Troubleshooting, pages 23 through 26.
10. Do not run fireplace
• where flammable liquids or vapors are used
or stored
• under dusty conditions
11. Do not use this fireplace to cook food or burn paper or other objects.
12. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
13. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
14. Turn fireplace off and let cool before servic­ing. Only a qualified service person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16. To prevent performance problems in pro­pane/LP units, do not use propane/LP fuel tanks of less than 100 lbs. capacity (pro­pane/LP units only).
17. Provide adequate clearances around air openings.
PRODUCT
IDENTIFICATION
Rear Log
Middle Log Front
Log
Piezo Ignitor
Front
Optional Remote Control
Burner
Base Assembly
Figure 1 - Log Base Assembly
(VSGF33NRB Shown)
Fireplace Hood
Firebox Support
Screen Assembly
Top Outer Casing
Figure 2 - Fireplace (VSGF33NRB Shown)
Rear Burner
Top Louver Assembly
Optional Blower Assembly (Not Included)
Bottom Louver Assembly
4
www.desatech.com 113132-01A
LOCAL CODES
Install and use fireplace with care. Follow all lo­cal codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI
Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
Note:
Where listed vented decorative logs are re-
quired, thermostat operation is not permitted.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
UNPACKING
CAUTION: Do not remove the data plates attached to the heater base assembly. The data plates contain important war­ranty and safety information.
1. With utility knife, cut the carton all the way around above the staples on the bottom tray. Lift the carton off the heater. Remove pack­ing.
Note:
on the right hand side of the heater front. Lift the heater off the bottom tray.
2. Locate two screws above top corners of the fire­place screen. Remove and discard these screws. Lift fireplace screen up and pull out to remove.
3. Remove protective packaging applied to logs, log base assembly, and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought fireplace.
The hood is located in the packing
PRODUCT FEATURES
OPERATION
This vent-free fireplace is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing embers. When used without the optional blower, the fireplace requires no elec­tricity making it ideal for emergency backup heat.
113132-01A 5
www.desatech.com
SAFETY DEVICE
This fireplace has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot system shuts off the fire­place if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system re­quires no matches, batteries, or other sources to light fireplace.
OPTIONAL REMOTE CONTROL ACCESSORY
There are four optional remote controls (not included) that can be purchased separately for this log heater:
• wall switch
• wall thermostat
• hand-held ON/OFF remote
• hand-held thermostat remote See Accessories, pages 32 through 34.
OPTIONAL BLOWER ASSEMBLY ACCESSORY
This fireplace accepts an optional blower assem­bly (not included). The GA3650T Series blower operates thermostatically and features a variable speed control. The GA3750 Series operates manu­ally and also features a variable speed control. The blower circulates heated air from the fireplace into the room. Use of blower is optional. See Accesso- ries, pages 32 through 34.
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight con­struction unless provisions are provided for adequate combus­tion and ventilation air. Read the following instructions to in­sure proper fresh air for this and other fuel-burning appli­ances in your home.
Today’ s homes are built more ener gy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
AIR FOR COMBUSTION
AND VENTILATION
Continued
While it is good to make your home energy effi­cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFP A 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol­lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 5 through 7 will help you
classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ven­tilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 with openings gasketed or sealed
b. weather stripping has been added on
openable windows and doors
c. caulking or sealants are applied to ar-
eas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, be­tween wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you m ust provide additional fresh air . See
Ventilation Air From Outdoor s
If your home does not meet all of the three criteria above, proceed to
Fresh-Air Flow For Heater Location
6
-11
kg per pa-sec-m2) or less
and
, page 7.
Determining
.
www.desatech.com 113132-01A
and
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 defines a confined space as a space
whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate in­put rating of all appliances installed in that space and an unconfined space as a space whose vol­ume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through open­ings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills be­tween them.
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless pas­sageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example:
(width) x 8 ft. (ceiling height) = 2,560 cu. ft. (vol­ume of space)
If additional ventilation to adjoining room is sup­plied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example:
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace _________ Btu/Hr Gas water heater* _________ Btu/Hr Gas furnace _________ Btu/Hr Vented gas heater _________ Btu/Hr Gas fireplace logs _________ Btu/Hr Other gas appliances* + ________ Btu/Hr Total = ________ Btu/Hr * Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors and vents to the outdoors.
Space size 20 ft. (length) x 16 ft.
2,560 cu. ft. (volume of space) x 20 =
AIR FOR COMBUSTION
AND VENTILATION
Continued
Example:
Gas water heater _____________ Btu/Hr Vent-free fireplace _____________ Btu/Hr Total _____________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
________ ________
Example:
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used) 51,200 Btu/Hr (maximum the space
can support) 73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad­ditional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an uncon­fined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un­confined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be oper­ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section
5.3
or applicable local codes
40,000 33,000 73,000
.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un­confined space. When ventilating to an adjoining unconfined space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). Y ou can also remove door into adjoining room (see op­tion 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
12"
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove Door into Adjoining
Room, Option
3
Figure 3 - Ventilation Air from Inside
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent open­ings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
or outlet air into attic if attic has a thermostat-con­trolled power vent. Heated air entering the attic will activate the power vent.
Outlet Air
Outlet Air
Ventilation Grills
Into Adjoining Room,
Option 2
12"
Building
Do not provide openings for inlet
Ventilated Attic
To Attic
To
Crawl
Inlet Air
Inlet Air
Crawl Space
Space
Ventilated
Figure 4 - Ventilation Air from Outdoors
113132-01A 7
www.desatech.com
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser-
vice person must install fire­place. Follow all local codes.
WARNING: Never install the
fireplace
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This fireplace cre-
ates warm air currents. These currents move heat to wall sur­faces next to fireplace. Install­ing fireplace next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited, to tobacco smoke, aromatic candles, clean­ing fluids, oil or kerosene lamps, etc.) in the air exist, may dis­color walls or cause odors.
Note:
Y our fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough openings to create the easiest installation. See Built-In Fire- place Installation, pages 11 and 12.
IMPORTANT:
air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and V entilation, pages 5 through 7.
IMPORTANT:
fireplace is not level, log set will not work properly.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your fireplace. If your gas supply is not cor­rect, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
V ent-free heaters add moisture to the
Make sure the fireplace is level. If
WARNING: This appliance is equipped for (natural or pro­pane/LP) gas. Field conversion is not permitted.
ELECTRICAL HOOKUP
(Models GA3750 Series and GA3650T Series Blower Accessories, and GA3555 Internal Duplex Kit)
This fireplace accepts a blower assembly with an elec­trical cord. The electrical cord is five feet in length. Y ou must locate fireplace within reach of a 120 volt grounded electrical outlet. If not, you must install an electrical outlet within reach of fireplace power cord. The GA3555 outlet accessory may be used for built­in applications with blower accessory installed.
INSTALLING HOOD
Install hood to rail already installed in fireplace as shown in Figure 5. Use 3 Phillips screws provided.
Rail
Hood
Screw
Figure 5 - Installing Hood
8
www.desatech.com 113132-01A
INSTALLATION
Continued
ASSEMBLING AND ATTACHING OPTIONAL PERIMETER TRIM (Included with Mantel Accessory)
IMPORTANT:
a wall, do not attach trim at this time. See Built-In Fireplace Installation, pages 11 and 12.
Note:
attaching trim to fireplace.
1. Remove packaging from three pieces of trim.
2. Locate four screws, two adjusting plates with set screws, and two shims in the hard­ware packet.
3. Align shim under adjusting plate as shown in Figure 6.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top trim (see Figure 6).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side trim (see Figure 6).
6. While firmly holding edges of trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other side.
8. Tighten trim hanging screws (#10 x 6.25 shoulder) into holes in cabinets. Place the as­sembled trim onto fireplace cabinet. Align hanging notches on trim with hanging screws on side of fireplace (see Figure 7). Push trim firmly into place, sliding hanging notches over hanging screws.
Side Trim
Figure 6 - Assembling Perimeter Trim
If you are recessing the firebox in
The instructions below show assembling and
Set Screws
Top Trim
Slot
Slot
Adjusting Plate
Shim
Mitered Edge
Trim Hanging Screws
Hanging Notches on Trim
Assembled Trim
Figure 7 - Attaching Perimeter Trim to
Fireplace (VSGF33NRB Shown)
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling, and adjoining wall.
Carefully follow the instructions below. This will ensure safe installation.
Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabi-
net to any combustible material and wall should follow diagram in Figure 8.
Example:
etc. is made of combustible material and pro­trudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fire­place opening (see Figure 8).
B. Clearances from the top of the fireplace opening
to the ceiling should not be less than 42 inches.
Top Left and Bottom
The face of a mantel, bookshelf,
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Right Sides and Rear
0" 16" 0"
Example
*
*Minimum 16 inches from Side Wall
Figure 8 - Minimum Clearance for
Combustible to Wall
113132-01A 9
www.desatech.com
INSTALLATION
Continued
CONVENTIONAL FIREPLACE INSTALLATION
Conventional installation of this fireplace involves installing fireplace along with the corner, face, or cabinet mantel with hearth base accessories against a wall in your home. Follow the instructions in this section to install the fireplace in this manner.
Note:
The instructions in this section show instal­lation using the cabinet mantel and the G3333F/G3334U/G3004W/G3335F/G3007U se­ries hearth base accessories. The hearth base ac­cessory shown is optional for this installation. Y ou can install fireplace and cabinet/corner mantel di­rectly on the floor. The corner mantel accessory cannot be installed with the G3333F/G3334U/ G3004W/G3335F/G3007U hearth base. The cor­ner mantel can be paired with the G3008F/ G3009U/G3010F corner hearth base. If mounting fireplace and cabinet or corner mantel to the floor, an optional G3005J/3005S/3005B Slim Base kit may be installed.
1. Assemble cabinet mantel, hearth base, and
trim accessories. Assembly instructions are in­cluded with each accessory.
2. When installing blower, install a properly
grounded, 120 volt three-prong electrical out­let at fireplace location if an outlet is not there. If possible, locate outlet so cabinet mantel will cover it when installed (see Figure 9).
3. Install gas piping to fireplace location. This
installation includes an approved flexible gas line (if allowed by local codes) after the equip­ment shutoff valve. The flexible gas line must be the last item installed on the gas piping. See Installing Gas Piping to Fireplace Loca- tion, pages 12 and 13.
Electrical Outlet
Rigid Pipe and Gas Shutoff Valve
4. Place hearth base accessory against wall at installation location. Cut an access hole in hearth top to run flexible gas line to fireplace (see Figure 9). Make sure to locate access hole so cabinet mantel will cover it when installed.
Note:
Y ou can secure base to floor using wood
screws. Countersink screw heads and putty over.
5. Route flexible gas line through access hole in hearth base.
6. Center cabinet mantel on hearth base (see Fig­ure 10). Make sure mantel is flush against wall.
7. Break off nailing flanges (see Figure 11) with hammer or pliers.
8. Place cardboard or other protective material on top of hearth base. Carefully set fireplace on protective material, with back of fireplace inside mantel opening.
9. Attach flexible gas line from fireplace gas regulator to gas supply. See Connecting Fir e- place to Gas Supply, page 14.
10. If blower is installed, route blower electrical cord through access holes in either side of fire­place.
Note:
sary. Plug electrical cord into electrical outlet.
Bushing may be moved if neces-
Cabinet Mantel
Figure 10 - Installing Cabinet Mantel
Hearth Base
Figure 9 - Placing Hearth Base
Accessory Against Wall
10
Nailing Flanges
Gas Line Access Hole
Figure 11 - Location of Nailing Flanges
www.desatech.com 113132-01A
INSTALLATION
Continued
11. Carefully insert fireplace into cabinet mantel. Be careful not to scratch or damage hearth base, cabinet mantel, or any laminate trim on hearth base. Remove protective material from top of hearth base and from front of fireplace (if any).
Note:
You can secure fireplace to hearth or floor. Open lower louver. Locate screw holes in bottom of base. Tighten wood screws through these holes and into hearth or floor.
12. Check all gas connections for leaks. See Checking Gas Connections, pages 15 and 16.
3. Install gas piping into fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the equip­ment shutoff valve. The flexible gas line must be the last item installed on the gas piping. See Installing Gas Piping to Fireplace Loca- tion, pages 12 and 13.
4. Carefully set fireplace in front of rough open­ing with back of fireplace inside wall opening.
5. Carefully insert fireplace into rough opening.
6. Attach flexible gas line to gas supply. See Connecting Fireplace to Gas Supply , page 14.
7. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange (see Figure 15).
8. Check all gas connections for leaks. See Checking Gas Connections, pages 15 and 16.
9. Plug electrical cord into electrical outlet in­stalled in step 2.
10. Install trim after final finishing and/or paint­ing of wall (see Figure 7, page 9).
3
17
Figure 12 - Inserting Fireplace Into
Cabinet Mantel
33"
/4"
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves in­stalling fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. If in­stalling a mantel above the fireplace, you must fol­low the clearances shown in Figure 16, page 12. Follow the instructions below to install the fire­place in this manner.
Actual Framing
Height 32 3/8" 33" Front Width 34 5/16" 35 1/2" Depth 16 11/16"17 3/4"
1. Frame in rough opening. Use dimensions shown in Figure 13 for the rough opening. If installing in a corner, use dimensions shown in Figure 14 for the rough opening. The height is 33" which is the same as the wall opening above.
2. If using blower, install and properly ground GA3555, three-prong 120 volt electrical outlet, in fireplace. Follow instructions included in kit.
113132-01A 11
www.desatech.com
Figure 13 - Rough Opening for Installing
3
39
Figure 14 - Rough Opening for Installing
Nails or Wood Screws
Figure 15 - Attaching Fireplace to Wall
in Wall
/8
"
35 55
in Corner
Nailing Flanges
35 1/2"
1
/2
"
5
/8
"
Studs
7
/8
"
27