Data sheet
Thermal actuator
TWA-ZL
Description
Ordering
Danfoss thermal actuator TWA-ZL is used with
Danfoss valves type VZL. The actuator can be
controlled with a on/o controller or switch.
Type Power supply Code No.
TWA-ZL NC 24 V AC/DC 082H3100
TWA-ZL NO 24V AC/DC 082H3101
TWA-ZL NC 230 V AC 082H3102
TWA-ZL NO 230 V AC 082H3103
These provide a cost eective solution for
the control of hot and/or chilled water for fan
coil units, small reheaters and recoolers in
temperature control systems.
Features:
• Position indicator
• Normaly opened (NO) or normaly closed (NC)
version
• Cable included
Main data:
• Nominal voltage:
- 24 V AC/DC or 230 V AC ; 50/60 Hz
• Control input: on/o
• Force: 105 N
• Stroke: 2,8 mm
• Full stroke travel time: 3 min
• Max. medium temperature: 120 °C
Technical data
DEN-SMT/SI
Power supply V 24 AC/DC or 230 AC
Power consumption VA 2
Frequency Hz 50/60
Control Input on/o
Closing force N 105
Max. stroke mm 2,8
Full stroke travel time min 3
Max. medium temperature
Ambient temperature 2 … 60
Storage and transport temperature -40 … +70
Protection Class II
Grade of enclosure IP 41
Weight kg 0,5
Cable length m 1,2
1)
When heating th e actuator full stroke time i ncreases up to some minutes – it dep ends on the ambient temperat ure
VD.LE. R2.02 © Danfoss 05/2012
1)
120
°C
1
Data sheet Thermal actuators TWA-ZL
Operation
TWA-ZL actuator works on the thermal
expansion principle:
- moves actuator stem in one direction in case
of heating of the actuator and
- moves actuator stem in another direction in
case of no heating of the actuator
Two versions of actuators are available:
- TWA-ZL NC version, in the non-energized
state actuator’s stem is retracted
- TWA-ZL NO version, in the non-energized
state actuator’s stem is extracted
Both versions are available in 24V (SELV) or 230V.
The TWA-ZL NO has an internal spring, which is
factory xed with a split ring (g.1) to hold the
spring retracted in its o -the-shelf state. The use
of split ring allows the actuator to be mounted to
the valve. Once mounted, the split ring has to be
removed.
Remark:
In case the actuator has been dismounted and split
ring removed, split ring can be added back to the
actuator after the heating of the actuator.
The actuator is equipped with a position
indicator to show the position of the actuator
stem (g.2).
Fig. 1 Normaly opened (NO) version
Actuator stem up Actuator stem down
Fig. 2
Blue/Brown
VZL valve has closed AB port in stem up position.
This is done by means of valve internal spring in
case of no actuator force.
TWA-ZL & VZL combinations
TWA-ZL NC & VZL:
- in the non-energized state valve path A-AB is
closed (g.3)
- in the energized state valve path A-AB is
opened
TWA-ZL NO & VZL:
- in the non-energized state path A-AB is
opened (g.4)
- in the energized state path A-AB is closed
Remark for 3-port or 4- port VZL valves:
Due to shorter actuator stroke in compare to the
valve stroke port B can not be closed. Therefore this
combination can not be used as a switch over valve.
Disposal The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
Normaly Closed (NC)
Fig. 3 TWA-ZL NC & VZL
Blue/Brown
Normaly Opened (NO)
Fig. 4 TWA-ZL NO & VZL
2
VD.LE. R2.02 © Danfoss 05/2012