The user manual details the process of using Delta DT series temperature controllers step by step
for beginners to easily set up all kinds of parameters in a short time.
Clear the user’s settings.
Function address = 4724; Write data = 1234
(Please DO NOT modify this value; otherwise
system confusion may occur.)
Switch off DTA and re-power it.
The model adopted in this example is: DTA4896R1 with firmware V3.50.
After the above procedures are completed, DTA
will display the information on the left hand side,
representing that DTA has return to default
settings successfully.
Return to default value. The default sensor is
PT100, which will be displayed when DTA is not
connected to a sensor or thermocouple.
Clear the user’s settings.
Function address = 474E; Write data = 1234
(Please DO NOT modify this value; otherwise
system confusion may occur.)
Switch off DTB and re-power it.
The model adopted in this example is: DTB4896RR with firmware V1.50.
After the above procedures are completed, DTB
will display the information on the left hand side,
representing that DTB has return to default
settings successfully.
Return to default value. The default sensor is
PT100, which will be displayed when DTC is not
connected to a sensor or thermocouple.
1.4 How to Return to Default Settings in DTC
1. Make sure RS-485 hardware communication cable in DTC has been connected to the computer.
2. Make sure the communication parameters in DTC are consistent with those in the computer.
(Please DO NOT modify this value; otherwise
system confusion may occur.)
Clear the user’s settings.
Function address = 474E; Write data = 1234
(Please DO NOT modify this value; otherwise
system confusion may occur.)
Switch off DTC and re-power it. Return to default settings
The model adopted in this example is: DTC1000R with firmware V1.40.
CHAPTER 2: CONTROL MODES IN DTA
2.1 ON/OFF
There are three control modes in DTA: ON/OFF, MANUAL and PID. First, press for 3 seconds
to enter the “initial setting” mode. See below for how to switch between each mode:
Press in the main screen of DTA to enter the “regulation mode”.
Display Explanations
PV SV Status of the temperature controller
or
Set up hysteresis. Default = heating hysteresis. Can be set as
cooling hysteresis as well. Both default values are “0”.
2.2 MANUAL
Press for 3 seconds in the main screen to enter the “initial setting mode”. Press several
times until the parameter is displayed.
Display Explanations
PV SV Status of the temperature controller
Back
to top
Parameters relevant to MANUAL control
Press in the main screen of DTA to enter the “regulation mode”.
Display Explanations
The control modes include: PID, ON/OFF, MANUAL.
Default = PID. Select “MANUAL” here.
Press to return to the main screen.
PV SV Status of the temperature controller
or
Set up heating or cooling control cycle. Default = heating, 20
seconds per cycle.
Press in the main screen of DTA to enter the “operation mode”.
Display Explanations
PV SV Status of the temperature controller
Run/stop
Key-locked function
Manually adjust the output percentage. Assume the percentage
value = 50 and the cycle = 20 seconds plus heating control, the
system will conduct heating output for 10 seconds and stop for the
other 10 seconds.
2.3 PID
Press for 3 seconds in the main screen to enter the “initial setting mode”. Press several
The control modes include: ON/OFF, MANUAL, PID and PID
PROG. Default = PID. Select “MANUAL” here.
Press to return to the main screen.
Back to
top
Parameters relevant to MANUAL control
Press in the main screen of DTB to enter the “regulation mode”.
Display Explanations
PV SV Status of the temperature controller
or
Set up heating or cooling control cycle. Default = heating, 20
seconds per cycle.
Press in the main screen of DTB to enter the “operation mode”.
Display Explanations
PV SV Status of the temperature controller
Run/stop
Set up the position of decimal point.
1 = value with decimal point; 2 = value without decimal point
Key-locked function
Manually adjust the output percentage. Assume the percentage
value = 50 and the cycle = 20 seconds plus heating control, the
system will conduct heating output for 10 seconds and stop for
the other 10 seconds.
3.3 PID
Press for 3 seconds in the main screen to enter the “initial setting mode”. Press several
times until the parameter is displayed.
Display Explanations
PV SV Status of the temperature controller
The control modes include: ON/OFF, MANUAL, PID and PID PROG.
Default = PID.
Press to return to the main screen.
top
Back to
Parameters relevant to PID control
Press in the main screen of DTB to enter the “regulation mode”.
Press in the main screen of DTB to enter the “regulation mode”.
Display Explanations
PV SV Status of the temperature controller
The 0th PID parameter. There are 4 groups of PID parameters
built in DTB. When the parameter is set ass PID4, the system will
automatically adopt the PID value of the current temperature
closest to PID0 ~ 3.
The 0th SV
The 0th default value for proportional control
The 0th default value for integral control
The 0th default value for derivative control
The 0th default integral value
Heating/cooling control cycle
Temperature inaccuracy adjustment value
Press in the main screen of DTB to enter the “operation mode”.
Display Explanations
PV SV Status of the temperature controller
//
Stop/run/program stop/program hold。
Program stop: Run the system again, and DTB will start from
/
the initial step.
Program hold: Run the system again, and DTB will follow and
Set up heating or cooling control cycle. Default = heating, 20 seconds per cycle.
Manually adjust the output percentage. Assume the percentage value = 50 and the cycle = 20
seconds plus heating control, the system will conduct heating output for 10 seconds and stop for
the other 10 seconds.
You can conduct auto-tuning on the default PID parameters according to the environment where
your equipment is in or its temperature control capability, allowing the temperature controller to
generate relevant PID parameters by itself in order to achieve an accurate temperature control.