Danfoss MCX06C Data sheet

Data Sheet
Programmable controller, 6 relays Type MCX06C
Electronic controller suitable for all HVAC/R software application needs.
MCX06C is an electronic controller that holds all the typical functionalities of MCX controllers in the 32 x 74 mm standard size:
• programmability
• connection to the CANbus local network
• Modbus RS485 serial interface
Features:
• 4 analog and 6 digital inputs
• Insulated power supply 20 / 60 V DC - 24 V AC
• Easy upload of application software through CANbus connection for programming key
• Remote access to data through CANbus connection for additional display (LCD available) and keyboard
• RTC clock for managing weekly time programs and data logging information
• Modbus RS485 serial interface
• Display LED with 2 groups of digits for showing the desired information in one screen
• Dimensions 33 x 75 mm
• Panel mounting
AI183786420797en-000601
MCX family
MCX06C
MCX06D
MCX061V
MCX08M2
MCX152V
MCX15B2
MCX20B2
Product image
Power supply
24 V
24 V
24 V or
110/230 V
24 V or
110/230 V
24 V or
110/230 V
24/110/230 V
24/110/230 V
Built-in display (optional)
LED
LCD
LCD
LCD
LCD
LCD
LCD
Analog Inputs44781410
16
Digital Inputs68881822
22
Analog Outputs
2334666
Digital Outputs66681515
20
EXV driver embedded
1
2
RS485111121
2
CANbus••••••
Ethernet / Web server
optional
optional••
USB/Memory Card
•••
Dimensions (1 DIN module = 17,5 mm)
33 x 75 mm
4 DIN
8 DIN
8 DIN
16 DIN
16 DIN
16 DIN
Programmable controller, 6 relays, type MCX06C
Portfolio overview
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2021.03 AI183786420797en-000601 | 2
Features
Description
Power supply
20 / 60 V DC and 24 V AC ± 15% 50/60 Hz SELV Maximum power consumption: 6 W, 9 VA
Insulation between power supply and the extra-low voltage: functional
Plastic housing
Self extinguishing V0 according to IEC 60695-11-10 and glowing / hot wire test at 960 °C according to IEC 60695-2-12
Ball test
125 °C according to IEC 60730-1 Leakage current: ≥ 250 V according to IEC 60112
Operating conditions
CE: -20T60 / UL: 0T55, 90% RH non-condensing
Storage conditions
-30T80, 90% RH non-condensing
Integration
In Class I and / or II appliances
Index of protection
IP64 ~ NEMA3R only on the front cover
Period of electric stress across insulat­ing parts
Long Resistance to heat and re
Category D
Immunity against voltage surges
Category II
Software class and structure
Class A
Type
Num
Specications
NTC 0 / 1 V 0 / 5 V
2
AI1, AI2
Analog inputs selectable via software between:
• NTC temperature probes, default: 10 kΩ at 25 °C
• Pressure transducers with 0/5 V output
• 0/5V type: impedance is 18 kΩ
Universal
2
AI3, AI4
Universal analog inputs selectable via software between:
• ON/OFF (current: 20 mA)
• 0 / 1 V, 0 / 5 V, 0 / 10 V
• 0 / 20 mA, 4 / 20 mA
• NTC (10 kΩ at 25 °C)
• Pt1000 12 V+ power supply 12 V DC, 50 mA max for 4 / 20 mA transmitter (total on all outputs) 5 V+ power supply 5 V DC, 80 mA max for 0 / 5 V transmitter (total on all outputs) 0/5V type: impedance is 18 kΩ 0/10V type: impedance is 2 kΩ
Type
Num
Specications
Voltage free con­tact
6
DI1, DI2, DI3, DI4, DI5, DI6
Current consumption: 5 mA
Type
Num
Specications
0 / 10 V PWM PPM
1
AO1
Analog output selectable via software between:
• pulsing output, synchronous with the line, at modulation of impulse position (PPM) or modulation of impulse width (PWM):
open circuit voltage: 6.8 Vminimum load: 1 kΩ
• pulsing output, at modulation of impulse width (PWM) with range 100 – 500 Hz:
open circuit voltage: 6.8 V
minimum load: 1 kΩ
• 0 / 10 V DC non optoinsulated output, referred to the ground
minimum load 1 kΩ (10 mA)
PWM PPM
1
AO2
Analog output selectable via software between:
• pulsing output, synchronous with the line, at modulation of impulse position (PPM) or modulation of impulse width (PWM):
open circuit voltage: 6.8 Vminimum load 1 kΩ (10 mA)
• pulsing output, at modulation of impulse width (PWM) with range 100 – 500 Hz:
open circuit voltage: 6.8 V
minimum load 1 kΩ (10 mA)
Programmable controller, 6 relays, type MCX06C
Product specication
General features
Table 2: General features
Input/Output
Table 3: Analog inputs
Table 4: Digital inputs
Table 5: Analog outputs
© Danfoss | Climate Solutions | 2021.03 AI183786420797en-000601 | 3