Danfoss Midi-Shunts Data sheet

Data Sheet
Premounted Midi Shunts
Application
Ordering
Midi Shunt 088U0181
- with one circuit
The Danfoss oor heating midi shunt is a series of pre-mounted shunts for one, two or three heating circuits. It comes pre-mounted with CF2 master controller, manifolds, mixing shunt and actuators in a small and compact solution.
Midi Shunt version For room size Code no.
For 1 circuit, pre-mounted with CF2+ master controller, mixing shunt with Alpha 2L 15-40 circulation pump, manifold/control valve and TWA-A 24V NC actuators
For 2 circuits, pre-mounted with CF2+ master controller, mixing shunt with Alpha 2L 15-40 circulation pump, manifold/ control valve and TWA-A 24V NC actuators
Midi Shunt 088U0182
- with two circuits
Features:
• Compact design - ts in even the smallest places.
• Pre-mounted - minimal risk of installation faults.
• Easy ordering - only one number nessecary.
• Short installation time.
• Free choice between four dierent CF2+ ther­mostats (ordered separately).
• Grundfos Alpha 2L pump ensures the lowest possible operating costs.
Midi Shunt 088U0183
- with three circuits
up to 20 m
up to 40 m
2
2
088U0181
088U0182
VDIKC202
For 3 circuits, pre-mounted with CF2+ master controller, mixing shunt with Alpha 2L 15-40 circulation pump, manifold/ control valve and TWA-A 24V NC actuators
up to 60 m
2
088U0183
© Danfoss | FHH | 2015.10 | 1
Data Sheet Premounted Midi Shunts
Technical specications
CF-MC Master Controller
Midi Shunt 088U0181 088U0182 088U0183
Number of circuits 1 2 3
Heating area up to 20 m
2
up to 40 m
2
up to 60 m
Pump type/capacity Grundfos Alpha 2l 15-40
Temperature controller FH-TC, self-acting, 15-52° C
Room control CF2+ MC5 230V supply / 24 V output
Actuators TWA-A NC 24 V
CF-MC is the Master Controller in Danfoss’ CF2+ wireless oor heating control system. CF-MC is connected directly to 230 V power supply, and it provides all actuator outputs with 24 V.
Code no. 088U0245
2
Supply voltage 230 VAC
Output voltage 24 VDC
Number of outputs 5
Transmission frequency 868.42 MHz
Transmission range up to 30 m (in normal buildings)
Transmission power < 1 mW
Max. running load of actuator output 35 VA (total for all outputs)
Max. load for pump relay 230 V, 8 A / 2 A (inductive)
Max. load for boiler relay 230 V, 8 A / 2 A (inductive)
Approvals CE
Standard EN 60730
Directives R&TTE, LVD, EMC
Protection class IP30
Length of mains cable 1.5 m
Weight 700 g
For further technical information, see specic CF-MC Master Controller data sheet.
2 | © Danfoss | FHH | 2015.10
VDIKC202
Data Sheet Premounted Midi Shunts
RA-N Valve / FHF Manifold
Midi Shunt 088U0181 has one heating circuit and is equipped with a Danfoss RA-N pre-setting valve. Midi Shunt 088U0182 is equipped with a FHF manifold with two circuits, and Midi Shunt 088U0183 has a three circuit manifold. The FHF manifold is used for controlling water ow in under oor heating systems and consists of a supply and return manifold. The supply manifold includes possibility for indi-
RA-N 15 valve FHF-3 manifold
Valve / Manifold Code no.
RA-N 15 valve 013G0013
vidual shut-o of each circuit and. The return manifold is equipped with integrated Danfoss RA-N pre-setting valves securing optimal hydraulic balance in the system. The valves are controlled electronically by TWA thermal actuators.
TWA Thermal Actuator
FHF-2 manifold 088U0502
FHF-3 manifold 088U0503
See specic data sheets for FHF manifolds and RA-N pre-setting valves for further technical information.
TWA is a small actuator for electrical on/o-con­trol to activate valves and oor heating mani­folds. TWA is equipped with a visual position indicator to show the open or closed position of the valve.
For Midi Shunts is used the TWA-A 24 V NC (Normally Closed) version.
Code no. 088H3110
Supply voltage 24 V
Max. inrush current 350 mA
Frequency 50-60 Hz
Running power consumption 2 W
VDIKC202
Spindle travel time ~3 min.
Ambient temperature 0-60° C
Enclosure IP 41
Cable length 120 0 mm
For further technical information, see specic TWA actuator data sheet.
© Danfoss Danfoss | FHH | 2015.10 | 3
Data Sheet Premounted Midi Shunts
FH-TC Temperature controller
Thermostats
FH-TC is a self-acting thermostatic sensor, used for ow temperature control of oor heating and radiator heating systems. The water temperature is directly measured by a stainless steel immersion sensor.
Code no.: 088U0302
Features:
• Closes on rising sensor temperature.
• Closes against dierential pressure of up to 6 bar.
• Temperature range: 18 - 52° C.
• Designed for pressure PN 10.
Room thermostats must be ordered separately. Choose between these models:
CF-RS Standard Thermostat
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
Code no.: 088U0210
Temperature setting
1 2 3 4 5 6 max.
20°C 25°C 30°C 35°C 40°C 45°C 52°C
CF-RP Public Thermostat (tamperproof)
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
• Hidden set point adjustment for use in childrens rooms, schools, oce buildings etc.
Code no.: 088U0211
CF-RD Display Thermostat
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
• Digital display showing actual or set room temperature.
Code no.: 088U0214
CF-RF Display Thermostat with InfraRed oor sensor
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
• Digital display showing actual or set room temperature.
• InfraRed oor sensor for minimum and maximum oor surface temperature limitation.
Code no.: 088U0215
For further technical information, see specic CF-Rx data sheet.
4 | © Danfoss | FHH | 2015.10
VDIKC202
Data Sheet Premounted Midi Shunts
325 mm
425 mm
165 mm
47 mm
425 mm
325 mm
165 mm
47 mm
369 mm
425 mm
165 mm
47 mm
Dimensions
Midi Shunt 088U0181
Midi Shunt 088U0182
Midi Shunt 088U0183
VDIKC202
© Danfoss Danfoss | FHH | 2015.10 | 5
Danfoss A/S
Floor Heating Hydronics • Ulvehavevej 61 • DK-7100 Vejle • Denmark • Phone: +45 7488 8500 • Fax: +45 7488 8501 heating@danfoss.com • www.oorheating.danfoss.com
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserves t he right to alter its p roducts with out notice. This als o applies to produ cts already o n order provided t hat such alteratio ns can be made with out subsequenti al changes being n ecessary in spe cications alr eady agreed. All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Dan foss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.
6 | © Danfoss | Danfoss | FHH | 2015.010
VDIKC202
Loading...