Datasheet EM4-DIN Datasheet (YZ)

Page 1
1
Product description
Three-phase energy meter with built-in configuration key-pad; particularly indicat­ed for the metering and the management of the energy in addition to the metering and the management of the signals coming from the water and gas meters. Housing for DIN-rail or wall­mounting, IP40 (front) pro­tection degree. Completely sealable housing. In case of direct connection up to 90A, the measuring
input terminals are suitable for cables with a cross-sec­tion area from 6 to 35 mm
2
. The special design of the instrument’s housing allows to add at any time the inter­face modules, even when the instrument is already installed. The following mod­ules are available:
- for all versions: pulse output;
- only for the versions with
auxiliary power supply: digital inputs, RS485 serial port.
Energy Management Three-phase energy meter with output modules Type EM4-DIN
Type selection
Power supply
For all versions A: 24VAC
-15+10%, 50-60Hz
B: 48VAC
-15+10%, 50-60Hz
C: 115VAC
-15+10%, 50-60Hz
D: 230VAC
-15+10%, 50-60Hz
4: 18 to 60VDC 5: 77 to 143VDC AV2, AV8 and AV9
only
X: Self Power Supply
400V
L-L
(-20+15%, 50-60Hz) 208V
L-L
(-20+15%, 50-60Hz) 220V
L-L
(-10+15%, 50-60Hz)
Range Code
Auxiliary Power Supply: AV0: 208V
L-L
/20(90)AAC [3]
AV1: 400V
L-L
/20(90)AAC [1]
AV3: 660V
L-L
/20(90)AAC [2]
AV4: 208V
L-L
/5(10)AAC [3]
AV5: 400V
L-L
/5(10)AAC [1]
AV6: 100V
L-L
/5(10)AAC [3]
AV7: 660V
L-L
/5(10)AAC [2]
Self Power Supply: AV2: 220V
L-L
/20(90)AAC [4]
AV8: 208V
L-L
/20(90)AAC [1]
AV9: 400V
L-L
/20(90)AAC [1]
Slot A (retransmission)
X:
None
O:
AO2900 module Dual open collector out­put. Three operating modes:
two pulse outputs
(kWh and kvarh);
one alarm output
(kW dmd)
and one pulse output (kWh or kvarh)
one output
remotely controlled by a serial port and one pulse output
(kWh or kvarh)
D: AQ2940 module
Two digital inputs for the management of water and gas meters
Slot A (retransmission) cont.
R:
AO2910 module. One relay output + one open collector output. Operation modes like module AO2900
Slot B (retransmission)
Only with A-B-C-D-4 power supply
XX:
None
S0: AR2950 module
RS422/485 serial port
Model Range code System Power supply Slot A Slot B
How to order
EM4-DIN AV5 3 X X XX
System
3 : Three-phase,
unbalanced load with or without neutral
[1] Un: -20+15% [2] Un: -30+15% [3] Un: -20+20% [4] Un: -10 +15%
Class 1 (active energy)
Class 2 (reactive energy)
Three-phase multi-function energy meter
Back-lighted LCD display
3
1
/2DGT instantaneous variables read-out
8 DGT + 7
1
/2DGT energy read-out
Measurements of system and phase variables:
W, Wdmd
Measurements of total energies: kWh, kvarh
Measurements of partial energies: kWh, kvarh
Energy measurements according to EN61036 and EN61268
Energy measurements by time periods (t1-t2-t3-t4)
selectable by input contacts
Measurements of m3H2O and m3GAS by means of input contacts
TRMS measurements of distorted wave forms
(voltages/currents)
Two basic models: direct connection 20(90)AAC,
CT 5(10)AAC and VT connection
Self power supply (available for some models only) or
auxiliary power supply: 24V, 48V, 115V, 230V, 50-60Hz; 18 to 60VDC, 77 to 143VDC
Degree of protection (front): IP 40
Front dimensions: 9 DIN modules
RS 422/485 Serial port by means of optional module
Dual pulse output by means of optional module
Alarm output (kW dmd) by means of optional module
Digital inputs for the management of the time periods
and of the
H2O and GAS meters
Important note:
The models from AV0 to AV7 can be equipped with any
type of available modules (slot A and B).
The models AV8 and AV9 can be equipped only with the
“O” and “R” type modules.
The AV8 and AV9 models can measure all the parameters
even if the three phase system being connected is missing one phase.
The AV2 model is suitable only for three-phase unbalanced
system without neutral.
Page 2
2
EM4-DIN
2000 V
RMS
output to
supply input
Digital outputs (on request)
AO2900 module To be used as energy
retransmission, water and gas, remote static outputs and alarm. Three working modes are selectable:
two pulse outputs
(kWh and kvarh);
one alarm output (kW
dmd) and one pulse output
(kWh or kvarh);
one output remotely con-
trolled by means of the serial port and one pulse output
(kWh or kvarh) Pulse outputs Number of outputs 2 Number of pulses
From 0.01 to 100 pulses programmable according to the selected CT and VT ratios
Output type
Open collector (NPN transistor ) VON1.2 VDC / max. 100 mA
RS422/RS485 (on request) AR2950 module
Type Multidrop
bidirectional (static and dynamic variables)
Connections 2 or 4 wires, max. distance
1200m, termination directly
on the module Addresses 255, selectable by key-pad Protocol MODBUS/JBUS Data (bidirectional)
Dynamic (reading only)
Phase and system variables:
see table “Display pages”
Static (writing only ) All the programming data,
reset of energy, activation of
static output.
Stored energy (EEPROM)
max. 99.999.999 kWh/kvarh Data format 1 start bit, 8 data bit,
no parity, 1 stop bit Baud-rate 9600 bit/s Insulation By means of optocouplers,
2000 V
RMS
output
to measuring inputs
Number of inputs
Current 3 Voltage 4
Accuracy
(display, RS485)
Ib: 5A, Imax: 10A Ib: 20A, Imax:90A Un: see “Range code” on previous page
Current from 0.003Ib to 0.2Ib:
±(0.5%RDG +3DGT) from 0.2Ib to Imax: ±(0.5%RDG +1DGT)
Voltage in the range Un:
±(0,5% RDG + 1DGT)
Frequency ±0.1% RDG (50 to 60 Hz) Active power
(@ 25°C ± 5°C, R.H. 90%) ±(1% RDG +1DGT). PF 1,
0.1Ib to Imax, in the Un range; PF 0.5L, PF 0.8C, 0.2Ib to Imax, in the Un range
Energies
(@ 25°C ± 5°C, R.H. 90%) Class 1 acc. to
EN61036 Class 2 acc. to EN61268 Ib: 5A, Imax: 10A
0.1Ib: 500mA, Start up current: 20mA Un: see table “range code” Ib: 20A, Imax: 90A
0.1Ib: 2A, Start up current: 80mA Un: see table “range code”
Additional errors
Acc. to EN61036, EN61268
Wave form <1% (3rdharmonic: 10%) Voltage asymmetry < 0.5% (referred to Un) Magnetic induction 0 (up to 0.5 mT) HF Electromagnetic fields < 1% Operation of accessories 0
Temperature drift 200ppm/°C Sampling rate 1000 samplings/s @ 50Hz Display
Type Back-lighted LCD Instantan. variables read-out 3
1
/2DGT
Energies Total: 8 DGT + 7
1
/2DGT;
Partial: 8 DGT + 71/2DGT;
Max. and Min. indication
Max. 1999 (99999999), Min. 0
Measurements Power, energy.
TRMS measurements of distorted wave forms.
Coupling type Direct
Crest factor
Ib 5A 3 (15A max. peak) Ib 20A 6 (127A max. peak)
Current overload
5(10) A, for 10ms 300A max, @ 50Hz 5(10) A, for 500ms 200A max, @ 50Hz 5(10) A, permanent 10A, @ 50Hz 20(90) A, for 10ms 2700A max, @ 50Hz 20(90) A, permanent 90A, @ 50Hz
Voltage overload
Permanent 1.2 Un For 1s 2 Un
Input impedance
400V
L-L
(AV1-AV5-AV9) > 720KΩ
208V
L-L
(AV0-AV4-AV8-AV2) > 720K
660V
L-L
(AV3-AV7) > 1.97M
100V
L-L
(AV6) > 400K
5(10) A (AV4-AV5-AV6-AV7) < 0.3VA 20(90) A (AV0-AV1-AV3-AV8-AV9) < 4VA 20(90) A (AV2) < 4VA
Frequency 50 to 60 Hz
Interface module specifications
Input specifications
Page 3
3
EM4-DIN
V
OFF
30 VDC max.
Pulse duration
220 ms (ON), 220 ms (OFF) According to DIN43864
Alarm output
Number of outputs 1 Alarm type Up alarm, down alarm.
Setpoint adjustment 0 to 100% of the electrical
scale
Hysteresis 0 to 100% of the electrical
scale On-time delay 0 to 255 seconds Response time 700 ms Output type
Open collector (transistor NPN)
VON1.2 VDC / max. 100 mA
V
OFF
30 VDC max.
Insulation By means of optocouplers,
2000 V
RMS
outputs to measuring inputs, 2000 V
RMS
output to supply input. Insulation between the two outputs: functional
AO2910 module Relay + open collector
output. Working mode like AO2900.
Pulse output One static output+one relay
output, other characteristics like AO2900.
Alarm output Only relay output, other
characteristics like AO2900.
Output type Static type like module
AO2900; Relay type: SPDT, AC1, AC15: 1AAC @250VAC
Insulation 2000 V
RMS
outputs to measuring inputs, 2000 V
RMS
output to
supply input. Insulation between the two outputs: 2000 V
RMS
Digital inputs (on request) AQ2940 module
Four working modes are selectable:
total and partial energy
meters (kWh and kvarh) without the use of digital inputs
total and partial energy
meters (kWh and kvarh) managed by time periods (t
1-t2-t3-t4
);
total energy meters
(kWh, kvarh) and total “day-time/night” GAS meter;
total energy meters
(kWh, kvarh), GAS and WATER meters;
Number of inputs 2
Input frequency 20Hz max. Duty cycle 50% Prescaler adjustment from 0,1 to 100,0 m
3
/ pulse
Contact measur. voltage 12V < +Aux < 24VDC
Logic status: OFF < 2V, ON > 10V
Contact measur. current 15mA max Input impedance 1k Contact resistance 1k, close contact
100k, open contact
Insulation By means of optocouplers,
2000 V
RMS
digital inputs to measuring inputs, 2000 V
RMS
digital inputs to supply input.
Interface module specifications (cont.)
to 5A)
Display
Variables Up to 4 variables per page
Page 1: k
Wh-kvarh
Page 2a:
k Wh
(t1-t2-t3-t4)
k varh
(t1-t2-t3-t4)
Page 2b:
GAS m3day-time tariff,
GAS m3night tariff
Page 2c:
H2O m3, GAS m
3
Page 3: W
L1
Page 4: W
L2
Page 5: W
L3
Page 6: W
dmd
Errors
Phase sequence, serial communication status, wrong connection of current measuring inputs.
Password Numeric code of max.
3 digits 2 protection levels of the programming data
1
st
level Password “0”, no protection
2
nd
level Password from 1 to 1000,
all data are protected
Transformer ratio
CT 1 to 5000 VT 1.0 to 199.9 and 200 to 1999
Note:
The CT ratio * VT ratio
must
never exceed the value 5000. The current measuring inputs can manage CT’s with a secondary of 1A and 5A (accuracy always refers
Software functions
Self supplied version 400V
L-L
(-20% +15%, 50-60Hz) 208V
L-L
(-20% +15% , 50-60Hz) 220V
L-L
(-10+15%, 50-60Hz)
Auxiliary power supply 230VAC -15 +10%, 50-60Hz
115VAC -15 +10%, 50-60Hz 48VAC; -15 +10%, 50-60Hz 24VAC; -15 +10%, 50-60Hz 18 to 60VDC; 77 to 143VDC
Energy consumption ≤ 7VA
Supply specifications
Page 4
4
EM4-DIN
Variables that can be displayed No 1stvariable 2ndvariable Notes
1 kWh kvarh 2a kWh (t1or t1-t2-t3-t4) kvarh (t1or t1-t2-t3-t4) Depending on the type of selection you have chosen. 2b Day-time GAS m
3
Night GAS m
3
For the energy it is possible to choose the following operating mode:
2c H2O m
3
GAS m
3
t1 partial meters or t1-t2-t3-t4multitariff selection
3W
L1
4W
L2
5W
L3
6W
dmd
dmd = demand (integration time selectable from 1 to 30 min.)
7 Display of the serial communication status, phase sequence, wrong connection of current measuring inputs
Display pages
Pulse voltage (1.2/50µs)
8kV (EN61000-4-5)
Standards
Safety IEC60664-1 Metrology Energy measurements:
EN61036, EN61268.
Pulse output DIN43864
Approvals CE Connections 5(10) A Screw-type,
Cable cross-section area 4 mm
2
Connections 20(90) A Screw-type,
Min./
Max. cable cross-section area
6 mm2 / 35 mm
2
Min./Max. screws tightening torque 2 Nm / 6 Nm (90A inputs)
Housing
Dimensions 162.5 x 90 x 63 mm Material ABS, NORYL, PC
self-extinguishing: UL 94 V-0
Mounting DIN-rail and wall Degree of protection Front: IP40
Connections: IP20
Weight
800 g approx. (packing included)
Operating 0 to +55°C temperature
(R.H. < 90% non-condensing 40°C)
Storage -20 to +60°C temperature
(R.H. < 90% non-condensing 40°C)
Installation category Cat. III (IEC60664) Insulation
2000 V
RMS
between all inputs
/
outputs to earth
Dielectric strength 4000 VRMS for 1 minute Noise rejection
CMRR 100 dB, 48 to 62 Hz
EMC
Burst 4kV/level 4 (EN61000-4-4) Immunity to irradiated
electromagnetic fields 10V/m 26-1000MHz
(EN61000-4-3) Electrostatic discharges 15kV (EN61000-4-2) Radio frequency emissions according to CISPR 14
and CISPR 22
General Specifications
System variables
Equivalent system voltage
System reactive power
System active power
System apparent power
System power factor
(TPF)
Used calculation formulas
Phase variables
Instantaneous effective voltage
Instantaneous active power
Instantaneous power factor
(TPF)
Instantaneous effective current
Instantaneous apparent power
Instantaneous reactive power
Consumption recording
Note: i = phase (L1, L2 or L3) P = active power Q = reactive power t
1
, t2= starting and ending time
points of consumption recording n = time unit t= time interval of consumption
recording n
1
, n2= starting and ending discrete
time points of consumption recording
Note: RS422/RS485 “dynamic data”. The variables transmitted are the ones listed in the table above and those mentioned in the “Display pages” of WM22-DIN data sheet except for: THDA, THDV, A max, W
dmd
max, and VA
dmd
max.
Page 5
5
EM4-DIN
Type Inputs Power supply Ordering code
EM4-DIN AV9.3.X. 400V
L-L
, 20(90)A Self power supply AG2200
EM4-DIN AV8.3.X. 208V
L-L
, 20(90)A Self power supply AG2201
EM4-DIN AV2.3.x 220V
L-L
, 20(90)A Self power supply AG2244
EM4-DIN AV1.3.D. 400V
L-L
, 20(90)A 230VAC, 50-60Hz AG2202
EM4-DIN AV0.3.D. 208V
L-L
, 20(90)A 230VAC, 50-60Hz AG2203
EM4-DIN AV3.3.D. 660V
L-L
, 20(90)A 230VAC, 50-60Hz AG2204
EM4-DIN AV1.3.C. 400V
L-L
, 20(90)A 115VAC, 50-60Hz AG2205
EM4-DIN AV0.3.C. 208V
L-L
, 20(90)A 115VAC, 50-60Hz AG2206
EM4-DIN AV3.3.C. 660V
L-L
, 20(90)A 115VAC, 50-60Hz AG2207
EM4-DIN AV1.3.B. 400V
L-L
, 20(90)A 48VAC, 50-60Hz AG2208
EM4-DIN AV0.3.B. 208V
L-L
, 20(90)A 48VAC, 50-60Hz AG2209
EM4-DIN AV3.3.B. 660V
L-L
, 20(90)A 48VAC, 50-60Hz AG2210
EM4-DIN AV1.3.A. 400V
L-L
, 20(90)A 24VAC, 50-60Hz AG2211
EM4-DIN AV0.3.A. 208V
L-L
, 20(90)A 24VAC, 50-60Hz AG2212
EM4-DIN AV3.3.A. 660V
L-L
, 20(90)A 24VAC, 50-60Hz AG2213
EM4-DIN AV5.3.D. 400V
L-L
, 5(10)A 230VAC, 50-60Hz AG2214
EM4-DIN AV4.3.D. 208V
L-L
, 5(10)A 230VAC, 50-60Hz AG2215
EM4-DIN AV7.3.D. 660V
L-L
, 5(10)A 230VAC, 50-60Hz AG2216
EM4-DIN AV5.3.C. 400V
L-L
, 5(10)A 115VAC, 50-60Hz AG2217
EM4-DIN AV4.3.C. 208V
L-L
, 5(10)A 115VAC, 50-60Hz AG2218
EM4-DIN AV7.3.C. 660V
L-L
, 5(10)A 115VAC, 50-60Hz AG2219
EM4-DIN AV5.3.B. 400V
L-L
, 5(10)A 48VAC, 50-60Hz AG2220
EM4-DIN AV4.3.B. 208V
L-L
, 5(10)A 48VAC, 50-60Hz AG2221
EM4-DIN AV7.3.B. 660V
L-L
, 5(10)A 48VAC, 50-60Hz AG2222
EM4-DIN AV5.3.A. 400V
L-L
, 5(10)A 24VAC, 50-60Hz AG2223
EM4-DIN AV4.3.A. 208V
L-L
, 5(10)A 24VAC, 50-60Hz AG2224
EM4-DIN AV7.3.A. 660V
L-L
, 5(10)A 24VAC, 50-60Hz AG2225
EM4-DIN AV6.3.D. 100V
L-L
, 5(10)A 230VAC, 50-60Hz AG2226
EM4-DIN AV6.3.C. 100V
L-L
, 5(10)A 115VAC, 50-60Hz AG2227
EM4-DIN AV6.3.B. 100V
L-L
, 5(10)A 48VAC, 50-60Hz AG2228
EM4-DIN AV6.3.A. 100V
L-L
, 5(10)A 24VAC, 50-60Hz AG2229
EM4-DIN AV1.3.4 / [5] 400V
L-L
, 20(90)A 18-60VDC [77-143VDC] AG2230 [AG2237]
EM4-DIN AV0.3.4 / [5] 208V
L-L
, 20(90)A 18-60VDC [77-143VDC] AG2231 [AG2238]
EM4-DIN AV3.3.4 / [5] 660V
L-L
, 20(90)A 18-60VDC [77-143VDC] AG2232 [AG2239]
EM4-DIN AV5.3.4 / [5] 400V
L-L
, 5(10)A 18-60VDC [77-143VDC] AG2233 [AG2240]
EM4-DIN AV4.3.4 / [5] 208V
L-L
, 5(10)A 18-60VDC [77-143VDC] AG2234 [AG2241]
EM4-DIN AV7.3.4 / [5] 660V
L-L
, 5(10)A 18-60VDC [77-143VDC] AG2235 [AG2242]
EM4-DIN AV6.3.4 / [5] 100V
L-L
, 5(10)A 18-60VDC [77-143VDC] AG2236 [AG2243]
Available models
Possible module combinations
Available modules
Power supply Self p.s. Auxiliary p.s.
Basic unit
Slot A Slot B Slot A Slot B
Digital inputs RS485 Serial Output (*) AV2 only
Type Channels Code
Open collector output 2 AO2900 Relay + open coll. output 2 AO2910
Power supply Self p.s. Auxiliary p.s.
Basic unit
Slot A Slot B Slot A Slot B
Open collector output Relay + open coll. output
Type Channels Code
Digital inputs 2 AQ2940 RS485 Serial Output 1 AR2950
(*)
Page 6
6
EM4-DIN
Wiring diagrams
20(90)A model: three-phase unbalanced load
Direct connection (3-phase system w/out N
)
Direct connection (3-phase system)
Direct connection (3-phase system + N)
Self-power supply Fig. 3
5(10)A model: three-phase unbalanced load
Direct connection (3-phase system +
N)
Direct connection (3-phase system
with or without neutral)
CT connection (3-phase system with neu
tral)
Self-power supply Fig. 4
5(10)A model: three-phase unbalanced load
VT and CT connection (3-phase system)
20(90)A model: three-phase unbalanced load
Auxiliary power supply Fig. 2
Auxiliary power supply Fig. 1
Auxiliary power supply Fig. 5
Auxiliary power supply Fig. 6
Auxiliary power supply Fig. 9
AC power supply AC power supply
AC power supply AC power supply
AC power supply
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
CT ARON connection (3-phase system) VT and CT ARON connection (3-phase system)
Auxiliary power supply Fig. 8
Auxiliary power supply Fig. 7
AC power supply
AC power supply
LOAD
LOAD
Page 7
7
EM4-DIN
Wiring diagrams (optional modules)
Only open collector outputs: the grounds of the outputs are separated, and therefore it’s possible to carry out, for the same module, two different connections. The load resistance (Rc) must be designed so that the closed contact current is lower than 100mA; the VDC voltage must be lower than or equal to 30V. VDC: power supply voltage output. Vo+: positive output contact (open collector transistor). GND: ground output contact (open collector transistor).
Open collector output Fig.10
VDC max 30V
PNP-NPN connections
Contact and voltage connection
2 and 4-wire connection
Digital inputs Fig. 12
Digital inputs Fig. 13 RS485 Serial output Fig. 14
Accuracy
Accuracy (RDG) depending on the current
Error
10A (Imax) 90A (Imax) 10A (Imax) 90A (Imax)
5A (Ib) 20A (Ib) 5A (Ib) 20A (Ib)
0,5A 2A 1A 4A
0,25A
1A
0.5A 2A
+1%
+4%
-4%
0%
+1.5%
-1%
EN 61036/ IEC 61036 limits (Active energy)
5(10A) Start-up current: 20mA 20(90A) Start-up current: 80mA
-1.5%
Accuracy (RDG) depending on the current
Error
+2%
+4%
-4%
0%
+2.5%
-2%
EN 61268/ IEC 61268 limits (Reactive energy)
5(6A) Start-up current: 20mA 20(90A) Start-up current: 80mA
-2.5%
Relay + open coll. output Fig. 11
10A (Imax) 10A (Imax) 90A (Imax) 90A (Imax)
5A (Ib) 5A (Ib) 20A (Ib) 20A (Ib)
0.25A
0.5A 2A 4A
0.1A
0.25A 1A 2A
sinϕ=1
sinϕ=0.5
sinϕ=1
sinϕ=0.5
PF=1
PF=L0.5
or C0.8
Page 8
8
EM4-DIN
Terminal boards
Dimensions and panel cut-out
Open collector dual output module
RS485 Serial output module
AO 2900
Relay output + open coll. output module
AO 2910 AR 2950
Digital inputs module
AQ 2940
Keys for:
- values programming;
- function selection;
- displaying the measuring pages.
2. Display
LCD with alphanumeric indications to:
- display configuration parameters;
- display all the measured variables.
3. Removable label
It shows the following information:
- year of manufacturing
- serial number
- input voltages and currents
- operating frequency
- kWh measuring class
- kvarh measuring class
- symbols: electric system, attention and dual insulation.
4. Hidden dip-switch
Enable/disable the access to the programming procedure.
Front panel description
1. Key-pad
To program configuration parameters and to display variables.
S-key to enter programming and confirm selections;
1
2
3
4