Danfoss Turbocor Operating guide

MAKING MODERN LIVING POSSIBLE
Installation Guide
Danfoss Turbocor
www.danfoss.com/drives
Contents Installation Guide
Contents
1 Introduction
1.1 Product Overview
1.3 Product Overview
1.4 Internal Controller Functions
2 Safety
2.1 Safety Symbols
3 Installation
3.1 Planning the Installation Site
3.2 Pre-Installation Check List
3.3 Mechanical Installation
3.3.1 Cooling 6
3.3.1.1 Refrigerant Cooling 6
3.3.2 Lifting 7
3.3.3 Wall Mounting - IP21 (NEMA 1) Units 7
3.4 Electrical Installation
3 3 4 4 4
5 5
6 6 6 6
7
3.4.1 General Requirements 7
3.4.2 Grounding Requirements 10
3.4.2.1 Leakage Current (>3.5 mA) 10
3.4.2.2 Grounding IP21 Enclosures 11
3.4.3 Motor Connection 11
3.4.3.1 Terminal Locations 12
3.4.4 Motor Cable 13
3.4.5 Motor Rotation Check 13
3.4.6 AC Mains Connection 13
3.4.7 DC-Link Connection 13
3.5 Control Wiring Connection
3.5.1 Access 14
3.5.2 Using Screened Control Cables 14
3.5.3 Grounding of Screened Control Cables 14
3.5.4 Control Terminal Types 15
3.5.5 Wiring to Control Terminals 16
3.6 Serial Communication
14
16
4 Start Up and Commissioning
4.1 Pre-start
4.2 Applying Power
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 1
17 17 18
Contents Danfoss Turbocor
5 Specifications
5.1 Power-dependent Specifications
5.2 General Technical Data
5.3 Fuse Tables
5.3.1 Protection 22
5.3.2 Fuse Selection 22
5.3.3 Short Circuit Current Rating (SCCR) 23
5.3.4 Connection Tightening Torques 23
Index
19 19 20 22
24
2 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
1
15
14
8
9
12
13 (IP 20/Chassis)
13
(IP 21/54
NEMA 1/12)
11
10
16
130BC252.11
130BC301.11
1
2
3
4
5
6
7
8
9
10
11
Introduction
1 Introduction
1.1 Product Overview
1.1.1 Interior Views
Installation Guide
1
1
Illustration 1.1 D1 Interior Components
LCP (Local Control Panel) 9 Relay 2 (04, 05, 06)
1 2 RS-485 serial bus connector 10 Lifting ring 3 Digital I/O and 24 V power supply 11 Mounting slot 4 Analog I/O connector 12 Cable clamp (PE) 5 USB connector 13 Earth (ground) 6 Serial bus terminal switch 14 Motor output terminals 96 (U), 97 (V), 98 (W) 7 Analog switches (A53), (A54) 15 Mains input terminals 91 (L1), 92 (L2), 93 (L3) 8 Relay 1 (01, 02, 03) 16 TB5 (IP21 only). Terminal block for anti-condensation heater
Table 1.1 Legend to Illustration 1.1 and Illustration 1.2
Illustration 1.2 Close-up View: LCP and Control Functions
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 3
Introduction Danfoss Turbocor
1
1.2 Purpose of the Manual
This manual provides detailed information for the instal­lation and start up of the frequency converter. Chapter 3 Installation provides requirements for mechanical and electrical installation, including:
Input
Motor
Control wiring
Serial communications wiring
Control terminal functions
VLT® is a registered trademark.
1.3 Product Overview
A frequency converter is an electronic motor controller that converts DC into a variable AC waveform output. The frequency and voltage of the output are regulated to control the motor speed or torque. The frequency converter can vary the speed of the motor in response to remote commands from external controllers.
The frequency converter offers many control, monitoring and efficiency functions such as
monitoring the system and motor status
Issuing warnings or alarms for fault conditions
starting and stopping the motor
optimising energy efficiency
Operation and monitoring functions are available as status indications to an outside control system or serial communi­cation network.
1.4
Internal Controller Functions
Illustration 1.3 is a block diagram of the frequency converter's internal components.
Area Title Functions
3-phase AC mains supply to the
1 Mains input
2 Rectifier
3 DC-bus
4 DC reactors
5 Capacitor bank
6 Inverter
7 Output to motor
8 Control circuitry
Table 1.2 Legend to Illustration 1.3
frequency converter
The rectifier bridge converts the
AC input to DC current to supply inverter power.
Intermediate DC-bus circuit
handles the DC current.
Filter the intermediate DC circuit
voltage.
Prove line transient protection.
Reduce RMS current.
Raise the power factor reflected
back to the line.
Reduce harmonics on the AC
input.
Stores the DC power.
Provides ride-through protection
for short power losses.
Converts the DC into a
controlled PWM AC waveform for a controlled variable output to the motor.
Regulated 3-phase output
power to the motor
Input power, internal processing,
output, and motor current are monitored to provide efficient operation and control.
User interface and external
commands are monitored and performed.
Status output and control can
be provided.
Illustration 1.3 Frequency Converter Block Diagram
4 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Safety
Installation Guide
2 Safety
2.1 Safety Symbols
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input power. Qualified personnel only should perform installation, start up, and maintenance. Failure to perform installation, start up, and maintenance by qualified personnel could result in death or serious injury.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, the motor may start at any time. The frequency converter, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the frequency converter is connected to AC mains could result in death, serious injury, equipment, or property damage.
2 2
Table 2.2 Approvals
The frequency converter complies with UL508C thermal memory retention requirements. For more information, refer to the section Motor Thermal Protection in the product specific design guide.
NOTICE
Imposed limitations on the output frequency (due to export control regulations):
From software version 6.72 onwards, the output frequency of the frequency converter is limited to 590 Hz. Software versions 6x.xx also limit the maximum output frequency to 590 Hz, but these versions cannot be flashed, that is, neither downgraded nor upgraded.
WARNING
DISCHARGE TIME
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DC-link power supplies, including battery back­ups, UPS, and DC-link connections to other frequency converters. Wait for the capacitors to fully discharge before performing any service or repair work. The amount of wait time is listed in the Discharge Time table. Failure to wait the specified time after power has been removed before doing service or repair could result in death or serious injury.
Voltage [V] Power range [kW] Minimum waiting time
(minutes)
3x400 110-315 20 3x460 110-315 20 3x575 110-315 20
Table 2.1 Discharge Time
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 5
Installation
Danfoss Turbocor
3 Installation
3.1 Planning the Installation Site
Ensure that frequency converter output current
33
NOTICE
Before performing the installation it is important to plan the installation of the frequency converter. Neglecting this may result in extra work during and after instal­lation.
Select the best possible operation site by considering the following (see details on the following pages and the respective Design Guides):
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Ensure the power source supplies the correct
voltage and necessary current Ensure that the motor current rating is within the
maximum current from the frequency converter If the frequency converter is without built-in
fuses, ensure that the external fuses are rated correctly
Voltage [V] Altitude restrictions
380-500 At altitudes above 3,000 m, contact Danfoss
regarding PELV
525-690 At altitudes above 2,000 m, contact Danfoss
regarding PELV
Table 3.1 Installation in High Altitudes
3.2
Pre-Installation Check List
Before unpacking the frequency converter, ensure
the packaging is intact. If any damage has occurred, immediately contact the shipping company to claim the damage.
Before unpacking the frequency converter, locate
it as close as possible to the final installation site Compare the model number on the nameplate to
what was ordered to verify the proper equipment Ensure each of the following are rated for the
same voltage:
Mains (power)
Frequency converter
Motor
rating is equal to or greater than motor full load current for peak motor performance
Motor size and frequency converter
power must match for proper overload protection
3.3 Mechanical Installation
3.3.1 Cooling
Top and bottom clearance for air cooling must be
provided. Generally, 225 mm (9 in) is required. Improper mounting can result in over heating
and reduced performance
NOTICE
A door fan(s) is required on the enclosure to remove the heat not contained in the backchannel of the frequency converters and any additional losses generated by other components inside the enclosure. The total required air flow must be calculated so that the appropriate fans can be selected.
Airflow
The necessary airflow over the heat sink must be secured. The flow rate is shown in Table 3.2.
Frame Door fan/top fan Heat sink fan
D1h D2h
Table 3.2 Airflow
3.3.1.1
The Danfoss Turbocor frequency converters are equipped with refrigerant cooling.
The refrigerant inlet is on the top of the frequency converter to the left. The refrigerant outlet is on the top of the frequency converters to the right.
Dimensions Material COPPER ALLOY 122, ASTM B-75, annealed Nominal operating pressure Maximum working pressure
Table 3.3 Tubing Specifications
102 m3/hr (60 CFM) 420 m3/hr (250 CFM) 204 m3/hr (120 CFM) 840 m3/hr (500 CFM)
Refrigerant Cooling
3/8 inch OD X 0.049 inch wall thk
10 bar/145 psi
12 bar/174 psi
6 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Installation
Installation Guide
WARNING
CONDENSATION
Condensation must not be allowed to form on the inside of the frequency converter. The flow of refrigerant must be controlled in a way that ensures that the temperature of the internal heatsink stays above the dew point. Failure to control condensation will result in damage to the frequency converter.
3.3.2 Lifting
WARNING
RISK OF INJURY OR DEATH
The lifting bar must be able to handle the weight of the frequency converter to ensure that it will not break during lifting.
See chapter 5.1 Power-dependent Specifications
for the weight of the different enclosure types. Maximum diameter for bar is 2.5 cm (1 inch).
The angle from the top of the frequency
converter to the lifting cable should be 60° or greater.
Failure to follow recommendations could result in death or serious injury.
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous. All electrical work must conform to national and local electrical codes. It is strongly recommended that installation, start up, and maintenance be performed only by trained and qualified personnel. Failure to follow these guidelines could result in death or serious injury.
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in three separate metallic conduits or use separated shielded cable for high frequency noise isolation. Failure to isolate power, motor and control wiring could result in less than optimum frequency converter and associated equipment performance.
3 3
Wall Mounting - IP21 (NEMA 1) Units
3.3.3
Consider the following before selecting the final instal­lation site:
Free space for cooling
Access to open the door
Cable entry from the bottom
3.4
Electrical Installation
3.4.1 General Requirements
This section contains detailed instructions for wiring the frequency converter. The following tasks are described:
Wiring the motor to the frequency converter
output terminals Wiring the AC mains to the frequency converter
input terminals Connecting control and serial communication
wiring After power has been applied, checking input
and motor power
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 7
230 VAC 50/60 Hz
230 VAC 50/60 Hz
TB6 Contactor
TB5
R1
1
2
Brake Temp (NC)
Anti-condensation heater (optional)
(optional)
91 (L1) 92 (L2) 93 (L3)
PE
88 (-) 89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
20 (COM D IN)
15 mA
200 mA
(U) 96
(V) 97 (W) 98 (PE) 99
(COM A OUT) 39
(A OUT) 42
0/4-20 mA
03
+10 VDC
0 VDC - 10 VDC
0/4-20 mA
24 VDC
02
01
05
04
06
240 VAC, 2A
24 V (NPN) 0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN) 0 V (PNP)
27
24 V
0 V
(D IN/OUT)
0 V (PNP)
24 V (NPN)
(D IN/OUT)
0 V
24 V
29
24 V (NPN) 0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
A53 U-I (S201)
ON
21
A54 U-I (S202)
ON=0-20 mA OFF=0-10 V
95
400 VAC, 2A
P 5-00
(R+) 82
(R-) 81
+ - + -
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0 V
5 V
S801
RS-485
RS-485
21
ON
S801/Bus Term. OFF-ON
3 Phase power
input
Load Share
Switch Mode
Power Supply
Motor
Analog Output
Interface
Relay1
Relay2
ON=Terminated OFF=Open
Brake resistor
(NPN) = Sink
(PNP) = Source
= ==
240 VAC, 2A
400 VAC, 2A
0 VDC - 10 VDC
10 VDC
37 (D IN) - option
130BC548.12
Installation Danfoss Turbocor
33
8 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Illustration 3.1 Interconnect Diagram
Motor
Line Power
Stop
Start
Speed
Control
130BX370.10
Installation Installation Guide
For safety, comply with the following requirements
Electronic controls equipment is connected to
hazardous mains voltage. Extreme care should be taken to protect against electrical hazards when applying power to the unit.
Run motor cables from multiple frequency
converters separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out.
Field wiring terminals are not intended to receive
a conductor one size larger.
Overload and equipment protection
An electronically activated function within the
frequency converter provides overload protection for the motor. The overload calculates the level of increase to activate timing for the trip (controller output stop) function. The higher the current draw, the quicker the trip response. The overload provides Class 20 motor protection.
Because the motor wiring carries high frequency
current, it is important that wiring for mains, motor power, and control are run separately. Use metallic conduit or separated shielded wire. See Illustration 3.2. Failure to isolate power, motor, and control wiring could result in less than optimum equipment performance.
3 3
Illustration 3.2 Example of Proper Electrical Installation Using Conduit
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 9
L1
L1L2L2L3L3
2
91 92 93
1
130BB460.11
Installation Danfoss Turbocor
A dedicated ground wire is required for input
power, motor power and control wiring Use the clamps provided with the equipment for
proper ground connections Do not ground one frequency converter to
33
3.4.2.1
1 Fuses 2 Ground
Illustration 3.3 Frequency Converter Fuses
Wire Type and Ratings
All wiring must comply with local and national
regulations regarding cross-section and ambient temperature requirements.
Danfoss recommends that all power connections
be made with a minimum 75 °C rated copper wire.
Grounding Requirements
3.4.2
WARNING
GROUNDING HAZARD!
For operator safety, it is important to ground the frequency converter properly in accordance with national and local electrical codes as well as instructions contained within this document. Do not use conduit connected to the frequency converter as a replacement for proper grounding. Ground currents are higher than
3.5 mA. Failure to ground the frequency converter properly could result in death or serious injury.
Follow national and local codes regarding protective earthing of equipment with a leakage current >3.5 mA. Frequency converter technology implies high frequency switching at high power. This will generate a leakage current in the earth connection. A fault current in the frequency converter at the output power terminals might contain a DC component, which can charge the filter capacitors and cause a transient earth current. The earth leakage current depends on various system configurations including RFI filtering, screened motor cables, and frequency converter power.
EN/IEC61800-5-1 (Power Drive System Product Standard) requires special care if the leakage current exceeds 3.5 mA. Earthing (grounding) must be reinforced in one of the following ways:
See EN 60364-5-54 § 543.7 for further information.
another in a “daisy chain” fashion Keep the ground wire connections as short as
possible Using high-strand wire to reduce electrical noise
is recommended Follow motor manufacturer wiring requirements
Leakage Current (>3.5 mA)
Earth (ground) wire of at least 10 mm
Two separate earth (ground) wires both
complying with the dimensioning rules
2
NOTICE
It is the responsibility of the user or certified electrical installer to ensure correct grounding of the equipment in accordance with national and local electrical codes and standards.
Follow all local and national electrical codes to
ground electrical equipment properly Proper protective earthing for equipment with
ground currents higher than 3.5 mA must be established, see chapter 3.4.2.1 Leakage Current
(>3.5 mA)
10 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
130BC304.10
Installation Installation Guide
3.4.2.2 Grounding IP21 Enclosures
The frequency converter can be grounded using conduit or shielded cable. For grounding of the power connections, use the dedicated grounding points as shown in Illustration 3.4.
Illustration 3.4 Grounding for IP21 Enclosures.
Motor Connection
3.4.3
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency converters separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately could result in death or serious injury.
For maximum cable sizes, see chapter 5.1 Power-
dependent Specifications
Comply with local and national electrical codes
for cable sizes Gland plates are provided at the base of IP21
units Do not install power factor correction capacitors
between the frequency converter and the motor Do not wire a starting or pole-changing device
between the frequency converter and the motor Connect the 3-phase motor wiring to terminals
96 (U), 97 (V), and 98 (W) Earth (ground) the cable in accordance with the
instructions provided Torque terminals in accordance with the
information provided in chapter 5.3.4 Connection Tightening Torques
Follow motor manufacturer wiring requirements
3 3
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 11
A
A
B
B
33
1.3[ ]
0
0.0[ ]
62
2.4[ ]
101
4.0[ ]
140
5.5[ ]
163
6.4[ ]
185
7.3[ ]
224
8.8[ ]
263
10.4[ ]
293
11.5[ ]
GROUND 88
3.5[ ]
0
0.0[ ]
200
7.9[ ]
94
3.7[ ]
244
9.6[ ] 0
0.0[ ]
272
10.7[ ]
0
0.0[ ]
S
U
W
R T V
3X M8x20 STUD WITH NUT
SECTION A-A
MAINS TERMINALS
MAINS TERMINAL
SECTION B-B
MOTOR TERMINALS
MOTOR
TERMINAL
130BC305.10
B
B
A
A
254.7
10[ ]
0.0
0[ ]
GROUND 143.4
6[ ]
0.0 0[ ]
GROUND 168.4
7[ ]
331.2 13[ ]
211.1 8[ ]
GROUND168.4
7[ ]
GROUND143.4
6[ ]
42.4
2[ ]
0.0
0[ ]
68.1
3[ ]
125.8
5[ ]
183.5
7[ ]
245.8
10[ ]
299.8
12[ ]
353.8
14[ ]
377.6
15[ ]
284.2
11[ ]
0.0
0[ ]
R
S
T
U
V
W
4X M10x20 STUD WITH NUT
SECTION B-B
MOTOR TERMINALS AND
BRAKE TERMINALS
MOTOR TERMINAL
SECTION A-A
MAINS TERMINALS
MAINS TERMINAL
130BC332.10
Installation Danfoss Turbocor
3.4.3.1 Terminal Locations
33
Illustration 3.5 Terminal Locations D1h
Illustration 3.6 Terminal Locations D2h
12 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
175HA036.11
U1V
1
W
1
96 97 98
FC
Motor
U
2V2
W
2
U1V
1
W
1
96 97 98
FC
Motor
U
2V2
W
2
130BC254.10
2
1
Installation
Installation Guide
3.4.4 Motor Cable
The motor must be connected to terminals U/T1/96, V/ T2/97, W/T3/98. Earth (ground) to terminal 99. The factory setting is for clockwise rotation with the frequency converter output connected as follows:
Terminal number Function
96, 97, 98, 99
Table 3.4 Terminals for Motor Cable Connection
Motor Rotation Check
3.4.5
The direction of rotation can be changed by switching 2 phases in the motor cable.
Terminal U/T1/96 connected
to U-phase
Terminal V/T2/97 connected
to V-phase
Terminal W/T3/98
connected to W-phase
Mains U/T1, V/T2, W/T3 Earth (ground)
1. Ground the cable in accordance with the instructions provided.
2. Connect 3-phase AC input power wiring to terminals L1, L2, and L3 (see Illustration 3.7).
3 3
Table 3.5 Wiring for Changing Motor Direction
AC Mains Connection
3.4.6
All frequency converters may be used with an
isolated input source as well as with ground reference power lines. When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), set 14-50 RFI Filter to [0] Off. When off, the internal RFI filter capacitors between the chassis and the intermediate circuit are isolated. Isolating the capacitors prevents damage to the intermediate circuit and reduces ground capacity currents in accordance with IEC 61800-3.
Size wiring is based upon the input current of the
frequency converter. Comply with local and national electrical codes
for cable sizes.
1 Mains connection 2 Motor connection
Illustration 3.7 Connecting to AC Mains
DC-Link Connection
3.4.7
Two field terminals are provided for connecting to the DC­Link. The terminals are marked “+REGEN82” and “­REGEN83”.
WARNING
REGEN TERMINALS
Frequency converters contain high voltage The REGEN terminals must be connected to the correct polarity and properly insulated from ground. Qualified personnel only should perform installation, start up, and maintenance. Failure to perform installation, start up, and maintenance by qualified personnel could result in death or serious injury.
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 13
175ZA166.13
0,01 0,1 1 10 100 MHz
10
10
10
1
10
10
10
10
10
a
b
c
d
e
f
g
The lower the Z the better the cable screening performance
Transfer impedance, Z
t
mOhm/m
Installation
Danfoss Turbocor
WARNING
HIGH VOLTAGE
The DC-link of a frequency converter contains high voltage when connected to AC mains input power. Qualified personnel only should perform installation,
33
start-up, and maintenance. Failure to perform instal­lation, start-up, and maintenance by qualified personnel could result in death or serious injury.
Transfer impedance (Z the following factors:
The conductibility of the screen material.
The contact resistance between the individual
screen conductors. The screen coverage, i.e. the physical area of the
cable covered by the screen - often stated as a percentage value.
Screen type, i.e. braided or twisted pattern.
) can be assessed on the basis of
T
WARNING
DISCHARGE TIME
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DC-link power supplies, including battery back­ups, UPS, and DC-link connections to other frequency converters. Wait for the capacitors to fully discharge before performing any service or repair work. The amount of wait time is listed in Table 2.1. Failure to wait the specified time after power has been removed before doing service or repair could result in death or serious injury.
3.5 Control Wiring Connection
3.5.1
All terminals to the control cables are located on the inside of the frequency converter. To access, open the door (IP21).
3.5.2
Danfoss recommends braided screened/armoured cables to optimise EMC immunity of the control cables and the EMC emission from the motor cables.
The ability of a cable to reduce the incoming and outgoing radiation of electric noise depends on the transfer impedance (ZT). The screen of a cable is normally designed to reduce the transfer of electric noise; however, a screen with a lower transfer impedance (ZT) value is more effective than a screen with a higher transfer impedance (ZT).
Transfer impedance (ZT) is rarely stated by cable manufac­turers, but it is often possible to estimate transfer impedance (ZT) by assessing the physical design of the cable.
Isolate control wiring from high power
components in the frequency converter
Access
Using Screened Control Cables
a Aluminium-clad with copper wire b Twisted copper wire or armoured steel wire cable c Single-layer braided copper wire with varying percentage
screen coverage (this is the typical Danfoss reference
cable). d Double-layer braided copper wire e Twin layer of braided copper wire with a magnetic,
screened/armoured intermediate layer f Cable that runs in copper tube or steel tube g Lead cable with 1.1 mm wall thickness
Illustration 3.8 Cable Screening Performance
Grounding of Screened Control
3.5.3 Cables
Correct screening
The preferred method in most cases is to secure control and serial communication cables with screening clamps provided at both ends to ensure best possible high frequency cable contact. If the ground potential between the frequency converter and the PLC is different, electric noise may occur that disturbs the entire system. Solve this
14 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
1
2
PE
FC
PE
PLC
130BB922.12
PE PE
<10 mm
100nF
FC
PE
PE
PLC
<10 mm
130BB609.12
PE
FC
PE
FC
130BB923.12
PE PE
69 68 61
69 68 61
1
2
<10 mm
PE
FC
PE
FC
130BB924.12
PE PE
69
69
68
68
1
2
<10 mm
1
4
2
3
130BA012.12
61
68
69
39
42
50
53
54
55
12
13
18
19
27
29
32
33
20
37
Installation
Installation Guide
problem by fitting an equalizing cable next to the control cable. Minimum cable cross section: 16 mm2.
1
Min. 16 mm
2 Equalizing cable
Illustration 3.9 Correct Screening
2
50/60 Hz ground loops
With very long control cables, ground loops may occur. To eliminate ground loops, connect one end of the screen-to­ground with a 100 nF capacitor (keeping leads short).
Illustration 3.10 Avoiding Ground Loops
1
Min. 16 mm
2
2 Equalizing cable
Illustration 3.12 Screening without Using Terminal 61
3.5.4 Control Terminal Types
3 3
Avoid EMC noise on serial communication
This terminal is connected to ground via an internal RC link. Use twisted-pair cables to reduce interference between conductors. The recommended method is shown below:
Illustration 3.13 Control Terminal Locations
Connector 1 provides four programmable digital
input terminals, two additional digital terminals programmable as either input or output, a 24 V
1
Min. 16 mm
2
2 Equalizing cable
Illustration 3.11 Avoiding EMC Noise
DC terminal supply voltage, and a common for optional customer supplied 24 V DC voltage
Connector 2 terminals (+)68 and (-)69 are for an
RS485 serial communications connection
Connector 3 provides 2 analog inputs, one
analog output, 10 V DC supply voltage, and
Alternatively, the connection to terminal 61 can be omitted:
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 15
commons for the inputs and output
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software Also provided are 2 Form C relay outputs that are
located on the power card
130BT306.10
130BT310.11
Installation Danfoss Turbocor
3.5.5 Wiring to Control Terminals
Terminal plugs can be removed for easy access.
33
Illustration 3.14 Removal of Control Terminals
3.6
Serial Communication
RS485 is a two-wire bus interface compatible with multi­drop network topology. Terminate each segment at both ends, using the termination switch (S801) of the frequency converter. Always use screened twisted pair (STP) cable for bus cabling, and always follow good common installation practice. Low-impedance earth (ground) connection of the screen at every node is important, including at high frequencies. Thus, connect a large surface of the screen to earth (ground), for example with a cable clamp or a conductive cable gland. It may be necessary to apply potential­equalizing cables to maintain the same earth (ground) potential throughout the network. Particularly in instal­lations with long cables.
Cable Screened twisted pair (STP) Impedance
Max. cable length
Table 3.6
120 Ω 1200 m (including drop lines) 500 m station-to-station
Illustration 3.15 Location of Bus Termination Switch
To run STO, additional wiring for the frequency converter is required. Refer to VLT® Frequency Converters Safe Torque
Off Operating Instructions for further information.
16 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Start Up and Commissioning
Installation Guide
4 Start Up and Commissioning
4.1 Pre-start
CAUTION
Before applying power to the unit, inspect the entire installation as detailed in Table 4.1. Check mark those items when completed.
Inspect for Description
Auxiliary equipment
Cable routing
Control wiring
Cooling clearance
EMC considerations
Environmental consider­ations
Fusing and circuit breakers
Grounding
Input and output power wiring
Panel interior
Switches
Vibration
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers on the input
power side of the frequency converter or output side to the motor. Ensure that they are ready for full speed operation.
Check function and installation of any sensors used for feedback to the frequency converter.
Remove power factor correction caps on motors, if present.
Use separate metallic conduits for each of the following:
-
-
-
Check for broken or damaged wires and loose connections.
Check that control wiring is isolated from power and motor wiring for noise immunity.
Check the voltage source of the signals, if necessary.
Use shielded or twisted pair cable. Ensure that the shield is terminated correctly.
Measure that top and bottom clearance is adequate to ensure proper air flow for cooling.
Check for proper installation regarding electromagnetic compatibility.
See equipment label for the maximum ambient operating temperature limits.
Humidity levels must be 5–95%, non-condensing.
Check for proper fusing or circuit breakers.
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are
in the open position.
The unit requires a ground wire from its chassis to the building ground.
Check for good ground connections that are tight and free of oxidation.
Grounding to conduit or mounting the back panel to a metal surface is not sufficient.
Check for loose connections.
Check that motor and mains are in separate conduit or separated screened cables.
Inspect that the unit interior is free of debris and corrosion.
Ensure that all switch and disconnect settings are in the proper positions.
Check that the unit is mounted solidly or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
Input power
Motor wiring
Control wiring
4 4
Table 4.1 Start-up Checklist
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 17
Start Up and Commissioning Danfoss Turbocor
4.2 Applying Power
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when connected to the energised DC bus. Only qualified personnel should install, start up and maintain the freqeuncy converters. Failure to let qualified personnel
44
install, start up and maintain the frequency converters could result in death or serious injury.
WARNING
UNINTENDED START!
When the frequency converter is connected to the energised DC bus, the motor may start at any time. The frequency converter, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the frequency converter is connected to the energised DC bus could result in death, serious injury, equipment, or property damage.
1. Confirm input voltage is balanced within 3%. If not, correct input voltage imbalance before proceeding. Repeat procedure after voltage correction.
2. Ensure optional equipment wiring, if present, matches installation application.
3. Ensure that all operator devices are in the OFF position. Panel doors closed, or a cover mounted.
4. Apply power to the unit. DO NOT start the frequency converter now. For units with a disconnect switch, turn to the ON position to apply power to the frequency converter.
18 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Specifications
Installation Guide
5 Specifications
5.1 Power-dependent Specifications
DTC 302 N165 N232 N262
Typical shaft output at 400 V [kW] 165 232 262 Typical shaft output at 460 V [hp] 221 311 352 Enclosure IP21 D1h D2h D2h
Output current
Continuous (at 400 V) [A] 318 424 480 Continuous (at 460 V) [A] 263 350 443 Continuous kVA (at 400 V) [kVA] 179 252 285 Continuous kVA (at 460 V) [kVA] 179 252 285
Max. input current
Continuous (at 400 V) [A] 271 380 430 Continuous (at 460 V) [A] 235 330 374 Max. cable size: mains, motor, mm (AWG) 2x95 (2x3/0 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm) Max. external mains fuses [A] 400 550 630 Estimated power loss at 400 V [W] 4271 5232 6203 Estimated power loss at 460 V [W] 3561 4390 5830 Efficiency 0.98 Output frequency [Hz] 0–590 Heat sink overtemperature trip [°F] ([°C]) Control card ambient trip [°F] ([°C])
158 (70) 149 (65) 149 (65)
230 (110)
5 5
Table 5.1 Mains Supply 3x380-500 V AC
DTC 302 N165 N232
Typical shaft output at 575 V [kW] 165 232 Typical shaft output at 575 V [hp] 221 311 Enclosure IP21 D1h D2h
Output current
Continuous (at 575 V) [A] 205 286 Continuous kVA (at 575 V) [kVA] 179 252
Max. input current
Continuous (at 575 V) [A] 188 264 Max. cable size: mains, motor, mm (AWG) 2x95 (2x3/0) 2x185 (2x350) Max. external mains fuses [A] 315 550 Estimated power loss at 575 V [W] 3873 5288 Weight, enclosure IP21 kg (lbs.) 62 (135) 125 (275) Efficiency 0.98 Output frequency [Hz] 0–590 Heat sink overtemperature trip [°F] ([°C]) Control card ambient trip [°F] ([°C])
Table 5.2 Mains Supply 3x575 V AC
The typical power loss is at nominal load conditions and expected to be within ±15% (tolerance relates to variety
167 (75) 176 (80)
230 (110)
in voltage and cable conditions). The losses are based on the default switching frequency. The losses increase significantly at higher switching
frequencies.
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 19
Specifications
Danfoss Turbocor
5.2 General Technical Data
Mains supply (L1, L2, L3) Supply voltage 380-500 V ±10%, 575 V ±10%
Mains voltage low/mains voltage drop-out: During low mains voltage or a mains drop-out, the frequency converters continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply voltage.
Supply frequency 50/60 Hz ±5% Max. imbalance temporary between mains phases 3.0% of rated supply voltage
55
True Power Factor (λ) 0.9 nominal at rated load Displacement Power Factor (cos Φ) near unity (>0.98) Switching on input supply L1, L2, L3 (power ups) maximum one time/2 minutes Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480/600 V
Motor Output (U, V, W) Output voltage 0-100% of supply voltage Output frequency 0-590 Hz* Switching on output Unlimited Ramp times 0.01-3600 s
* Dependent on voltage and power
Cable lengths and cross sections Max. motor cable length, screened/armoured 150 m Max. motor cable length, unscreened/unarmoured 300 m Max. cross section to motor, mains* Maximum cross section to control terminals, rigid wire 1.5 mm2/16 AWG (2x0.75 mm2) Maximum cross section to control terminals, flexible cable 1 mm2/18 AWG Maximum cross section to control terminals, cable with enclosed core 0.5 mm2/20 AWG Minimum cross section to control terminals 0.25 mm
Digital inputs Programmable digital inputs 4 (6) Terminal number 18, 19, 271), 291), 32, 33 Logic PNP or NPN Voltage level 0-24 V DC Voltage level, logic '0' PNP <5 V DC Voltage level, logic '1' PNP >10 V DC Voltage level, logic '0' NPN >19 V DC Voltage level, logic '1' NPN <14 V DC Maximum voltage on input 28 V DC Input resistance, R
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Control card, RS485 serial communication Terminal number 68 (P,TX+, RX+), 69 (N,TX-, RX-) Terminal number 61 Common for terminals 68 and 69
The RS485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the supply voltage (PELV).
i
approx. 4 kΩ
2
20 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Specifications Installation Guide
Control card, 24 V DC output Terminal number 12, 13 Max. load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV ), but has the same potential as the analog and digital inputs and outputs.
Control characteristics Resolution of output frequency at 0-1000 Hz ±0.003 Hz System response time (terminals 18, 19, 27, 29, 32, 33) 2 ms Speed control range (open loop) 1:100 of synchronous speed Speed accuracy (open loop) 30-4000 rpm: Maximum error of ±8 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings Enclosure type D1h/D2h IP21/Type 1 Vibration test all enclosure types 0.7 g Relative humidity 5%-95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation Aggressive environment (IEC 60068-2-43) H2S test Test method according to IEC 60068-2-43 H2S (10 days) Ambient temperature (at 60AVM switching mode)
- at full continuous FC output current max. 104 °F [40 °C]
class Kd
5 5
Minimum ambient temperature during full-scale operation 0 °C Minimum ambient temperature at reduced performance - 10 °C Temperature during storage/transport -25 to +65/70 °C Maximum altitude above sea level without derating 1,000 m Maximum altitude above sea level with derating 3,000 m
1) For more information on derating see the Design Guide, section on Special Conditions.
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
EMC standards, Immunity
See the Design Guide, section on Special Conditions.
Control card performance Scan interval 5 ms Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips if the temperature reaches
95 °C ±5 °C. An overload temperature cannot be reset until the temperature of the heat sink is below 70 °C ±5 °C (Guideline - these temperatures may vary for different power sizes, enclosures etc.).
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high. The frequency converter is protected against earth (ground) faults on motor terminals U, V, W.
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 21
Specifications Danfoss Turbocor
5.3 Fuse Tables
5.3.1 Protection
Branch circuit protection
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and over-current protected according to national/international regulations.
Short-circuit protection
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below to protect service personnel and equipment in case of an internal failure in the frequency conveter. The frequency converter provides full short-circuit protection in case of a short-circuit on the motor output.
55
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The frequency converter is equipped with an internal over-current protection that can be used for upstream overload protection (UL­applications excluded). Moreover, fuses or circuit breakers can be used to provide the over-current protection in the installation. Over-current protection must always be carried out according to national regulations.
Fuse Selection
5.3.2
Danfoss recommends using the following fuses which ensures compliance with EN 50178. In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical).
N165, N232, N262 N165, N232 575 V type aR
Table 5.3 Recommended Fuses
VLT Model
N165 T5 170M2621 LA50QS400-4 L50S-400 FWH-400A 20 610
N232 T5 170M4015 LA50QS500-4 L50S-500 FWH-500A 20 610
N262 T5 170M4016 LA50QS600-4 L50S-600 FWH-600A 20 610
Table 5.4 Fuse Options for 380–500 V Frequency Converters
Table 5.5 Fuse Options for 575 V Frequency Converters
BussmanPNLittelfuse PN LittelfusePNBussmannPNSiba PN Ferraz ShawmutPNFerraz Shawmut PN
VLT Model Bussmann PN Siba PN Ferraz Shawmut European PN Ferraz Shawmut North American PN
N165 T7 170M2619 20 610 31.315 6,9URD31D08A0315 A070URD31KI0315 N232 T7 170M4015 20 620 31.550 6,9URD32D08A0550 A070URD32KI0550
380–500 V type aR
31.400
31.550
31.630
Ferraz Shawmut PN
(Europe)
A50QS400-4 6,9URD31D08A0400 A070URD31KI0400
A50QS500-4 6,9URD31D08A0550 A070URD31KI0550
A50QS600-4 6,9URD31D08A0630 A070URD31KI0630
(North America)
For UL compliance, use the Bussmann 170M series.
22 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Specifications Installation Guide
5.3.3 Short Circuit Current Rating (SCCR)
The Short Circuit Current Rating (SCCR) of the frequency converters is 100,000 amps at all voltages (380–575 V).
5.3.4 Connection Tightening Torques
When tightening all electrical connections it is very important to tighten with the correct torque. Too low or too high torque results in a bad electrical connection. Use a torque wrench to ensure correct torque. Always use a torque wrench to tighten the bolts.
5 5
Frame size
D1h Mains
D2h Mains
Table 5.6 Torque for Terminals
Terminal Torque [Nm (in-lbs)] Bolt
Motor Load sharing Regen Earth (Ground) Brake
Motor Regen Load sharing Earth (ground) Brake 8.5-20.5 (75-181) M8
size
19-40 (168-354) M10
8.5-20.5 (75-181) M8
19-40 (168-354) M10
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 23
Index Danfoss Turbocor
Index
A
AC input............................................................................................... 4, 13
AC mains................................................................................................ 4, 5
AC mains connection.......................................................................... 13
AC waveform............................................................................................ 4
Airflow......................................................................................................... 6
Analog input.......................................................................................... 15
Analog output....................................................................................... 15
B
Block diagram........................................................................................... 4
C
Cable length........................................................................................... 20
Check list, pre-installation.................................................................... 6
Circuit breaker....................................................................................... 17
Conduit................................................................................................ 9, 17
Control cable.......................................................................................... 15
Control cable, screened..................................................................... 15
Control card performance................................................................. 21
Control card, 24 V DC output........................................................... 21
Control card, RS485 serial communication................................. 20
Control characteristic.......................................................................... 21
Control system......................................................................................... 4
Control terminal.................................................................................... 16
Control terminal type.......................................................................... 15
Control wiring........................................................................ 7, 9, 10, 17
Control wiring connection................................................................ 14
Cooling clearance................................................................................. 17
Cross section.......................................................................................... 20
Current rating........................................................................................... 6
D
DC current.................................................................................................. 4
Derating............................................................................................... 6, 21
Digital input..................................................................................... 15, 20
Discharge time......................................................................................... 5
Disconnect switch................................................................................ 18
E
Electrical installation.............................................................................. 7
Electrical noise....................................................................................... 10
EMC.............................................................................................. 15, 17, 21
Equalizing cable.................................................................................... 15
External command................................................................................. 4
External controller.................................................................................. 4
F
Feedback................................................................................................. 17
Floating delta......................................................................................... 13
Frequency converter block diagram................................................ 4
Full load current...................................................................................... 6
Functional testing................................................................................... 4
Fuse........................................................................................................... 17
Fusing................................................................................................... 9, 17
G
Ground connection....................................................................... 10, 17
Ground loop........................................................................................... 15
Ground wire..................................................................................... 10, 17
Grounded delta..................................................................................... 13
Grounding........................................................................................ 10, 17
Grounding hazard................................................................................ 10
Grounding, IP21/54 enclosure......................................................... 11
Grounding, screened control cable............................................... 15
H
Harmonic.................................................................................................... 4
I
IEC 61800-3............................................................................................. 21
Induced voltage....................................................................................... 9
Input current.......................................................................................... 13
Input power....................................................................... 4, 5, 7, 10, 17
Input voltage.......................................................................................... 18
Installation.............................................................................. 4, 9, 17, 18
Installation site......................................................................................... 6
Installation, electrical............................................................................. 7
Installation, mechanical........................................................................ 6
Isolated mains........................................................................................ 13
L
Leakage current (>3.5 mA)................................................................ 10
M
Mains........................................................................................................... 9
Mains supply (L1, L2, L3).................................................................... 20
Mechanical installation......................................................................... 6
Motor cable................................................................................. 9, 11, 13
Motor connection................................................................................. 11
24 Danfoss A/S © 01/2015 All rights reserved. MG35Q202
Index Installation Guide
Motor current........................................................................................... 4
Motor output (U, V, W)........................................................................ 20
Motor power............................................................................................. 9
Motor protection.............................................................................. 9, 21
Motor rotation check.......................................................................... 13
Motor status.............................................................................................. 4
Motor wiring.................................................................................. 7, 9, 17
Mounting................................................................................................. 17
Multiple frequency converters.................................................... 9, 11
N
Noise isolation................................................................................... 7, 17
O
Open loop............................................................................................... 21
Optional equipment............................................................................ 18
Overload protection.......................................................................... 6, 9
P
PELV.................................................................................................... 14, 21
Power........................................................................................................ 10
Power connection................................................................................ 10
Power factor................................................................................ 4, 11, 17
Pre-installation check list..................................................................... 6
Product overview.................................................................................... 3
Programming........................................................................................... 4
Protection................................................................................................ 22
Protection, feature............................................................................... 21
STO............................................................................................................. 16
Supply voltage................................................................................ 14, 15
Surroundings......................................................................................... 21
System feedback..................................................................................... 4
T
Temperature limit................................................................................. 17
Terminal location, D1h....................................................................... 12
Terminal location, D2h....................................................................... 12
Thermal protection................................................................................ 5
Thermistor............................................................................................... 14
Thermistor control wiring................................................................. 14
Torque, terminal................................................................................... 23
Transient protection.............................................................................. 4
Trip function............................................................................................. 9
Troubleshooting...................................................................................... 4
W
Wire type, rating................................................................................... 10
Wiring, control terminal..................................................................... 16
R
Relay output........................................................................................... 15
Remote command.................................................................................. 4
Reset.......................................................................................................... 21
RFI filter.................................................................................................... 13
RMS current............................................................................................... 4
RS485........................................................................................................ 16
S
Safe torque off....................................................................................... 16
Screened control cable....................................................................... 15
Screened control cable, using.......................................................... 14
Serial communication............................................................. 4, 15, 16
Shielded cable................................................................................... 7, 17
Shielded wire............................................................................................ 9
Specification............................................................................................. 4
Start-up....................................................................................................... 4
MG35Q202 Danfoss A/S © 01/2015 All rights reserved. 25
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten www.danfoss.com/drives
130R0572 MG35Q202 01/2015
*MG35Q202*
Loading...