Danfoss MCX 15b Installation guide

Installation guide
Pre-programmed Controller MCX 15b for IPS 8
Replacement of MCX controller
Prior to disconnect and remove the old MCX controller it is important to depressurize the ammonia side of the purger unit by following these steps (see g. 1)
148R9647
1. Close all supply lines from the purge points of the ammonia system (a)
3. Wait for 20 minutes
4. Stop the compressor by turning the compressor switch QM1 to the o position
5. Close the SVA shut-o valve in the drain line (located under the IPS8 (b))
6. Release the remaining system pressure to ambient pressure by opening the SNV drain valve (c). This can also be done by attaching a permanent magnet on the AKVA 10 valve for forced opening
148R9647
Fig. 1
Switch QM2 to the o position
MC X15B controller
c
SNV
NH₃ bypass for draining purger
SVA
b
Purge line to water tank
a
AO5
AO6
COM
DI 1
COM
D1 H
COM
COM
NO 15
NO 14
NC 14
DIGITAL INPUT 1DIGITAL OUTPUT 14
DIGITAL INPUT 3
DI 3
COM
DI 3H
NC 15
DIGITAL OUTPUT 15
DIGITAL INPUT 4
DIGITAL INPUT 9-12
DIGITAL INPUT 5-8
DI 5
DI 9
DI 7
DI 6
DI 8
COM
DI 4
COM
DI 4H
ANALOG OUTPUT 5-6
DIGITAL INPUT 2
DI 2
COM
DI 2H
AI3
AI7
AI8
AI9
AI1
AI2
COM
ANALOG INPIT 1-6
DIGITAL INPUT 13-16
COM
DI 11
DI 10
DI 12
DI 13
DI 15
DI 14
DI 16
AI10
AI6
AI4
AI5
COM
5V+
COM
5V+
5V+
12V+
DIGITAL INPUT 17-18
COM
COM
COM
DI 17
DI 18
L
N
ANALOG INPUT 7-10
POWER
MCX
CAN RJ
CAN
Rail lock: Pull to release controller from suspension rail
Fig. 2 Fig. 3
© Danfoss | DCS (ms) | 2021.03 AN316921824979en-000201 | 1
Info for UK customers only:Danfoss Ltd. Oxford Road, UB9 4LH Denham, UK
Unplug all connections and re-plug in the same sockets of the new controller
A05
A06
COM
Analog Ouptu 5-6
DI1H
COM
DI1
Digital Input 1
NO14
NO14
COM
Digital Output 14
NO15
NO15
COM
Digital Output 15
MCX
DI2H
Digital Input 2
DI2
Digital Input 3
Digital Input 4
COM
DI3H
COM
DI3
DI4H
COM
DI4
Fig. 4 . Controller Upper level
NO1C1NO2C2NO3C3NO4C4NO5
Digital Output 1-5
C5
Digital Input 5-8
DI5
DI6
DI7
DI8
COM
Digital Input 9-12
DI9
DI10
DI11
DI12
Digital Input 13-16
DI13
DI14
DI15
DI16
COM
COM
Digital Input 17-18
DI17
DI18
COM
COM
Unplug all connections and re-plug in the same sockets of the new controller
NO6C6NO7C7NO8
Digital Output 6-8
C8
COM
AI1
AI2
AI3
5V+
12V+
5V+
AI4
AI5
AI6
COM
Analog Output 1-6 Analog Input 7-10 Power
COM
AI7
MCX
AI8
AI9
AI10
5V+
L
N
Digital Output 9-12
C9
NO9
NO10
C10
NO10
NO11
C11
NO11
NO12
Digital Output 1-3 Analog Output 1-4 CAN RJCANRS485-1RS485-2
AO1
AO2
C12
NO12
NO13
C13
NO13
AO3
AO4L1N1
GND2
D2+
D2-
GND1
D1+
D1-
R120
CANH
CANL
CGND
CAN
Fig. 5 Controller Lower level
1. Switch QM2 to the on position
2. Congure the number of purge points (see IPS 8 user guide): Activate multipurger (label y02) Enter the number of purge points
3. Congure any other customer specic setting: The pre-programmed MCX15B (code 084H5052) is plug & play ready, and only where customer specic settings are applicable, these values must be entered.