Chapter 1: About this guide........................................................................................................... 6
Related documents..............................................................................................................................................................7
Information symbols............................................................................................................................................................ 7
Chapter 2: N3200-ON Series switch.............................................................................................. 8
LED display.......................................................................................................................................................................... 14
LED behavior................................................................................................................................................................. 14
N3200-ON Series switch configurations..................................................................................................................... 18
Chapter 3: Site preparations........................................................................................................ 21
Site selection....................................................................................................................................................................... 21
Fans and airflow.................................................................................................................................................................22
DIN buckle rail installation......................................................................................................................................... 29
Standard bracket two-post installation........................................................................................................................ 31
Wall- or ceiling-mount switch installation....................................................................................................................33
One RU ReadyRails installation......................................................................................................................................36
1U Tool-less mount ReadyRails installation........................................................................................................... 36
After switch placement.................................................................................................................................................... 41
Chapter 5: External power adapter.............................................................................................. 43
Power adapter holder assembly.....................................................................................................................................43
Wall or ceiling installation................................................................................................................................................ 44
DIN rail installation............................................................................................................................................................ 46
Single-EPA and switch four-post installation............................................................................................................. 47
Single-EPA and switch two-post center-mount installation...................................................................................47
Single-EPA and switch two-post front-mount installation..................................................................................... 49
AC or DC power supply installation...............................................................................................................................57
AC or DC power supply replacement........................................................................................................................... 58
550W DC power connections........................................................................................................................................ 58
1300W DC power connections.......................................................................................................................................59
Connect the EPS shelf..................................................................................................................................................... 61
Fan module installation.....................................................................................................................................................67
Fan module replacement........................................................................................................................................... 68
RJ45 console port access............................................................................................................................................... 69
MicroUSB Type-B console port access....................................................................................................................... 70
USB storage mount........................................................................................................................................................... 71
Chapter 9: Installation using ONIE...............................................................................................72
Before you install an operating system........................................................................................................................ 72
Check your switch.............................................................................................................................................................73
Uninstall an existing OS................................................................................................................................................... 73
Install a NOS....................................................................................................................................................................... 74
Automatic NOS installation....................................................................................................................................... 74
Manual NOS installation............................................................................................................................................. 75
USA Federal Communications Commission statement...................................................................................... 82
European Union EMC directive conformance statement.................................................................................. 83
Japan VCCI compliance for class A equipment....................................................................................................83
Korean certification of compliance......................................................................................................................... 84
Safety standards and compliance agency certifications......................................................................................... 84
Product recycling and disposal...................................................................................................................................... 85
This guide provides site preparation recommendations, step-by-step procedures for rack mounting and desk mounting your
switch, inserting modules, and connecting to a power source.
CAUTION: To avoid electrostatic discharge (ESD) damage, wear grounding wrist straps when handling this
equipment.
NOTE: Only trained and qualified personnel can install this equipment. Read this guide before you install and power on this
equipment. This equipment contains two power cables. Disconnect both power cables before servicing.
NOTE: This equipment contains optical transceivers, which comply with the limits of Class 1 laser radiation.
1
Figure 1. Class 1 laser product tag
NOTE: When no cable is connected, visible and invisible laser radiation may emit from the aperture of the optical
transceiver ports. Avoid exposure to laser radiation. Do not stare into open apertures.
NOTE: Read this guide before unpacking the switch. For unpacking instructions, see Unpack.
Visual display workplaces
This device is not intended for use in the direct field of view at visual display workplaces. To avoid incommoding reflexions at
visual display workplaces this device must not be placed in the direct field of view.
Bemerkung: Dieses Gerät ist nicht für den Einsatz im direkten Sichtfeld am Bildschirmarbeitsplatz vorgesehen. Um störende
Reflexionen am Bildschirmarbeitsplatz zu vermeiden, darf dieses Gerät nicht im direkten Sichtfeld platziert werden.
Regulatory
● Marketing model N3208PX-ON is represented by the regulatory model E30W and the regulatory type E30W001.
● Marketing model N3224T-ON is represented by the regulatory model E31W and the regulatory type E31W002.
● Marketing model N3224F-ON is represented by the regulatory model E31W and the regulatory type E31W003.
● Marketing model N3224P-ON is represented by the regulatory model E32W and the regulatory type E32W002.
● Marketing model N3224PX-ON is represented by the regulatory model E32W and the regulatory type E32W001.
● Marketing model N3248TE-ON is represented by the regulatory model E31W and the regulatory type E31W005.
● Marketing model N3248P-ON is represented by the regulatory model E32W and the regulatory type E32W003.
● Marketing model N3248X-ON is represented by the regulatory model E31W and the regulatory type E31W004.
● Marketing model N3248PXE-ON is represented by the regulatory model E32W and the regulatory type E32W004.
Topics:
•Related documents
•Information symbols
6About this guide
Related documents
For more information about the N3200-ON Series, see the following documents:
● Dell EMC PowerSwitch N3200-ON Series Warnings Guide
● Dell EMC PowerSwitch N3200-ON Series Setup Placemat
● Dell EMC PowerSwitch N3200-ON Series Release Notes
● Open Networking Hardware Diagnostic Guide N2200-ON and N3200-ON Series Switches
● External Power Supply (EPS) Installation for the Dell EMC PowerSwitch N2200-ON and N3200-ON Series Switches
NOTE: For the most recent documentation, see Dell EMC support: www.dell.com/support.
Information symbols
This book uses the following information symbols:
NOTE: The Note icon signals important operational information.
CAUTION: The Caution icon signals information about situations that could result in equipment damage or loss
of data.
NOTE: The Warning icon signals information about hardware handling that could result in injury.
NOTE: The ESD Warning icon requires that you take electrostatic precautions when handling the device.
About this guide7
N3200-ON Series switch
The following sections describe the Dell EMC N3200-ON Series (N3208PX-ON, N3224T-ON, N322F-ON, N3224P-ON,
N3224PX-ON, N3248TE-ON, N3248P-ON, N3248X-ON, and N3248PXE-ON) switches:
Topics:
•Introduction
•Features
•Physical dimensions
•LED display
•Prerequisites
•N3200-ON Series switch configurations
•Luggage tag
Introduction
The N3200-ON Series switches are compact and full width, one rack unit (RU), full-featured fixed form-factor switches.
Table 1. N3200-ON Series switch summary
2
Marketing model name (MMN)DescriptionPower supply unit (PSU) and fans
3. 5GBASE-T RJ45 with 802.3bt Type-4 (90W) PoE4. RJ45 serial management port
5. RJ45 Ethernet console port6. USB Type-A port
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP+ ports
N3224T-ON I/O-side view
Luggage tag2. 1GBASE-T RJ45
1.
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
N3200-ON Series switch9
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP+ ports
N3224F-ON I/O-side view
1. Luggage tag2. 1G SFP
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP+ ports
N3224P-ON I/O-side view
Luggage tag2. 1GBASE-T RJ45 with 802.3at Type-2 (30W) PoE
1.
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP+ ports
N3224PX-ON I/O-side view
10
N3200-ON Series switch
1. Luggage tag2. 10GBASE-T RJ45 with 802.3bt Type-4 (90W) PoE
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP28 ports
N3248TE-ON I/O-side view
1. Luggage tag2. 1GBASE-T RJ45
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP28 ports
N3248P-ON I/O-side view
Luggage tag2. 1GBASE-T RJ45 with 802.3at Type-2 (30W) PoE
1.
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP+ ports
N3248X-ON I/O-side view
N3200-ON Series switch
11
1. Luggage tag2. 10GBASE-T RJ45
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP28 ports
N3248PXE-ON I/O-side view
1. Luggage tag2. 10GBASE-T RJ45 with 802.3bt Type-4 (90W) PoE
3. RJ45 serial management port4. RJ45 Ethernet console port
5. USB Type-A port6. Stack ID
7. MicroUSB Type-B port8. Status LEDs
9. 10G SFP28 ports
N3200-ON Series PSU-side views:
N3208PX-ON PSU-side view
1. Fan
2. External power adapter connection
3. AC power connection
N3224F-ON, N3224P-ON, N3224T-ON, N3248TE-ON, and N3248X-ON PSU-side view
12
N3200-ON Series switch
1. 100G QSFP28 stacking ports
2. Fans
3. AC or DC PSUs
N3224PX-ON, N3248P-ON, N3248PXE-ON PSU-side view
1. 100G QSFP28 stacking ports2. Fans
3. EPS connections4. AC or DC PSUs
Features
The N3200-ON Series switch offers the following features:
● Ports:
○ N3208PX-ON—Compact, four ports 1GBASE-T RJ45 with 802.3bt Type-4 90W PoE, four ports 5GBASE-T RJ45 with
802.3bt Type-4 90W PoE, and two ports 10G SFP+
○ N3224T-ON—1U, 24 ports 1GBASE-T RJ45, four ports 10G SFP+, and two ports 100G QSFP28 for stacking
○ N3224F-ON—1U, 24 ports 1GBASE-T RJ45, four ports 10G SFP+, and two ports 100G QSFP28 for stacking
○ N3224P-ON—1U, 24 ports 1GBASE-T RJ45 with 802.3at Type-2 30W PoE, four ports 10G SFP+, and two ports 100G
QSFP28 for stacking
○ N3224PX-ON—1U, 24 ports multigigabit 10GBASE-T RJ45 with 802.3bt Type-4 90W PoE, four ports 25G SFP28, and
two ports 100G QSFP28 for stacking
○ N3248TE-ON—1U, 48 ports 1GBASE-T RJ45, four ports 10G SFP+, and two ports 100G QSFP28 for stacking
○ N3248P-ON—1U, 48 ports 1GBASE-T RJ45 with 802.3at Type-2 30W PoE, four ports 10G SFP+, and two ports 100G
QSFP28 for stacking
○ N3248X-ON—1U, 48 ports 10GBASE-T RJ45, four ports 25G SFP28, and two ports 100G QSFP28 for stacking
○ N3248PXE—1U, 48 ports multigigabit 10GBASE-T RJ45 with 802.3bt Type-4 90W PoE, four ports 25G SFP28, and two
● N3224PX-ON, N3248P-ON, and N3248PXE-ON—External power supply connectors to connect the MPS-1S or MPS-3S
shelf
● N3224T-ON, N3248X-ON, and N3248TE-ON—Normal and reverse airflow options
● System ground connector
● Switch-monitoring LEDs
Physical dimensions
The N3200-ON Series switch has the following physical dimensions, excluding the PSU and fan tray handle:
● N3208PX-ON:
○ 43.5 mm x 279.4 mm x 312 mm (H x W x D)
○ 1.71 in x 11 in x 12.28 in (H x W x D)
● All N3200-ON Series switches except the N3208PX-ON:
○ 43.5 mm x 434 mm x 400 mm (H x W x D)
○ 1.71 in x 17.09 in x 15.75 in (H x W x D)
(PSU and fan tray handle adds 30 mm or 1.18 in)
LED display
The N3200-ON Series switch includes LED displays on the I/O and PSU sides of the switch. This section describes open
networking installation environment (ONIE) LED behaviors. Some LED behaviors may change after you install your software.
LED behavior
The following N3200-ON Series switch LED behavior is seen during ONIE operations:
N3208PX-ON LEDs
Link status LEDs2. Console port LEDs on the left side—management port on
1.
the right side
3. SFP+ port activity LEDs4. Stack Master ID LED
5. System Status/Health LED6. Power LED
7. Fan LED8. Locator LED/System Beacon
N3224F-ON, N3224P-ON, N3224PX-ON, N3224T-ON, N3248P-ON, N3248PXE-ON, and N3248TE-ON LEDs
14
N3200-ON Series switch
1. Link status LEDs2. Console port LEDs on the left side—management port on
the right side
3. SFP+ port activity LEDs4. Stack ID LED
5. Stack Master LED6. System Status/health LED
7. Power LED8. Fan LED
9. Locator LED/System Beacon10. Stacking port activity LEDs
Table 2. N3200-ON Series switch LED behavior
LEDDescription
7-Segment LED for stacking
Stack Master LED
System Status/Health LED
Power LED
● Off—No power
● Solid green—Hex digit representing the stack unit ID
● Off—Switch is in Stacking Slave mode
● Solid green—Switch is in Stacking Master or Standalone
mode
● Solid green—Normal operation
● Flashing green—Booting
● Solid yellow—Critical system error; major fault
● Flashing yellow—Noncritical system error, minor fault, fan
failure, or power supply failure
● Off—No power
● Solid Green—Normal operation
● Solid yellow—POST is in process
N3200-ON Series switch15
Table 2. N3200-ON Series switch LED behavior (continued)
LEDDescription
● Flashing yellow—Power supply failed
FAN LED
Locator LED/System Beacon
● Off—No power
● Solid green—Normal operation; fan powered and running
at the expected RPM
● Flashing yellow—Fan fault—including incompatible airflow
direction when you insert the PSU, fan trays with differing
airflows, missing a fan, or fan tray not functioning properly
● Off—Locator function disabled
● Flashing blue—Locator function enabled
Table 3. 1000MBase-T and 10/100MBase-T PoE System management Ethernet port LEDs
LEDDescription
Link LED
Activity LED
● Off—No link
● Solid green—Link operating at a maximum speed,
autonegotiated/forced to 1000MBase-T mode
● Solid yellow—Link operating at a lower speed,
autonegotiated/forced or 10/100MBase-T mode
● Off—No activity
● Solid Yellow—No port activity and PoE power on
● Flashing green—Port activity and PoE power off
● Flashing yellow—Port activity and PoE power on
Table 4. 1000MBase-T and 10/100MBase-T non-PoE System management Ethernet port LEDs
LEDDescription
Link LED
Activity LED
● Off—No link
● Solid green—Link operating at a maximum speed,
autonegotiated/forced to 1000MBase-T mode
● Solid yellow—Link operating at a lower speed,
autonegotiated/forced or 10/100MBase-T mode
● Off—No activity
● Flashing green—Port activity
Table 5. 1G, 5G, 10G Base-T PoE port LEDs
LEDDescription
Link LEDAll four LEDs:
● Off—No link
● Solid green—Link operating at maximum speed,
autonegotiated/forced to 2.5GBase-T mode
● Solid yellow—Link operating at a lower speed,
autonegotiated/forced to 10/100/1000MBase-T
● Flashing green, ~30ms—Port activity
Activity LED
● Off—No activity and PoE power off
● Solid yellow—No port activity and PoE power on
● Flashing green—port activity and PoE power off
● Flashing yellow—port activity and PoE power on
Table 6. 1G or 10G Base-T non-PoE port LEDs
LEDDescription
Link LEDAll four LEDs:
16N3200-ON Series switch
Table 6. 1G or 10G Base-T non-PoE port LEDs (continued)
LEDDescription
● Off—No link
● Solid green—Link operating at maximum speed,
autonegotiated/forced to 2.5GBase-T mode
● Solid yellow—Link operating at a lower speed,
autonegotiated/forced to 10/100/1000MBase-T
Activity LED
● Off—No activity
● Flashing green, ~30ms—Port activity
Table 7. SFP+ port LEDs
LEDDescription
Link LEDAll four LEDs:
● Off—No link
● Solid green—Link operating at maximum speed, 10G
● Solid yellow—Link operating at a speed less than 10G
● Flashing green, ~30ms—Port activity
Activity LED
● Off—No activity
● Flashing green—port activity at maximum speed
● Flashing yellow—port activity at lower speed
Table 8. SFP28 port LEDs
LEDDescription
Link LEDAll four LEDs:
● Off—No link
● Solid green—Link operating at maximum speed, 25G
● Solid yellow—Link operating at a speed less than 25G
● Flashing green, ~30ms—Port activity
Activity LED
● Off—No activity
● Flashing green—port activity at maximum speed
● Flashing yellow—port activity at lower speed
Table 9. QSFP28 port LEDs
LEDDescription
Link LEDAll four LEDs:
● Off—No link
● Solid green—Link operating at maximum speed, 100G
● Solid yellow—Link operating at a speed less than 100G
● Flashing green, ~30ms—Port activity
Activity LED
● Off—No activity
● Flashing green, ~30ms—port activity at maximum speed,
100G
● Flashing yellow, ~30ms—port activity at speed less than
100G
● Flashing yellow, 1 second on/off—port beacon
Prerequisites
The following is a list of components that are required for successful switch installation:
NOTE: For detailed installation instructions, see Site preparations and N3200-ON Series switch installation.
N3200-ON Series switch17
● N3200-ON Series switch or multiple switches, if stacking
● AC or DC country- and regional-specific cables to connect the AC or DC power source to the AC or DC PSU
● Hot-swappable AC or DC power supply units; minimum one AC or DC PSU—excluding N3208PX-ON
● Hot-swappable fan modules—excluding N3208PX-ON
● All N3200-ON DC versions—excluding N3208PX-ON; order DC PSUs separately
● All N3200-ON AC platforms—no ground lug ships with the accessories
● L-bracket and screws for two-post rack mount, or rubber feet for table or shelf placement, or bracket and screws for wall or
ceiling mount—excluding N3208PX-ON
● N3208PX-ON only—Wire clip for PSU cable
● Copper and fiber cables
N3248PXE-ON DC only—Ground lug and screws ship with the accessories
●
● N3248PXE-ON AC only—No-OS SKU: Ground lug and screws ship with the accessories.
● N3248P-ON DC only—Ground lug and screws ship with the accessories
● #1 and #2 Phillips screwdrivers, not included
● Torx screwdriver, not included
Other optional components are:
● Extra mounting brackets and screws
● Second AC PSU or DC PSUs—except N3208PX-ON
● MPS-1S shelf with AC or DC PSU
● MPS-3S shelf with AC or DC PSUs
N3208PX-ON only—External power adapter
●
N3200-ON Series switch configurations
You can order the N3200-ON Series switch in several different configurations.
● N3200-ON Series AC switch (optional DC PSU available)
○ N3208PX-ON—Compact, four ports 1G BASE-T RJ45 with 802.3bt Type-4 90W PoE, four ports 5G BASE-T RJ45 with
802.3bt Type-4 90W PoE, two ports 10G SFP+, one fixed AC PSU, two external power adapters, and one fan
○ N3224T-ON—1U, 24 ports 1G BASE-T RJ45, four ports 10G SFP+, two 100G QSFP28 ports for stacking, two pluggable
AC or (optional) DC PSUs, three pluggable fan modules, and normal and reverse airflow options
○ N3224F-ON—1U, 24 ports 1G SFP ports, four ports 10G SFP+, two 100G QSFP28 ports for stacking, two pluggable AC
or (optional) DC PSUs, and three pluggable fan modules
○ N3224P-ON—1U, 24 ports 1G BASE-T RJ45 with 802.3at Type-2 30W PoE, four ports 10G SFP+, two 100G QSFP28
ports for stacking, two pluggable AC or (optional) DC PSUs, and three pluggable fan modules
○ N3224PX-ON—1U, 24 ports 10G BASE-T RJ45 with 802.3bt Type-4 90W PoE, four ports 25G SFP28, two 100G
QSFP28 ports for stacking, two pluggable AC or (optional) DC PSUs, three pluggable fan modules, and (optional) EPS
○ N3248TE-ON—1U, 48 ports 1G BASE-T RJ45, four ports 10G SFP28, two 100G QSFP28 ports for stacking, two
pluggable AC or (optional) DC PSUs, three pluggable fan modules, and normal and reverse airflow options
○ N3248P-ON—1U, 48 ports 1G BASE-T RJ45 with 802.3at Type-2 30W PoE, four ports 10G SFP+, two 100G QSFP28
ports for stacking, two pluggable AC or (optional) DC PSUs, three pluggable fan modules, and (optional) EPS
○ N3248X-ON—1U, 48 ports 10G BASE-T RJ45, four ports 25G SFP28, two 100G QSFP28 ports for stacking, two
pluggable AC or (optional) DC PSUs, three pluggable fan modules, and normal and reverse airflow options
○ N3248PXE—1U, 48 ports 10G BASE-T RJ45 with 802.3bt Type-4 90W PoE, four ports 25G SFP28, two 100G QSFP28
ports for stacking, two pluggable AC or (optional) DC PSUs, three pluggable fan modules, and (optional) EPS
● Normal airflow:
○ All N3200-ON Series switches—Fan with airflow from the I/O side to the PSU side—normal airflow
● Reverse airflow:
○ N3224T-ON, N3248TE-ON, N3248X-ON only—Fan with airflow from the PSU side to the I/O side—reverse airflow
Luggage tag
The switch has a pull-out tag, which is known as a luggage tag, on the I/O-side of the switch. The front of the luggage tag
includes switch ID information. The back of the luggage tag includes a QRL that takes you to a How-To site where you can
watch videos about racking the switch, replacing components, configuring port channels, and so on.
18
N3200-ON Series switch
N3208PX-ON, N3224F-ON, N3224P-ON, N3224PX-ON, and N3224T-ON luggage tag
1. Product ID QRL2. Product information QRL
3. SVC tag4. MAC address
5. Exp Svc code
N3248P-ON, N3248PXE-ON, N3248TE-ON, N3248X-ON luggage tag
N3200-ON Series switch
19
1. Product ID QRL2. Product information QRL
3. SVC tag4. MAC address
5. Exp Svc code
20N3200-ON Series switch
Site preparations
The N3200-ON Series switch is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
● Network telecommunication facilities
● Data centers
● Other locations where the National Electric Code (NEC) applies
NOTE: Install the switch into a rack or cabinet before installing any additional components such as cables or optics.
Topics:
•Site selection
•Cabinet placement
•Rack mounting
•Switch ground
Fans and airflow
•
•Power
•Storing components
3
Site selection
Install the switch equipment in restricted access areas.
A restricted access area is one in which service personnel can only gain access using a special tool, lock, key or other means of
security. The authority responsible for the location controls access to the restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
● Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local
electrical codes.
● Switch environmental temperature is from 32° to 113°F (0° to 45°C).
● Relative humidity is from 5 to 95 percent (RH), noncondensing.
● In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot air vents or direct
sunlight
● Away from sources of severe electromagnetic noise.
● Inside the restricted access area, which is positioned in a rack or cabinet, or on a desktop with adequate space in the front,
back, and sides for proper ventilation and access
●
Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75.
For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the N3200-ON Series switch only in indoor cabinets that are designed for use in a controlled environment.
Do not install the switch in cabinets that are outdoors. For cabinet placement requirements, see Site selection.
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 12.7 cm (5 inches) between the intake and exhaust vents and the cabinet wall.
Site preparations21
Rack mounting
When you prepare your equipment rack, ensure that the rack is grounded.
Ground the equipment rack to the same ground point the power service in your area uses. The ground path must be permanent.
Switch ground
Dell Technologies recommends you ground your switch. Use the N3200-ON Series switch in a common bond network (CBN).
Connect the grounding cables as described in N3200-ON Series switch installation.
NOTE: For an AC-powered switch, although the third conductor of the AC power cable provides a ground path, Dell
Technologies recommends grounding your switch with a dedicated ground wire.
NOTE: For a DC-powered switch, the only way to safely ground your switch is to attach a dedicated ground wire. The
ground lug kit ships in a plastic bag that is placed with the other accessories inside the shipping box. To ground your switch,
first attach the ground lug to the switch using the screws. Then attach the DC ground wire to the ground lug.
Fans and airflow
The N3200-ON Series include three hot-swappable fan units, except the N3208PX-ON, which has one fan.
Fan combinations
Fan installation is completed as part of the factory install based on stock keeping unit (SKU) type. The N3200-ON Series switch
has SKUs that support the following configurations:
● AC or DC PSU with fan airflow from the I/O to the PSU—the red indicator is the normal airflow direction.
● AC or DC PSU with fan airflow from the PSU to the I/O—the blue indicator is the reverse airflow direction.
NOTE: All N3200-ON Series switches except N3208PX-ON support normal airflow.
NOTE: Only N3224T-ON, N3248TE-ON, and N3248X-ON AC switches support reverse airflow.
Order the fans suitable to support the ventilation at your site. Use a single type of airflow fan in your switch. Do not mix reverse
and normal airflows in a single N3200-ON Series switch.
For proper ventilation, position the switch in an equipment rack or cabinet with a minimum of 12.7 cm (5 inches) of clearance
around the exhaust vents. When you install two N3200-ON switches near each other, to permit proper airflow, position the
two switches at least 12.7 cm (5 inches) apart. The fan speed varies based on internal temperature monitoring. The N3200-ON
Series switch never intentionally turns off the fans.
For more information, see Fans.
Power
To connect the switch to the applicable power source, use the appropriate power cable. An AC power cable is included with
each PSU. If you optionally order DC PSUs, they ship with a DC power cable.
When installing AC or DC switches, follow the requirements of the National Electrical Code, ANSI/NFPA 70, where applicable.
The switch is powered-up when you connect the power cable between the switch and the power source. For more information,
see Power supplies.
WARNING:
outlet.
CAUTION: Always disconnect the power cable before you service the power slots. The switch has multiple power
cables. Before servicing, ensure that all power cables are disconnected.
22Site preparations
This equipment must be earthed. Connect the power plug to a properly wired earth ground socket
CAUTION: On an AC switch, use the power cable as the main disconnect device. Ensure that the socket-outlet is
located and installed near the equipment and is accessible.
NOTE: Software controls the module power. You do not see module LEDs when the switch powers up in ONIE.
Storing components
If you do not install your N3200-ON Series switch and components immediately, properly store the switch and all components
using these guidelines:
● Storage location temperature must remain constant. The storage range is from -40°C to 70°C (-40° to 158°F).
● Store on a dry surface or floor, away from direct sunlight, heat, and air conditioning ducts.
● Store in a dust-free environment.
NOTE: ESD damage can occur when components are mishandled. Always wear an ESD-preventive wrist or heel ground
strap when handling the N3200-ON Series switch and accessories. After you remove the original packaging, place the
N3200-ON Series switch and components on an antistatic surface.
Site preparations23
N3200-ON Series switch installation
To install the N3200-ON Series switch, complete the installation procedures in the order that is presented in this chapter.
Always handle the switch and components with care. Avoid dropping the switch or its field replaceable units (FRUs).
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the N3200-ON Series switch and components. As with all electrical devices of this type, take all the
necessary safety precautions to prevent injury when installing this switch.
Topics:
•Unpack
•Rack or cabinet hardware installation
•Ground cable
•Desktop
•N3208PX-ON ceiling-mount switch installation
N3208PX-ON wall-mount switch installation
•
•Standard bracket two-post installation
•Two-post five-inch-offset switch installation
•Two-post flush-mount switch installation
•Wall- or ceiling-mount switch installation
•One RU ReadyRails installation
•Optics installation
•Switch start-up
•After switch placement
•Switch replacement
4
Unpack
NOTE: Before unpacking the switch, inspect the container and immediately report any evidence of damage.
When unpacking the switch, ensure that the following items are included:
● One N3200-ON Series switch
● One RJ45 to DB-9 female cable
● One MicroUSB console cable
●
Two sets of rack mounting brackets and screws—except N3208PX-ON
● Four rubber feet
● N3208PX-ON only—ceiling or wall mount tray and screws
● N3208PX-ON only—one wire clip for the power connector
● One pluggable AC PSU (second AC PSU if ordered)—except N3208PX-ON
● One or two pluggable DC PSUs, if ordered
● DC only: Ground lug and screws—except N3208PX-ON.
● Three pluggable fan units, except N3208PX-ON
● (Optional) N3208PX-ON only—two external power adapters
● One AC power cable; country or region specific
● DC only: DC power cable
● N3200-ON Series Quick Setup Guide
● N3200-ON Series Warning Guide
● Safety and Regulatory Information
● Warranty and Support Information
24N3200-ON Series switch installation
Unpacking Steps
Unpack the system carefully.
1. Place the container on a clean, flat surface and cut all straps securing the container.
2. Open the container, or remove the container top.
3. Carefully remove the switch from the container and place it on a secure and clean surface.
4. Remove all packing material.
5. Inspect the product and accessories for damage.
Rack or cabinet hardware installation
You may either place the switch on a rack shelf or mount the switch directly into a 19" wide, EIA-310- E-compliant rack.
For 1U switches:
● By default, the switch ships with a two-post rack mount system
● You can order separately the ReadyRail system and/or the four-post L-bracket rail system for two-post or four-post rack
mounting
The ReadyRails system includes separately packaged rail assemblies.
WARNING: This document is a condensed reference. Read the safety instructions in your
and Regulatory
NOTE: The figures in this document are not intended to represent a specific switch.
NOTE: Do not the use the mounted ReadyRails as a shelf or a workplace.
information booklet before you begin.
Safety, Environmental,
Rackmount safety considerations
● Rack loading—Overloading or uneven loading of racks may result in shelf or rack failure, possibly damaging the equipment
and causing personal injury. Stabilize racks in a permanent location before loading begins. Mount the components starting at
the bottom of the rack, and then work to the top. Do not exceed the load rating of your rack.
● Power considerations—Connect only to the power source specified on the unit. When you install multiple electrical
components in a rack, ensure that the total component power ratings do not exceed the circuit capabilities. Overloaded
power sources and extension cables present fire and shock hazards.
● Elevated ambient temperature—If installed in a closed rack assembly, the operating temperature of the rack environment
may be greater than the room ambient temperature. Use care not to exceed the 45°C (113°F) maximum ambient
temperature of the switch.
● Reduced airflow—Install the equipment in the rack so that the amount of airflow that is required for safe operation of the
equipment is not compromised.
● Reliable earthing—Maintain reliable earthing of rack-mounted equipment. Pay particular attention to the supply connections
other than the direct connections to the branch circuit, for example, use of power strips.
● Do not mount the equipment with the backpanel facing downward.
Ground cable
To attach a ground cable to the switch, use the included M4 screws.
For an AC-powered switch, although the third conductor of the AC power cable provides a ground path, Dell
NOTE:
Technologies recommends grounding your switch with a dedicated ground wire.
NOTE: For a DC-powered switch, the only way to safely ground your switch is to attach a dedicated ground wire. The
ground lug kit ships in a plastic bag that is placed with the other accessories inside the shipping box. To ground your switch,
first attach the ground lug to the switch using the screws. Then attach the DC ground wire to the ground lug.
The ground cable is not included.
N3200-ON Series switch installation
25
The ground lug ships with the optionally ordered DC version PSUs. The AC-no-OS version of the N3248PXE-ON switch, which
you must special order, also ships with the ground lug.
CAUTION: Grounding conductors must be made of copper. Do not use aluminum conductors.
NOTE: Coat the one-hole lug with an antioxidant compound before crimping. Also, bring any unplated mating surfaces to a
shiny finish and coat with an antioxidant before mating. Plated mating surfaces must be clean and free from contamination.
NOTE: The rack installation ears are not suitable for grounding.
To connect the ground cable to the switch:
1. Cut your user-supplied ground cable to the wanted length.
The cable length must facilitate proper operation of the fault interrupt circuits. Use the shortest cable route allowable.
2. Crimp the ground cable inside the ground lug.
3. Attach the other end of the ground cable to a suitable ground point such as the rack or cabinet.
The rack installation ears are not a suitable grounding point.
Desktop
One mounting option is to place the N3200-ON Series switch on a desktop.
The mounting supplies for this installation ship with the switch.
1. Locate the four rubber feet shipped with the switch.
2. Remove the paper backing on the bottom of one of the rubber feet.
3. Adhere the rubber foot to one of the four round position marks on the underside of the switch.
4. Repeat the process for the remaining three rubber feet.
5. Turn the switch over and place on a desktop.
N3208PX-ON ceiling-mount switch installation
This switch installation procedure applies to the compact N3208PX-ON switch only.
NOTE: Do not use this installation procedure for the full-width N3200-ON Series switches.
The mounting supplies for this installation ship with the switch. To complete this installation, you need a pencil, drill, and
Phillips-head drill bit.
26
N3200-ON Series switch installation
1. Locate the ceiling mount tray, ceiling anchors, and 32 mm (1.26 in) M4 screws that are included with your switch.
2. Using the ceiling mount tray as a template, hold the tray on the ceiling where you want to mount the switch. Mark the four
mounting hole locations with the pencil.
3. Drill four holes into the ceiling at the pencil marks.
4. Install the four ceiling-anchors into the ceiling.
5. Attach the ceiling mount tray to the ceiling by drilling the 32 mm (1.26 in) M4 screws into the ceiling anchors.
6. Slide the switch into the ceiling mount tray.
7. Line up the two mushroom-heads on the switch to the ceiling mount tray hook cutouts until the switch locks into place.
8. Fix the switch to the ceiling mount tray using two screws on each side.
N3200-ON Series switch installation
27
To uninstall the switch, unscrew the four ceiling mount tray screws and slide the switch from the mushroom head hooks.
N3208PX-ON wall-mount switch installation
This switch installation procedure is for the compact N3208PX-ON switch only.
NOTE: Do not use this installation procedure for the full-width N3200-ON Series switches.
The mounting supplies for this installation ship with the switch. To complete this installation, you need a pencil, drill, and
Phillips-head drill bit.
1. Locate the wall mount tray, wall anchors, and 4.95 mm (0.19 in) M3 screws that are included with your switch.
2. Using the wall mount tray as a template, hold the tray on the wall where you want to mount the switch. Mark the four
mounting hole locations with the pencil.
3. Drill four holes into the wall at the pencil marks.
4. Install the four wall-anchors into the wall.
5. Attach the wall mount tray to the wall by drilling the 4.95 mm (0.19 in) M3 screws into the wall anchors.
6. Slide the switch into the wall mount tray.
28
N3200-ON Series switch installation
7. Line up the two mushroom-heads on the switch to the wall mount tray hook cutouts until the switch locks into place.
8. Fix the switch to the wall mount tray using two screws on each side.
To uninstall the switch, unscrew the four wall mount tray screws and slide the switch from the mushroom head hooks.
DIN buckle rail installation
Use the DIN buckle with wall- or ceiling-mount installations. This switch installation procedure applies to the compact N3208PXON switch only.
NOTE: Do not use this installation procedure for the full-width N3200-ON Series switches.
This installation requires both the DIN rail mount kit and the wall- or ceiling-mount tray and screws. The wall- and ceiling- mount
tray and screws ship with the switch. You must order the DIN rail mount kit separately.
1. Remove the two DIN buckles, wall- or ceiling-mount tray, and screws from the shipping box.
DIN buckles
N3200-ON Series switch installation
29
wall- or ceiling-mount tray
2. Screw the DIN buckles to the bottom of the wall- or ceiling-mount tray using three screws for each DIN buckle.
3. Slide the switch into the wall-mount tray.
4. Line up the two mushroom-head hooks on the switch to the tray hook cutouts until the switch locks into place.
5. Fix the switch to the tray using two screws on each side.
6. Snap the two DIN buckles into the DIN rails.
30
N3200-ON Series switch installation
To uninstall the switch, unscrew the four mounting tray screws and slide the switch from the mushroom head hooks.
Standard bracket two-post installation
This switch installation procedure is for the compact N3208PX-ON switch only. Use these brackets for front- or center-mount
installation.
NOTE: Do not use this installation procedure for the full-width N3200-ON Series switches.
You must order the mounting supplies for this installation separately.
For a front-mount installation, align the standard bracket rackmount ends with the I/O-side of the switch. For a center-mount
installation, align the standard bracket rackmount ends away from the I/O-side of the switch.
1. Remove the two standard brackets and screws from the shipping box.
2. Insert the standard bracket onto the mushroom head on each side of the switch and slide the bracket back to lock it into
place.
● For a front-mount installation, the standard bracket ears face the I/O-side of the switch.
● For a center-mount installation, the standard bracket ears face the PSU-side of the switch.
3. Attach the standard brackets to the switch using four screws for each bracket.
4. Slide the switch into the two-post rack until the standard bracket ears line up with the rack.
5. Attach the switch to the two-post rack using two #12-24 screws on each side.
To uninstall the switch from the rack, unscrew the four #12-24 rackmount screws and slide the switch out of the rack.
Two-post five-inch-offset switch installation
This switch installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure for the compact N3208PX-ON switch.
NOTE: For the N3224PX-ON, N3248P-ON, and N3248PXE-ON switches, to install an external power supply, see the
External Power Supply (EPS) Installation for the Dell EMC PowerSwitch N2200-ON and N3200-ON Series Switches at
www.dell.com/support.
The mounting supplies for this installation ship with the switch.
1. Locate the mounting brackets and screws.
N3200-ON Series switch installation
31
2. Insert the mounting brackets onto the mushroom head on each side of the switch and slide the mounting bracket back to
lock it into place.
The mounting bracket ears face the PSU-side of the switch.
3. Attach the mounting brackets to the switch using four screws for each bracket.
4. Slide the switch into the two-post rack until the mounting bracket ears line up with the rack.
5. Attach the switch to the two-post rack using two #12-24 screws on each side.
To uninstall the switch from the rack, unscrew the four #12-24 rackmount screws and slide the switch from the rack.
Two-post flush-mount switch installation
This switch installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure for the compact N3208PX-ON switch.
NOTE: For the N3224PX-ON, N3248P-ON, and N3248PXE-ON switches, to install an external power supply, see the
External Power Supply (EPS) Installation for the Dell EMC PowerSwitch N2200-ON and N3200-ON Series Switches at
www.dell.com/support.
The mounting supplies for this installation ship with the switch.
1. Locate the mounting brackets and screws.
32
N3200-ON Series switch installation
2. Insert the mounting brackets onto the mushroom head on each side of the switch and slide the mounting bracket back to
lock it into place.
The mounting bracket ears face the I/O-side of the switch.
3. Attach the mounting brackets to the switch using four screws for each bracket.
4. Slide the switch into the two-post rack until the mounting bracket ears line up with the rack.
5. Attach the switch to the two-post rack using two #12-24 screws on each side.
To uninstall the switch from the rack, unscrew the four #12-24 rackmount screws and slide the switch from the rack.
Wall- or ceiling-mount switch installation
This installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure to wall- or ceiling-mount the compact N3208PX-ON switch.
NOTE: For the N3224PX-ON, N3248P-ON, and N3248PXE-ON switches, to install an external power supply, see the
External Power Supply (EPS) Installation for the Dell EMC PowerSwitch N2200-ON and N3200-ON Series Switches at
www.dell.com/support.
You must order the mounting supplies for this installation separately. You need a drill and a pencil to complete this procedure.
1. Remove the four wall- or ceiling-mount brackets, wall anchors, and screws.
2. Screw two brackets to the left side of the switch using two screws for each bracket.
Torque the screws to 10 in-lbs.
N3200-ON Series switch installation
33
3. Repeat to attach two brackets to the right side of the switch.
4. Hold the wall- or ceiling-mount template to the wall or ceiling. Mark the screw-hole locations on the wall with the pencil.
Wall- or ceiling-mount dimensions
5. Drill eight 8 mm (0.3 in) holes in the wall or ceiling at the pencil marks.
6. Install the eight anchors into the holes.
34
N3200-ON Series switch installation
7. Screw one M5 screw on each corner, four screws total, into the anchors, leaving approximately 5 mm (0.20 in) gap between
the anchor and the screw.
8. Slide the switch onto the screws and tighten the screws to secure the switch in place.
Torque the screws to 24 in-lbs.
Wall mount
9. Screw the remaining four M5 screws into the anchors and tighten the screws.
Torque the screws to 24 in-lbs.
Wall mount
ceiling mount
N3200-ON Series switch installation
35
One RU ReadyRails installation
Install the N3200-ON Series switch, excluding the N3208PX-ON switch, using one of the following installation instructions.
You can install the ReadyRails system using the 1U tool-less square-hole method or one of three possible 1U threaded round-hole
methods. The tooled installation methods include two-post flush mount, two-post center mount, or four-post threaded mount.
NOTE: You must order the ReadyRails mounting supplies for this installation separately.
To begin installation, separate each rail assembly by sliding the inside rail out of the outside rail.
NOTE: For more installation instructions, see the installation labels attached to the rail assembly.
Figure 2. Separate rails
1U Tool-less mount ReadyRails installation
This switch installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure for the compact N3208PX-ON switch.
36N3200-ON Series switch installation
NOTE: For more installation instructions, see the installation labels attached to the rail assembly.
1. Face the ReadyRails flange ears facing outward. Place one rail between the left and right vertical posts. Align and seat the
back flange rail pegs in the back vertical post flange.
The center extractions show how the pegs appear in both the square and nonthreaded round holes.
2. Align and seat the front flange pegs in the holes on the front side of the vertical post.
NOTE: Be sure that the rails click into place and are secure.
3. Repeat this procedure for the second rail.
To uninstall each rail, pull on the latch release on each flange ear and unseat each rail.
Flush-mount ReadyRail installation
This switch installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure for the compact N3208PX-ON switch.
NOTE: For more installation instructions, see the installation labels attached to the rail assembly.
1. Remove the latch castings from the front side of each ReadyRails assembly, item 1.
To remove the two screws from each front flange ear on the switch side of the rail and remove each latch casting, use
a Torx screwdriver. Retain the latch castings for future rack requirements. It is not necessary to remove the back flange
castings.
N3200-ON Series switch installation
37
2. Attach one rail to the front post flange with two user-supplied screws, item 2.
3. Slide the plunger bracket forward against the vertical post and secure the plunger bracket to the post flange with two
user-supplied screws, item 3.
4. Repeat this procedure for the second rail.
Center-mount ReadyRail installation
This switch installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure for the compact N3208PX-ON switch.
NOTE: For more installation instructions, see the installation labels attached to the rail assembly.
1. Slide the plunger bracket rearward until it clicks into place and secure the bracket to the front post flange with two
user-supplied screws, item 1.
38
N3200-ON Series switch installation
2. Slide the back bracket towards the post. Secure it to the post flange with two user-supplied screws, items 2 and 3.
3. Repeat this procedure for the second rail.
Threaded ReadyRails installation
This switch installation procedure is for the full-width N3200-ON Series switches only.
NOTE: Do not use this installation procedure for the compact N3208PX-ON switch.
NOTE: For more installation instructions, see the installation labels attached to the rail assembly.
1. Remove the tool-less latch castings from the front side of each ReadyRails assembly, as shown in the following figure:
Use a torx screwdriver to remove the two screws from each front latch on the switch side of the rail. Remove the tool-less
latch casting. Retain the castings for future rack requirements.
2. Attach the front and back flanges for each rail to the post flanges with two user-supplied screws at each end.
Optics installation
The N3200-ON Series has SFP+, SFP28, and QSFP28 optical ports.
For a list of supported optics, see the specification sheets at www.dell.com/support or contact your Dell EMC Sales
representative.
CAUTION:
ground strap when handling the N3200-ON Series switch and components.
WARNING: When working with optical fibers, follow all warning labels and always wear eye protection. Never
look directly into the end of a terminated or unterminated fiber or connector as it may cause eye damage.
1. Position the optic to enter the port correctly.
The optic has a key that prevents it from being inserted incorrectly.
2. Insert the optic into the port until it gently snaps into place.
NOTE:
the ports.
ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel
When you cable the ports, be sure not to interfere with the airflow from the small vent holes above and below
Optics removal
Remove an optic by pushing the tab on the optic and sliding the optic from the port.
When removing optics with direct attach cables (DACs) from the port, pull the release tab firmly and steadily. Before pulling the
release tab, you must gently push the optic into the port to ensure that it is seated properly. Do not jerk or tug repeatedly on
the tab.
40
N3200-ON Series switch installation
Switch start-up
Supply power to the N3200-ON Series switch after you install your switch.
Dell Technologies recommends reinspecting your switch before powering it up. Verify the following:
● Optional: The equipment is properly secured to the rack and properly grounded.
● Optional: The equipment rack is properly mounted and grounded.
● The ambient temperature around the unit, which may be higher than the room temperature, is within the limits that are
specified for the N3200-ON Series switch.
● There is sufficient airflow around the unit.
The input circuits are correctly sized for the loads and that you use sufficient overcurrent protection devices.
●
CAUTION: Do not start up the switch if a fan module is not installed.
NOTE: A US AC or DC power cable is included for powering up an AC or DC power supply. You must order all other power
cables separately.
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the N3200-ON Series switch and components.
After switch placement
After you have securely installed and powered on the N3200-ON Series switch:
● For switch documentation and resources, see www.dell.com/support.
● For ONIE documentation and resources, see www.onie.org.
NOTE:
If necessary, to upgrade your software or firmware images, go to the Drivers and Downloads page for your switch
at www.dell.com/support.
Switch replacement
The following steps describe uninstalling and replacing a switch with an identical replacement switch. For further assistance
when replacing a switch, contact your Dell EMC support representative.
NOTE: Some steps do not apply if you are replacing a different switch or non-Dell EMC switch.
NOTE: ESD damage can occur when components are mishandled. Always wear an ESD-preventive wrist or heel ground
strap when handling the switch and accessories. After you remove the original packaging, place the switch and components
on an antistatic surface.
1. Back up the switch configuration to your back-up system or laptop TFTP server using a copy command.
2. Disconnect the power source.
3. Label and remove all cables.
4. Remove the switch from your installation.
If you are using ReadyRails, simultaneously press in the two side-release bars on the switch and slide the switch forward.
If you are using the fan trays or PSUs in the replacement switch, uninstall them from the switch.
5. Unpack the new switch.
For more information, see UnpackUnpack.
6. Install the new switch in your rack or cabinet.
For detailed installation instructions, see N3200-ON Series switch installation.
If you are using the fan trays or PSUs from the uninstalled switch, reinsert them in the replacement switch.
7. Connect all the cables.
8. Power on the switch.
For more information, see Switch start-up.
N3200-ON Series switch installation
41
9. Establish a connection to the switch CLI.
10. Confirm that the software version of the replacement switch is the same as the previously installed switch.
show version
If the software versions do not match, upgrade the replacement switch software using the firmware download procedure.
11. Copy the backed-up switch configuration to the new switch.
copy tftp://hostip/filepath running-config
NOTE: For firmware update procedures, see the most current switch-specific release notes at www.dell.con/support,
Drivers and Downloads section.
42N3200-ON Series switch installation
5
External power adapter
This section describes how to install the external power adapter (EPA) inside the power adapter holder. It also describes how to
attach the power adapter holder assembly to the switch. This EPA installation instruction procedure applies to the N3208PX-ON
switch only.
NOTE: Do not use this installation procedure for the full-width N3200-ON Series switches.
You can use one or two EPAs with your adapter holder in a two-post or four-post rack. You can side-mount a single EPA to the
switch. You can center-mount or front-mount the dual-EPA assembly.
You must order the mounting supplies for the EPA-related installation separately.
NOTE: If you are using two external power adapters (EPAs) in a two-post front- or center-mount rack, you must have
two-rack units space available in your rack. Install the switch in the bottom portion of the two-rack units and the EPA in the
top portion above the switch.
Topics:
•Power adapter holder assembly
•Wall or ceiling installation
•DIN rail installation
•Single-EPA and switch four-post installation
•Single-EPA and switch two-post center-mount installation
•Single-EPA and switch two-post front-mount installation
•Dual-EPAs two-post front-mount installation
•Dual-EPAs two-post center-mount installation
Power adapter holder assembly
To install your EPA into the power adapter holder:
1. Set the EPA inside the power adapter holder.
2. Secure the EPA in place using the two metal straps and four screws that ship with the holder.
3. Attach the wire cable clips to the front and back of the power adapter holder.
External power adapter43
4. Install the AC power cable to the EPA and secure with the wire clip.
5. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
6. Secure the wire clip over the EPA cable.
Wall or ceiling installation
To install a single EPA power adapter holder on a wall or ceiling:
NOTE: This installation instruction procedure applies to the external power adapter.
You must order the mounting supplies for this installation separately. You need a drill and a pencil to complete this procedure.
1. Install the EPA in the power adapter holder using Steps 1 through 3 in the Power adapter holder assembly section.
2. Hold the EPA power adapter assembly to the wall or ceiling. Mark the screw-hole locations on the wall or ceiling with the
pencil.
3. Drill four holes in the wall or ceiling at the pencil marks.
4. Screw the power adapter holder assembly to the wall or ceiling using four screws.
Ceiling mount
44
External power adapter
Wall mount
5. Install the AC power cable to the EPA and secure with the wire clip.
6. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
External power adapter
45
DIN rail installation
To install an external power adapter to DIN rails:
NOTE: This installation instruction procedure applies to the external power adapter only.
You must order the mounting supplies for this installation separately.
1. Remove the two DIN buckles and screws from the shipping box.
2. Install the EPA in the power adapter holder using Steps 1 through 3 in the Power adapter holder assembly section.
3. Fix the two DIN buckles to the bottom side of the EPA power adapter assembly using three screws for each DIN rail.
4. Snap the two DIN buckles into the DIN rails.
5. Install the AC power cable to the EPA and secure with the wire clip.
6. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
46
External power adapter
Single-EPA and switch four-post installation
To install a single EPA power adapter holder on the side of your switch in a four-post rack:
NOTE: This installation instruction procedure applies to the N3208PX-ON switch only.
1. Install the single EPA in the power adapter holder using the instructions in Power adapter holder assembly.
2. Align the two mushroom heads on the switch with the two holes on the power adapter holder. Slide the power adapter
holder forward to lock it in place.
3. Use two screws to secure the power adapter holder to the side of the switch.
4. Install the AC power cable to the EPA and secure with the wire clip.
5. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
6. Install the four-post rail-brackets to the switch and the power adapter holder.
7. Install the rail bracket to the four-post rack and secure it with the rack-mounting screws.
Single-EPA and switch two-post center-mount
installation
To install a single EPA power adapter holder on the side of your switch in a center-mount two-post rack:
NOTE: This installation instruction procedure applies to the N3208PX-ON switch only.
1. Install the single EPA in the power adapter holder using the instructions in Power adapter holder assembly.
External power adapter
47
2. Align the two mushroom heads on the switch with the two holes on the power adapter holder. Slide the power adapter
holder forward to lock it in place.
3. Use two screws to secure the power adapter holder to the side of the switch.
4. Install the AC power cable to the EPA and secure with the wire clip.
5. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
6. Align the L-bracket with mushroom head on the switch and the power adapter holder.
Face the L-bracket flange towards the rear of the assembly.
7. Secure the L-brackets to the switch and the power adapter holder using four screws on each side.
8. Install the L-bracket to the two-post rack, and secure it with the rack-mounting screws.
48
External power adapter
Single-EPA and switch two-post front-mount
installation
To install a single EPA power adapter holder on the side of your switch in a front-mount two-post rack:
NOTE: This installation instruction procedure applies to the N3208PX-ON switch only.
1. Install the single EPA in the power adapter holder using the instructions in Power adapter holder assembly.
2. Align the two mushroom heads on the switch with the two holes on the power adapter holder. Slide the power adapter
holder forward to lock it in place.
3. Use two screws to secure the power adapter holder to the side of the switch.
4. Install the AC power cable to the EPA and secure with the wire clip.
5. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
6. Align the L-bracket with mushroom head on the switch and the power adapter holder.
Face the L-bracket flange towards the rear of the assembly.
7. Secure the L-brackets to the switch and the power adapter holder using four screws on each side.
8. Install the L-bracket to the two-post rack, and secure it with the rack-mounting screws.
External power adapter
49
Dual-EPAs two-post front-mount installation
To install two EPA power adapter holders in a front-mount two-post rack:
NOTE: This installation instruction procedure applies to the N3208PX-ON switch only.
NOTE: For this installation, you need two-rack units of space in your mounting rack. Install the switch in the bottom portion
of the two-rack units and keep the top portion open.
1. Align the mushroom heads on one power adapter holder with the two cutouts on the second power adapter holder and slide
together.
2. Secure the two power adapter holders together with four screws—two at the front and two at the back of the assembly.
3. Install the two EPAs in your power adapter assembly and secure with metal straps and screws.
For EPA installation instructions, see Power adapter holder assembly.
4. Align the right L-bracket with the mushroom heads on the right side of the assembly.
Face the L-bracket flange towards the front of the assembly.
5. Secure the left L-bracket with four screws.
50
External power adapter
6. Repeat with the right L-bracket.
7. Install the AC power cable to the EPA and secure with the wire clip.
8. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
9. Install the dual-EPA assembly above the switch in the two-post rack.
For rack installation instructions, see N3200-ON Series switch installation.
External power adapter
51
Dual-EPAs two-post center-mount installation
To install two EPA power adapter holders in a center-mount two-post rack:
NOTE: This installation instruction procedure applies to the N3208PX-ON switch only.
NOTE: For this installation, you need two-rack units of space in your mounting rack. Install the switch in the bottom portion
of the two-rack units and keep the top portion open.
1. Align the mushroom heads on one power adapter holder with the two cutouts on the second power adapter holder and slide
together.
2. Secure the two power adapter holders together with four screws—two at the front and two at the back of the assembly.
3. Install the two EPAs in your power adapter assembly and secure with metal straps and screws.
For EPA installation instructions, see Power adapter holder assembly.
4. Align the right L-bracket with the mushroom heads on the right side of the assembly.
Face the L-bracket flange towards the rear of the assembly.
5. Secure the left L-bracket with four screws.
52
External power adapter
6. Repeat with the right L-bracket.
7. Install the AC power cable to the EPA and secure with the wire clip.
8. Bend the AC power cable 180 degrees along the holder wall and through the cable cutout.
9. Install the dual-EPA assembly above the switch in the two-post rack.
For rack installation instructions, see N3200-ON Series switch installation.
External power adapter
53
54External power adapter
Power supply
The N3200-ON Series switch ships with one pluggable AC power supply. You can order a second AC PSU separately. If you
require DC power, you can order one or two DC PSUs.
The N3224PX-ON, N3248P-ON, and N3248PXE-ON switches also support an optional external power supply that connects
to the switch using an MPS-1S or MPS-3S shelf. Use the EPS to add redundancy, or extend the PoE budget based on
your requirement. To install an external power supply, see the External Power Supply (EPS) Installation for the Dell EMCPowerSwitch N2200-ON and N3200-ON Series Switches at www.dell.com/support.
Table 10. AC PSU input voltage
AC PSUInput voltageOutput
6
DPS-320AP (For N3208PX-ON only)
DPS-550
DPS-1050
DPS-1600
● Low line = 110 V
● High line = 220 V
● Low line = 110 V
● High line = 220 V
● Low line = 110 V
● High line = 220 V
● Low line = 110 V
● High line = 220 V
● 300 W
● 300 W
● 550 W
● 550 W
● 950 W
● 1050 W
● 950 W
● 1600 W
Table 11. DC PSU input voltage
DC PSUInput voltageOutput
DPS-550
DPS-1300
CAUTION: To prevent electrical shock, ensure that the N3200-ON Series switch is grounded properly. If you do
not ground your equipment correctly, excessive emissions may result. Use a qualified electrician to ensure that
the power cables meet your local electrical requirements.
WARNING: Equipment that provides DC input to the DC port must be certified for CCC and meet the relevant
standards.
NOTE: Reserve airflow, from the PSU-side to the I/O-side of the switch, is only supported on the N3224T-ON, N3248X-
ON, and N3248TE-ON switches.
● -40 V to -60 V● 550 W
● -40 V to -60 V● 1300 W
NOTE: Connect the power supply to the appropriate branch circuit protection as defined by your local electrical codes.
Verify that the remote power source complies with the switch input power specifications.
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the N3200-ON Series switch and components.
Topics:
•Components
•AC or DC power supply installation
•AC or DC power supply replacement
•550W DC power connections
•1300W DC power connections
•Connect the EPS shelf
Power supply55
Components
The following power supply options are available for the N3200-ON Series switch:
● AC or DC power supply with integrated fan
● AC or DC power supply with integrated reverse-flow fan
NOTE: Reserve airflow is only supported on the N3224T-ON, N3248TE-ON, and N3248X-ON switches.
For the N3200-ON Series switches, power supply 1 (PSU1) and power supply 2 (PSU2) are on the right side of the switch. PSU1
is near the center of the switch; PSU2 is on the right edge of the switch.
N3224F-ON, N3224P-ON, N3224T-ON, N3248TE-ON, and N3248X-ON PSUs
1. Default PSU and ordered-separately PSU. PSU1 is near the center of the switch; PSU2 is on the right edge of the switch.
N3224PX-ON, N3248P-ON, and N3248PXE-ON PSUs
1. Default PSU and ordered-separately PSU. PSU1 is near the center of the switch; PSU2 is on the right edge of the switch.
The PSU has an integrated fan, which you cannot replace individually; if the fan integrated in a PSU fails, you must replace the
entire PSU.
WARNING:
the safety cover uninstalled.
CAUTION: Remove the power cable from the PSU before uninstalling the PSU. Also, do not connect the power
cable before you insert the PSU in the switch.
NOTE: To comply with the GR-1089 Lightning Criteria for Equipment Interfacing with AC or DC Power Ports, use an
external surge protection device (SPD) at the AC or DC input of the router.
Prevent exposure and contact with hazardous voltages. Do not attempt to operate this switch with
AC power cable clips
NOTE: These AC power cable clips apply to the compact N3208PX-ON switch only.
After you connect the AC power cable to the N3208PX-ON switch, attach the metal wire clip to the switch over each AC power
cable.
56
Power supply
Figure 4. AC power cable clips
PSU LEDs
● Solid green—Input is OK.
● Flashing green blink at 1 Hz—PSU is in a faulty state.
● Off—PSU is off.
AC or DC power supply installation
NOTE:
The PSU slides into the slot smoothly. Do not force a PSU into a slot as this action may damage the PSU or the
switch.
NOTE: Ensure that you correctly install the PSU. When you install the PSU correctly, the power connector is on the right
side of the PSU.
1. Remove the PSU slot cover from the N3200-ON Series switch using a small #1 Phillips screwdriver. The PSU slot cover has
two screws on the top and two screws on the bottom of the platform.
2. Remove the PSU from the electro-static bag.
3. Insert the PSU into the switch PSU slot—insert the exposed PSU connector first.
The PSU slot is keyed so that you can only fully insert the PSU in one orientation. When you install the PSU correctly, it
snaps into place and is flushed with the back of the switch.
4. Plug in the appropriate AC three-prongs cable from the switch PSU to the external power source.
N3224T-ON, N3224F-ON, N3224P-ON, N3248TE-ON, and N3248X-ON PSU installation
1. PSU. Optional PSU also shown.
N3224PX-ON, N3248P-ON, and N3248PXE-ON PSU installation
Power supply
57
1. PSU. Optional PSU also shown.
NOTE: The N3200-ON Series switch powers up when you connect the cables between the power supply and the power
source.
NOTE: For hot-swappable PSUs, after you have connected the power cable to the switch, use the included black
power-cable tie to secure the cable in place.
AC or DC power supply replacement
CAUTION:
before servicing.
NOTE: The PSU slides into the slot smoothly. Do not force a PSU into a slot as this action may damage the PSU or the
N3200-ON Series switch.
NOTE: If a PSU fails, you must replace the entire unit. There are no field serviceable components in the PSU. To request a
hardware replacement, see www.dell.com/support/.
1. Disconnect the power cable from the PSU.
2. Use the grab handle to slide the PSU out of the power supply bay.
3. Use the grab handle on the replacement PSU to slide it into the power supply bay.
4. Attach the power cable to the replacement PSU.
NOTE: The switch powers up when the cables are connected between the power supply and the power source.
Disconnect the power cable before uninstalling the power supplies. Also, disconnect all power cables
550W DC power connections
Each 550W DC PSU comes with a connector cable. One cable is provided for each 550W DC PSU.
58
Power supply
Figure 5. DC power connector and wiring block
1. Wiring block
2. Power connector
3. PSU connector
1. Strip a one-half inch section of insulation from each of the power connector wires, as shown.
2. Insert each of the bare wire power connector lengths into the wiring block. The blue wire is -48 V, the black wire is the
positive return, and the yellow/green wire is the ground wire, as shown.
3. Use a flat-head screwdriver to tighten the screws that secures the bare wires into the wiring block.
4. Secure the 550W DC power source wires to the other side of the wiring block, see steps 1 and 3.
NOTE: Do not cross the wires.
5. Insert the 550W DC power connector into the power socket of the 550W DC PSU. Ensure that the connector pins firmly
seat and you hear the click of the left and right levered power connector clamps lock into place.
NOTE: Never try to force the power connector into or out of the 550W DC PSU power socket.
6. Secure the 550W DC power cable to the 550W DC power connector using the attached thumbscrews.
To uninstall the power connector from a 550W DC PSU, unscrew the thumbscrews, unplug the 550W DC power cable, and pull
the 550W DC power connector from the 550W DC PSU socket.
1300W DC power connections
Each 1300W DC PSU comes with one 1300W DC cable. The cable ships in a separate plastic bag.
CAUTION:
and Tma = 45-degree C minimum. The altitude of operation is 5000 m. The product must be supplied by a
UL-Listed DC power source that is separated from AC mains by double or reinforced insulation when the switch
is connected to 1300W DC power. For more information, contact your Dell sales representative.
This product must be supplied by a 1300W DC power source rated -48 Vdc to -60 Vdc, 40 A minimum,
Power supply59
NOTE: The conductor screw can not be smaller than the conductors supplying power. Secure all screws and ground-wire
connections.
NOTE: Dell Technologies recommends using a 40 A circuit breaker. Before you supply 1300W DC current to the switch,
review the current rating of your protective device.
NOTE: You need a user-supplied flat-head screwdriver to complete this installation.
1. Wiring block
2. 1300W DC cable
3. PSU socket
1. Strip a one-half inch section of insulation from each of the power connector wires.
2. Insert each of the bare wire power connector lengths into the wiring block.
The blue wire is -48 V, the black wire is the positive return, and the yellow and green wire is the ground wire, 10 AWG
minimum.
3. Use a flat-head screwdriver to tighten the screws that secures the bare wires into the wiring block.
4. Remove the plastic cover, the two M4 screws and one M5 screw from the PSU socket. Keep all the removed parts.
5. Attach the blue wire and black wire to the PSU socket. Secure the wires with the two M4 screws.
NOTE: Attach the blue wire to the V- terminal. Attach the black wire to the V+ terminal.
60Power supply
6. Return the plastic cover back to the PSU socket.
7. Attach the yellow and green wire to the PSU GND. Secure the wire with the M5 screw.
NOTE:
To uninstall the cable from the 1300W DC PSU, remove the plastic cover and unscrew the M4 and M5 screws.
Pull the 1300W DC cable out from the 1300W DC PSU socket.
Connect the EPS shelf
This section applies to the N3224PX-ON, N3248P-ON, and N3248PXE-ON switches only.
NOTE:
For more information about the external power supply, see External Power Supply (EPS) Installation for the Dell
EMC PowerSwitch N2200-ON and N3200-ON Series Switches at www.dell.com/support.
NOTE: The EPS power cable supports a maximum of 2400 W. If you require more power than 2400 W, you must connect
two EPS power cables.
To connect the EPS shelf to the switch, use the EPS power cable.
1. Unscrew the DC power cover from the rear of the switch.
Power supply
61
NOTE: If you are connecting a single EPS power cable to your switch, always use primary A-slot. Leave the secondary
B-slot DC power cover in place, as shown:
2. Unscrew the DC-power-OUT cover from the rear of the EPS shelf.
NOTE:
If you are connecting a single EPS power cable to your MPS-3S shelf, always use primary A-slot. Leave the
secondary B-slot DC power cover in place.
MPS-1S shelf
MPS-3S shelf
62
Power supply
3. Connect the EPS power cable to the EPS-DC-In on the switch.
Torque the screw to 10 in-lbs.
One EPS power cable connected
Two EPS power cables connected
4. Connect the other end of the DC cable to either a MPS-1S shelf or MPS-3S shelf.
Power supply
63
Torque the screw to 10 in-lbs.
One EPS power cable connected to a MPS-1S shelf.
One EPS power cable connected to a MPS-3S shelf
Two EPS power cables connected to a MPS-3S shelf
64
Power supply
5. Repeat until all EPS power cables are connected.
To disconnect an EPS power cable, unscrew the cable and disconnect the cable from the switch.
Power supply
65
7
Fans
The N3200-ON Series switch, except the N3208PX-ON switch, comes from the factory with three pluggable fan modules.
● N3208X-ON—one fan
● N3224T-ON, N3224F-ON, N3224P-ON, N3224PX-ON, N3248TE-ON, N3248P-ON, N3248X-ON, and N3248PXE-ON—
three pluggable fans
The N3200-ON Series switch supports two airflow direction options. Do not mix airflow types in a switch. You can use only a
single airflow direction in a switch. If the airflow directions are mismatched, you must correct the mismatched airflow direction.
● Airflow is from the I/O panel to the PSU—the red indicator is the normal airflow direction.
● Airflow is from the PSU to the I/O panel—the blue indicator is the reverse airflow direction.
NOTE: Reverse airflow is only supported on the N3224T-ON, N3248TE-ON, and N3248X-ON switches.
All fans and PSUs in a configuration must be in the same airflow direction.
Environmental factors can decrease the amount of time that is required between fan replacements. Check the environmental
factors regularly. An increase in temperature and/or particulate matter in the air might affect performance—for example, new
equipment installation.
Topics:
•Components
•Fan module installation
Components
The following are the N3200-ON Series switch fan components:
N3208PX-ON fan
1. Fan
N3224F-ON, N3224P-ON, N3224T-ON, N3248TE-ON, and N3248X-ON fans
1. Fans—Fan1 is near the left edge of the switch; Fan3 is near the center of the switch.
N3224PX-ON, N3248P-ON, and N3248PXE-ON fans
66Fans
1. Fans—Fan1 is near the left edge of the switch; Fan3 is near the center of the switch.
Fan LEDs
● Solid green—Fan input is normal
● Flashing green blink at 1 Hz—Fan is in a faulty state
● Off—Fan is off
Fan module installation
The fan module in the N3200-ON Series switch, excluding N3208X-ON, is field replaceable.
1. Remove the fan slot cover from the N3200-ON Series switch using a small #1 Phillips screwdriver. The fan slot cover has
one screw on the top and one screw on the bottom of the platform.
2. Take the fan module out of the shipping box.
3. Slide the module into the bay.
N3224F-ON, N3224P-ON, N3224T-ON, N3248TE-ON, and N3248X-ON fan installation
● Fan installation
N3224PX-ON, N3248P-ON, and N3248PXE-ON fan installation
Fans
67
● Fan installation
Fan module replacement
To request a hardware replacement, see www.dell.com/support/.
1. Take the replacement fan module out of the shipping box.
2. Slide the installed fan module out of the bay.
3. Slide the replacement module into the bay.
68Fans
Management ports
The N3200-ON Series switch provides two ports for management and one USB flash drive mount for file transfers.
NOTE: The output examples in this section are for reference only. Your output may vary.
Topics:
•RJ45 console port access
•MicroUSB Type-B console port access
•USB storage mount
RJ45 console port access
For the N3200-ON Series switch, the management ports are on the I/O-side of the switch.
N3208PX-ON management ports
8
1. Out-of-band management port (right), RJ45 console port (left)
N3224F-ON management ports
1. Out-of-band management port (right), RJ45 console port (left)
N3224P-ON, N3224T-ON and N3224PX-ON management ports
Management ports69
1. Out-of-band management port (right), RJ45 console port (left)
N3248P-ON, N3248PXE-ON N3248TE-ON, and N3248X-ON management ports
1. Out-of-band management port (right), RJ45 console port (left)
NOTE: Ensure that any equipment that is attached to the serial port can support the required 115200 baud rate.
NOTE: If the serial port of your computer cannot accept a female DB-9 connector, use a DB-9 to USB adapter.
NOTE: When connecting the RJ45 console to the patch panel or terminal server using Cat5e or Cat6 Ethernet cables, the
maximum cable length is 100 m. However, if the Ethernet cable is disconnected from the patch panel or terminal server but
connected to the RJ45 console, the maximum cable length is 6 m. If the cable is longer than 6 m when disconnected from
the panel or server, your switch may not boot.
1. Install the provided RJ45 connector-side of the provided cable into the switch console port.
2. Install the DB-9 female-side of the provided copper cable into the serial port of your computer.
Alternately, install the DB-9 cable into other data terminal equipment (DTE) server hardware.
3. Use the following settings to make the serial port connection:
● 115200 baud rate
● No parity
● Eight data bits
● One stop bit
● No flow control
MicroUSB Type-B console port access
The MicroUSB Type-B console port is on the I/O side of the switch.
The N3200-ON Series switches use the Silicon Labs CP2102 USB-B chip. To find the correct USB-B universal
NOTE:
asynchronous receiver-transmitter (UART) driver, see https://www.silabs.com/products/development-tools/software/
usb-to-uart-bridge-vcp-drivers.
When you connect the microUSB Type-B port, it becomes the primary connection and, while connected, all messages are sent
to the microUSB Type-B port.
70
Management ports
NOTE: Before starting this procedure, be sure that you have a terminal emulation program that is already installed on your
computer. If your computer requires non-Dell EMC drivers, and you have issues with your USB console port, contact Dell
EMC technical support for assistance.
1. Start up the computer.
2. Connect the USB Type-A end of cable into an available USB port on the computer.
3. Connect the microUSB Type-B end of cable into the microUSB Type-B console port on the switch.
4. Start up the switch.
5. Install the necessary USB device drivers.
6. Open your terminal software emulation program to access the switch.
7. Confirm that the terminal settings on your terminal software emulation program are as follows:
● 115200 baud rate
● No parity
● Eight data bits
● One stop bit
● No flow control
USB storage mount
USB storage does not automatically mount. USB storage supports the FAT file system. To use USB storage, first mount the
device using the following steps:
1. Start up the switch.
2. Press Enter on the ONIE rescue mode menu option from the ONIE Grub boot loader.
3. Create a mount directory for the USB storage.
ONIE:/ # mkdir /mnt/usb
4. View the fixed disks using the fdisk command.
ONIE:/mnt # fdisk -l
For internal storage
Disk /dev/sda: 15.8 GB, 15829303296 bytes
255 heads, 63 sectors/track, 1924 cylinders
Units = cylinders of 16065 * 512 = 8225280 bytes
Device Boot Start End Blocks Id System
/dev/sda1 1 1925 15458303+ ee EFI GPT
For USB storage
Disk /dev/sdb<number>: 30.9 GB, 30942946304 bytes
64 heads, 32 sectors/track, 29509 cylinders
Units = cylinders of 2048 * 512 = 1048576 bytes
Device Boot Start End Blocks Id System
5. Mount the device /dev/sdb<number> to the /mnt/usb directory.
ONIE:/ # mount -t vfat /dev/sdb<number> /mnt/usb
If the /mnt/usb directory is missing, the following message displays: mount: mounting /dev/
NOTE:
sdb<number> on /mnt/usb failed: No such file or directory.
NOTE: If the USB device is not seen, the following message displays: mount: mounting /dev/sdb<number>
on /mnt/usb failed: No such device or address.
Management ports71
Installation using ONIE
This section describes uninstalling an operating system and installing ONIE on your switch. For more information, see switchspecific information at www.dell.com/support.
NOTE: Before you install an operating system, ensure that the switch has the most current ONIE and firmware version. To
upgrade your switch, go to the Drivers and Downloads page for your switch at www.dell.com/support.
Topics:
•Before you install an operating system
•Check your switch
•Uninstall an existing OS
•Install a NOS
Before you install an operating system
After powering on the N3200-ON Series switch, it goes through a power-on self-test (POST).
POST runs every time that the switch is initialized and checks the hardware components to determine if the switch is fully
operational before booting. After POST, the switch uses the Grub bootloader.
To select an entry, use the up and down arrow keys. Press Enter to select an operating system or enter e to edit the
commands before booting. Enter c for a command line. The selected entry runs automatically in the operating system.
NOTE: To access ONIE, use the RJ45 or MicroUSB console port.
ONIE options
ONIE: Install OS
For downloading and installing an OS from a URL
Starts ONIE with ONIE Discovery Service
(factory default boot)
ONIE: Rescue
Starts ONIE without ONIE Discovery Service
Useful for running Diagnostics manually
ONIE: Uninstall OS
Restore to factory defaults erases any installed OS
ONIE: Update ONIE
72Installation using ONIE
For downloading and updating ONIE from a URL
ONIE: Embed ONIE
For downloading and updating ONIE from a URL and erases any installed OS
During the initial setup, the switch boots to ONIE Install. ONIE Install starts the discovery process. For more information, see
Installation using ONIE.
NOTE: For more information, see the Open Networking Hardware Diagnostic Guide for N2200-ON and N3200-ON
Switches at www.dell.com/support.
NOTE: After you have securely installed and powered on the N3200-ON Series switch, to configure your switch, see your
third-party ONIE-compatible operating system or the Dell EMC operating system documentation.
Check your switch
To confirm that ONIE is working properly, use the onie-sysinfo command at the ONIE prompt.
ONIE:/ # onie-sysinfo
x86_64-dellemc_<platform>_c3338-r0
ONIE:/ # onie-sysinfo -c
x86_64
ONIE:/ # onie-sysinfo -v
x.xx.x.x-x
ONIE:/ #
ONIE:/ # uname -a
Linux onie x.x.xx-onie+ #1 SMP Mon Jun 24 21:50:18 PDT 2019 x86_64
ONIE:/ # lspci
00:1f.5 Class 0c80: 8086:19e0
00:00.0 Class 0600: 8086:1980
00:12.0 Class 0880: 8086:19ac
00:15.0 Class 0c03: 8086:19d0
00:0b.0 Class 0604: 8086:19a6
00:18.0 Class 0780: 8086:19d3
00:09.0 Class 0604: 8086:19a4
00:14.0 Class 0106: 8086:19c2
00:1f.4 Class 0c05: 8086:19df
00:05.0 Class 0807: 8086:19a2
00:1f.2 Class 0580: 8086:19de
00:1c.0 Class 0805: 8086:19db
00:1f.0 Class 0601: 8086:19dc
02:00.0 Class 0200: 8086:1533
00:04.0 Class 0600: 8086:19a1
01:00.0 Class 0200: 14e4:b771 (NPU PCI detection)
ONIE:/ #
Uninstall an existing OS
CAUTION:
must first uninstall the existing OS. The ONIE: Uninstall OS option deletes the switch configuration and all
disk partitions.
To uninstall an existing NOS, boot up the switch. When the ONIE boot menu displays, use the arrow keys to scroll the asterisk
to select the ONIE: Uninstall OS option. This selection stops the switch from booting to the default setting of ONIE:
To install a networking operating system (NOS) on a switch that has a previously installed OS, you
Installation using ONIE
73
After the ONIE uninstall process completes, the switch boots to ONIE: Install OS mode.
Install a NOS
CAUTION: Installing a NOS using ONIE erases all software configurations on the switch. The configuration
settings are not recoverable. Back up all software configurations and installed licenses on the switch before
performing OS updates or changes. Store a regular backup of the switch configuration off the switch.
● Automatic installation—ONIE discovers network information including the Dynamic Host Configuration Protocol (DHCP)
server, connects to an image server, and downloads and installs an image automatically.
● Manual installation—Manually configure your network information if a DHCP server is not available or if you install the
NOS software image using USB media.
System setup
Before installation, verify that the system is connected correctly:
● Connect a serial cable and terminal emulator to the console serial port. The serial port settings are 115200 baud rate, 8 data
bits, and no parity.
● Connect the Management port to the network to download an image over a network. To locate the Console port and the
Management port, see the platform-specific Installation Guide at www.dell.com/support.
Install the NOS
For an ONIE-enabled switch, go to the ONIE boot menu. An ONIE-enabled switch boots with preloaded diagnostics (DIAGs) and
ONIE software.
● Install OS—Boots to the ONIE prompt and installs an NOS image using the Automatic Discovery process. When ONIE installs
a new OS image, the previously installed image and configuration are deleted.
● Rescue—Boots to the ONIE prompt and enables manual installation of an NOS image or ONIE update.
● Uninstall OS—Deletes the contents of all disk partitions, including the NOS configuration, except ONIE and diagnostics.
● Update ONIE—Installs a new ONIE version.
● Embed ONIE—Formats the disk and installs ONIE.
● EDA DIAG—Runs the system diagnostics.
After the ONIE process installs an NOS image and you later reboot the switch in ONIE: Install OS mode (default), ONIE
takes ownership of the system and remains in Install mode (ONIE Install mode is sticky) until an NOS image successfully installs
again. To boot the switch from ONIE for any reason other than installation, select the ONIE: Rescue or ONIE: UpdateONIE option from the ONIE boot menu.
CAUTION:
unsuccessful installation and if there is an existing OS on the device, select Uni nst all OS to clear the
partitions. If the problem persists, contact Dell EMC Technical Support.
During an automatic or manual NOS installation, if an error condition occurs that results in an
Automatic NOS installation
You can automatically install an NOS image on a Dell EMC ONIE-enabled device. This process is known as zero-touch install.
After the device boots to ONIE: Install OS, ONIE autodiscovery follows these steps to locate the installer file and uses the
first successful method:
1. Use a statically configured path that is passed from the boot loader.
2. Search file systems on locally attached devices, such as USB.
3. Search the exact URLs from a DHCPv4 server.
4. Search the inexact URLs based on the DHCP responses.
74
Installation using ONIE
5. Search IPv6 neighbors.
6. Start a TFTP waterfall.
The ONIE automatic discovery process locates the stored software image, downloads, and installs it, and reboots the device
with the new image. Autodiscovery repeats until a successful software image installation occurs and reboots the switch.
ONIE discovery — Usage information
● All ONIE autodiscovery methods download and run only supported default file names, such as onie-installer. The
required file names and search order are described on the Open Network Install Environment website at Image Discovery and
Execution. For more information, see the Open Networking Hardware Diagnostic Guide on the Dell EMC Support site.
● If you use a DHCPv4 server, ONIE autodiscovery obtains the hostname, domain name, Management interface IP address,
and the IP address of the domain name server (DNS) from the DHCP server and DHCP options. It also searches SCP, FTP,
or TFTP servers with the default DNS of the ONIE server. DHCP options are not used to provide the server IP.
● If you use a USB storage device, ONIE searches only FAT or EXT2 file systems for an NOS image.
Example: NOS automatic installation
1. On the TFTP server, rename the NOS image to a supported installer file name, such as onie-installer, using the mvimage-name default-filename command.
mv <NOS-image-name>.bin onie-installer
2. Boot up the switch in ONIE: Install mode to install an NOS image.
Starting: discover... done.
ONIE:/ # Info: eth0: Checking link... up.
Info: Trying DHCPv4 on interface: eth0
ONIE: Using DHCPv4 addr: eth0: xx.xx.xx.xx / xxx.x.x.x
Info: eth1: Checking link... down.
ONIE: eth1: link down. Skipping configuration.
ONIE: Failed to configure eth1 interface
ONIE: Starting ONIE Service Discovery
Info: Fetching tftp://xx.xx.xx.x/onie-installer-x86_64-dellemc_<platform>_c2338 ...
Info: Fetching tftp://xx.xx.xx.x/onie-installer-dellemc_<platform>_c2338 ...
Info: Fetching tftp://xx.xx.xx.x/onie-installer-x86_64-bcm ...
Info: Fetching tftp://xx.xx.xx.x/onie-installer-x86_64 ...
Info: Fetching tftp://xx.xx.xx.x/onie-installer ...
ONIE: Executing installer: tftp://xx.xx.xx.x/onie-installer
...
...
...
Press <DEL> or <F2> to enter setup.
Welcome to GRUB!
Manual NOS installation
If you do not use the ONIE-based automatic installation of a NOS image and if a DHCP server is not available, you can manually
install the image. Configure the Management port and provide the software image file to start the installation.
1. Save the NOS software image on an SCP/TFTP/FTP server.
2. Power up the switch and select ONIE Rescue for manual installation.
3. (optional) Stop DHCP discovery if you were not able to select ONIE Rescue mode.
$ onie-discovery-stop
4. Configure the IP addresses on the Management port, where x.x.x.x represents your internal IP address. After you configure
the Management port, the response is up.
$ ifconfig eth0 x.x.x.x netmask xxx.xxx.x.x up
5. Install the software on the device. The installation command accesses the NOS from the specified SCP, TFTP, or FTP URL,
creates partitions, verifies installation, and reboots itself.
$ onie-nos-install image_url
For example, enter
ONIE:/ # onie-nos-install ftp://a.b.c.d/
<NOS-image_name>
.bin
Installation using ONIE
75
Where a.b.c.d represents the location to download the image file from, and x.x.xx represents the version number of the
software to install.
The NOS installer image may create multiple partitions during the installation process. After the installation process completes,
the switch automatically reboots into the new OS.
Install manually using a USB drive You can manually install the NOS software image using a USB device. Verify that the
USB device supports a FAT or EXT2 file system. For instructions to format a USB device in FAT or EXT2 format, see the
accompanying Windows documentation for FAT formatting or Linux documentation for FAT or EXT2 formatting.
1. Plug the USB storage device into the USB storage port on the switch.
2. Power up the switch to automatically boot using the ONIE: Rescue option.
3. (Optional) Stop ONIE discovery if the device boots to ONIE: Install.
$ onie-discovery-stop
4. Create a USB mount location on the system.
$ mkdir /mnt/media
5. Identify the path to the USB drive.
$ fdisk -l
6. Mount the USB media plugged in the USB port on the device.
$ mount -t vfat usb-drive-path /mnt/media
7. Install the software from the USB, where /mnt/media specifies the path where the USB partition is mounted.
$ onie-nos-install /mnt/media/image_file
The ONIE autodiscovery process discovers the image file at the specified USB path, loads the software image, and reboots the
switch. For more information, see the ONIE User Guide.
76
Installation using ONIE
Specifications
This section lists the N3200-ON Series switch specifications.
CAUTION: Operate the product at an ambient temperature not higher than 45°C (113°F).
NOTE: For RoHS information, see Restricted Material Compliance.
Topics:
•Chassis physical design
•PoE Budget Specifications
•IEEE standards
•Agency compliance
•Safety standards and compliance agency certifications
•Electromagnetic compatibility
Product recycling and disposal
•
Chassis physical design
10
Table 12. Chassis physical design
ParameterSpecifications
Height x Width x Depth, excluding the PSU and fan tray
handles
Chassis weight with factory-installed components
● N3208PX-ON:
○ 43.5 mm x 279.4 mm x 312 mm
○ 1.71 in x 11 in x 12.28 in (H x W x D)
NOTE: The N3208PX-ON can use one or two external
power adapters (EPAs). To install two EPAs, you must
have 2RU rack space. Install the two EPAs above the
switch in the rack.
● All other N3200-ON Series switches:
○ 43.5 mm x 434 mm x 400 mm (H x W x D)
○ 1.71 in x 17.09 in x 15.75 in (H x W x D)
Table 14. Power consumption parameters (continued)
ParameterSpecifications
PSU configurationMain PSU
Maximum steady current consumption
PoE output per port
● 7 A@110 VAC
● 3.5 A@220 VAC
● N3208PX-ON: 4x1G Base-T Ports with 4 ports of 802.3bt
Type-4 (90W) PoE, + 4x5GBase-T Ports with 4 ports of
802.3bt Type-4 (90W) PoE
● N3224P-ON: 24x1G Base-T Ports with 802.3at Type-2
(30W) PoE
● N3224PX-ON: 24x10GBase-T Ports with 802.3bt Type-4
(90W) PoE
● N3248P-ON: 48x1G Base-T Ports with 802.3at Type-2
(30W) PoE
● N3248PXE-ON: 48x10GBase-T Ports with 802.3bt Type-4
(90W) PoE
NOTE: 802.3bt Type-4 can support a minimum of 90 W
and a maximum of 99.99 W at PSE output.
Table 15. AC power requirements
ParameterSpecifications
Power supply
● N3208PX-ON: 100–240 VAC 50/60 Hz
● N3224T-ON: 100–240 VAC 50/60 Hz
● N3224F-ON: 100–240 VAC 50/60 Hz
● N3224P-ON: 100–240 VAC 50/60 Hz
● N3224PX-ON: 100–240 VAC 50/60 Hz
● N3248TE-ON: 100–240 VAC 50/60 Hz
● N3248P-ON: 100–240 VAC 50/60 Hz
● N3248X-ON: 100–240 VAC 50/60 Hz
● N3248PXE-ON: 100–240 VAC 50/60 Hz
Maximum current draw per system
Maximum power consumption without PoE
● N3208PX-ON: 7A@110VAC and 3.5A@220VAC
● N3224T-ON: 7A@110VAC and 3.5A@220VAC
● N3224F-ON: 7A@110VAC and 3.5A@220VAC
● N3224P-ON: 7A@110VAC and 3.5A@220VAC
● N3224PX-ON: 17A@110VAC and 3.5A@220VAC
● N3248TE-ON: 7A@110VAC and 3.5A@220VAC
● N3248P-ON: 7A@110VAC and 3.5A@220VAC
● N3248X-ON: 7A@110VAC and 3.5A@220VAC
● N3248PXE-ON: 7A@110VAC and 3.5A@220VAC
● N3208PX-ON: 107 W @ 54 VDC
● N3224T-ON: 201 W @ 54 VDC
● N3224F-ON: 224 W @ 54 VDC
● N3224P-ON: 224 W @ 54 VDC
● N3224PX-ON: 340 W @ 54 VDC
● N3248TE-ON: 212 W @ 54 VDC
● N3248P-ON: 237 W @ 54 VDC
● N3248X-ON: 480 W @ 54 VDC
● N3248PXE-ON: 554 W @ 54 VDC
Table 16. DC power requirements
ParameterSpecifications
Minimum and maximum input voltage–40 VDC to -60 VDC
Specifications79
Table 16. DC power requirements (continued)
ParameterSpecifications
NOTE: For more information, see Power supplies.
Maximum current at full load with fan without PoE550W DC PSU:
● N3224T-ON: 11.5 A @ 48 V
● N3224F-ON: 11.5 A @ 48 V
● N3248TE-ON: 11.5 A @ 48 V
● N3248X-ON: 11.5 A @ 48 V
1300W DC PSU:
● N3224P-ON: 28 A @ 48 V
● N3248P-ON: 28 A @ 48 V
● N3224PX-ON: 28 A @ 48 V
● N3248PXE-ON: 28 A @ 48 V
PoE Budget Specifications
The following details the PoE budget specifications for high-line and low-line AC inputs and general guidelines about how to
derive the available PoE budgets based on the PSUs you use.
PoE load condition—high-line AC input
N3208PX-ON Max PoE power:
● One internal PSU: 193 W
● One internal PSU + one external power adapter: 493 W
● One internal PSU + two external power adapters: 793 W
N3224P-ON Max PoE power:
● One internal PSU: Can meet 720 W
Max PoE power shall be no more than 720 W for 24 ports x 30 W per port.
N3224PX-ON Max PoE power:
● One internal PSU: 1260 W
● Two internal PSUs: can meet 2400 W
● One internal PSU + at least 1 x 2000 W or 2 x 1050 W in MPS-3S shelf: can meet 2400 W
+ MPS-3S PSU(s) power) * 0.85 - N3224PX-ON maximum system power consumption > 2400 W]
Max PoE power shall be no more than 2400 W for 24 ports x 99.99 W per port.
(1)
The maximum PoE power reduces if you connect the MPS-3S shelf to more than one PoE switch.
N3248P-ON Max PoE power:
●
One internal PSU: 813 W
● Two internal PSUs: Can meet 1440 W
● One internal PSU + any 1 PSU in MPS-3S shelf: can meet 1440 W
power) * 0.85 - N3248P-ON maximum system power consumption > 1440 W]
Max PoE power shall be no more than 1440 W for 48 ports x 30 W per port.
(1)
The maximum PoE power reduces if you connect the MPS-3S shelf to more than one PoE switch.
N3248PXE-ON Max PoE power:
● One internal PSU: 1056 W
● Two internal PSUs: 2496 W
● Two internal PSUs + 1 x 2000 W PSU in MPS-1S shelf: 3663 W
● One internal PSU + at least 3 x 1600 W PSUs in MPS-3S shelf: can meet 4800 W
MPS-3S PSU(s) power) * 0.85 - N3248PXE-ON maximum system power consumption > 4800 W]
● Two internal PSUs + at least 2 x 1600 W PSUs in MPS-3S shelf: can meet 4800 W
MPS-3S PSU(s) power) * 0.85 - N3248PXE-ON maximum system power consumption > 4800 W]
Max PoE power shall be no more than 4800 W for 48 ports x 99.99 W per port.
(1)
[Note: (One internal PSU power + MPS-3S PSU(s)
(1)
(1)
[Note: (One internal PSU power +
(1)
[Note: (Two internal PSUs power +
[Note: One internal PSU power
80
Specifications
(1)
The maximum PoE power reduces if you connect the MPS-3S shelf to more than one PoE switch.
PoE load condition—low-line AC input
N3208PX-ON Max PoE power:
● One internal PSU: 193 W
● One internal PSU + one external power adapter: 493 W
● One internal PSU + two external power adapters: 793 W
N3224P-ON Max PoE power:
● One internal PSU: can meet 720 W
Max PoE power shall be no more than 720 W for 24 ports x 30 W per port.
N3224PX-ON Max PoE power:
● One internal PSU: 610 W
● Two internal PSUs: 1465 W
● Two internal PSUs + any PSU in MPS-1S shelf: 2082 W
● Two internal PSUs + any two PSUs in MPS-3S shelf: can meet 2400 W
PSU(s) power) * 0.85 - N3224PX-ON maximum system power consumption > 2400 W]
● One internal PSU + any three PSUs in MPS-3S shelf: can meet 2400 W
power) * 0.85 - N3224PX-ON maximum system power consumption > 2400 W]
Max PoE power shall be no more than 2400 W for 24 ports x 99.99 W per port.
(1)
The maximum PoE power reduces if you connect the MPS-3S shelf to more than one PoE switch.
N3248P-ON Max PoE power:
● One internal PSU: 713 W
● Two internal PSUs: Can meet 1440 W
● One internal PSU + any two PSUs in MPS-3S shelf: can meet 1440 W
power) * 0.85 - N3248P-ON maximum system power consumption > 1440 W]
Max PoE power shall be no more than 1440 W for 48 ports x 30 W per port.
(1)
The maximum PoE power reduces if you connect the MPS-3S shelf to more than one PoE switch.
N3248PXE-ON Max PoE power:
● One internal PSU: 406 W
● Two internal PSUs: 1261 W
● Two internal PSUs + any PSU in MPS-1S shelf: 1878 W
● One internal PSU + any three PSUs in MPS-3S shelf: 2686 W
● Two internal PSus + any three PSUs in MPS-3S shelf: 3493 W
(1)
(1)
Max PoE power shall be no more than 4800 W for 48 ports x 99.99 W per port.
(1)
The maximum PoE power reduces if you connect the MPS-3S shelf to more than one PoE switch.
(1)
[Note: (Two internal PSUs power + MPS-3S
(1)
[Note: (One internal PSU power + MPS-3S PSU(s)
(1 )
[Note: (One internal PSU power + MPS-3S PSU(s)
General guidelines on PoE budget calculations
PoE budget for the N3224P-ON, N3224PX-ON, N3248P-ON, and N3248PXE-ON switches
● One internal PSU: PSU1 power output - maximum system power consumption
● Two internal PSUs: PSU1 power output + PSU2 power output * 0.9 - maximum system power consumption
● One internal PSU + MPS-1S shelf: (PSU1 power output + MPS-1S PSU power output) * 0.85 - maximum system power
consumption
● Two internal PSUs + MPS-1S shelf: (PSU1 power output + PSU2 power output + MPS-1S PSU power output) * 0.85 maximum system power consumption
● One internal PSU + MPS-3S shelf: (PSU1 power output + MPS-3S PSU(s) power output) * 0.85 - maximum system power
consumption
● Two internal PSUs + MPS-3S shelf: (PSU1 power output + PSU2 power output + MPS-3S PSU(s) power output) * 0.85 maximum system power consumption
PoE budget for the N3208PX-ON switch
● Internal PSU only: Internal PSU power output - maximum system power consumption
● Internal PSU + one external power adapter: Internal PSU power output + one external power adapter power output -
maximum system power consumption
Specifications
81
● Internal PSU + two external power adapters: Internal PSU power output + two external power adapters power output maximum system power consumption
IEEE standards
The N3200-ON Series switch complies with the following IEEE standards.
The N3200-ON Series switch is designed to comply with the following safety and agency requirements:
India
This product conforms to the relevant Essential Requirements of the Telecommunication Engineering Centre (TEC) regulations.
USA Federal Communications Commission statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC
rules. These limits are designated to provide reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and
used in accordance to the instructions, it may cause harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference, in which case users will be required to take whatever measures
necessary to correct the interference at their own expense.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. Dell EMC is not
responsible for any radio or television interference caused by using other than recommended cables and connectors or by
unauthorized changes or modifications in the equipment. Unauthorized changes or modification could void the user’s authority
to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may cause
undesired operation.
Figure 6. Canadian Department of Communication Statement
82
Specifications
European Union EMC directive conformance statement
This product is in conformity with the protection requirements of EU Council Directive 2004/108/EC on the approximation of
the laws of the Member States relating to electromagnetic compatibility. Dell EMC cannot accept responsibility for any failure
to satisfy the protection requirements resulting from a non-recommended modification of this product, including the fitting of
non-Dell EMC option cards.
This product has been tested and found to comply with the limits for Class A Information Technology Equipment according
to CISPR 32/CISPR34 and EN55032 / EN55034. The limits for Class A equipment were derived for commercial and industrial
environments to provide reasonable protection against interference with licensed communication equipment.
NOTE: This is a Class A product. In a domestic environment, this device may cause radio interference, in which case, you
may be required to take adequate measures.
European Community Contact
Dell EMC, EMEA - Central
Dahlienweg 19
66265 Heusweiler
Germany
Tel: +49 172 6802630
Email: EMEA Central Sales
Japan VCCI compliance for class A equipment
Figure 7. Japan: VCCI compliance for class A equipment
This is Class A product based on the standard of the Voluntary Control Council For Interference by Information Technology
Equipment (VCCI). If this equipment is used in a domestic environment, radio disturbance may arise. When such trouble occurs,
the user may be required to take corrective actions.
NOTE:
Use the AC power cords with Dell EMC equipment only. Do not use Dell EMC AC power cords with any
unauthorized hardware.
Figure 8. Japan: warning label
Specifications
83
Korean certification of compliance
Figure 9. Korean certification of compliance
Figure 10. Korean package label
Safety standards and compliance agency
certifications
● CUS UL 60950-1, 2nd Edition
○ Meets or exceeds Hi Pot and Ground Continuity testing per UL 60950-1.
● CSA 60950-1-03, 2nd Edition
● EN 60950-1, 2nd Edition
● EN 60825-1, 1st Edition
● EN 60825-1 Safety of Laser Products—Part 1: Equipment Classification Requirements and User’s Guide
● EN 60825-2 Safety of Laser Products—Part 2: Safety of Optical Fibre Communication Systems
● FDA Regulation 21CFR 1040.10 and 1040.11
● IEC 60950-1, 2nd Ed, including all National Deviations and Group Differences
● IEC 62368-1
Electromagnetic compatibility
Emissions
● International: CISPR32: Class A
● Australia/New Zealand: AS/NZS CISPR 32: Class A
84
Specifications
● Canada: ICES-003, Issue-4, Class A
● Europe: EN55032: CISPR 32: Class A
● International: CISPR 32: Class A
● EN55032
● Japan: VCCI V-3/2011.04, Class A
● Korea: KN32, Class A
● Taiwan: CNS13438, Class A
● USA: FCC CFR47 Part 15, Subpart B, Class A
Immunity
● EN 300 386 v2.1.1 (2016-07) EMC for Network Equipment
● EN 55024 + A1 + A2
● EN 61000-3-2 Harmonic Current Emissions
● EN 61000-3-3 Voltage Fluctuations and Flicker
● EN 61000-4-2 ESD
● EN 61000-4-3 Radiated Immunity
● EN 61000-4-4 EFT
● EN 61000-4-5 Surge
● EN 61000-4-6 Low Frequency Conducted Immunity
● EN 61000-6-1
● EN 61000-4-11 Voltage Dips/Interruptions
Product recycling and disposal
You must recycle or discard this switch according to applicable local and national regulations. Dell EMC encourages owners of
information technology (IT) equipment to responsibly recycle their equipment when it is no longer needed. Dell EMC offers a
variety of product return programs and services in several countries to assist equipment owners in recycling their IT products.
Waste electrical and electronic equipment (WEEE) directive for recovery,
recycle and reuse of IT and telecommunications products
Dell EMC switches are labeled in accordance with European Directive 2002/96/EC concerning waste electrical and electronic
equipment (WEEE). The Directive determines the framework for the return and recycling of used appliances as applicable
throughout the European Union. This label is applied to various products to indicate that the product is not to be thrown away,
but rather reclaimed upon end of life per this Directive.
Figure 11. The European WEEE symbol
In accordance with the European WEEE Directive, electrical and electronic equipment (EEE) is to be collected separately and to
be reused, recycled, or recovered at end of life. Users of EEE with the WEEE marking per Annex IV of the WEEE Directive, as
shown above, must not dispose of end of life EEE as unsorted municipal waste, but use the collection framework available to
customers for the return, recycling and recovery of WEEE. Customer participation is important to minimize any potential effects
of EEE on the environment and human health due to the potential presence of hazardous substances in EEE.
Dell EMC products, which fall within the scope of the WEEE, are labeled with the crossed-out wheelie-bin symbol, as shown
above, as required by WEEE.
For information on Dell EMC product recycling offerings, see the WEEE Recycling instructions on Support. For more
information, contact the Dell EMC Technical Assistance Center.
Specifications
85
11
Dell EMC support
The Dell EMC support site provides documents and tools to help you use Dell EMC equipment and mitigate network outages.
Through the support site you can obtain technical information, access software upgrades and patches, download available
management software, and manage your open cases. The Dell EMC support site provides integrated, secure access to these
services.
To access the Dell EMC support site, go to www.dell.com/support/. To display information in your language, scroll down to the
bottom of the web page and select your country from the drop-down menu.
● To obtain product-specific information, enter the 7-character Service Tag or 11-digit express service code of your switch,
which is found on the pull-out tag, also known as a luggage tag, and click Submit.
● To receive more technical support, click Contact Us. On the Contact Information web page, click Technical Support. To
find the service tag number, from the ONIE prompt, use the onie-syseeprom command.
ONIE:/ # onie-syseeprom
TlvInfo Header:
Id String: TlvInfo
Version: 1
Total Length: 184
TLV Name Code Len Value
-------------------- ---- --- ----Product Name 0x21 11 <platform>
Part Number 0x22 6 xxxxxx
Serial Number 0x23 20 xxxxxxxxxxxxxxxx
Base MAC Address 0x24 6 D8:9E:F3:AC:A5:A0
Manufacture Date 0x25 19 02/21/2018 08:05:01
Device Version 0x26 1 1
Label Revision 0x27 3 A00
MAC Addresses 0x2A 2 256
Manufacturer 0x2B 5 CES00
Country Code 0x2C 2 CN
Vendor Name 0x2D 8 Dell EMC
Service Tag 0x2F 7 xxxxxxx
Vendor Extension 0xFD 4 0x00 0x00 0x02 0xA2
Platform Name 0x28 32 x86_64-dellemc_<platform>_c2538-r0
ONIE Version 0x29 10 x.xx.x.x-x
Diag Version 0x2E 10 x.xx.x.x-x
CRC-32 0xFE 4 0x17E6ED32
Checksum is valid.
ONIE:/ #
To access switch documentation, go to www.dell.com/manuals/ and enter your switch type.
To search for drivers and downloads, go to the Drivers & Downloads tab for your switch.
To participate in Dell EMC community blogs and forums, go to www.dell.com/community.
86Dell EMC support
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.