Dell PowerSwitch S4248FB-ON, PowerSwitch S4248FBL-ON User Manual

Dell EMC PowerSwitch S4200-ON Series

Set-up Guide

March 2021

Rev. A01

Notes, cautions, and warnings

NOTE: A NOTE indicates important information that helps you make better use of your product.

CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid the problem.

WARNING: A WARNING indicates a potential for property damage, personal injury, or death.

Copyright © 2017 Dell Inc. or its subsidiaries. All rights reserved. Dell, EMC, and other trademarks are trademarks of Dell Inc. or its subsidiaries. Other trademarks may be trademarks of their respective owners.

Contents

Chapter 1: About this guide...........................................................................................................

4

Related documents.............................................................................................................................................................

4

Information Symbols...........................................................................................................................................................

4

Chapter 2: Site preparations.........................................................................................................

6

Site selection........................................................................................................................................................................

6

Cabinet placement..............................................................................................................................................................

6

Rack mounting......................................................................................................................................................................

7

Switch ground......................................................................................................................................................................

7

Fans and airflow...................................................................................................................................................................

7

Power......................................................................................................................................................................................

7

Storing components............................................................................................................................................................

7

Chapter 3: S4200-ON Series Installation.......................................................................................

8

Unpack...................................................................................................................................................................................

8

Rack or cabinet installation...............................................................................................................................................

9

ReadyRails installation........................................................................................................................................................

9

1U Tool-less mount installation.......................................................................................................................................

10

Two-post flush-mount installation..................................................................................................................................

11

Two-post center-mount installation..............................................................................................................................

12

Four-post threaded installation......................................................................................................................................

13

S4200-ON Series switch installation.............................................................................................................................

14

1U front-rack installation..................................................................................................................................................

14

Optics installation...............................................................................................................................................................

16

Switch power-up................................................................................................................................................................

16

After switch installation....................................................................................................................................................

16

Chapter 4: Specifications.............................................................................................................

17

Chassis physical design.....................................................................................................................................................

17

Chapter 5: Support......................................................................................................................

19

Contents 3

Dell PowerSwitch S4248FB-ON, PowerSwitch S4248FBL-ON User Manual

1

About this guide

This guide provides site preparation recommendations, step-by-step procedures for rack mounting and desk mounting, inserting modules, and connecting to a power source.

CAUTION: To avoid electrostatic discharge (ESD) damage, wear grounding wrist straps when handling this equipment.

NOTE: Only trained and qualified personnel can install this equipment. Read this guide before you install and power up this equipment. This equipment contains two power cords. Disconnect both power cords before servicing.

NOTE: This equipment contains optical transceivers, which comply with the limits of Class 1 laser radiation.

Figure 1. Class 1 laser product tag

NOTE: When no cable is connected, visible and invisible laser radiation may be emitted from the aperture of the optical transceiver ports. Avoid exposure to laser radiation and do not stare into open apertures.

Topics:

Related documents

Information Symbols

Related documents

For more information about the S4200-ON Series (S4248FB-ON and S4248FBL-ON), see the following documents.

OS10 Enterprise Edition Release Notes

OS10 Enterprise Edition User Guide

S4200-ON Series Installation Guide

Dell Open Networking Hardware Diagnostic Guide

S4200-ON Series Release Notes

NOTE: For the most recent documentation, visit the support site: www.dell.com/support.

Information Symbols

This book uses the following information symbols:

NOTE: The Note icon signals important operational information.

CAUTION: The Caution icon signals information about situations that could result in equipment damage or loss of data.

NOTE: The Warning icon signals information about hardware handling that could result in injury.

4 About this guide

NOTE: The ESD Warning icon requires that you take electrostatic precautions when handling the device.

About this guide

5

2

Site preparations

The S4200-ON Series (S4248FB-ON and S4248FBL-ON) is suitable for installation as part of a common bond network (CBN).

You can install the switch in:

Network telecommunication facilities

Data centers

Other locations where the National Electric Code (NEC) applies

For more information about the S4200-ON Series specifications, see Specifications.

NOTE: Install the switch into a rack or cabinet before installing any optional components.

Topics:

Site selection

Cabinet placement

Rack mounting

Switch ground

Fans and airflow

Power

Storing components

Site selection

Install your equipment in restricted access areas. A restricted access area is one where service personnel can only gain access using a special tool, lock, key, or other means of security. The authority responsible for the location controls access to the restricted area.

Ensure that the area where you install your switch meets the following safety requirements:

Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local electrical codes.

Environmental—switch location—continuous temperature range is from 0°C to 45°C (32°F to 113°F).

Operating humidity is from 5 to 85 percent noncondensing, continuous.

In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or direct sunlight.

Away from sources of severe electromagnetic noise.

Positioned in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for proper ventilation and access.

Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA 75.

For more information about switch storage and environmental temperatures, see Specifications.

Cabinet placement

Install the S4200-ON Series (S4248FB-ON and S4248FBL-ON) switch only in indoor cabinets designed for use in a controlled environment.

Do not install the switch in outside cabinets. For cabinet placement requirements, see Site selection.

The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA) standard. Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.

6 Site preparations

Loading...
+ 13 hidden pages