Danfoss Midi-Shunts Data sheet

Data Sheet
Premounted Midi Shunts
Application
Ordering
Midi Shunt 088U0181
- with one circuit
The Danfoss oor heating midi shunt is a series of pre-mounted shunts for one, two or three heating circuits. It comes pre-mounted with CF2 master controller, manifolds, mixing shunt and actuators in a small and compact solution.
Midi Shunt version For room size Code no.
For 1 circuit, pre-mounted with CF2+ master controller, mixing shunt with Alpha 2L 15-40 circulation pump, manifold/control valve and TWA-A 24V NC actuators
For 2 circuits, pre-mounted with CF2+ master controller, mixing shunt with Alpha 2L 15-40 circulation pump, manifold/ control valve and TWA-A 24V NC actuators
Midi Shunt 088U0182
- with two circuits
Features:
• Compact design - ts in even the smallest places.
• Pre-mounted - minimal risk of installation faults.
• Easy ordering - only one number nessecary.
• Short installation time.
• Free choice between four dierent CF2+ ther­mostats (ordered separately).
• Grundfos Alpha 2L pump ensures the lowest possible operating costs.
Midi Shunt 088U0183
- with three circuits
up to 20 m
up to 40 m
2
2
088U0181
088U0182
VDIKC202
For 3 circuits, pre-mounted with CF2+ master controller, mixing shunt with Alpha 2L 15-40 circulation pump, manifold/ control valve and TWA-A 24V NC actuators
up to 60 m
2
088U0183
© Danfoss | FHH | 2015.10 | 1
Data Sheet Premounted Midi Shunts
Technical specications
CF-MC Master Controller
Midi Shunt 088U0181 088U0182 088U0183
Number of circuits 1 2 3
Heating area up to 20 m
2
up to 40 m
2
up to 60 m
Pump type/capacity Grundfos Alpha 2l 15-40
Temperature controller FH-TC, self-acting, 15-52° C
Room control CF2+ MC5 230V supply / 24 V output
Actuators TWA-A NC 24 V
CF-MC is the Master Controller in Danfoss’ CF2+ wireless oor heating control system. CF-MC is connected directly to 230 V power supply, and it provides all actuator outputs with 24 V.
Code no. 088U0245
2
Supply voltage 230 VAC
Output voltage 24 VDC
Number of outputs 5
Transmission frequency 868.42 MHz
Transmission range up to 30 m (in normal buildings)
Transmission power < 1 mW
Max. running load of actuator output 35 VA (total for all outputs)
Max. load for pump relay 230 V, 8 A / 2 A (inductive)
Max. load for boiler relay 230 V, 8 A / 2 A (inductive)
Approvals CE
Standard EN 60730
Directives R&TTE, LVD, EMC
Protection class IP30
Length of mains cable 1.5 m
Weight 700 g
For further technical information, see specic CF-MC Master Controller data sheet.