Danfoss TWA-A, TWA-V Data sheet

Data Sheet
TWA Electric Valve Actuator
Features:
Ordering Information:
the TWA is energized, an internal wax element gradually heats up opening or closing the valve. TWA can be wired with Danfoss RET-B, RET-24 or FH-WS low voltage thermostats.
Hot water radiator / baseboard / n tube
heating systems
Hydronic oor heating systems (zone
controls)
Hot or chilled water applications
Slow acting wax element eliminates water
hammer associated with motorized valves.
Silent operation
Visual position indicator to show the open or
Code No. Typ e suitable Valve Actuator Position Replaces
088 H 3110
088 H 3111 Normally open 082F1143 (ABNR)
088 H 3114
08 8H3120
08 8H3121 Normally open 082F1142 (ABNV)
* TWA-V is not to be used with VMT valves having Cv > 2.7 GMP
TWA-A RA 2000, RA-C
TWA-V RAV, VMT*
closed position of the valve
Low power consumption
Compact size
Normally closed 082F1043 (ABNR)
Normally closed w/ end
switch
Normally closed 082F1042 (ABNV)
-
Specications:
Suitable systems Hot water applications*
Supply voltage 24V ac/dc (Class II, SELV)
Frequency 50 - 60 Hz
Avg. power consumption 2W
Travel time of spindle ~3 min
Ambient temperature 32 - 140°F (0 - 60°C)
Wire lead length 4ft (1200 mm)
End switch, max. Output 24VAC / 2 A
TWA-A (Maximum ∆p for quiet operation) 8.7 psi (0.6 bar)
TWA-V (Maximum ∆p for quiet operation) 11.6 psi (0.8 bar)
*TWA's are not recommended for steam valves or inside tight enclosures. Excessive ambient temperatures past 140°F (60°C) can place the wax in a semi-liqueed state causing the valve to falsely operate and the regulation to be lost.
VDSKE322 © Danfoss 01/17
1
Data Sheet TWA Electric Valve Actuator
Electric Connection & Mounting Orientation:
Identifying Mounting Valve Type:
When 24 volts is applied to the actuator, the internal wax element heats up allowing the valve to actuate. Unlike valves that open and close quickly, the actuation of the TWA is slow, reduc­ing water hammer and as a result performs simi­lar to a modulating valve in certain situations.
Valve Style Distinguishing Dimension
RA 2000
RAV / VMT
When the TWA is used on systems with excessive temperatures, the orientation of the actuator should be horizontal to ensure proper airow across the actuator. If it is mounted within an enclosure, proper airow through the enclosure is essential to oset the increased ambient tem­perature's inuence on the actuator.
7/8” (22.5 mm) outside diameter
1 - 5/16" (34 mm) outside diameter
2
VDSKE322 © Danfoss 01/17