Features:
Ease of wire connection to
terminals
Comes with detachable
connectors
Overload, Overvoltage &
Thermal protection
Efficiency > 89% Power boost 150% for 3
seconds
Expected life time: 10
years
Redundancy: Yes (with
external ORing diode)
RoHS & IP20 compliant Meet Energy Star Level 5 3 years warranty
Switch Mode Power Supply DRP024V060W1BA
60W 1Phase CliQ ll DIN Rail
DRP024V060W1BA
Summary
The new CliQ II DRP024V060W1BA is the
latest offering from one of the world’s largest
power supply manufacturers - Delta. The product offers a nominal output voltage of 24 V, a wide temperature range from -20°C to +80°C and a minimum holdup time of 20 ms. The state-of-the-art design is made to withstand harsh industrial environments. The rugged, ultra-compact metal case is shock and vibration resistant according to IEC60068-2.
1/13 Rev: 00, 1/10/2011
The 60 watts DIN Rail power supply provides overvoltage, overload and thermal protection. Due to the wide input voltage range from 85 to 264 VAC, the Delta’s CliQ II power supply is worldwide usable. It also comes with multiple output terminals for fast wiring and easy installation.
60W1Ph
Input Data (1)
Nominal input voltage and frequency
100-240VAC / 50-60Hz
Voltage range
85-264VAC (120 – 375 VDC)
Frequency Range
47-63Hz
Nominal current
1.5A max @115VAC, 1.0A max @230VAC
Inrush current limitation. I2t (+25°C) typ.
< 35A @ 230VAC
Mains buffering at nominal load (typ.)
> 20ms @ 115VAC, > 125ms @ 230VAC
Turn-on time
< 3.0sec.
Internal fuse
T 3.15 AH / 250V
Recommended backup fuse: Power circuit-breaker characteristic
6A, 10A or 16A : B
Leakage current
< 1mA
Energy Star Level
V
Output Data (2)
Nominal output voltage UN / tolerance
24VDC±2%
Setting range of the output voltage
24-28VDC
Nominal current
2.5A
De-rating above +50°C
> 50°C (2.5% / °C)
Startup with capacitive loads
Max 8,000µF at 25°C
Max. power dissipation idling / nominal load approx.
7.4W
Efficiency
> 89% typical.
Residual ripple / peak switching (20 MHz) (at nominal values)
< 50mV / < 150mVpp.
Can be connected in parallel for redundancy and increased capacity
YES with ORing Diode or Redundancy module
Surge voltage protection against internal surge voltages
YES
Certification/Standards
Electrical equipment of machines
IEC60204-1 (overvoltage category III)
Safety transformers for switched-mode power supply units
Electrical safety (of information technology equipment)
TUV BAUART to EN60950-1, UL/C-UL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL / C-UL Listed UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No.107.1-01 (file no. 181564)
Electronic equipment for use in electrical power Installations
EN50178 / IEC62103
Safety entry low voltage
PELV (EN60204), SELV (EN60950)
Safe isolation
DIN.VDE 0100-410
Protection against electric shock
DIN 57100-410
Protection against shock currents, basic requirements for protective separation in electrical equipment
VDE 0106-101 Limitation of mains harmonic currents
DIN57100-410
Switch Mode Power Supply DRP024V060W1BA
Technical Data
2/13 Rev: 00, 1/10/2011
General Data
Isolation voltage: Input / output type test/routine test Input / PE type test/routine test output / PE type test/routine test
4 KVAC / 3 KVAC
1.5 KVAC / 1.5 KVAC
1.5 KVAC / 500 VAC
Degree of protection
IP20
Class of protection
Class I with PE connection
MTBF
> 1,000,000hrs.
Type of housing
Aluminium (AI5052)
Dimensions (L / W / H )
121mmx32mmx125mm
Weight
0.37Kg
STATUS Indicator
LED (6) DC OUTPUT OK
YES (GREEN LED)
Climatic Data
Ambient temperature (Operating) Ambient temperature (Storage)
-20°C to 80°C (> 50°C de-rating)
-25°C to 85°C
Humidity at 25°C, non-condensing
< 95% RH
Vibration (Non-Operating)
10Hz to 500Hz @ 30 m/ S2 (3G peak); displacement of 0.35mm; 60min per axis for all X, Y, Z direction. in acc. with IEC 68000-2-6. Shock (in all directions)
30G (300m/S2) in all directions according to IEC60068-2-27
Pollution degree
2 according to EN50178
Climatic class
3K3 according to EN 60721
In conformance with EMC guideline 89/336/EEC and low voltage directive 73/23/EEC EMC (electromagnetic compatibility)
DINRAIL 1AC / 24V DC / 2.5A (EOE11010248)
Immunity to interference according to EN 61000-6-2 EN 61000-4-2 1) Housing Discharge of static electricity (ESD) Contact discharge: Air Discharge:
LEVEL 4 8 KV 15 KV
EN 61000-4-3 1) Housing Radiate Field Immunity Frequency/Field intensity:
LEVEL 3 80MHz - 1GHz / 10V/M with 1kHz tone / 80% modulation
EN 61000-4-4 1)
Fast transients (Burst):
2KV4)
EN 61000-4-5 1)
Surge voltage Immunity (Surge):
2KV
3)
/ 2KV
4)
(Level 3)  EN 61000-4-6 1) I/O: Conducted Immunity Frequency / Uo:
Level 3
0.15MHz - 80MHz / 10Vrms.
EN 61000-4-11 2) Voltage dips
Input: Main Buffering > 20ms.
Noise emission according to EN 61000-6-3
Emitted radio interface Radio interference voltage
EN55011 (EN55022) CLASS B5 EN55011 (EN55022) CLASS B5
EN55011 corresponds to CISPR11 / EN55022 corresponds to CISPR22 / EN 61000 corresponds to IEC 61000
1) Criterion A: Normal operating behavior within the defined limits.
2) Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
3) Symmetrical: Conductor to conductor.
4) Asymmetrical: Conductor to ground.
5) Class B: Area of application industry and residential.
Switch Mode Power Supply DRP024V060W1BA
3/13 Rev: 00, 1/10/2011
DR
DinRail
P
Power Supply
024V
24 Voltage
060W
60 Watt
120W
120 Watt
240W
240 Watt
480W
480 Watt
1
1 Phase
3
3 Phase
BA
Delta standard – metal case
Switch Mode Power Supply DRP024V060W1BA
Numbering for DIN Rail Power Supply
For example: DRP024V060W1BA
XX X XXXX XXXX X XX
XX………………….Product Type
XX X XXXX XXXX X XX X………………….Model
XX X XXXX XXXX X XX XXXX………………….Voltage
4/13 Rev: 00, 1/10/2011
XX X XXXX XXXX X XX XXXX……………Watt
XX X XXXX XXXX X XX X………………….Phase
XX X XXXX XXXX X XX
XX………………….Variation (Eg,
Customer, material,Etc.)