Danfoss TP75 Data sheet

Danfoss TP75 Data sheet

Data Sheet

TP75 Heating Controller Programmable

 

Room Thermostats

 

 

 

 

Application & Features The TP75 is a true seven-day programmable thermostat incorporating many useful features.

An optional Optimum Start function will enable a required comfort temperature to be achieved by a programmed time, without wasting fuel because the heating plant started earlier than necessary. The chrono-proportional control logic ensures optimum comfort with minimal fuel consumption.

The basic model incorporates a temperature sensor within the casing, but a remote sensor version is also available. Both can be converted to operate as an electronic thermostat, controlling at a constant, user selected, temperature. The Holiday Mode uses this temperature for a selected number of days, before automatically returning to programmable thermostat mode.

Versions are available for use with a thirdparty telephone line switching device so that frost mode or holiday mode can be cancelled whilst away from home.

Battery powered, programme unaffected by mains power failures

Volt-free output contacts, rated 10 to 250Vac, 50/60Hz, or dc 10mA to 2(1)Amp.

Integral or remote temperature sensing

Up to 6 programmable temperature changes per day, including a programmable "OFF" function

Selectable 7 day or 5/2 day programme

Selectable time or temperature display

Temperature range, 5°C to 30°C, in increments of 0.5°C.

Selectable Chrono-proportional control or On/Off control

Optional Optimum Start

Frost protection function

Thermostat function for constant temperature setting

Holiday function, up to 99 days at a constant, selectable temperature

Extend override, maintains existing set temperature for a further 1, 2 or 3 hours

Selectable All Day programme, 1st event temperature lasts until 6th event becomes active

Remote reset of Frost or Holiday functions possible

Typical System

Connections

Direct Burner Control

Wallplate teminals

 

 

Live

 

Heating

 

 

Input

 

On

Off

A B C

1

2

3

4

5

6

 

 

3 amp

 

 

N

 

 

 

 

E

 

 

fuse

 

 

NL N E Mains

Zone control with motor open/ motor close two port valve

 

Live

Heating

Wallplate teminals

Input

On

Off

A B C 1 2 3 4 5 6

EARTHS NOT SHOWN.

3 amp

 

N

ENSURE EARTH

 

CONTINUITY

fuse

 

E

THROUGHOUT

 

 

N

 

 

N

L

N E

 

 

Mains

 

1

Data Sheet

TP75 Heating Controller

 

 

 

 

 

 

 

Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Designations

 

 

 

Feature

Integral

 

Remote

 

Remote

 

Remote temp

 

 

temperature

 

temperature

 

teleswitch

 

sensor &

 

 

sensor

 

sensor

 

reset

 

teleswitch reset

 

3* or 6 cycles per hour,

TP75

 

TP75A

 

TP75B

 

TP75AB

 

chrono-proportional control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12* or 6 cycles per hour,

TP75C

 

TP75AC

 

TP75BC

 

TP75ABC

 

chrono-proportional control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Programmes

Profiled - (up to 6 temperature changes per day)

 

 

 

 

 

All Day - ( 1st event temperature lasts until 6th event time)

 

 

 

 

 

 

 

 

Raise or lower temperature setting

 

 

 

 

 

User overrides

Extend duration of existing temperature setting by 1, 2 or 3 hours

 

 

Select Profiled or All Day programme

 

 

 

 

 

 

Monday to Friday

 

Event

 

 

Saturday & Sunday

 

 

20°C at 06:30

 

1

 

 

 

20°C at 07:30

 

Factory pre-set programme,

15°C at 08:30

 

2

 

 

 

20°C at 09:30

 

all may be changed

20°C at 11:30

 

3

 

 

 

20°C at 11:30

 

Note: An "OFF" event can

15°C at 13:30

 

4

 

 

 

20°C at 13:30

 

also be programmed

21°C at 16:30

 

5

 

 

 

21°C at 16:30

 

 

15°C at 22:30

 

6

 

 

 

15°C at 22:30

 

 

DIL Switch No.

 

Factory Pre-set

 

Installer Alternative

 

 

1

 

 

7 day programme

 

5/2 day programme

 

 

2

 

 

Optimum Start

 

 

Optimum Start

 

DIL switch options

 

 

Control Disabled

 

Control Enabled

 

 

 

 

 

 

at the time of installation

3

 

 

On/Off control

 

 

Chrono control

 

 

 

 

enabled

 

 

 

enabled

 

 

 

 

 

 

 

 

 

 

4

 

 

3 or 12 control cycles

 

6 control cycles

 

 

 

 

per hour (see above *)

 

 

per hour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

10-250Vac, 50/60Hz or 10-250Vdc

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact Current Rating

 

 

10mA to 2 Amp (res), 1 Amp (ind)

 

 

 

Switching Action

 

 

 

SPDT voltage free

 

 

 

Main Batteries

2 x AA alkaline dry cells (Duracell preferred) to be renewed every

 

 

 

 

24 months

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Memory Retention

Sufficient to remove and replace batteries within one minute

 

Max. Ambient Temperature

 

 

 

45°C

 

 

 

 

 

Dimensions mm

 

 

135 wide x 88 high x 32 deep

 

 

 

 

 

 

 

 

 

 

 

 

 

Fixing clearances, internal wiring & DIL switch settings

 

 

 

 

 

 

Internal wiring

 

 

 

 

Factory pre-set DIL

30

mm

Terminals

Outline of unit

 

 

 

 

 

 

 

 

 

 

 

 

switch settings

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall or plaster

 

 

 

 

 

ELECTRONICS

 

 

 

 

 

 

 

5/2 day

 

 

7 day

 

N &

E

 

 

 

 

 

 

 

 

 

 

box mounting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

looping

 

 

 

 

 

 

 

 

 

 

 

 

 

OSC ON

 

 

OSC OFF

holes

 

terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHRONO

 

 

ON/OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

C

1

2

3

4

5

6

Chrono 6

 

 

Chrono 3 or 12

 

 

 

 

 

 

 

Clearance

 

Knockouts for

Aperture for rear

 

 

 

 

 

Live

On

Off

 

 

 

 

 

 

 

for

 

 

 

 

 

 

Input

Heating

 

 

 

 

bottom cable

cable entry

 

 

 

 

 

 

 

 

screwdriver

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

entry

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

access

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Control

 

A

B

C

1

2

3

4

5

6

 

 

A

B

C

1

2

3

4

5

6

 

 

A

B

C

1

2

3

4

5

6

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* NOTE: Remote start-up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

 

* TP75B

 

 

 

 

 

 

 

 

Remote

* TP75AB

Remote

 

TP75A

 

start-up

 

 

Remote

 

 

start-up

connections vary with model.

 

Sensor

 

TP75AC

 

 

circuit

 

TP75BC

 

Sensor

 

 

circuit

 

TP75ABC

 

 

 

 

 

 

 

 

 

Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material, and reserves the right to

 

 

 

 

alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent

 

 

 

 

changes being necessary in specifications already agreed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Danfoss Randall Limited

Ampthill Road

Bedford, MK42 9ER

Tel: (01234) 364621 Fax: (01234) 219705

Email: danfossrandall@danfoss.com

Website: www.danfoss-randall.co.uk