Datasheet FWP-50A22FA Specification

Page 1
Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional
Dimensions - mm (inches)
Specifications Description: Ferrule style high
speed fuses with and without indicating striker.
Dimensions: See dimensions illustration.
Ratings:
Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 20-100A
IR: — 200kA RMS Sym.
— 50kA @ 500Vdc
Agency Information: CE, UL Recognition Electrical Characteristics Total Clearing I
2
t
The total clearing I
2
t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I
2
t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Catalog Numbers
Electrical Characteristics
Rated I2t (A2Sec) Catalog Current Minimum Clearing At Watts Numbers Size RMS-Amps Melting Rated Voltage Loss
Without Striker FWP-20A22Fa 20 19.0 260 5 FWP-25A22Fa 25 34.0 410 6 FWP-32A22Fa 22 x 58mm 32 53.5 605 8 FWP-40A22Fa (
7
8" x 29⁄32") 40 68 750 9 FWP-50A22Fa 50 135 1600 9.5 FWP-63A22Fa 63 280 3080 11 FWP-80A22Fa 80 600 6600 13.5 FWP-100A22Fa 100* 1100 12500 16 With Striker FWP-20A22FI 20 19.0 260 5 FWP-25A22FI 25 34.0 410 6 FWP-32A22FI 22 x 58mm 32 53.5 605 8 FWP-40A22FI (
7
8" x 29⁄32") 40 68 750 9 FWP-50A22FI 50 135 1600 9.5 FWP-63A22FI 63 280 3080 11 FWP-80A22FI 80 600 6600 13.5 FWP-100A22FI 100* 1100 12500 16
*IEC/UL Voltage rating 690/700
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (I
2
t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
K
1.4
1.2
1.0
0.6
0.8
0.7
0.9
0.5
0.4
0.3 200 300 400 500 600 700
E
g
U
L
1.4
1.2
10
3
6
8 7
9
5
4
3
200 300 400 500 600 700
E
g
Kp
1.0
0.8
0.4
0.5
0.6
0.3
0.2
0.1 30 40 50 60
70
80 90 100%
I
b
Data Sheet: 720026
58.0
(2.283")
15.0
(0.591")
22.2
(0.875")
With Striker
Without Striker
FWP with
striker
option.
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
209
High Speed
Fuses
High Speed Fuses
5
(0.197")
66 (2.598")
58 (2.283")
16 (0.630"
22.2 (0.874")
Page 2
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
210
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 20-100A, Striker Optional
10
4
Prospective Short-Circuit Current Symmetrical RMS
Peak Let-Through Current
2
6
4
2
6
4
246 246 246
10
2
10
3
10
2
10
3
10
4
10
5
FWP-20A22F
FWP-25A22F
FWP-32A22F
FWP-40A22F
FWP-50A22F
FWP-63A22F
FWP-80A22F
FWP-100A22F
2
Peak Let-Through Curve
Without Striker FWP 20-100A: 660V/700V (22 x 58mm)
Time-Current Curve
Data Sheet: 35785291
4
10
6 4
2
3
10
6 4
2
2
10
6 4
2
1
10
6 4
FWP-20A22F
2
FWP-25A22F
0
FWP-32A22F
10
FWP-40A22F
6 4
2
–1
10
Virtual Pre-Arcing Time In Seconds
6 4
2
–2
10
6 4
2
–3
10
6 4
2
–4
10
1
10
22468 2
2
10
Prospective Current In Amps RMS
FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F
2468
3
10