Delta Electronics DTV User Manual

Http://www.delta.com.tw/industrialautomation
5011664500-DVE0
2007-05-25
When the power is on, DO NOT touch the AC terminals in case an
DTV
12345
3
4
Regulation
Initial Setting
Pre ss for less than 3 secs
Upper limit for the temperature
Lower limit for the temperature
select the pattern No. to be
PV
Heating hysteresis
Cooling hysteresis
PV
OFF
AL-H
OFF
AL-H
OFF
AL-H
AL-L
Series Valve Temperature Controller
Instruction Sheet
Thanks you very much for choosing Delta DTV series valve temperature controller. Please read this instruction sheet before using your DTV to ensure proper operation. Keep this instruction handy for quick reference.
Warning
DANGER! CAUTION! ELECTRIC SHOCK!
electric shock may occur. Make sure the power is disconnected when you check the input power.
DTV is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments when used in a dangerous environment, please make sure it is installed in an automatic safety protection device.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be sure to tighten them properly and make sure the wire is connected to the correct terminal.
2. Prevent dust or metallic debris from falling into the device and cause malfunction. DO NOT modify or uninstall DTV series without being permitted. DO NOT use empty terminals.
3. Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using DTV in premises which contain:
(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration
4. The power has to be switched off when wiring or changing temperature sensor.
5. Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple wire.
6. Use wires with resistance when extending or connecting the platinum resistance sensor.
7. Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load wire in order to prevent interference and induced noise.
8. DTV is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an electric shock.
9. Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious damage may occur.
10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur.
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge. DO NOT touch the internal wiring within this period.
12. DO use dry cloth and DONOT use acid or alkaline liquid to clean the device.
Display, LED & Pushbuttons
PV: Present value SV: Set value %: Output percentage AT: Auto-tuning indicator A/M: Manual control indicator OUT1/OUT2: Output indicator ALM1/ALM2: Alarm output indicator
Manual/auto mode switch key
Selection/setup key
Switching page key
Left-shifting the digit
Adjusting numbers
Ordering information
Series name
1 2
Panel size (W × H)
5
DTV: Delta V series valve temperature controller
4896: 1/8 DIN W48 × H96 mm 9696: 1/4 DIN W96 × H96 mm
R: Valve, relay output SPST (250VAC, 5A)
Specifications
Power input AC100 ~ 240V, 50/60Hz Input power range 85% ~ 110%, rated voltage Power consumption Less than 5VA
Display
Input temperature sensor
Control method PID, PID programmable control, manual, On/Off Control output type Relay output: SPST, Max. load 250V, 5A resistive load Display scale 1 digit after the decimal point, or no decimal point Sampling cycle Analog input: 0.15 sec; thermocouple/platinum resistance: 0.4 sec Vibration resistance 10 ~ 55Hz 10m/s Shock resistance Max. 300m/s2 3 axes 6 directions, 3 times each Ambient temperature 0°C ~ +50°C Storage temperature -20°C ~ +65°C Operation altitude Less than 2,000m Ambient humidity 35% to 80% RH (non-condensing)
2-line, 7-segment LED, 4bits and 2 bits of valve openness display PV in red, SV and valve openness in green.
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Platinum resistance: Pt100, JPt100
Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mA
2
3 axes 10 min.
Setting up Parameters
Switching Modes: DTV is in the operation mode when the power is switched on, displaying PV and SV. Press more than 3 seconds to enter the initial setting mode. Press the regulation mode. Press
once in the regulation or initial setting mode to return to the operation mode.
Selecting parameters: In the operation, regulation or initial setting mode, press
Setting up number parameters: Find the parameters to be set up or modified. Use
Press
to move to the desired digit to be modified and the digit will flash. Press to complete and save the
setting.
Setting up non-number parameters: Find the parameter to be set up or modified and use setting. The parameter will flash at this time. Press
Mode
Press
Operation
for less than 3 seconds in the operation mode to enter
to select parameters for setup.
to modify the settings.
to modify the
to complete and save the setting.
Pre ss for more than 3 secs
Mode
Press
Mode
Regulation Mode Operation Mode Initial Setting Mode
Auto-tuning
(Set up when in PID control and RUN) Press V
Select the PID group (0 ~ 4) (4 groups of PID are available in PID control. n = 4: PID is auto-selected. See the next table.)
Press
V
PD control offset
Press
V
Heating hysteresis setting
(Set up when in On/Off control)
Press
V
Cooling hysteresis setting
(Set up when in On/Off control)
Press
V
/ Heating/cooling control cycle
Press
V
Switch for valve feedback
setting
Press
V
Auto adjusting feedback value (Displayed when in valve feedback mode and STOP)
Press
V
Time from valve fully closed to fully open
Press
V
Valve DeadBand Setting
Press
feedback output
V
Upper limit adjusting with
(Displayed when in valve feedback mode)
Press
V
Lower limit adjusting with feedback output (Displayed when in valve feedback mode)
Press
V
Adjusting PV offset
Press
V
Upper limit for control output
Press
V
Lower limit for control output
Press Z Back to top
Select the PID group: The user can select one of the 4 groups. When n = 4, the program will automatically select the PID group that is the closest to the SV.
Select the PID group (n = 0~4)
Press Z PID group 0 ~ 3
for
Editing patterns and steps: In parameter , select for editing. Take pattern 0 for example:
Select the pattern No. to be
edited
Select No.
Z
Press V Select OFF Leave pattern and step editing
V
Use to set up SV
Press
V
Control loop RUN/STOP
Press
V
Start setting up patterns (Set up when in PID programmable control mode)
Press
V
Set up the position of decimal point
thermocouple B, R, S type)
(Not for
Press
V
Upper limit for alarm 1 (Adjustable when ALA1 is enabled)
Press
V
Lower limit for alarm 1 (Adjustable when ALA1 is enabled)
Press
V
Upper limit for alarm 2
(Adjustable when ALA2 is enabled)
Press
V
Lower limit for alarm 2 (Adjustable when ALA2 is enabled)
Press
V
Key-locked mode
Press
V
Displaying and adjusting output percentage (Displayed when in PID mode and manual RUN)
Press
V
Output percentage of valve feedback (Displayed when there is valve feedback)
Press
V
D/A value of valve feedback (Displayed when there is valve feedback)
Press Z Back to top
Set up the temperature SV for
PID group 0
Press
V
Set up the proportion band for
PID group 0
Press
V
Set up the Ti value for PID
group 0
Press
V
Set up the Td value for PID
group 0
Press
V
Set up the integration offset
for PID group 0, AT auto-setting
Z PD control offset
Pres
Edit the temperature in step 0
Press
V
Edit the time for step 0
(unit: hour/minute)
Set up input type
Press
V
Set up temperature unit (Not displayed when in analog input mode)
Press
V
range
Press
V
range
Press
V
Select control mode (Enter step editing when PID programmable control is selected. See the next table)
Press
V
Select heating or cooling
Press
V
Set up alarm mode 1
Press
V
Set up alarm mode 2
Press
V
Set up system alarm
Press
V
Enable/disable communication
write-in
Press
V
Select ASCII/RTU communication format
Press
V
Set up communication address
Press
V
Set up baud rate
Press
V
Set up data length
Press
V
Set up stop bit
Press Z Back to top
Set up the temperature SV for PID group 3
Press
V
Set up the proportion band for PID group 3
Press
V
Set up the Ti value for PID group 3
Press
V
Set up the Td value for PID group 3
Press
V
Set up the integration offset
for PID group 3, AT auto-setting
Press
Z PD control offset
Select the actual number of
steps in the program
Press
V
Set up the number of
additional cycles (0 ~ 99)
Continue the setup in
Press
Set up from step 0 ~ step 7 in order
Press V
V Press V
OFF = end of program
Press
Edit the temperature in step 7
Return to “ edited”
Edit the time for step 7
Set up the link pattern.
V
(unit: hour/minute)
Press
V
Following the actual number of steps
Output Control
DTV offers heating and cooling outputs.
In parameter
output and
, you can select either to operate heating control or cooling control. Select for heating
for cooling output.
Output
ON
Heating
OFF
Figure 1: Output operation when in On/Off control
Set point
Cooling
Heating
Set point
Figure 2: PID control
Cooling
Key-locked Function
: Lock all the keys on the panel.
: Only SV can be modified. : Only SV and auto/manual mode can be modified (The control mode has to be PID control).
Press and at the same time to unlock the keys.
Types of Temperature Sensors & Temperature Range
Input Sensor Type Register Value Display Range
0 ~ 50mV analog input 17
4 ~ 20mA analog input 16
0 ~ 20mA analog input 15
0V ~ 10V analog input 14
0V ~ 5V analog input 13
Platinum resistance (Pt100) 12
Platinum resistance (JPt100) 11
Thermocouple TXK type 10
Thermocouple U type 9
Thermocouple L type 8
Thermocouple B type 7
Thermocouple S type 6
Thermocouple R type 5
Thermocouple N type 4
Thermocouple E type 3
Thermocouple T type 2
Thermocouple J type 1
Thermocouple K type 0
Note 1: The current input is built-in with a 249 precision resistor. See “How to Set up Current Input” section. Note 2: The default setting is Pt100 input.
Note 3: To display the decimal point, you have to set up the parameter
modes except for thermocouple B, R, and S type.
Note 4: The range for analog input is -999 ~ 9,999. Take 0 ~ 20mA for example, -999 refers to 0mA input and 9,999 refers to 20mA input. If we change
the range into 0 ~ 2,000, 0 will thus refer to 0mA input and 2,000 refers to 20mA input (1 display scale = 0.01mA).
(in the operation mode). The decimal point display is available for all
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-200 ~ 600°C
-20 ~ 400°C
-200 ~ 800°C
-200 ~ 500°C
-200 ~ 850°C
100 ~ 1,800°C
0 ~ 1,700°C
0 ~ 1,700°C
-200 ~ 1,300°C
0 ~ 600°C
-200 ~ 400°C
-100 ~ 1,200°C
-200 ~ 1,300°C
Alarm Output
DTV offers 2 groups of alarm outputs and 17 modes for each group under the initial setting mode. When the PV exceeds or falls below SV, the alarm output will be enabled. See the table below for the 17 alarm output modes.
Mode Alarm Type Alarm Output Operation
No alarm
0
Alarm output is enabled when the temperature reaches upper and lower limits.
1
Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV - AL-L.
Alarm output will be enabled when the temperature reaches the upper limit.
2
Alarm will be enabled when the PV exceeds SV + AL-H.
Alarm output is enabled when the temperature reaches the lower limit.
3
Alarm will be enabled when the PV falls below SV – AL-L.
4 Alarm output will be enabled when the PV is between SV + AL-H and SV – AL-L.
Alarm output is enabled when the temperature reaches the absolute value of the upper
5
and lower limits. Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.
Alarm output is enabled when the temperature reaches the absolute value of the upper
limit.
6
Alarm will be enabled when the PV exceeds AL-H.
Alarm output is enabled when the temperature reaches the absolute value of the lower
7
limit. Alarm will be enabled when the PV falls below AL-L.
Off
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
AL-L SV AL-H
SV
AL-L
SV
AL-L SV
AL-L
AL-H
Mode Alarm Type Alarm Output Operation
AL-H
OFF
ill be enabled when the PV reaches SV and falls below
ON
OFF
OFF
Read start address
JUMPER
Standby upper/lower limit alarm: Alarm will be enabled when the PV reaches SV and
8
exceeds SV + AL-H or falls below SV – AL-L.
Upper limit standby alarm: Alarm will be enabled when the PV reaches SV and exceeds
9
SV + AL-H.
Lower limit standby alarm: Alarm w
10
SV – AL-L.
Upper limit hysteresis alarm: Alarm will be enabled when the PV exceeds SV + AL-H.
11
Alarm will be disabled when the PV falls below SV + AL-L.
Lower limit hysteresis alarm: Alarm will be enabled when the PV falls below SV – AL-H.
12
Alarm will be disabled when the PV exceeds SV – AL-L.
14 Programmable STOP: Alarm will be enabled when the program is in STOP status.
Programmable RAMP UP: Alarm will be enabled when the program is in RAMP UP
15
status.
Programmable RAMP DOWN: Alarm will be enabled when the program is in RAMP
16
DOWN status.
17 Programmable SOAK: Alarm will be enabled when the program is in SOAK status.
18 Programmable RUN: Alarm will be enabled when the program is in RUN status.
Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L. There is no mode 13 (reserved for CT function).
OFF
OFF
ON
AL-L
ON
ON
AL-L SV
ON
AL-H
PID Programmable Control
Functions and Parameter Setting:
The PID programmable control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and parameters: link pattern, cycle and the number of steps.
Start Pattern
: This parameter can be set in the operation mode. The user can set up which pattern is the start
pattern for the programmable control. This function is only available when the program is in STOP status.
Step: Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV) has to rise to temperature X after the period of execution time T. If the result of the set point X is the same as that of the previous setting, the process is called Soak; otherwise, it is called Ramp. Therefore, the programmable control is also known as Ramp/Soak control. The default setting of the first step program is Soak control. The temperature will first rise to the set point X and remain at X. The total execution time is T.
Link Pattern: For example, if the parameter
execution of pattern 0. If the link pattern is set as
is set as 2, it refers to the execution of pattern 2 will follow the
, it refers to the program will end after the execution of the
pattern is completed and the temperature will remain at the SV for the last step.
Cycle: The additional number of cycles for a pattern. For example, if the parameter
is set as 2, it refers to
pattern 4 has to execute twice additionally, totaling the executions to 3 times including the original one.
The Number of Steps: The number of steps in each pattern (range: 0 ~ 7). For example, if the parameter set as 2, it refers to pattern 7 will execute step 0 ~ step 2 and other steps will not be executed.
The Execution:
1. When the parameter
2. When the parameter
is set as , the program will start its execution from step 0 of the start pattern.
is set as , the program will stop and the control output will be disabled.
3. When the parameter is set as , the program will stop and the temperature will stop at the SV before
the program stops. When you select
4. When the parameter
the program stops. When you select
is set as , the program will stop and the temperature will stop at the SV before
again, the program will execute again from step 0 of the start pattern.
again, the program will resume the step before the program stops
and execute by the remaining time.
Display:
In PID programmable control, some SVs are re-set as P-XX. P refers to the current pattern and XX refers to the current step. Press
Select
Select
to modify the display.
and press . SV will display the target temperature for the current step.
and press . SV will display the remaining time of the current step.
PID Control
In PID control, you can select any one of the 4 groups of PID parameter (P, I, D, IOF). After auto-tuning, the PID value and the temperature SV will be stored into the selected PID parameter.
~ : PIDn, n = 0 ~ 4. 0 ~ 3 are the corresponding selected PID parameter. refers to
auto-selected PID and the program will automatically select a most useful PID parameter based on the current SV. SV
displays will be
~ corresponding to n = 0 ~ 3.
~ : The SV for the selected PID parameter, can be set by the user or auto-generated by auto-tuning.
Valve Control
Heaters and coolers can be used to control the temperature and the openness of the valve in order to control the flow of the medium. Current and voltage can control the openness of the valve; however, the most direct and economic way to control the openness of the valve is the relay. To control the valve by voltage and current, you can use the DTB series analog output controller. If you tend to use relay for the control output, you have to choose the valve function in DTV series. The two control outputs are relay output for the forward/reverse running of the motor to drive the opening and closing of the valve. Control output1 controls the opening of the valve and control output 2 controls the closing of the valve in order to adjust the position of the valve. In order to detect the position of the valve, DTV is able to receive “feedback signal” and “no feedback signal”. When there is no feedback signal and the valve is fully open, control output 1 will output continuously. If at the moment the valve is fully closed, control output 2 will output continuously. If the valve you use is with feedback output, you can connect the output of the valve to the feedback part of DTV and set
to On to precisely control the openness of the valve. If there is no feedback signal or the feedback signal is
incorrect, and the pre-set openness of the valve is not reached after twice as long as the time set in the parameter
, the program will automatically switch back to the no feedback state. To ensure the correctness of the valve
control, please make sure that you have set up the parameters below:
: Time required from the valve fully closed to fully open. This parameter has to be correct when the valve is without feedback signal; otherwise, the accuracy for the temperature control will be affected. The PID control will correspond to the openness of the valve according to the setting of this parameter.
: DeadBand value of the valve. The parameter is to prevent frequent movement of the valve. For example, assume the DeadBand is 4%, PID control will correspond to the openness of the valve within 4% and the valve will not move within the range unless the value is accumulated and exceeds 4%. If the Deadband value is too small and the valve is set to have feedback signals, moving back and forth of the valve will shorten the life of the valve motor.
SV
SV AL-H
AL-L
AL-L
AL-H
is
: With or without feedback signals.
When
a) : Automatically adjusting the upper/lower limit of the valve feedback. This parameter will only be displayed
is set as “On”, it refers to “with feedback signals” and the following parameters will be displayed.
when
is set as . When this parameter is set as On, the relay will enable the forward and reverse running of the motor in order to calculate the time needed from the valve fully closed to fully open and the feedback signal of fully closed and open. The feedback signal is the hardware D/A value of the valve control, which is for the calculation of the valve controller.
b) : Upper limit of the valve signal. Set as “On”, can be set automatically or manually.
c)
: Lower limit of the valve signal. Set as ”On”, can be set automatically or manually.
Auto/Manual Mode Switch
A/M indicator On refers to manual mode; A/M indicator Off refers to auto mode. Besides On/Off, PID, programmable and manual controls, the valve control is also able to forcibly switch to manual control (fixing the openness of the
valve, unit: % from valve fully closed to fully open) when in PID control mode. You simply need to press control mode to switch to manual mode and A/M indicator will be On. Press
again to return to PID control and A/M
in PID
indicator will be Off.
Upper/Lower Limits of Valve Openness
Assume we would like the maximum openness of the valve to be 80% and the minimum to be 20%, set the parameter
as 80 and as 20, and the valve openness of PID control, programmable control and manual control
will fall within this range.
RS-485 Communication
1. Supports transmission speed 2,400bps, 4,800bps, 9,600bps, 19,200bps and 38,400bps; does not support communication format 7, N, 1/8, E, 2/8, O, 2. Communication protocol: Modbus (ASCII or RTU). Function: 03H (able to read max. 8 words in the register), 06H (able to write 1 word into the register), 01H (able to read max. 16 bits of data), 05H (able to write 1 bit into the register).
2. Address and content of the data register.
Address Content Explanation
Unit: 0.1 degree, updated every 0.4 second. The read values below indicate the occurrence of errors: 8002H: temperature not acquired yet
1000H Present temperature value (PV)
1001H Set point (SV) Unit: 0.1 degree 1002H Upper limit of temperature range The content shall not be bigger than the range. 1003H Lower limit of temperature range The content shall not be smaller than the range. 1004H Input sensor type See “Types of Temperature Sensors and Temperature Range" table. 1005H Control method 0: PID; 1: On/Off; 2: manual control; 3: PID programmable control 1006H Selecting heating/cooling control 0: heating; 1: cooling
1009H Proportion band value 0.1 ~ 999.9 100AH Ti value 0 ~ 9,999 100BH Td value 0 ~ 9,999 100CH Default integration value 0 ~ 100%, unit: 0.1%
100DH
1010H SV of output hysteresis 0 ~ 9,999
1012H Read/write of output percentage Unit: 0.1%, only applicable in manual control mode
1014H
1015H
1016H Temperature offset regulation value -99.9 ~ +99.9, unit: 0.1
1017H Analog decimal point setting 0 ~ 3
1018H Time from valve fully closed to fully open 0.1 ~ 999.9
1019H DeadBand setting of valve 0 ~ 100%, unit: 0.1% 101AH Upper limit for valve feedback signal 0 ~ 1,024 101BH Lower limit for valve feedback signal 0 ~ 1,024 101CH PID group setting 0 ~ 4 101DH SV for the corresponding PID setting In valid range. Unit: 0.1 101EH Upper limit for control output Lower limit for control output ~ 100%, unit: 0.1% 101FH Lower limit for control output 0 ~ Upper limit for control output, unit: 0.1%
1020H Output mode for alarm 1 See “Alarm Output” section.
1021H Output mode for alarm 2 See “Alarm Output” section.
1023H System alarm setting 0: None (default); 1 ~ 2: Set alarm 1 ~ alarm 2
1024H Upper limit for alarm 1 See “Alarm Output” section.
1025H Lower limit for alarm 1 See “Alarm Output” section.
1026H Upper limit for alarm 2 See “Alarm Output” section.
1027H Lower limit for alarm 2 See “Alarm Output” section. 102AH Read/write LED status b0: °F; b1: °C; b2: ALM2; b3: x; b4: OUT1; b5: OUT2; b6: AT; b7: ALM1 102BH Read/write key status b0: Set; b1: Select; b2: Up; b3: Down; 0 refers to push.
102CH Panel lock status
102FH Software version V1.00 refers to 0x100
1030H No. of start pattern 0 ~ 7
1040H ~
1047H
1050H ~
1057H
1060H ~
1067H
2000H ~
203FH
2080H ~
20BFH
Offset compensation value for proportional control (when Ti = 0)
Upper limit regulation for analog linear output Lower limit regulation for analog linear output
Number of steps in a pattern 0 ~ 7 = N refers to the pattern will be executed from step 0 to step N.
Additional number of cycles for a pattern 0 ~ 99 refers to the pattern will be executed for 1 ~ 100 times.
No. of the link pattern for the current pattern SV temperature for pattern0 ~ 7 SV for pattern 0 is set in 2000H ~ 2007H Execution time for pattern 0 ~ 7 Time for pattern 0 is set in 2080H ~ 2087H
3. Address and content of the bit register (read bits are stored starting from LAB and written data is FF00H, set the bit as 1. 0000H sets the bit data as 0.)
0810H Selecting communication write-in Communication write-in forbidden: 0 (default), allowed: 1
0811H Selecting temperature unit 0: °F; 1: °C/linear input (default) 0812H Position of the decimal point 0 or 1. Available for all modes except for thermocouple type B, S, R. 0813H Read/write auto-tuning (AT) 0: AT stops (default); 1: AT starts 0814H RUN/STOP of the control 0: stop; 1: run (default) 0815H Programmable control RUN/STOP 0: run (default); 1: stop 0816H Programmable control RUN/PAUSE 0: run (default); 1: pause 0817H Read/write valve feedback 0: without feedback (default); 1: with feedback 0818H Read/write AT of valve feedback 0: AT stops (default); 1: AT starts
8003H: temperature sensor not connected 8004H: wrong sensor type 8006H: unable to acquire temperature, ADC input error 8007H: unable to read/write the memory
0 ~ 100%, unit: 0.1%
1 scale = 2.8μA = 1.3mV
1 scale = 2.8μA = 1.3mV
0: normal; 1: lock all; 11: SV adjustable; 111: SV adjustable, A/M
available
0 ~ 8. 8 refers to end of the program; 0 ~ 7 refers to the next pattern No. following the current pattern.
-999 ~ 9,999
0 ~ 900 (Every scale = 1 minute)
4. Communication transmission format: command 01: read bit, 05: write bit, 03: read word, 06: write word.
ASCII Mode
Read Command Read Response Message Write Command Write Response Message
Star t wo rd Machine address 1 ‘0’ ‘0’ Machine address 1 ‘0’ ‘0’ Machine address 1 ‘0’ ‘0’ Machine address 1 ‘0’ ‘0’ Machine address 0 ‘1’ ‘1’ Machine address 0 ‘1’ ‘1’ Machine address 0 ‘1’ ‘1’ Machine address 0 ‘1’ ‘1’
Command 1 ‘0’ ‘0’ Command 1 ‘0’ ‘0’ Command 1 ‘0’ ‘0’ Command 1 ‘0’ ‘0’ Command 0 ‘3’ ‘1’ Command 0 ‘3’ ‘1’ Command 0 ‘6’ ‘5’ Command 0 ‘6’ ‘5’
of data/bit
Read length of
data/bit (word/bit)
LRC1 check ‘E’ ‘D’ LRC0 check ‘A’ ‘C’
End word 1 CR CR LRC1 check ‘0’ ‘E’ End word 1 CR CR End word 1 CR CR End word 0 LF LF LRC0 check ‘3’ ‘3’ End word 0 LF LF End word 0 LF LF
End word 1 CR CR End word 0 LF LF
‘1’ ‘0’ ‘0’ ‘8’ ‘0’ ‘1’ ‘0’ ‘0’ ‘0’ ‘0’ ‘0’ ‘0’ ‘0’ ‘2’ ‘9’
Length of response
‘0’
Data content in
1000H/081xH
Data content in
Star t wo rd
data (byte)
1001H
Star t wo rd
‘0’ ‘0’ ‘4’
‘2’
Write data address
‘0’ ‘1’ ‘1’ ‘7’ ‘F’ ‘0’ ‘4’
‘1’ ‘0’ ‘E’ ‘0’ ‘0’ ‘0’ LRC1 ‘F’ ‘E’ ‘0’
Write data content
LRC 0 ‘D’ ‘3’
‘1’ ‘0’ ‘0’ ‘8’ ‘0’ ‘1’ ‘1’ ‘0’ ‘0’ ‘F’ ‘3’ ‘F’
‘8’ ‘0’
Write data address
Write data content
Star t wo rd
LRC1 ‘F’ ‘E’
LRC 0 ‘D’ ‘3’
‘1’ ‘0’ ‘0’ ‘8’ ‘0’ ‘1’ ‘1’ ‘0’ ‘0’ ‘F’ ‘3’ ‘F’ ‘E’ ‘0’ ‘8’ ‘0’
LRC check: Sum up from “machine address” to “data content”, e.g. 01H + 03H + 10H + 00H + 00H + 02H = 16H. Obtain 2’s complement EA.
RTU Mode
Read Command Read Response Message Write Command Write Response Message
Machine address 01H 01H Machine address 01H 01H Machine address 01H 01H Machine address 01H 01H
Command 03H 01H Command 03H 01H Command 06H 05H Command 06H 05H Read start
address of data
Read length of data (bit/word)
CRC low byte C0H BBH
CRC high byte CBH A9H CRC low byte BBH 77H CRC high byte 15H 88H
10H 08H 00H 10H 00H 00H 02H 09H
Length of response
data (byte)
Data content 1
Data content 2
04H
01H 17H F4H 03H CRC low byte DDH 8FH CRC low byte DDH 8FH 20H
address
Write data
content
01H
CRC high byte E2H 9FH CRC high byte E2H 9FH
Write data
02H
10H 08H
10H
01H 03H FFH 20H
00H
Write data
address
Write data
content
10H 08H 01H 03H FFH 20H
10H
00H
CRC (Cyclical Redundancy Check) is obtained by the following steps.
1. Load in a 16-bit register FFFFH as the CRC register.
2. Do an exclusive OR operation of the first byte of the data and low byte of CRC register, and place the operation
result back to the CRC register.
3. Right shift the bits in the CRC register and fill the high bits with “0”. Check the removed lowest bit.
4. If the removed lowest bit is “0”, repeat step 3. Otherwise, do an exclusive OR operation of the CRC register and the
value A001H and place the operation result back to the CRC register.
5. Repeat step 3 and 4 until the 8 bits (1 byte) are all right shifted.
6. Repeat step 2 and 5 and calcualte all the bits to obtain CRC check. Please be aware of the high/low byte transmission order in the CRC register.
How to Mount How to Install Mounting Bracket
1. Insert DTV into the panel cutout
2. Insert the mounting bracket into the mounting groove at the top and bottom of DTV.
3. Push the mounting bracket forward until the bracket stops at the panel wall.
4. Tighten the screw.
Dimensions
DTV4896 DTV9696
Panel Cutout Terminals
DTV4896/DTV9696 DTV4896R/DTV9696R
48*96
60.0 min.
120.0 min.
0
+0.6
91.5
+0.6
44.5
0
96*96
110.0 min.
120.0 min.
0
+0.6
91
+0.6 0
91
How to Set up Current Input
For normal input (default) Current input (4 ~ 20mA, 0 ~ 20mA)
DEFAULT SETTI NG
JP1
JUMP ER
PIN HEADER
JP1
PIN HEADER
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation
Loading...