TPOne is an intelligent programmable heating control
made easy. TPOne includes features which are designed
to save energy. Look out for the leaf symbol throughout
this guide for settings which can directly inuence the
energy saved.
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other
printed material. All trademarks in this material are property of the respective companies.
Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2
TPOne-M
Installation Instructions
ErP
4
SpecicationsTPOne-M
Operating Voltage230Vac, 50/60Hz
Output 1 (Heating)Volt Free
Setting temperature range5-35°C
Operating temprature range0-45°C
Switch rating 13A (1) at 230Vac
Switch type 11 x SPDT Type 1B
Output 2 (Domestic Hot Water) 230Vac
Switch rating 2 3A (1) at 230Vac
Switch type 2 1 x SPDT Type 1B
IP ratingIP20
On/o controlYes
Chrono-proportional controlYes
Operating modeHeating
ConstructionEN 60730-2-9
Control pollution situationDegree 2
Rated impulse voltage2.5kV
Ball pressure test75°C
Dimensions (mm)H67 x W154 x D30
Software ClassicationA
ErP Class
The products represented within this document are classied according
to, and allow completion of, the Energy Related Product (ErP) Directive
System Package che and the ErP system data label. ErP Labelling
obligation is applicable from 26th September 2015.
ERP Class Product Function and ErP Description
TPI Room Thermostat, for use with on/off
IV
output heaters
An electronic room thermostat that controls
both thermostat cycle rate and in-cycle on/
o ratio of the heater proportional to room
temperature. TPI control strategy reduces
mean water temperature, improves room
Product
temperature control accuracy and enhances
Class
system eciency.
Additional
efficiency
gain
2%
Danfoss Heating
3
OK
Mounting
Thermostat or Remote Room Sensor positioning:
Please note: This product should only be installed by
a qualied electrician or competent heating installer
and should be in accordance with the local wiring
regulations.
4
TPOne-M
ELECTRONICS
NC2
NO2
N
L
COM
COM
ON
NO1
S1
S2
ON
OFF
Remote
Sensor
Channel 2
*DHW
3A at 230Vac
Channel 1
Heating
Volt Free
3A at 230Vac
230Vac
50/60Hz
Wiring
* Domestic hot water, optional timed output only
P
O
Remote sensor inputs
S1
S2
S1
S2
Remote room or limit sensor
Window switch contact
NOTE:
Remote Sensor to be wired with 1mm 2 core double insulated cable
only. Cable length should not exceed 10 metres. Sensor cable should
NOT be run parallel to mains cable.
Danfoss Heating
5
User Interface
Comfort modes
Display
Navigation
Comfort Modes
Heating made easy: TPOne Comfort Modes simplify the way you
plan your heating day to day. You dene your comfort modes in the
user schedule and manually override when you need, allowing you
to adapt your schedule to the way you live.
The Home, Away and Asleep comfort modes are linked to your
dened comfort temperatures. The schedule follows the daily
routine you have set or you just choose the comfort mode required
and TPOne will recall the settings you have dened.
The TPOne Standby Mode allows you to switch your heating o
when not required although the thermostat continues to monitor
the room temperature and call for heating should there be a risk of
frost damage.
NOTE:
TPOne has been designed with touch sensitive user interface
buttons. To avoid accidental setting changes the interface buttons
stay in an idle state during which time the first button press needs
to be made for 1sec, this will place the TPOne into an active setting
state. While active the TPOne will respond immediately to any valid
key press. If no key presses are made for 30secs the buttons will go
back to an idle state.
6
TPOne-M
Comfort Modes
Home Mode selects the home comfort
temperature typically when the home is
occupied during the day. The required
temperatures for Home mode are selectable
in the Temperature setting (see User Menu
> Temperatures.) A separate Home AM and
Home PM temperature can be chosen and
these are automatically set according to the
Home
time of the day.
Note: When in Home mode if the home button
is pressed again a 1, 2 or 3 hour heating boost
is selected and the current home period is
extended by the chosen time period. The
chosen boost period is displayed under the
Home icon on the display.
Away Mode selects the away comfort
temperature typically when the home is
unoccupied during the day. The required
Away
temperature for Away mode is selectable in
the Temperature setting (see User Menu >
Temperatures).
Asleep Mode selects the nightime comfort
temperature which is set between the end
of the last home period of the day and the
Asleep
beginning of the rst home period of the
following day. The required temperature for
Asleep mode is selectable in the Temperature
setting (see User Menu > Temperatures).
The TPOne can be placed in Standby Mode. While in Standby the TPOne will
not control the heating system other than
to protect against frost damage (see User
Menu > Installer Settings > Frost Protect for
Standby
information on frost protect). Standby can
be cancelled by pressing the Standby button
again or by selecting another comfort mode.
Note: the standby option places the heating
control in standby only, if Hot Water is set
up this is not affected. To switch Hot Water
control off see User Menu > Hot Water > Mode
Danfoss Heating
7
Navigation
Menu
Select /
OK
Conrm
Menu
Back
Naviga-
OK
tion
Press Menu to access the intuitive text menu.
The common feature User Menu will be
displayed rst. Additional settings can found
in the User Setting option and more advance
settings can be found in the Installer Setting
option.
Press OK to select menu options or conrm
settings. OK will be shown on the display
when it can be used or is required.
Press to exit a menu option. Pressing
while in a setting will result in that setting
change not be accepted. will also exit the
menu system. will be shown on the display
when it can be used
The Navigation buttons are used to navigate
the TPOne menus and change setting values.
The up & down buttons are also used to
manually change the required temperature.
Navigation arrows will be shown on the
display when these buttons can be used.
8
TPOne-M
Display
16:35 Mon
21
°
.5
Info & SettingsStatus Icons
Indicates that Button Lock has been
Button
Lock
Heat
Calling
Hot
Water
Calling
NOTE:
TPOne monitors several conditions and will provide warning or
information messages when necessary. Details on these can be
found on pages 24 - 26.
activated to avoid unintentional setting
changes. To activate buttons while button
lock is active press the OK button for 5
seconds. The Button Lock setting is found in
the Installer Menu.
When the current room temperature is
below the required room set temperature
the TPOne will call for heating from the
connected heat source. This is indicated by
the Heat Calling icon.
Where the TPOne has been set up for control
of domestic hot water the TPOne will call for
hot water heating according to the user set
schedule. This is indicated by the Hot Water
Calling icon.
Dates &
Warnings
Danfoss Heating
9
Setup Wizard
OK
OKOKOK
OK
OK
OK
The setup wizard will run when power is rst applied to the TPOne.
Once set the further changes can be made in the user and installer
setting menus.
Language
English
OK
Set Date
04 - 02 - 2016
OK
OK
OK
OK
Set Time
24hr - 10 : 45
OK
Hot Water Setup
O
OK
10:45 Thurs
o
21.
READY
10
5
TPOne-M
Set Temperatures
OK
OK
OK
OK
Follow this routine to set required Comfort Mode temperatures.
Changes can be made for each mode, once all changes have been
made press OK and a conrmation screen will display the new
settings.
See page 22 for default temperatures
10:45 Thurs
o
21.
5
User Menu
OK
OK
Temperatures
Danfoss Heating
21.
o
0
OK
OK
Temperatures
AM 21.
OK
Home AM - 21.
Home PM - 22.
Away - 16.
Asleep - 12.
o
0
o
0
o
0
C
o
5
C
o
0
C
C
OK
User Menu
Temperatures
OK
11
Setup Schedule
OK
OK
OK
OK
Follow this routine to set Heating Schedule. Days can be set
individually or grouped and options for weekdays and weekend
settings can be selected. All day combinations can then have one,
two or three Home Periods selected. TPOne will automatically ll in
the gaps with Away and Asleep Periods depending on the time of
the day.
Where TPOne is set up to control domestic hot water as well as
heating there is a dedicated Hot Water schedule which can be set
See page 22 for default schedule times
10:45 Thurs
o
21.
5
User Menu
Schedule
OK
OK
OK
OK
Schedule
Heating
OK
Schedule - Heating
Select Days
OK
Schedule - Heating
Mon Tues Weds Thurs
OK
Mon
12
Thurs
OK
FriSatSun
OK
TPOne-M
OKOKOK
OKOKOK
OK
OK
OK
OK
Setup Schedule (Continued)
Schedule - Heating
Mon Tues Weds Thurs
SatSun
OK
OK
OK
OK
OK
Fri
OK
Select Home Periods
3
OK
Home Period - 1
From To
06.00 08.30
OK
Home Period - 2
From To
12.30 13.30
OK
Home Period - 3
From To
17.30 22.30
OK
Danfoss Heating
3s
Sechedule - Heating
Your heating schedule
has been saved
User Menu
Schedule
OK
13
User Menu
Hot WaterUser override settings for Domestic Hot Water:
Click & Save Click & Save is an easy access saving function.
Heating
Mode
Boost - choose to extend the current hot water
heating period for 1, 2 or 3 hours. Once boost
time is nished hot water heating will return to
user set schedule.
Mode - choose between scheduled on or o.
Scheduled mode will follow the user set hot water
heating schedule. O mode will switch hot water
heating o and will remain o until set back to
scheduled.
Default settings:
Boost - O
Mode - Scheduled
Note: The Domestic Hot Water feature will be set at
installation and will require a separate hot water
cylinder thermostat and suitable wiring to the
boiler. If the TPOne has been installed for heating
only this menu option will not be given. The hot
water heating feature can be deactivated after
installation, see User Menu > Installer Settings >
Hot Water Setup
Switching Click & Save ON will reduce the user set
comfort temperatures by 1°C. Switching Click &
Save OFF will return TPOne to the user set comfort
temperatures.
Default setting: O
Note: Independent tests have shown that a
reduction in home heating temperatures by 1oC
can save on average 10% energy.
Heating Mode will change the TPOne from a
thermostat with full user set heating schedule to a
manually set temperature only thermostat.
In schedule mode the thermostat will follow the
user set heating schedule.
In manual mode the user set schedule will be
ignored, the required comfort mode is then
chosen manually.
Default setting: Scheduled
14
TPOne-M
User Menu (Continued)
ScheduleUser set heating schedule option:
Tempertures User set comfort temperatures (heating),
HolidayHoliday feature allows you to set in advance your
Heating - settings for the daily heating schedule.
Choose weekday, weekend or independent daily
options and 1,2 or 3 periods per day.
Option to reset daily heating schedule to factory
defaults.
Hot Water - settings for the daily domestic hot
water schedule. Choose weekdays, weekend or
independent daily options and 1,2 or 3 periods
per day. (Option only available if TPOne has been
congured for domestic hot water control)
Option available to reset daily domestic hot water
schedule to factory defaults.
Summary - graphical overview of the set daily
heating or hot water schedule
Default settings: see default heating times later
in this guide
individual comfort temperatures for Home AM,
Home PM, Away and Asleep.
Home AM and Home PM temperatures will be set
during the home periods chosen in the user set
heating schedule, see User Menu > Schedule
Away temperature will be set during the day
between the home periods. Asleep temperature
will be set during the night between the home
periods.
Default settings:
Home AM - 20°C
Home PM - 20°C
Away - 15°C
Asleep - 15°C
holiday dates. TPOne will reduce the heating
to your chosen Holiday temperature on the rst
day set to save energy and will return to your set
schedule and mode temperatures on the return
date to ensure the home is comfortable for your
return.
Enter start and end date of your holiday and the
required energy saving home temperature..
Danfoss Heating
15
User Settings
Set Date
Set Time
Button Click Button Click is an audible feedback feature
BacklightWhen buttons are pressed on the TPOne the
Temperature
Scale
LanguageChoose menu language
User ResetUser Reset will return user settings only to the
Information
Option to set the current date.
Option to set the current time and 12 or 24hr clock
setting.
to conrm button press. Button Click can be
switched On or O
Default setting: On
display backlight will come on to aid viewing.
Where backlight is not required this feature can be
switched o.
Default setting: On
Choose between centigrade °C or fahrenheit °F
Default setting: °C
Default: English
Note: if required a reset menu language feature
is available, press and hold OK for 5secs and the
option to change language will be given.
TPOne factory default.
Note: User Reset will not reset settings in the first
level user menu or the date and time.
Information on product type, software level and
boiler service interval date if set.
16
TPOne-M
Installer Settings
Hot Water
Setup
Control Type This allows the thermostat to be set to run in On/
The TPOne-M can be used as a single channel
programmable thermostat to control the
temperature regulation of the heating system only
or as a two channel programmable thermostat
to control the heating and the time schedule of
a domestic hot water circuit. The domestic hot
water selection will have been chosen in the
startup wizard on initial installation. Choose this
setting after installation to switch the domestic
hot water option on/o.
Default: Set at startup
Note: Settings in the menu which are required for
domestic hot water are only accessable if the Hot
Water Setup is switched on. TPOne-M controls
only the time schedule for domestic hot water and
should always be used with a suitable hot water
cylinder thermostat.
O mode or in chrono-proportional 3, 6 or 12
cycle rate.
Default: Chrono 6
Note: for condensing boiler control tests have
shown that boiler efficiency is significantly
improved when controlled by a chronoproportional type controller
Danfoss Heating
17
Installer Settings (Continued)
Start-up
Method
Temperature
Limits
Frost Protect To help protect against damage to the heating
Temperature
Override
This feature allows the thermostat to start up the
heating system in three dierent ways.
Normal - Heating is turned up or down at the
programmed times.
Delayed start (or Economy Setting) Set the period start times in the normal way
taking into account the time that the building
takes to heat on an average day. The thermostat
monitors switch on time, actual temperature and
wanted temperature and delays the start of the
heating if the actual temperature is close to the
programmed temperature. Delayed Start in TPOne
is dynamic and will adjust automatically to the
home heating characteristics while maximising
energy savings.
Optimised Start (or Comfort Setting) -
This allows you to programme the time at
which you would like to be up to the required
temperature. The thermostat then calculates
how soon before the required time the heating is
turned up. Optimised Start in TPOne is dynamic
and will adjust automatically to the home heating
characteristics to reach required temperature at
the required time.
Default: Normal
This allows the upper and lower temperature of
the thermostat setting range to be limited.
Defaults:
Minimum 5°C,
Maximum 35°C
system caused by extreme low temperatures the
TPOne includes a Frost Protect level. This is the
minimum temperature level and is also used when
the TPOne is placed in standby mode.
Default: 5°C
This establishes the degree of manual temperature
override available to the user, No Limit, Limited +/2°C or No Override
Default: No Limit
18
TPOne-M
Installer Settings (Continued)
Daylight
Saving
Button Lock Button lock can be set to avoid unintentional
Display Idle
Mode
External
Sensor
Danfoss Heating
Choose to set automatic daylight saving changes
on or o.
Default: On
setting changes. To activate buttons while button
lock is active the user must press the OK button
for 5 seconds.
Default: O
When the TPOne is in idle mode the display can be
set to go o. The display will come on when any
button is pressed.
Default: On
TPOne includes an optional external sensor input.
If tted select the type of external sensor:
None - No external sensor tted
Room Sensor - Remote room sensor tted. This
will take priority over the TPOne internal sensing.
Danfoss part TS2A - sold seperately
Window Sensor - Where a window sensor has
been tted the TPOne will go into standby mode
while the window is open. Window open feature
is activated 60secs after input is made open circuit.
Window open feature is deactivated 30secs after
input is made closed circuit.
Floor Limit Sensor - This allows for a thermostat
limit sensor to be set, typical application is oor
heating. If the temperature sensed by the limit
sensor exceeds the limit setting the output will be
turned o until the temperature has dropped by
2°C. A warning will be shown on the display that
the oor limit temperature has been exceeded.
Room temperature will be controlled by the
TPOne internal sensor.
The temperature set for the limit point sensor will
be determined by the type of oor.
The recommended limits are:
Tiles on chipboard and wooden oors 27°C
Carpet or vinyl on chipboard 35°C
Tiles on concrete oor 40°C
Concrete, screed, etc 45°C
Danfoss Part TS3 - sold seperately
Lockout - Where a Key lockout switch is tted
the TPOne can be forced into the standby mode
remotely. While activated none of the buttons
can be used and the TPOne will only call for heat
if room temperature falls below set frost protect
level. Lockout feature is activated 60secs after
input is made open circuit. Feature is deactivated
30secs after input is made closed circuit.
19
Installer Settings (Continued)
Service
Interval
Service
Demo
Installer Lock TPOne allows the installer to lock all installer
Installer
Reset
TPOne incorporates a service interval timer where
a service due date for the boiler can be set. The
service interval timer is passcode protected and
must only be set by a qualied heating installation
engineer. The installer can set the service due date
and select from one of four service due restriction
modes:
1 - Warning Only - visual and audible warnings
only, no reduction of heat.
2 - Heat 45min/hr - visual and audible warnings
with reduction of heat to 45 minutes per hour.
3 - Heat 30min/hr - visual and audible warnings
with reduction of heat to 30 minutes per hour.
4 - Heat 15min/hr - visual and audible warnings
with reduction of heat to 15 minutes per hour.
5 - No Heating - visual and audible warnings
with no heating.
Once set, the service interval timer can only be
reset or deactivated by an installer having the
correct access code. Additional information on
Service Interval can be found later in this guide
Note: If the TPOne is fitted to a combination
boiler, thefunction only works in conjunction
with a heating demand, hot water production is
unaffected.
Choose this feature to provide a demonstation of
the audible and visual warning which will be given
when service is due.
settings by means of a passcode. The 3 digit
passcode can be chosen and set by the installer
and once set will be required to make any installer
setting changes.
Select option to reset all installer settings to
factory defaults.
Note: Service interval will not be reset and can
only be reset or deactivated by entering the service
interval setup.
20
TPOne-M
Service Interval
If the property is owned by a landlord he may, for gas safety reasons,
have instructed the installer to set the service interval timer. The
feature is primarily aimed at the rented property sector where the
Landlord has a legal responsibility under gas safety regulations* to
ensure that the boiler is serviced every year.
- If set, 28 days prior to the service due date, an audible warning will
start each day at noon, the service icon will also be displayed. The
audible warning will last for 10 seconds and will be repeated every
hour until a button is pressed to cancel it. If cancelled the alarm will
recommence the following day at noon.
- If the boiler is not serviced before the due date, an audible
warning will start each day at noon, the service icon will also
be displayed. The audible warning will last for 1 minute and will
be repeated every hour until a button is pressed to cancel it. If
cancelled the alarm will recommence the following day at noon.
- In addition, all overrides and programming buttons will be
disabled and the Heating and Hot Water may operate for a limited
amount of time each hour.
- The installer may cancel or reset the service interval timer as part
of the boiler service.
- This is a gas safety feature that can only be accessed by a qualied
heating installation engineer.
*Gas Safety Regulations may vary according to region
Danfoss Heating
21
Default tables
SCHEDULE DEFAULTS
1
06:30 - 22:30
(Weekend
07:30 - 22:30)
2
06:30 - 08:30
(Weekend
07:30 - 09:30)
16:30 - 22:30
3
06:30 - 08:30
(Weekend
07:30 - 09:30)
11:30 - 13:30
16:30 - 22:30
Note: Where TPOne has been set up for domestic hot water
control the default schedule for hot water is the same as for
heating. In schedule set up user can set one, two or three ON
periods, TPOne will automatically ll in gaps with OFF periods
22
TPOne-M
Default tables (Continued)
TEMPERTURE DEFAULTS
20°C
AM
20°C
PM
15°C
15°C
Danfoss Heating
23
Information
TPOne will show information related to current operation, these
messages will be shown at the top of the display.
Information messages will be displayed while the operation is active
and will automatically reset when operation is completed
Window
Open
Product Lock This will be displayed where a product lock switch
Optimised
Start
Delayed
Start
This will be displayed where a window open
switch has been tted and the window is opened.
see page 19
has been tted and the switch has been activated.
see page 19
If the TPOne start up method is set to Optimised
Start this message will display while this feature
is active.
see page 18
If the TPOne start up method is set to Delayed
Start this message will display while this feature
is active.
see page 18
24
TPOne-M
Warnings
TPOne monitors several conditions and will provide warnings when
necessary, these messages will be shown at the top of the display.
If the condition that has created the warning has been corrected
then the message can be cancelled by selecting Clear Warnings
in the TPOne menu. Where more than one warning has occurred
the most recent will be shown on the display. All warnings can be
viewed and cleared in the Clear Warnings menu.
Frost RiskThis will be displayed if the TPOne monitors a
Low HeatIf set mode temperature is not reached within
Service Due Where the TPOne Service Interval timer has been
Heat
Reduced
High Floor
Temperature
temperature of below 5oC. TPOne will call for
heat if this occurs but if the heat source is faulty
then risk of frost damage may still occur. The
heating system should be checked to conrm it is
operating correctly
2 hours then TPOne will warn of Low Heat. The
heating system should be checked to conrm it is
operating correctly
set this warning will be shown when the timer has
expired. Contact the property owner or landlord
to arrange the boiler safety mainantance.
see page 21
Where the TPOne Service Interval timer has been
set this warning will show after the timer has
expired and will indicate that heating has been
reduced for your safety until a boiler service has
been completed. Contact the property owner or
landlord to arrange the boiler safety mainantance.
see page 21
Where a oor limit temperature sensor has been
tted if the oor temperature exceeds the set limit
this warning will show. If the oor temperature
has reduced to a safe level the TPOne will continue
to control heating but the reason for the overheat
may still exist. The oor heating system should be
checked to ensure overheating does not reoccur.
Danfoss Heating
25
Warnings (continued)
Sensor FailIf the TPOne in-built temperature sensor is
External
Sensor Fail
Floor
Sensor Fail
measuring outside it’s operational parameters
then it may have failed. If this warning cannot be
reset then contact your service provider for advice.
If an external temperature sensor has been
tted and the TPOne is measuring outside it’s
operational parameters then it may indicate a
problem with the external sensor or connecting
cable. If this warning cannot be reset then contact
your service provider for advice.
If a oor temperature sensor has been tted and
the TPOne is measuring outside it’s operational
parameters then it may indicate a problem with
the oor sensor or connecting cable. If this
warning cannot be reset then contact your service
provider for advice.