The items of equipment most often used for
locating faults in refrigeration systems are as
follows:
1. Pressure gauge
2. Thermometer
3. Hygrometer
4. Leak detector
5. Vacuum gauge
6. Clamp ammeter
7. Megger
8. Pole nder
Ae0_0045
Instruments for fault location and servicing
on refrigeration systems should full certain
reliability requirements.
Some of these requirements can be categorised
thus:
a. Uncertainty
b. Resolution
c. Reproducibility
d. Long-term stability
e. Temperature stability
The most important of these are a, b, and e.
a. Uncertainty
b. Resolution
Ae0_0046
The uncertainty (accuracy) of an instrument is the
accuracy with which it is able to give the value of
the measured variable.
Uncertainty is often expressed in % (±) of
either: Full scale (FS) or the measuring value.
An example of uncertainty for a particular
instrument is ±2% of measuring value, i.e. less
uncertain (more accurate) than if the uncertainty
is ±2% of FS.
Ae0_0047
The resolution of an instrument is the smallest
unit of measurement that can be read from it.
For example, a digital thermometer that shows
0.1°C as the last digit in the reading has a
resolution of 0.1°C.
Resolution is not an expression of accuracy. Even
with a resolution of 0.1°C, an accuracy as poor as
2 K is not uncommon.
It is therefore very important to distinguish
between the two.
The proper nal inspection and adjustment of
instruments can be performed by approved test
institutions.
Pressure gauges for fault location and servicing
are as a rule of the Bourdon tube type. Pressure
gauges in systems are also usually of this type.
In practice, pressure is nearly always measured as
overpressure.
The zero point for the pressure scale is equal to
the normal barometer reading.
Therefore pressure gauges have a scale from
–1 bar (–100 kPa) greater than 0 to + maximum
reading. Pressure gauges with a scale in absolute
pressure show about 1 bar in atmospheric
pressure.
Ae0_0007
Ae0_0008
Service pressure gauges
Vacuum gauges
As a rule, service pressure gauges have one
or more temperature scales for the saturation
temperature of common refrigerants.
Pressure gauges should have an accessible
setting screw for zero point adjustment, i.e. a
Bourdon tube becomes set if the instrument has
been exposed to high pressure for some time.
Pressure gauges should be regularly checked
against an accurate instrument. A daily check
should be made to ensure that the pressure
gauge shows 0 bar at atmospheric pressure.
Ae0_0009
Vacuum gauges are used in refrigeration to
measure the pressure in the pipework during and
after an evacuation process.
Vacuum gauges always show absolute pres-sure
(zero point corresponding to absolute vacuum).
Vacuum gauges should not normally be exposed
to marked overpressure and should therefore be
installed together with a safety valve set for the
maximum permissible pressure of the vacuum
gauge.
Electronic thermometers with digital read-out
are in widespread use for servicing. Examples of
sensor versions are surface sensors, room sensors
and insertion sensors.
Thermometer uncertainty should not be greater
than 0.1 K and the resolution should be 0.1°C.
A pointer thermometer with vapour charged
bulb and capillary tube is often recommended for
setting thermostatic expansion valves.
As a rule it is easier to follow temperature variations with this type of thermometer.
Thermometers can be relatively easily checked
at 0°C in that the bulb can be inserted 150 to 200
mm down into a thermos bottle containing a
mixture of crushed ice (from distilled water) and
distilled water. The crushed ice must ll the whole
bottle.
If the bulb will withstand boiling water, it can
be held in the surface of boilover water from
a container with lid. These are two reasonable
checks for 0°C and 100°C.
A proper check can be performed by a recognised test institute.
There are dierent types of hygrometers for
measuring the humidity in cold rooms and air
conditioned rooms or ducts:
Hair hygrometer
Psychrometer
Diverse electronic hygrometers
A hair hygrometer needs adjustment each time it
is used if reasonable accuracy is to be maintained.
A psychrometer (wet and dry thermometer) does
not require adjustment if its thermometers are of
high quality.
At low temperature and high humidity, the
temperature dierential between wet and dry
thermometers will be small.
Therefore, with psychrometers the uncertainty is
high under such conditions and an adjusted hair
hygrometer or one of the electronic hygrometers
will be more suitable.
A hair hygrometer can be adjusted by winding
a clean, damp cloth around it and then placing
it in an airtight container with water at the
bottom (no water must be allowed to enter the
hygrometer or come into contact with its bulb).
The container with hygrometer is then allowed
to stand for at least two hours in the same
temperature as that at which measurements are
to be taken.
The hygrometer must now show 100%. If it does
not, the setting screw can be adjusted.
This booklet deals with common faults in small,
relatively simple refrigeration systems.
The faults, fault causes, remedies and eects on
system operation mentioned also apply to more
complicated and large systems.
However, other faults can occur in such systems.
These and faults in electronic regulators are not
dealt with here.
Ae0_0001
After gaining a little experience, many common
faults in a refrigeration system can be localised
visually, by hearing, by feel, and sometimes
by smell. Other faults can only be detected by
instruments.
Categorisation
Knowledge of the system is
required
Ae0_0012
This booklet is divided into two sections. The
rst section deals exclusively with faults that
can be observed directly with the senses. Here,
symptoms, possible causes and the eect on
operation are given.
The second section deals with faults that can
be observed directly with the senses, and those
that can only be detected by instruments.
Here, symptoms and possible causes are given,
together with instructions on remedial action.
Ae0_0028
An important element in the fault location
procedure is familiarity with how the system
is built up, its function and control, both
mechanical and electrical.
Unfamiliarity with the system ought to be
remedied by carefully looking at piping layouts
and other key diagrams and by getting to know
the form of the system (piping, component
placing, and any connected systems, e.g. cooling
towers and brine systems).
A certain amount of theoretical knowledge is
required if faults and incorrect operation are to
be discovered and corrected.
The location of all forms of faults on even
relatively simple refrigeration systems is
conditional on a thorough knowledge of such
factors as:
The build-up of all components, their mode of
operation and characteristics.
Necessary measuring equipment and
measuring techniques.
All refrigeration processes in the system.
The inuence of the surroundings on system
operation.
The function and setting of controls and safety
equipment.
Legislation on the safety of refrigeration
systems and their inspection.
Before examining faults in refrigeration systems,
it could be advantageous to look briey at
the most important instruments used in fault
location.
Ae0_0033
In the following description of faults in refrigeration systems, sections 1 and 2 take as their
starting points the piping diagrams, g. 1, 2 and
3.
The systems are dealt with in the direction
followed by the circuit. Fault symptoms that
can occur are described in circuit order. The
description starts after the compressor discharge
side and proceeds in the direction of the arrows.
a)Valve closed.System stopped via low-pressure control.
b) Valve partly closed.Vapour bubbles in liquid line.
Liquid line
a)Too smallFaults under a), b) and c) cause:
[Sizing error]
b) Too long
[Sizing error]
c)Sharp bends and/or deformed
[Installation error]
Filter drier
Dew or frost formation on surface.Vapour in liquid line.
[Filter partly blocked with dirt on inlet side]
Sight glassRisk of:
a)YellowAcid formation, corrosion, motor burn-out, water freezing in
[Moisture in system]
b) BrownRisk of wear in moving parts and blockage in valves and lters.
[Dirt particles in system]
c)Pure vapour in sight glass.Standstill via low-pressure control or compressor cycling.
[Insucient liquid in system]
[Valve in liquid line closed]Standstill via low-pressure control.
[Complete blockage, e.g. of lter drier]Standstill via low-pressure control.
d) Liquid and vapour bubbles in sight glass.All faults under d):
[Insucient liquid in system]
[Valve in liquid line partly closed]
[Partial blockage, e.g. of lter drier]
[No subcooling]
- Increased condensing pressure.
- Reduced refrigeration output.
- Increased energy consumption.
For an air-cooled condenser, the dierence between air inlet
and condensing temperatures should lie between 10 K and 20 K,
preferably at the lower end.
For a water-cooled condenser, the dierence between condensing
and water inlet temperatures should lie between 10 K and 20 K,
preferably at the lower end.
Low suction pressure or compressor cycling.
Large pressure drop in liquid line.
Vapour in liquid line.
thermostatic expansion valve.
Compressor cycling or running at low suction pressure.
Visible faults and the eect on the system operation (cont.)Text in [ ] indicates fault cause
Visible faultsEect on system operation
Thermostatic expansion valve
a)Thermostatic expansion valve heavily frosted, frost on
evaporator only near valve.
[Dirt strainer partly blocked]
[Bulb charge partly lost]
[Previously described faults causing vapour bubbles in
liquid line]
b)Thermostatic expansion valve without external pressure
equalisation, evaporator with liquid distributor.
[Sizing or installation error]
c)Thermostatic expansion valve with external pressure
equalisation, equalising tube not mounted.
[Installation error]
d)Bulb not rmly secured.Faults under d), e), f) lead to overcharged evaporator with risk of
[Installation error]
e)Entire bulb length not in contact with tube.
[Installation error]
f)Bulb placed in air current.
[Installation error]
Air cooler
a)Evaporator frosted only on inlet side, thermostatic expansion
valve heavily frosted.
[Thermal valve fault]
[All previously described faults that cause vapour in
liquid line]
b)Front blocked with frost.Faults under a), b), c), d), e) cause:
[Lacking, incorrect or wrongly set up defrost procedure]
c)Fan does not run.
[Motor defect or motor protector cut-out]
d)Fan blades defective.
e)Fins deformed.
[Rough treatment]
Liquid cooler
a)Thermostatic expansion valve bulb not rmly secured.Causes overcharged evaporator with risk of liquid ow to
[Installation error]
b)Thermostatic expansion valve without external pressure
equalising on liquid cooler with high pressure drop, e.g.
coaxial evaporator.
[Sizing or installation error]
c) Thermostatic expansion valve with external pressure
equalisation, equalising tube not mounted.
[Installation error]
Faults under a) cause operation at low suction pressure or
compressor cycling via low-pressure control.
Faults under b), c) cause operation at low suction pressure or
compressor cycling via low-pressure control. or compressor
cycling via low-pressure control.
liquid ow to compressor and compressor damage.
Faults under a) cause:
High superheat at evaporator outlet and operation at mostly low
suction pressure.
- Operation with mostly low suction pressure.
- Reduced refrigeration output.
- Increased energy consumption.
For thermostatic expansion valve controlled evaporators:
The dierence between air inlet and evaporating temperatures
should lie between 6 K and 15 K, preferably at the lower end.
For level-controlled evaporators:
The dierence between air inlet and evaporating temperatures
should lie between 2 K and 8 K, preferably at the lower end.
compressor and compressor damage.
Faults b), c) cause:
- Operation with mostly low suction pressure.
- Reduced refrigeration output.
- Increased energy consumption.
For thermostatic expansion valve controlled evaporators:
The dierence between air inlet and evaporating temperatures
should lie between 6 K and 15 K, preferably at the lower end.
For level-controlled evaporators:
The dierence between air inlet and evaporating temperatures
should lie between 2 K and 8 K, preferably at the lower end.
Visible faults and the eect on the system operation (cont.)Text in [ ] indicates fault cause
Visible faultsEect on system operation
Suction line
a)Abnormally severe frosting.Risk of liquid ow to compressor and compressor damage.
[Thermal valve superheat too low]
b) Sharp bends and/or deformation.Low suction pressure or compressor cycling.
[Installation error]
Regulators in suction line
Dew/frost after regulator, no dew/frost ahead of regulator.Risk of liquid ow to compressor and compressor damage.
[Thermal valve superheat too low]
Compressor
a)Dew or frost on compressor inlet side.Liquid ow to compressor with risk of compressor damage.
[Superheat at evaporator outlet too low]
b) Oil level too low in crankcase.
[Insucient oil in system]System stop via oil dierential pressure control (if tted).
[Oil collection in evaporator]Causes wear of moving parts.
c)Oil level too high in crankcase.
[Oil overlling]Liquid hammer in cylinders, risk of compressor damage:
[Refrigerant mixed with oil in too cold a compressor]
[Refrigerant mixed with oil because superheat too low
at evaporator outlet]
d) Oil boils in crankcase during start.
[Refrigerant mixed with oil in too cold a compressor]Liquid hammer, damage as under c)
e) Oil boils in crankcase during operation.
[Refrigerant mixed with oil because superheat too low
at evaporator outlet]
Cold Room
a)Dry surface on meat, limp vegetables.
[Air humidity too low - evaporator probably too small] Leads to poor food quality and/or wastage.
b) Door not tight, or defective.Can give rise to personal injury.
c)Defective or missing alarm sign.Can give rise to personal injury.
d) Defective or missing exit sign.Can give rise to personal injury.
For b), c), d):
[Lack of maintenance or sizing error]
e) No alarm system.
[Sizing error]Can give rise to personal injury.
General
a)Oil drops under joints and/or oil spots on oor.
[Possible leakage at joints]Oil and refrigerant leakage.
b) Blown fuses.
[Overload on system or short-circuiting]System stopped.
c)Motor protector cut-out.
[Overload on system or short circuiting]System stopped.
d) Cut-out pressure controls or thermostats, etc.