Danfoss Turbocor TT-300 User Manual

TWIN-TURBINE CENTRIFUGAL
COMPRESSOR
MODEL TT-300
SERVICE MONITOR USER MANUAL
Danfoss Turbocor Compressors Inc. ECD-00007M Rev. 1
Contents
Cable Connection 3
RS232 Connection 3
RS485 Connection 3 Monitor Program Installation 5 Starting the Monitor Program 5 User Interface 5
Monitor Program Toolbar 5
Entering User Input 6 Serial Port Connection 6
Compressor Configuration 7
Using the Setup Wizard 7
Start-up Settings 8
Electronics Valve Control 9
Analog Output Setup 11
Modbus Communications 12
Downloading and Saving Configuration Data 12 Using a Saved Configuration File 13 Controlling User Access 14
Starting and Stopping the Compressor 15
Analog Input 15
How to Start the Compressor 15
How to Stop the Compressor 15 Modbus Network 15
How to Start the Compressor 15
How to Stop the Compressor 16 Chiller Control 16
How to Start the Compressor 16
How to Stop the Compressor 16
Monitor Program Data and Controls 18
Main System 18 Bearing Calibration 20
Bearing Calibration Procedure 22
Calibration Data Interpretation 23
“Gain” Interpretation 23 “Offset” Interpretation 23
Compressor Control 23
Compressor Control Modes 26
Calibration 26 Manual Control 26 Analog Input 27 Modbus Network 27 Chiller Control 27
Compressor Faults/Alarms 27
Danfoss Turbocor Compressors Inc. i
ECD-00007M Rev. 1
Contents
Motor Monitoring 28
Motor Monitoring Overview 28
Motor Faults / Alarms 30 Magnetic Bearing Monitoring 31
Bearing Monitoring Overview 31
Bearing Faults 33 Electronic Valve Data / Tuning 33 Chiller Control 36 System Information 38
Compressor Info 39
EEPROM Log Resets 39 EEPROM Settings 39
Compressor Controller Settings 40
Compressor Controller Alarms 41
Compressor Controller Fault Limits 43
Compressor Stepper Motor Settings 44
Stepper Motor Valve Controls 45
Analog Output Controls 47
Compressor Controller Impeller Specific Settings 49
Compressor Controller (CC) Critical Fault Lock Outs 50
Refrigerant 51 Compressor Event Log 51 History Data 52 Trending 53
Graphs 53
Trending & Data Acquisition 56 Compressor Map 57 Fault Captures 59 Data Capture 60
Appendix A: Determination of Actual Power Setting A-1
ii Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
1 Introduction
The Turbocor Service Monitor program is a rich, user­friendly, graphical user interface designed to control the Turbocor compressor and to provide status information about the compressor. Furthermore, it can be used as a tool for troubleshooting purposes.
This manual describes the functions provided by the Turbocor Service Monitor program.
Service Monitor User Manual
Danfoss Turbocor Compressors Inc. 1
ECD-00007M Rev. 1
System Requirements
2 System Requirements
The monitor program must be installed on a PC that meets the minimum requirements specified in Table 1. For optimum performance, a 533 MHz Pentium or higher CPU with 128 MB RAM running Windows 2000 (SP4) or XP is recommended.
The monitor program was developed for the .NET Framework and requires the .NET Framework to be installed on the PC where the program runs. Microsoft provides a re-distributable installer, Dotnetfx.exe, that
contains the common language runtime and .NET Framework components that are necessary to run the monitor program. Before installing the monitor program, the .NET framework 1.1 re-distributable must be installed. This can be downloaded from the Microsoft website.
The latest Windows service packs and security updates should also be installed on the PC.
Table 1: Minimum Requirements
Processor 533-MHz Intel Pentium-class processor
Operating System
The .NET Framework 1.1 Re-distributable is supported on the following platforms:
• Microsoft Windows® Server 2003 (.NET Framework 1.1 is installed as part of the operating system)
• Windows XP Professional
• Windows XP Home Edition
• Windows 2000
• Windows Millennium Edition (Windows Me)
• Windows 98
Memory
Hard Disk
Display
Input Device
Other
• Microsoft Windows NT® 4.0 Service Pack 6a
The .NET Framework 1.1 Re-distributable cannot be installed on 64-bit computers; Windows NT 4.0 Terminal Server is not supported
128 MB of RAM, 256 MB recommended
110 MB of hard disk space required, 40 MB additional hard disk space required for installation (150 MB total)
800 x 600 or higher-resolution display with 256 colors
Microsoft mouse or compatible pointing device
Install the latest Windows service packs and critical updates from the Windows Update site.
Installation of the .NET Framework 1.1 is split into two parts: the core and language packs. The core cont ains everything yo u need to run .NET Framework applications; all dialog boxes and error messages will be in English. If you want dialog boxes and error messages in another language, you must also install the corresponding language pack. For more information, see the .NET Frame wo rk Dow nlo a ds page.
2 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
3 Getting Started
3.1 Cable Connection
The monitoring program communicates with the compressor via the Modbus* protocol using either the RS232 or RS485 connection at the Chiller Interface module. RS485 communication requires an RS485/RS232 adapter (user-supplied). RS232 communication is recommended for cable lengths not exceeding 15 meters (50 feet) between the PC and compressor. For cables that run up to 100 meters (328 feet), use the RS485 communication line. Always use shielded, twisted-pair cable for data communications
*The Modbus protocol was originally developed to exchange information between products on the factory floor. This protocol has become a de f acto standard for exchanging data and control between PLC systems. Modbus is a registered trademark of Modicon Corp.
Service Monitor User Manual
3.1.1 RS232 Connection
1. Connect one end of the RS232 cable (user-supplied) to the DB9 connector on the Chiller Interface module; see Figure 1.
2. Connect the other end of the cable to an available COM port on the PC.
3. Confirm that jumpers JP2 and JP7 are in proper positions before starting.
JP2 is the Modbus termination jumper. Install the jumper if the Modbus connection is at the end of a cable run.
Remove JP7 to enable RS-232 communication with the PC.
Figure 1 RS232 Connector - Chiller Interface
Module
3.1.2 RS485 Connection
1. Connect the RS485/RS232 adapter directly onto the PC COM port.
Connect the other side of the adapter to the Modbus. Figure 2 shows the PC and adapter connections to the Modbus for a single compressor application. Ensure that the termination jumper (JP2) on the Chiller Interface module is installed.
Figure 3 shows the PC and adapter connections to the Modbus for a multiple compressor application. In this case, set the termination jumper only on the Chiller Interface module that is connected at the end of the Modbus cable run.
Danfoss Turbocor Compressors Inc. 3
ECD-00007M Rev. 1
Getting Started
Figure 2 PC to Modbus Connection (single compressor with > 10 m cable length)
Figure 3 PC to Modbus Connection (multiple compressors with > 10 m cable length)
4 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
3.2 Monitor Program Installation
Service Monitor User Manual
The monitor program is installed on the PC and communicates with the compressor using the ModBus protocol over a RS-232 or RS-485 serial link. Administrator privileges may be required to install and remove software on the PC.
NOTE:
If a previous version of the monitor program is already installed on the PC, it must be uninstalled before proceeding with the current installation. To uninstall the monitor program: from the “Start” menu, select “Settings” “Control Panel”. Double-click “Add/Remove Programs”. From the list, select “Danfoss Turbocor Service Monitoring Tool” and then click the “Remove” button.
3.3 Starting the Monitor Program
To start the monitor program: from the “Start” menu, select “Programs” “Danfoss Turbocor Monitoring Tool”.
3.4 User Interface
Installation Procedure:
1. Insert the monitor program CD into th e drive.
2. In Windows Explorer, navigate to the Turbocor_Service_Tool_Setup.msi file. Double-click the file to launch the setup wizard.
3. Follow the instructions provided by the wizard to complete the installation.
4. Click the Close button to exit the setup wizard.
3.4.1 Monitor Program Toolbar
NOTE:
The toolbar (located under the menu bar) provides the user with easy access to the monitoring windows. Table 2 provides details for each icon on the toolbar.
Table 2 Monitor Program Toolbar Icons
Icon Name Description
Serial Port Connection Clicking on the “Serial Port Connection” icon opens the “Serial Port
Connection” window. Refer to section 3.5 "Serial Port Connection" on page 6.
Compressor Controller Parameters
Motor Monitor Clicking on the “Motor Monitor” icon opens the “Variable Speed
Magnetic Bearings Clicking on the “Magnetic Bearings” icon opens the “Magnetic
Clicking on the “Compressor Controller Parameters” icon opens the “Compressor Controller” window. Refer to section 6.3 "Compressor Control" on page 23.
Permanent Magnet Motor Monitoring” window. Refer to section
6.4 "Motor Monitoring" on page 28.
Bearing Monitoring” window. Refer to section 6.5 "Magnetic Bearing Monitoring" on page 31.
Up to three windows can be displayed at one time. If three windows are already open, one must be closed before another window can be opened.
Danfoss Turbocor Compressors Inc. 5
ECD-00007M Rev. 1
Getting Started
Table 2 Monitor Program Toolbar Icons (Continued)
Icon Name Description
Expansion Valves Clicking on the “Expansion Valves” icon opens the “Electronic
Valve / Data Tuning” window. Refer to section 6.6 "Electronic Valve Data / Tuning" on page 33.
Event Log Clicking on the “Event Log” icon opens the “Compressor Event
Log” window. Refer to section 6.10 "Compressor Event Log" on page 51.
EEPROM Settings Clicking on the “EEPROM Settings” icon opens the “EEPROM
Settings” window. Refer to section 6.9 "EEPROM Settings" on page 39.
Load Profile Graphs Clicking on the “Load Profile Graphs” icon opens the “Compressor
History Data” window. Refer to section 6.1 1 "History Data" on p age
52.
Fault Captures Clicking on the “Fault Captures” icon opens the “Fault Captures”
window. Refer to section 6.14 "Fault Captures" on page 59.
Trending Clicking on down arrow next to the “Trending” icon, and selecting
“Charts 1” opens the trending “Graphs” window; selecting on “Charts 2” opens the “Trending and Data Acquisition” window. Refer to section 6.12 "Trending" on page 53.
Chiller Control Clicking on the “Chiller Control” icon opens the “Chiller Control”
window. Refer to section 6.7 "Chiller Control" on page 36.
Compressor Envelope Clicking on the “Compressor Envelope” icon opens the
“Compressor Map” window. Refer to section 6.13 "Compressor Map" on page 57.
3.4.2 Entering User Input
When user input is required for the monitor program fields, perform the following sequence:
1. Double-click the variable field. (This activates the field for user input.)
3.5 Serial Port Connection
The Serial Port Connection window contains fields that must be filled in order to enable communication between the monitor program and the compressor; refer to Figure 4. The comm settings of the compressor must be known in order for the monitor program to communicate with the compressor.
To access the “Serial Port Connection” window, select “Window”“Connection” from the menu bar, or click on the “Serial Port Connection” icon located below the menu bar.
2. Scroll or type in the new setting.
3. Press Enter. It is important to press Enter as this causes the user input to be validated.
The following paragraphs describe the dialog box fields. Comm Port - Serial communication port that the computer
will use to connect to the compressor. Enter the COM port number such as COM1 or COM2, etc.
Baud Rate -19,200 or 38,400 baud (38,400: default) Stop Bits - 1 or 2. (1: default) Slave Address - 1-63. (1: default)
6 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
Service Monitor User Manual
Access Code - The access code controls access to all adjustable parameters. The default user access level on power up is read only. Enter the code that corresponds to the access level you require. Contact Turbocor Product Support to obtain the required access code.
1. Once the serial port connection data has been set, click the Connect button. At this point, connection status, compressor details, and user access level appear in the right-hand pane of the dialog box.
2. If necessary, change the access level. Enter the access code in the “Access Code” parameter box, then click “Change Access Level”. Confirm that the correct access level has been set on the right-hand pane of the dialog box.
NOTE:
The access level connection cannot be changed prior to a establishing connection.
Entering the wrong access code more than 3 times will lock out all communications until a cycle of the power is performed.
3. Click the “OK to start monitoring” button.
Figure 4 Serial Port Connection Dialog Box
4 Compressor Configuration
4.1 Using the Setup Wizard
The monitor program features a commissioning setup wizard to guide the user through the complete compressor configuration process.
1. To launch the commissioning setup wizard, select “System Commissioning” from the “Advanced” menu item. The introduction screen for the commissioning setup wizard appears; refer to Figure 5. Click Next.
(To bypass the setup wizard and use a saved configuration file to setup the compressor, check the checkbox and click Next. Continue with 4.2 "Using a Saved Configuration File" on page 13.)
2. Select the appropriate units of measurement (metric or imperial). Refer to Figure 6.
3. Select the appropriate compressor control method. There are three modes available:
external controller. The variable demand signal corresponds to the range of 0-100% maximum power available.
• Analog Input: compressor loading controlled using
an analog demand signal of 0-10 VDC from an
Danfoss Turbocor Compressors Inc. 7
ECD-00007M Rev. 1
Figure 5 Commissioning Set-up Wizard
Compressor Configuration
• Modbus Network: the compressor receives a
demand from an external computer, PLC, or building management system using the Modbus protocol on a RS-232 or RS-485 communication link.
• Chiller Control: fully automatic; controls the chilled
water temperature using a temperature sensor connected directly to the Chiller Interface module. This mode can also be used to control evaporating temperature which is derived from the suction pressure measurement
6. Set the Chiller Control Set Point to the desired value.
7. Set the Proportional and Integral Gain values to obtain stable control (the Proportional and Integral Gain values will vary depending on the application).
NOTE:
The Integral part of the internal chiller controller is switched off until the compressor reaches a speed of 18,500 RPM. Stopping the compressor and restarting also resets the Integral part to 0.
8. Click in the Chiller Enable checkbox if you would like to have the compressor start automatically. It is advised, however, to open the interlock contact (located on the Chiller Interface module) to prevent the compressor from starting before the commissioning sequence is complete.
Figure 6 General Compressor Settings
NOTE:
If the compressor is linked to an external controller, changes made to the compressor demand via the monitor program can conflict with controller-issued commands. This situation can lead to unexpected results. Before testing the demand input, isolate the compressor from the controller.
4. Click the Next button.
Steps 5 through 8 apply to the Chil ler Control mode only.
5. Select the type of sensor that will control the chiller. If selecting Entering or Leaving Chiller Air/Water Temperature, connect an NTC temperature sensor (as specified in the compressor Application manual) to either the Entering- or Leaving Chilled Water temperature input on the Chiller Interface module.
8 Danfoss Turbocor Compressors Inc.
Figure 7 Chiller Control Commissioning
4.1.1 Start-up Settings
(Refer to Figure 8)
1. Enter the Temporary Suction Pressure Alarm %. The limit is set up as a % of the current suction pressure limit, e.g., if a suction pressure trip of 270 kPa was set and the temporary suction pressure alarm was set to 50%, the temporary suction pressure trip limit would be 135 kPa. This temporary alarm is only active while the Suction Pressure Delay timer is counting down.
ECD-00007M Rev. 1
Figure 8 Start-up Settings
Service Monitor User Manual
This section explains how to set up the expansion valves for various applications. Both valves can be operated independently or in parallel.
For Expansion Valve #1:
1. Enter the number of steps to drive the valve from fully closed to fully open. Expansion valves with different numbers of steps can be used.
If the incorrect number of steps is selected, the valves may not have enough travel to allow the required amount of mass flow or the valve may not be able to throttle down to the required amount of mass flow. This situation could cause liquid flood back and damage to the compressor.
2. Enter the Temporary Suction Pressure Delay Time. This parameter represents time in seconds that the temporary suction pressure alarm / fault limit should be enabled. The timer starts to count down once the shaft starts to rotate.
3. Enter the Compressor Starting Speed. If the estimated surge speed is greater than the starting speed setting, the compressor will ramp up to the surge speed. If the starting speed setting is greater than the estimated surge speed, the compressor will ramp up to the starting speed. In both cases, the compressor speed will increase at the full ramp rate.
4. Enter the Run Contact Close RPM. The compressor contains a NO relay contact that closes while the compressor is running. The speed at which the contact closes is determined by the Run Contact Close RPM.
5. Enter the Inlet Guide Vane Starting % Open. Typically, the vanes will be set to the closed or almost closed position at start-up.This is to minimize the possibility of liquid flood back and to reduce the compressor’s start-up current draw.
6. Click Next to continue.
4.1.2 Electronics Valve Control
(Refer to Figure 9)
Figure 9 Electronics Valve Control Setup
2. Select the control mode for the expansion valve. Available options are: superheat, liquid level, or load balance. See Table 3 for a description of the modes.
3. Enter the Starting Valve Position. If desired, at compressor start-up, the valves can be set to open to a pre-start value for a given time. This value represents the percentage of maximum steps sent to the motor upon start-up of the compressor. The stepper motor will hold at this position until the stepper start delay timer has expired.
4. Enter the Valve Starting Position Delay Time. The delay is the amount of time (from compressor start-up)
Danfoss Turbocor Compressors Inc. 9
ECD-00007M Rev. 1
Compressor Configuration
to hold the number of steps sent to the motor as determined by the Starting Valve Position %. Value is in seconds and starts to count down when the drive is enabled.
5. Enter the Control Setpoint, i.e., suction superheat or liquid level. (Not applicable to load balance control
mode.)
6. Enter the Valve Control Loop Speed. This value represents the reaction time of the control loop to a
7. Enter the Minimum Closure During Operation. This is
8. Click Next to continue. Repeat steps 1 through 7 for
Table 3 Control Modes
Control Mode Description
Superheat
The calculation of superheat can be based on the temperature and pressure measurements from one of the following sources:
Superheat control using the compressor flange temperature and pressure (this mode is not recommended as the temperature at the compressor flange is influenced by external factors).
Superheat control using the compressor flange pressure and a 10K thermistor that is connected to the terminals labeled “ENTRY” on the Chiller Interface module.
Superheat control using the compressor flange pressure and a 10K thermistor that is connected to the terminals labeled “LIQT” on the Chiller Interface module.
process error and replaces the PID controller gains (proportional, integral, and derivative).
the minimum close position for the valve while the compressor is spinning.
electronic expansion valve # 2.
Liquid Level
Load Balance
Superheat control using an external temperature and pressure sensor connected to the terminals on the IO pcb labeled “SPARE T” & “SPARE P”.
Liquid level can be measured from one of the following sources:
Liquid Level 1 contro l usin g a lev el sen so r co nn ec te d to the te rm ina ls on the Chiller Interface module labeled “LIQ LEV1”.
Liquid Level 2 contro l usin g a lev el sen so r co nn ec te d to the te rm ina ls on the Chiller Interface module labeled “LIQ LEV2”.
For liquid level sensing, two types of level sensors can be used: a level sensor with a supply of 15VDC and an output of 0-5VDC or a resistive-type level sensor, 0-90 Ohm. Refer to vendor documentation for wiri ng these types of se nsors to the Chiller Interface module.
The Load Balance control mode uses the compressor’s own internal control algorithm to determine the best mix of speed control, inlet guide vane opening and load balance valve opening. Use this mode only if a load balancing valve is installed in the system. Since the load balancing valve is connected to the compressor’s capacity control algorithm, selecting this mode without a valve installed will add a delay to the loading/unloading process, i.e., the compressor will try to open and close the valve for 2 minutes r ather th an clo se the va ne or change the speed.
10 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
Service Monitor User Manual
4.1.3 Analog Output Setup
The compressor features a universal analog output for load balancing valve, IGV position, discharge pressure, etc. The operating range can be set to 0-5V or 0-10V via jumpers on the Chiller Interface module.
Figure 10 shows a typical application for the analog output. In this example, the analog output from the Chiller Interface
module is connected to a 3-way valve that channels chilled water to a cooling coil. A temperature sensor at the cooling coil is connected to the Leave terminals of the Chiller Interface module. The analog output controls the amount of chilled water entering the cooling coil based on the air temperature setpoint.
Figure 10 Analog Output Application Example
Configure the analog output as follows (Refer to Figure 11):
1. Select the control mode for the analog output. The selection determines which control variable will be the source for the 0-10vdc output (at the ANALOG output terminals on the Chiller Interface module). The options are:
• Load Balance
•HP
•IGV
Danfoss Turbocor Compressors Inc. 11
ECD-00007M Rev. 1
•Auto
• Superheat - Flange TP
• Superheat - FlangeP, EWT
• Superheat - FlangeP, LIQT
• Suction Pressure.
• Leaving Temp
•Entering Temp
•Liquid Temp
Compressor Configuration
Figure 11 Analog Output Setup
2. Enter the Starting Output. This value equals the percentage of maximum voltage sent to the terminals of the Chiller Interface module on compressor start-up. The analog output will hold at this position until the start delay timer has expired.
3. Enter Starting Output Delay Time. This value is the amount of time from compressor start-up to hold the voltage at the start-up %. Value is in seconds and starts to count down when the drive is enabled.
4. Check the Control Action checkbox for reverse acting. Leaving the checkbox unchecked will enable direct acting.
5. Enter the Proportional, Integral, and Derivative gains to provide stable control.
6. Enter the minimum analog output (in DC volts) during operation, if required. This parameter can be used, for example, to maintain a minimum valve open position during operation.
4.1.4 Modbus Communications
(Refer to Figure 12)
Figure 12 Modbus Communications Setup
4.1.5 Downloading and Saving Configuration Data
At the end of the commissioning sequence, you have the choice of either downloading the configuration data to the compressor or saving it to a file for later use.
To save the data to a configuration file, click the Save to Configuration File button. In the Save As dialog box, name the file and save it in a designated location.
NOTE:
If modifications are made to the configuration data after the commissioning is complete, the new values must be recorded in a new commissioning session if the data is to be saved to a file.
Never attempt a download while the compressor is running as it can lead to a loss of compressor control. Open interlock contacts on the Chiller Interface module before downloading configuration data.
Set up the RS-485 and RS-232 ports, as required, on the Chiller Interface module to enable communication with an external PLC, computer or building management system.
12 Danfoss Turbocor Compressors Inc.
For immediate downloading of the configuration data to the compressor, click the Download to Compressor button. To enable the new configuration data, perform the following steps:
ECD-00007M Rev. 1
1. Turn OFF power to the compressor. Wait at least 5 minutes, then check that the LEDs on the Backplane are OFF.
2. Turn ON power to the compressor.
4.2 Using a Saved Configuration File
Service Monitor User Manual
IMPORTANT:
Record the comm settings before you close the monitor program since they will be necessary to communicate with the compressor when you restart the monitor program.
3. Close and then restart the Monitor program.
Follow the steps outlined here if you have bypassed the commissioning wizard in order to download a configuration file to the compressor.
Never attempt a download while the compressor is running as it can lead to a loss of compressor control. Open interlock contacts on the Chiller Interface module before downloading configuration data.
1. Click the “Load configuration from file” button; refer to Figure 13.
2. In the Open File dialog box, browse to the location of the .ttc file.
3. Click Open.
4. On the Download Settings form, click “Download to compressor” button.
5. When the message “Done. Cycle power before running the compressor” appears, turn OFF power to the compressor; refer to Figure 14. Wait at least 5 minutes, then check that the LEDs on the Backplane are OFF.
configuration file has been successfully downloaded to the compressor.
Figure 13 Download Settings Screen
6. Close the Monitor program.
7. Turn ON power to the compressor.
8. Restart the Monitor program.
9. Once reconnected, the text in the right-hand pane of the Serial Port Connection dialog box appears in red. When the text turns black, it indicates that the new
Figure 14 Download Settings Screen (After
Download)
Danfoss Turbocor Compressors Inc. 13
ECD-00007M Rev. 1
Compressor Configuration
4.3 Controlling User Access
The access code system allows OEM customers to set their own unique pass codes thereby restricting access to company authorized personnel.
These access codes control access to all adjustable parameters via the Modbus communications layer. The access levels are:
• Read only ~ User may only view values across the Modbus layer.
• Low Level ~ User may only alter basic settings such as leaving chilled water temp, display units, chiller enable/ disable, etc.
• Mid Level ~ User may alter all settings that are required for commissioning a compressor in the field. Values alterable, for example, are control mode, valve control settings, run status contact energize RPM, reset load profile data, and retrieve and save fault data.
• High level ~ User may alter all settings. This level of access is reserved for users that configure motor/ compressor and bearing control only.
Upon power-up of the compressor, the access codes are calculated and stored in RAM memory. The default user access level on power up is read only.
The Access Code Change form appears. To change the access code for a specific user level:
1. Select the appropriate radio button.
2. Enter the current access code followed by the new access code for the selected user level (if you enter the incorrect access code nothing will be changed).
3. Re-enter the new access code in the Confirm Access Code field.
4. Click the Change Access Code button.
NOTE:
The new access code does not take effect until the compressor has been restarted.
To change the access code, select “Access Codes” from the “Advanced” menu item; refer to Figure 15.
Figure 15 Navigating to the Access Code
Change Form
Figure 16 Access Code Change Form
14 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
Service Monitor User Manual
5 Starting and Stopping the Compressor
The following sections describes how to start and stop the compressor. Refer to the section corresponding to the
5.1 Analog Input
The Analog Input mode controls the compressor loading using an analog demand signal of 0-10 VDC from an external controller. The variable demand signal corresponds to the range of 0-100% maximum power available.
NOTE:
The Chiller Interface interlock switch must be closed and no errors present for the compressor to start up and run.
5.1.1 How to Start the Compressor
1. Make sure the contact to the ‘Interlock’ input on the Chiller Interface is closed.
Ensure that power to the compressor is OFF before connecting wiring to the Chiller Interface module.
control method selected during configuration of the compressor.
2. Connect a 0-10VDC demand signal to the Chiller Interface module.
3. Apply a signal between 2 and 10VDC to the ‘Demand’ input. (2VDC = min kW/min speed, 10VDC = max kW according to model capacity.)
5.1.2 How to Stop the Compressor
Decrease the demand signal to 0VDC or open the contact connected to the ‘Interlock’ input on the Chiller Interface module. The compressor will ramp down to 0 RPM and de­levitate.
5.2 Modbus Network
In Modbus Network mode, the compressor receives a demand from an external computer, PLC, or building management system using the Modbus protocol on a RS232 or RS485 communication link.
NOTE:
The Chiller Interface interlock switch must be closed and no errors present for the compressor to start up and run.
Danfoss Turbocor Compressors Inc. 15
ECD-00007M Rev. 1
5.2.1 How to Start the Compressor
Open the “Compressor Controller” window. Click on the “Compressor Controller Parameters” icon located below the menu bar.
On the Compressor Control Data form, click in the Loading Demand field and enter a value representing a percentage of maximum power available. (The maximum power available is dependent on the compressor model.) The compressor will levitate and spin up. Refer to Figure 17
Starting and Stopping the Compressor
5.2.2 How to Stop the Compressor
To stop the compressor, enter ‘0’ in the Loading Demand field.
Figure 17 Compressor Control Form
5.3 Chiller Control
The Chiller Control mode is fully automatic and controls the chilled water temperature using a temperature sensor connected directly to the Chiller Interface module. This mode can also be used to control evaporating temperature which is derived from the suction pressure measurement
NOTE:
The Chiller Interface interlock switch must be closed and no errors present for the compressor to start up and run.
5.3.1 How to Start the Compressor
Open the “Chiller Control” window. Select “Window” “Chiller Control” from the menu bar, or click on the “Chiller Control” icon located below the menu bar.
On the Chiller Control form, check the Chiller Enable Status box. The compressor will ramp up and adjust its speed to reach and maintain the setpoint. Refer to Figure 18.
5.3.2 How to Stop the Compressor
On the Chiller Control form, uncheck the Chiller Enable Status box. The compressor will ramp down to 0 RPM and de-levitate.
16 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
Service Monitor User Manual
Figure 18 Chiller Control Form
Danfoss Turbocor Compressors Inc. 17
ECD-00007M Rev. 1
Monitor Program Data and Controls
6 Monitor Program Data and Controls
This section provides a detailed description of the forms and related data and controls that are accessible via the monitor program’s user interface. The forms are organized as follows:
• main system
• bearing calibration
• compressor control
• motor monitoring
• magnetic bearing monitor
• electronic valve tuning
6.1 Main System
The “General Data Page” allows the user to quickly view the following major compressor parameters:
• AC input power
• compressor demand
• shaft speed
• suction temperature/pressure
• discharge temperature/pressure
• IGV % open
To view the “General Data Page”, select “Window” “Main System” from the menu bar. Table 4 provides a description of the “General Data Page” parameters.
The “General Data Page” also plots the following parameters with respect to time:
• chiller control
• system information
• EEPROM settings
• compressor event log
• history data
• trending
• compressor map
• fault captures
• data captures
• evaporating temperature
• condensing temperature
• power input
• shaft speed
•IGV % Open
• demand
The units used to display the temperature readings depend on the measurement unit set (Metric: ºC; Imperial: ºF). To verify or change the measurement unit, refer to section 6.3 "Compressor Control" on page 23. The time displayed corresponds to the PC system time, and is displayed in HH:MM format. To clear the graphs, click on the “Reset Graphs” button.
18 Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
Loading...
+ 47 hidden pages