The Danfoss oor heating midi shunt is a series of
pre-mounted shunts for one, two or three heating
circuits.
It comes pre-mounted with CF2 master controller,
manifolds, mixing shunt and actuators in a small
and compact solution.
Midi Shunt versionFor room sizeCode no.
For 1 circuit, pre-mounted with CF2+ master controller, mixing
shunt with Alpha 2L 15-40 circulation pump, manifold/control
valve and TWA-A 24V NC actuators
For 2 circuits, pre-mounted with CF2+ master controller,
mixing shunt with Alpha 2L 15-40 circulation pump, manifold/
control valve and TWA-A 24V NC actuators
Midi Shunt 088U0182
- with two circuits
Features:
• Compact design - ts in even the smallest
places.
• Pre-mounted - minimal risk of installation
faults.
• Easy ordering - only one number nessecary.
• Short installation time.
• Free choice between four dierent CF2+ thermostats (ordered separately).
• Grundfos Alpha 2L pump ensures the lowest
possible operating costs.
Midi Shunt 088U0183
- with three circuits
up to 20 m
up to 40 m
2
2
088U0181
088U0182
VDIKC202
For 3 circuits, pre-mounted with CF2+ master controller,
mixing shunt with Alpha 2L 15-40 circulation pump, manifold/
control valve and TWA-A 24V NC actuators
Temperature controllerFH-TC, self-acting, 15-52° C
Room controlCF2+ MC5 230V supply / 24 V output
ActuatorsTWA-A NC 24 V
CF-MC is the Master Controller in Danfoss’ CF2+
wireless oor heating control system.
CF-MC is connected directly to 230 V power
supply, and it provides all actuator outputs with
24 V.
Code no.088U0245
2
Supply voltage230 VAC
Output voltage24 VDC
Number of outputs5
Transmission frequency868.42 MHz
Transmission rangeup to 30 m (in normal buildings)
Transmission power < 1 mW
Max. running load of actuator output35 VA (total for all outputs)
Max. load for pump relay230 V, 8 A / 2 A (inductive)
Max. load for boiler relay230 V, 8 A / 2 A (inductive)
ApprovalsCE
StandardEN 60730
DirectivesR&TTE, LVD, EMC
Protection classIP30
Length of mains cable1.5 m
Weight700 g
For further technical information, see specic CF-MC Master Controller data sheet.
Midi Shunt 088U0181 has one heating circuit
and is equipped with a Danfoss RA-N pre-setting
valve.
Midi Shunt 088U0182 is equipped with a FHF
manifold with two circuits, and Midi Shunt
088U0183 has a three circuit manifold.
The FHF manifold is used for controlling water
ow in under oor heating systems and consists
of a supply and return manifold.
The supply manifold includes possibility for indi-
RA-N 15 valveFHF-3 manifold
Valve / ManifoldCode no.
RA-N 15 valve013G0013
vidual shut-o of each circuit and.
The return manifold is equipped with integrated
Danfoss RA-N pre-setting valves securing optimal
hydraulic balance in the system.
The valves are controlled electronically by TWA
thermal actuators.
TWA
Thermal Actuator
FHF-2 manifold088U0502
FHF-3 manifold088U0503
See specic data sheets for FHF manifolds and RA-N pre-setting valves for further technical information.
TWA is a small actuator for electrical on/o-control to activate valves and oor heating manifolds.
TWA is equipped with a visual position indicator
to show the open or closed position of the valve.
For Midi Shunts is used the TWA-A 24 V NC
(Normally Closed) version.
Code no.088H3110
Supply voltage24 V
Max. inrush current350 mA
Frequency50-60 Hz
Running power consumption2 W
VDIKC202
Spindle travel time ~3 min.
Ambient temperature0-60° C
EnclosureIP 41
Cable length120 0 mm
For further technical information, see specic TWA actuator data sheet.
FH-TC is a self-acting thermostatic sensor, used
for ow temperature control of oor heating and
radiator heating systems.
The water temperature is directly measured by a
stainless steel immersion sensor.
Code no.: 088U0302
Features:
• Closes on rising sensor temperature.
• Closes against dierential pressure of up to 6
bar.
• Temperature range: 18 - 52° C.
• Designed for pressure PN 10.
Room thermostats must be ordered separately.
Choose between these models:
CF-RS Standard Thermostat
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
Code no.: 088U0210
Temperature setting
123456max.
20°C 25°C 30°C 35°C 40°C 45°C 52°C
CF-RP Public Thermostat (tamperproof)
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
• Hidden set point adjustment for use in childrens rooms, schools, oce buildings etc.
Code no.: 088U0211
CF-RD Display Thermostat
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
• Digital display showing actual or set room temperature.
Code no.: 088U0214
CF-RF Display Thermostat with InfraRed oor sensor
• Easy wireless assignment with Link Test to Master Controller CF-MC.
• Min. and max. limitation of temperature settings.
• Powered by 2 x AA Alkaline 1.5V batteries.
• LED indication for low battery.
• Digital display showing actual or set room temperature.
• InfraRed oor sensor for minimum and maximum oor surface temperature limitation.
Code no.: 088U0215
For further technical information, see specic CF-Rx data sheet.
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserves t he right to alter its p roducts with out notice. This als o applies to produ cts
already o n order provided t hat such alteratio ns can be made with out subsequenti al changes being n ecessary in spe cications alr eady agreed.
All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Dan foss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.