subsidiaries. Other trademarks may be trademarks of their respec tiv e o wne rs.
Contents
Chapter 1: About this guide........................................................................................................... 4
Related documents............................................................................................................................................................. 4
Information Symbols........................................................................................................................................................... 4
Chapter 2: Site preparations......................................................................................................... 6
Site selection........................................................................................................................................................................ 6
Fans and airflow................................................................................................................................................................... 7
Rack or cabinet installation............................................................................................................................................... 9
1U Tool-less mount installation....................................................................................................................................... 10
S4200-ON Series switch installation.............................................................................................................................14
After switch installation....................................................................................................................................................16
This guide provides site preparation recommendations, step-by-step procedures for rack mounting and desk mounting, inserting
modules, and connecting to a power source.
CAUTION: To avoid electrostatic discharge (ESD) damage, wear grounding wrist straps when handling this
equipment.
NOTE: Only trained and qualified personnel can install this equipment. Read this guide before you install and power up this
equipment. This equipment contains two power cords. Disconnect both power cords before servicing.
NOTE: This equipment contains optical transceivers, which comply with the limits of Class 1 laser radiation.
Figure 1. Class 1 laser product tag
NOTE: When no cable is connected, visible and invisible laser radiation may be emitted from the aperture of the optical
transceiver ports. Avoid exposure to laser radiation and do not stare into open apertures.
Topics:
•Related documents
•Information Symbols
Related documents
For more information about the S4200-ON Series (S4248FB-ON and S4248FBL-ON), see the following documents.
● OS10 Enterprise Edition Release Notes
● OS10 Enterprise Edition User Guide
● S4200-ON Series Installation Guide
● Dell Open Networking Hardware Diagnostic Guide
● S4200-ON Series Release Notes
NOTE: For the most recent documentation, visit the support site: www.dell.com/support.
Information Symbols
This book uses the following information symbols:
NOTE: The Note icon signals important operational information.
CAUTION: The Caution icon signals information about situations that could result in equipment damage or loss
of data.
NOTE: The Warning icon signals information about hardware handling that could result in injury.
4About this guide
NOTE: The ESD Warning icon requires that you take electrostatic precautions when handling the device.
About this guide5
Site preparations
The S4200-ON Series (S4248FB-ON and S4248FBL-ON) is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
● Network telecommunication facilities
● Data centers
● Other locations where the National Electric Code (NEC) applies
For more information about the S4200-ON Series specifications, see Specifications.
NOTE: Install the switch into a rack or cabinet before installing any optional components.
Topics:
•Site selection
•Cabinet placement
•Rack mounting
•Switch ground
•Fans and airflow
•Power
•Storing components
2
Site selection
Install your equipment in restricted access areas. A restricted access area is one where service personnel can only gain access
using a special tool, lock, key, or other means of security. The authority responsible for the location controls access to the
restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
● Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local
electrical codes.
● Environmental—switch location—continuous temperature range is from 0°C to 45°C (32°F to 113°F).
● Operating humidity is from 5 to 85 percent noncondensing, continuous.
● In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or direct
sunlight.
● Away from sources of severe electromagnetic noise.
● Positioned in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for proper ventilation and
access.
● Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75.
For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the S4200-ON Series (S4248FB-ON and S4248FBL-ON) switch only in indoor cabinets designed for use in a controlled
environment.
Do not install the switch in outside cabinets. For cabinet placement requirements, see Site selection.
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.
6Site preparations