http://www.delta.com.tw/industr ialautoma tion/
Thermocouple Sensors
DVP04TC-S
1 WARNING
Always read this instruction thoroughly before using the DVP04TC-S.
Make sure that power is OFF before wiring.
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust,
humidity, electric shock risk and vibration. Also, it is equipped with protective methods such as
some special tools or keys to open the enclosure, in order to prevent hazard to users or damage
the PLC.
Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may
damage the PLC. Check all the wiring prior to power up.
Do NOT touch internal circuit within 1 minute after power is OFF.
Make sure that the DVP04TC-S is properly grounded , to avoid any electromagnetic noise.
2 INTRODUCTION
2.1 Model Explanation and Peripherals
Thank you for choosing DELTA’s DVP Series PLC. The DVP04TC-S allows the connection of
four thermocouple sensors (Type J/K). The DVP04TC-S series can read/write the data by using
instructions FROM / TO via DVP-PLC SS/SA/SX/SC MPU program. There are 49 CR (Control
Register) in each module and 16 bits for each register.
DVP04TC-S thermocouple sensor can update software version by RS-485. Power supply and
main processing units are sold separately.
The DVP04TC-S works with both Centigrade and Fahrenheit. The input resolution for
Centigrade is 0.1 degrees and for Fahrenheit is 0.18 degrees.
Nameplate Explanation
Input power Supp ly Spec.
Analog Input /Output Module Spec.
Barcode, series and version
Model Explanation
Model
Product Series
Input + Output points
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperatur e sensors (PT-100)
2.2 Product Profile and Outline
1
2
3
90.00
3.00
25.20
4.00
4
5
L+
C
L-
H
SLD
1
●
L+
C
L-
H
SLD
2
●
●
L+
C
L-
H
3
SLD
●
L+
C
L-
H
4
SLD
●
●
PLC model
S: for SS/SA series MPU
TC: Thermocouple sensors (Type J/K)
XA: Analog input/output mixed module
RT: Resistor Thermoc ouple( NTC)
60.00
6
7
8
10
9
3
Unit: mm
Instruction Sheet
MODEL
:
POWER INPUT
:
THERMOCOUPLES
RESOLUTION:14 BITS
Serial Number
24Vdc 2W
:
TYPE J , K
04TC-S0T50200 01VX.X
3.4
3.00
11
12
14
13
MADE IN XXXXX X
Producti on series
Producti on week
Production year (2005)
Producti on place (Taoyuan)
Serial number of version
Producti on Model
60.00
90.00
1. Status indicator (Power, RUN and ERROR) 8. Extension port
2. Model Number 9. Extension Clip
3. DIN rail clip 10. DIN rail location (35mm)
4. I/O terminals 11. RS-485 Communication port
5. I/O point indicator 12. Extension Clip
6. Extension hole of the extension unit mounting
pins
7. Specification Label 14. Extension port
13. DC Power input
2.3 External wiring
Note 1: Use only the wires that are
terminal of
power module
Thermocouple
Thermocouple
Shielded*1
+
-
Shielded*1
+
-
*3
System
Grounding
Class 3 Grounding
(100 of less)
CH1
CH4
*2
SLD
SLD
24+
24-
L+
L-
L+
L-
100
Cold-junction
Compensati on
DC/ DC
Converter
MUX
Note 2: Terminal SLD is a grounding
Note 3: Please connect
5V
AG
+15V
AG
-15V
Warning: DO NOT connect wires to the
2.4 Terminals of analog module
DVP04AD-S DVP02DA-S DVP04DA-S DVP04PT-S DVP04TC-S DVP06XA-S DVP08RT-S
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
+
I+
COM
FG
L+
L-
IFG
L+
L-
IFG
L+
L-
IFG
L+
L-
IFG
L+
L-
SLG
L+
L-
SLG
L+
L-
SLG
L+
L-
SLG
3 STANDARD SPECIFICATIONS
3.1 Function Specifications
Platinum Temperature Module (04TC)
Power Supply Voltage 24 VDC(20.4VDC~28.8VDC) ( –15%~+20%)
Analog Input Channel 4 channels per module
Sensors Type J-type or K-type thermocouple
Temperature Input Range
Digital Conversion Range
Resolution
Overall Accuracy
Response Time
Isolation Method
J-type: -100°C~700°C
K-type: -100°C~1000°C
J-type: K-1000~K7000
K-type: K-1000~K10000
14 bits(0.1°C) 14 bits(0.18°F)
±0.5% of full scale of 25°C(77°F), ±1% of full scale during 0~55°C
(32~131°F)
250 ms × channels
Isolation between digital and analog circuitry. There is no isolation between
channels.
Digital Data Format 2’s complement of 16-bit, (13 Significant Bits)
Average Function Yes (CR#2~CR#5 may be set and the range is K1~K4096)
Self Diagnostic Function Ye s
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 /
19200 / 38400 / 57600 / 115200. For ASCII mode, date format is 7Bits,
Communication Mode (RS-485)
even, 1 stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop
bit (8 E 1). The RS-485 is disabled when the DVP04TC-S is connected in
series to an MPU.
When DVP04TC-S modules are connected to an MPU, the modules are
Connection to a DVP-PLC MPU in
Series
numbered from 0 – 7. 0 is the closest to the MPU and 7 is the farthest. The
Maximum number of modules is 8 modules and they do not occupy any
digital I/O points of the MPU.
Centigrade (°C)
supplied with your
thermocouple sensor. Tighten
PLC terminal screws to a
torque of 1.95 kg-cm (1.7
in-lbs).
location for noise suppression.
terminal of
power supply module and
terminal of DVP04TC-S
thermocouple sensors module
to system earth ground.
No Connection ( ) terminals.
Use copper conductor only,
60℃
+
I+
COM
+
I+
COM
+
I+
COM
+
I+
COM
+
I+
COM
+
I+
COM
L+
LL+
LL+
LL+
L-
L+
LL+
LL+
LL+
L-
Fahrenheit (°F)
J-type: -148°F~1292°F
K-type: -148°F~1832°F
J-type: K-3280~K12920
K-type: K-1480~K18320
3.2 Other Specification
Power Specification
Maximum Power Consumption 2W at 24 VDC (20.4VDC~28.8VDC) ( -15 % ~ +20 %)
Environment Condition
Environment Condition Follow the DVP-PLC MPU.
Static Electricity Prevention All places between terminals and ground comply with the spec.
4 CR (Controlled Register)
DVP04TC-S platinum temperature sensors Explanation
RS-485
CR
Parameter
No.
#0
#1
#2
#3
#4
#5
#6
#7
#8
#9
#10
#11
#12
#13
#14
#15
#16
#17
#18 Reserved
#19
#20
#21
#22
#23 Reserved
#24
#25
#26
#27
#28~#29 Reserved
#30
#31
#32
#33
#34
#35~#48 System used
○ means latched.
╳ means not latched.
R means can read data by using FROM instruction or RS-485.
W means can write data by using TO instruction or RS-485.
Explanation:
1. CR#0: The PLC model type.
Latched Register name b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
address
H 4096
H 4097
H 4098
H 4099
H 409A
H 409B
H 409C
H 409D
H 409E
H 409F
H 40A2
H 40A3
H 40A4
H 40A5
H 40A8
H 40A9
H 40AA
H 40AB
H 40AE
H 40AF
H 40B0
H 40B1
H 40AE
H 40AF
H 40B0
H 40B1
H 40B4
H 40B5
H 40B6
H 40B7
R Model type System used, DVP04TC-S model code = H 8B
○
Reserved CH4 CH3 CH2 CH1
○
R/W Thermocouple type
R/W CH1 average number
○
R/W CH2 average number
○
R/W CH3 average number
○
R/W CH4 average number
○
R
╳
CH1 average degrees(°C)
R
╳
CH2 average degrees(°C)
R
╳
CH3 average degrees(°C)
R
╳
CH4 average degrees(°C)
R
╳
CH1 average degrees(°F)
R
╳
CH2 average degrees(°F)
R
╳
CH3 average degrees(°F)
R
╳
CH4 average degrees(°F)
Present temperature of
╳
R
CH1 (°C)
Present temperature of
╳
R
CH2 (°C)
Present temperature of
╳
R
CH3 (°C)
Present temperature of
╳
R
CH4 (°C)
Present temperature of
╳
R
CH1 (°F)
Present temperature of
╳
R
CH2 (°F)
Present temperature of
╳
R
CH3 (°F)
Present temperature of
╳
R
CH4 (°F)
R
○
CH1 OFFSET Value
R
○
CH2 OFFSET Value
R
○
CH3 OFFSET Value
R
○
CH4 OFFSET Value
R Error status Data register stores the error status, refer to fault code chart for details.
╳
R/W Communication address
○
setting
R/W Communication baud rate
○
setting
R/W Reset to factory setting
○
Example: Setting of CH1
1. b0: set 0 to use J-type and set 1 to use K-type
2. b1: Reserved.
3. b2: Reserved.
The number of readings used for “average” temperature on channels CH1~CH4.
Setting range is K1~K4096 and factory setting is K10.
Average degrees for channels CH1~CH4. (unit: 0.1 degrees C)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees F)
Present temperature of channels CH1~CH4. (unit: 0.1 degrees C)
Present temperature of channels CH1~CH4. (unit: 0.1degrees F)
Adjust offset value of channels CH1~CH4. The range is -1000~+1000 and
factory setting is K0. (unit: 0.1 degrees C)
RS-485 communication address.
Setting range is 01~255 and factory setting is K1
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps).
b0: 4800 bps (bit/sec).
b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec).
b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec).
b5: 115200 bps (bit/sec).
b6~b13: Reserved.
b14: switch between low bit and high bit of CRC code (only for RTU mode)
b15: RTU mode.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Definition of ERR
LED
Example: Setting of CH1
1. b0 Reserved
2. b1 Reserved
3. b2: Set to 1 and PLC will be reset to factory settings.
CH4 CH3 CH2 CH1
Definition of ERR LED: b12~b15=1111(factory settings)
1. b12 corresponds to CH1: when b12=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
2. b13 corresponds to CH2: when b13=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
3. b14 corresponds to CH3: when b14=1, scale exceeds the range or external
contact has no connection, ERR LED flashes.
4. b15 corresponds to CH4: when b15=1, scale exceeds the range or external
H 40B4
R Software version Display software version in hexadecimal. Example: H 010A = version 1.0A.
○
contact has no connection, ERR LED flashes.
2. CR#1: Used to set the working mode of four channels (CH1~CH4). There are 2 modes (J-type
and K-type) for each channel and can be set individually. For example, If you want to set
CH1~CH4 as following: CH1: mode 0 (b2~b0=000), CH2: mode 1(b5~b3=001), CH3: mode
0(b8~b6=000) and CH4: mode 1(b11~b9=001), you should set CR#1 to H0208. The higher
bits (b12~b15) will be reserved and the factory setting is H0000.
3. CR#2 ~ CR#5: Used to set the times of input readings for the average temperature calculation.
The available range is K1~K4096 and factory setting is K10. (Note: When PLC sets average
times via TO/DTO instructions, please use rising-edge/falling-edge detection instruction (such
as LDP and LDF) to get correct average times.)
4. CR#6 ~ CR#9: The average temperature (°C). The average temperature is calculated from
multiple temperature readings. Example: If CR#2 is 10, the temperature in CR#6 will be the
average of the last 10 readings in CH1.
5. CR#10 ~ CR#13: The average temperature (°F). The average temperature is calculated from
multiple temperature readings. Example: If CR#2 is 10, the temperature in CR#12 will be the
average of the last 10 readings in CH1.
6. CR#14 ~ CR#17: display present temperature (°C) of CH1~CH4 input signal.
7. CR#18, CR#23, CR#28, CR#29 are reserved.
8. CR#19 ~ CR#22: display present temperature (°F) of CH1~CH4 input signal.
9. CR#24 ~ CR#27: display offset value of channels CH1~CH4. The range is -1000~+1000 and
unit is 0.1 degrees C. The definition of OFFSET is Actual temperature = temperature
measured by DVP04TC-S – OFFSET value.
10. CR#30 is a fault code register. Refer to the following chart.
Fault description Content b15~b8 b7 b6 b5 b4 b3 b2 b1 b0
Power source abnormal K1(H1) 0 0 0 0 0 0 0 1
Analog input value error K2(H2) 0 0 0 0 0 0 1 0
Setting mode error K4(H4) 0 0 0 0 0 1 0 0
Offset/Gain error K8(H8) 0 0 0 0 1 0 0 0
Hardware malfunction K16(H10) 0 0 0 1 0 0 0 0
Digital range error K32(H20) 0 0 1 0 0 0 0 0
Average times setting error K64(H40) 0 1 0 0 0 0 0 0
Instruction error K128(H80)
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0
means normal and 1 means fault occurs.
Reserved
1 0 0 0 0 0 0 0
11. CR#31: RS-485 communication address. Setting range is 01~255 and factory setting is K1.
12. CR#32: RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600 and 115200.
b0:4800bps, b1:9600bps (factory setting), b2:19200bps, b3:38400 bps, b4:57600 bps,
b5:115200 bps, b6~b13: Reserved, b14: switch between low bit and high bit of CRC code
(only for RTU mode), b15: ASCII / RTU mode. For ASCII mode, date format is 7Bits, even, 1
stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop bit (8 E 1).
13. CR#33: Used to reset the settings of CR registers to factory settings.
14. CR#34: software version.
15. CR#35~ CR#48: Reserved for internal system use.
16. The corresponding parameters address H 4096~H 40C7 of CR#0~CR#48 may provide users
to read/write data via RS-485 communication.
a. Communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps.
b. Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication
format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
c. Function code: 03H—read data from register. 06H—write a WORD into register.
10H—write many WORDs into register.
5 Temperature/Digital Characteristic Curve
Temperature mode: (Centigrade)
J-type thermocouple
Digital output
+7000
C
-1000
Temperature
input
+700-100
Digital outpu
C
K-type thermocouple
+10000
C
-1000
+1000-100
Temperature
input
C
Temperature mode: (Fahrenheit)
J-type thermocouple
Digital output
+12920
Command
Explanation
K-type thermocouple
Digital output
+18320
m1: the number for special module. m2: the number of CR (Control Register) of special
module that will be read. D: the location to save reading data. n: the data number of
reading one time.
DVP-series PLC uses this instruction to read CR data of special module.
D: When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be used
for 32-bit.
Please refer the following footnote for calculationof special module number.
API
TO
D
79
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
m
1
m
2
S
n
Note: The usage range of operand m
The usage range of operand m2: SS/SA: 0-48, EH:
0-254.
The usage range of operand n: SS/SA n= 1~(49-m2),
EH: 1~(255-m2).
For SS series, it doesn’t support pulse execution
instruction (TOP, DTOP)
P
¼ ¼
¼ ¼
¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼
¼ ¼
is 0~7.
1
Command
Explanation
Footnote
m1: the number of special module. m2: the number of CR (Control Register) of special
module that will be wrote in. S: the data to write in CR. n: the data number to write in
one time.
DVP-series PLC uses this instruction to write data into CR of special module.
S: When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be used
for 32-bit.
The rule of instruction operand:
m1: arrangement number of special module. The number of special module that
connects to PLC MPU. The numbering order of special module from the near to
Special module CR
data write in
16-bit instruction (9 STEPS)
Continuous
TO
execution
32-bit instruction (17 STEPS)
Continuous
DTO
execution
Flag: When M1083=On, it allows
to insert interrupt during
FROM/TO.
Refer to following for detail.
Applicable model
SS SA/SX/SC EH
Pulse
TOP
execution
Pulse
DTOP
execution
-148
Tem pe r a tur e
input
-148
F
-1480
+1292
F
F
-1480
+1832
Tem pe r at ur e
input
F
6 Initial PLC Start-up
LED display:
1. Upon power-up, the ERROR LED will light for 0.5 seconds the POWER LED will light continuously.
2. No errors= POWER LED on and ERROR LED off.
Low Voltage error (lower than 19.5V), ERROR LED will blink continuously till the power supply
rises above 19.5V.
3. DVP04TC-S connected to PLC MPU in series = RUN LED on MPU will be lit and A/D LED or D/A
LED should blink.
4. After receiving the first RS-485 instruction the A/D LED or D/A LED will blink.
5. If the input or output exceeds the upper or lower bounds, then the ERROR LED will blink.
Example:
M1000
M1002
= H8B D0
FROM K0
TO K0
FROM K0
the distant of MPU is from 0 to 7. The maximum is 8 special modules and won’t
FROM K0
FROM K0
FROM K0
END
Explanation:
Reading the model type of extension module K0 (should be H8B for DVP04TC-S model type).
The averaging number for CH1~CH4 will be D10~D13.
occupy I/O point.
m2: the number of CR. Built in 16-bit of 49 groups memory of special module is
called CR (Control Register). The number of CR uses decimal digital (#0~#48). All
running status and setting values of special module has included.
If using FROM/TO instruction, the unit of read/write of CR is one number for one
time. If using DFROM/DTO instruction, the unit of read/write of CR is two numbers
in one time.
Upper 16-bit
CR #10 CR #9
The number of transmission groups n. The meaning of n=2 of 16-bit instruction
and n=1 of 32-bit are the same.
Specified device
Lower 16-bi t
Spec ified C
Specified CR number
Specified device
Spe ci fie d CR
If the model type is DVP04TC-S. Reading the average temperature (°C) of CH1~CH4 (4 data)
from CR#6~CR#9 and save them into D20~D23.
Reading the average temperature (°F) of CH1~CH4 (4 data) from CR#10~CR#13 and save them
into D24~D27.
Reading the present temperature (°C) of CH1~CH4 (4 data) from CR#14~CR#17 and save them
into D30~D33.
Reading the present temperature
(°F) of CH1~CH4 (4 data) from CR#19~CR#22 and save them
into D34~D37.
7 Related Instructions Explanation
API
FROM
D
78
Bit device Word device
X Y M S K H KnX KnY KnM KnS T C D E F
P
m1 ¼ ¼
m2 ¼ ¼
D ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼
n ¼ ¼
Note: The usage range of operand m
The usage range of operand m2: SS/SA: 0-48, EH:
0-254.
The usage range of operand n: SS/SA: n= 1~(49-m2),
EH: 1~(255-m2).
SS series model doesn’t support pulse execution
instruction (FROMP, DFROMP).
is 0~7.
1
Special module CR
data read out
16-bit instruction (9 STEPS)
Continuous
FROM
execution
32-bit instruction (17 STEPS)
DFROM
Flag: When M1083=On, it allows to
Continuous
execution
insert interrupt during FROM/TO.
Refer to following for detail.
Applicable model
SS SA/SX/SC EH
Pulse
FROMP
execution
DFROMP
Pulse
execution
In SS series models, flag M1083 is not provided. When FROM/TO instruction is
executed, all interrupts (including external or internal interrupt subroutines) will be
disabled. All interrupts will be executed after FROM/TO instruction is completed.
Besides, FROM/TO instruction also can be executed in the interrupt subroutine.
The function of the flag M1083 (FROM/TO mode exchange) provided in SA
models:
D0
D1
D2
D3
D4
D5
16-bit comma nd when n=6
1. When M1083=Off, FROM/TO instruction is executed, all interrupts (including
external or internal interrupt subroutines) will be disabled. All interrupts will be
executed after FROM/TO instruction is completed. Besides, FROM/TO
instruction also can be executed in the interrupt subroutine.
2. When M1083=On, if an interrupt occurs while FROM/TO instruction has been
programmed, FROM/TO instruction will be interruptted to execute the
interrupt. However, FROM/TO instruction cannot be executed in the interrupt
subroutine.
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
D0
D1
D2
D3
D4
D5
32-bit command when n=3
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
EH series