Danfoss MCX08M2 Data sheet

Data Sheet
Programmable controller, 8 relays Type MCX08M2
Electronic controller suitable for all HVAC/R software application needs.
MCX08M2 is an electronic controller that holds all the typical functionalities of MCX controllers in the compact size of 8 DIN modules:
• Programmability
• Connection to the CANbus local network
• Modbus RS485 opto-insulated serial interface
It is available in the version with or without graphic LCD display, and 110 / 230 V AC or 24 V AC power supply.
Features:
• 8 analog and 8 digital inputs
• 4 analog and 8 digital outputs
• Power supply 24 V AC / 20 / 60 V DC and 110 V / 230 V AC
• Remote access to data through CANbus connection for additional display (LCD available) and keyboard
• RTC clock for managing weekly time programs and data logging information
• Modbus RS485 opto-insulated serial interface
• Dimensions 8 DIN modules
• Available with graphic LCD display and without display for showing the desired information
AI217686427688en-000901
MCX family
MCX06C
MCX06D
MCX061V
MCX08M2
MCX152V
MCX15B2
MCX20B2
Product image
Power supply
24 V
24 V
24 V or
110/230 V
24 V or
110/230 V
24 V or
110/230 V
24/110/230 V
24/110/230 V
Built-in display (optional)
LED
LCD
LCD
LCD
LCD
LCD
LCD
Analog Inputs44781410
16
Digital Inputs68881822
22
Analog Outputs
2334666
Digital Outputs66681515
20
EXV driver embedded
1
2
RS485111121
2
CANbus••••••
Ethernet / Web server
optional
optional••
USB/Memory Card
•••
Dimensions (1 DIN module = 17,5 mm)
33 x 75 mm
4 DIN
8 DIN
8 DIN
16 DIN
16 DIN
16 DIN
Programmable controller, 8 relays, type MCX08M2
Portfolio overview
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2021.03 AI217686427688en-000901 | 2
Features
Description
Power supply
85 – 265 V AC, 50/60 Hz. Maximum power consumption: 20 V A Insulation between power supply and the extra-low voltage: reinforced
20 – 60 V DC and 24 V AC ± 15% 50/60 Hz SELV Maximum power consumption: 10 W, 17 V A Insulation between power supply and the extra-low voltage: functional
Plastic housing
DIN rail mounting complying with EN 60715
Self extinguishing V0 according to IEC 60695-11-10 and glowing / hot wire test at 960 °C according to IEC 60695-2-12
Ball test
125 °C according to IEC 60730-1 Leakage current: ≥ 250 V according to IEC 60112
Operating conditions
CE: -20T60 / UL: 0T55, 90% RH non-condensing
Storage conditions
-30T80, 90% RH non-condensing
Integration
In Class I and / or II appliances
Index of protection
IP40 only on the front cover
Period of electric stress across insulat­ing parts
Long Resistance to heat and re
Category D
Immunity against voltage surges
Category II
Software class and structure
Class A
Type
Num
Specications
NTC 0 / 1 V 0 / 10 V PT1000
4
AI5, AI6, AI7, AI8
Analog inputs selectable via software between:
• 0 / 1 V, 0 / 5 V, 0 / 10 V : impedance is greater than 1 MΩ
• NTC (10 kΩ at 25 °C)
• Pt1000
Universal
4
AI1, AI2, AI3, AI4
Universal analog inputs selectable via software between:
• ON/OFF (current: 20 mA)
• 0 / 1 V, 0 / 5 V, 0 / 10 V : impedance is greater than 1 MΩ
• 0 / 20 mA, 4 / 20 mA
• NTC (10 kΩ at 25 °C)
• Pt1000 12 V+ power supply 12 V DC, 50 mA max for 4 / 20 mA transmitter (total on all outputs) 5 V+ power supply 5 V DC, 80 mA max for 0 / 5 V transmitter (total on all outputs)
Type
Num
Specications
Voltage free con­tacts
8
DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8
Current consumption: 5 mA
Type
Num
Specications
0 / 10 V DC optoins
2
AO3, AO4
Analog outputs optoinsulated 0 / 10 V DC minimum load 1 kΩ (10 mA) for each output
PWM PPM 0 / 10 V DC
2
AO1, AO2
Analog outputs selectable via software between:
• 0 / 10 V DC minimum load 1 kΩ (10 mA) for each output
• pulsing output, synchronous with the line, at modulation of impulse position (PPM) or modulation of impulse width (PWM)
• pulsing output, at modulation of impulse width (PWM) with range 20 Hz to 1 KHz: open circuit voltage: 6.8 V
Programmable controller, 8 relays, type MCX08M2
Product specication
General features
Table 2: General features
Input/Output
Table 3: Analog inputs
Table 4: Digital inputs
Table 5: Analog outputs
© Danfoss | Climate Solutions | 2021.03 AI217686427688en-000901 | 3