Danfoss MCV116C1401 Installation guide

Unit Specification
MCV116C1401
Pressure Control Pilot Valve (PCP) Single Coil
3500 Annapolis Lane North, Minneapolis, MN 55447 Telephone: (763) 509-2084 Telefax: (763) 559-0108
GENERAL DESCRIPTION
This Pressure Control Pilot (PCP) is an intrinsically safe, torque motor-actuated, double-nozzle flapper valve that produces a differential output pressure proportional to the applied electrical input signal. It is a single-stage, stand-alone, closed-loop pressure control valve which uses internal hydraulic pressure reactions to achieve its closed-loop control characteristics. The intrinsically safe PCP contains an arc suppression circuit for use in hazardous areas.
The term "intrinsically safe" refers to a design technique based on limiting energy, electrical and thermal, to a level below that required to ignite a specific hazardous atmospheric mixture. This device is Factory Mutual certified for use in Class I, II, or III, Division 1, Group C, D, F, and G hazardous locations as defined by the National Electrical Code, NFPA-70 when used with approved barriers. This device is also Factory Mutual certified for use in Division 2, Group C, D, F, G. If a given application requires only Division 2 approval, an inline barrier may not be required. This PCP is typically used as the pilot section for the 4-20 mA Series 90 EDCs (KVEBSXXXX).
DIMENSIONS
MS CONNECTOR
Intrinsically Safe 4-20 mA
ISSUE: 2 DATE: January 2004
MANUAL OPERATOR
NULL ADJUST
ACCESS SCREW
78,7
(3.10)
56,1
(2.21)
DO NOT REMOVE
COVER SCREWS (4)
17,5 DIA (2)
(0.69)
ELECTRICAL
CONNECTION
5,5 (0.217) DIA (4)
Pin Orientation
50,8
D C
4-pin, 90
A B
Active Pins
° MS
Mating Connector
(2.00)
A, B
2009
MAX
6,3
(0.25)
38,1
(1.50)
34,9
(1.375)
Part No. MS3108E-14S-S
(Sauer-Danfoss Kit
No. K08106).
ELECTRICAL CHARACTERISTICS
The cover is filled with 45 cc of 4000 cs silicone oil. Ensure that minimal oil is lost if null access screw is removed.
INTRINSICALLY SAFE DEVICE ENCLOSURE GROUNDING TERMINAL
12,7
19,0
(0.75)
2,5 (0.10) (2)
3,0 (0.12)
9,5 (0.38)
(0.50)
REPLACEMENT FILTER PART NUMBER K08573
38,1
(1.50)
OUTPUT PORT - C1 4,8 (0.19) DIA 12,8 (0.50) O.D. X 1,78 (0.07) O-RING
PRESSURE PORT THRU FILTER 5,6 (0.22) DIA 12,8 (0.50) O.D. X 1,78 (0.07) O-RING
RETURN PORT 4,8 (0.19) DIA 12,8 (0.50) O.D. X 1,78 (0.07) O-RING
OUTPUT PORT - C2 4,8 (0.19) DIA 12,8 (0.50) O.D. X 1,78 (0.07) O-RING
Dimensions of the MCV116C1401 in Millimeters (Inches).
CAUTION
3016
Single coil, coil resistance 106 at 70° F, 130 at 200° F
Coil inductance: 0.435 henries at 70° F
Phasing: Positive voltage to pin A produces a pressure rise at output port C1 Positive voltage to pin B produces a pressure rise at output port C2
K28400 UNIT SPEC
AB
Typical current/voltage range at 70° F: 4 mA at 0.50 Vdc to 20 mA at 2.2 Vdc (maximum 40 mA at 4.4 Vdc)
Pulse Width Modulation (PWM) The PCP is designed to be controlled from a dc current source or voltage source. If a PWM signal is used, do not use a pulse current of more than 120% of that required.
Scale factor: 5.5 ± 0.5 psid / mA
1 OF 2
© Copyright 2004, Sauer-Danfoss (US) Company.
All rights reserved. Contents subject to change.
HYDRAULIC CHARACTERISTICS
Maximum supply pressure: 1000 psid Recommended range: 300 - 500 psid
Maximum return pressure: 200 psid
Maximum internal leakage: 0.65 gpm
Maximum linear psid output pressure: 220 psid at 300 psid supply
Load flow: the output differential flow across a 100 psid load pressure drop at maximum current: > 30 cim
Hydraulic Fluid: Petroleum based, other fluids may be used provided that thy are compatibile with viton and fluorosilicone seals. Fluid cleanliness is ISO 4406 code 18/15 or better
WIRING
A suppression circuit is incorporated in the PCP torque motor cover but by itself does not ensure intrinsic safety. An additional suppression circuit (Zener barrier) must be connected in series with the valve coils. The Zener barrier and electrical controller must be isolated from the hazardous
UNIDIRECTIONAL CONTROL, SELECT ONE OF THE FOLLOWING DC CURRENT BARRIERS
Stahl Barrier 9001/01-158-150-10 (12V) Impedence 127
• Groups A, B, C, D, F and G (maximum voltage 15.8V)
Hydraulic Null Adjustment: PCP null adjustment is sometimes required when configured with the servovalve (KVF) or used as a stand-alone. When the PCP is configured with an Electrical Displacement Control (EDC) mounted to a pump, never adjust an EDC neutral using the PCP null adjustment. EDCs are adjusted at their second stage. To adjust the PCP, remove the null access screw (see Dimensions) and, with a 3/32 inch hex wrench, insert the wrench a short distance into the access opening and engage the adjustment set-screw. Adjustments are make by turning the hex wrench very slowly either CW or CCW. Adjustments require less than 1/2 turn to achieve the desired results. The use of two pressure gages placed in the PCP control ports (C1 and C2) may be used. While observing the gages, adjust until the readings are the same pressure level.
area either through use of a purge enclosure or mounted in a safe area. See Dimensions for PCP enclosure grounding. Electrical connections and suggested barrier model numbers are shown in the connection diagram below .
A
3
MCV BARRIER
B
HAZARDOUS LOCATION
CLASS I, II, AND III
DIVISION 1
GROUPS C OR D, F AND G
BIDIRECTIONAL CONTROL, SELECT ONE OF THE FOLLOWING BARRIERS
Stahl Barrier 9001/02-175-200-10 (12V) Impedence 110
• Groups A, B, C, D, F and G (maximum voltage ±17.2V)
EARTH
GROUND
A
4
3
MCV BARRIER
B
HAZARDOUS LOCATION
CLASS I, II, AND III
DIVISION 1
GROUPS C OR D, F AND G
To obtain a barrier or specific information about a barrier, contact R. Stahl, Inc. at 1-800-782-4357 or e-mail www.rstahl.com
NO CHANGES TO THIS DRAWING WITHOUT PRIOR WRITTEN AUTHORIZATION FROM FACTORY MUTUAL.
EARTH
GROUND
4
(+)1
2
NON-HAZARDOUS LOCATION
(±)1
2
NON-HAZARDOUS LOCATION
CONTROLLER
OUTPUT
CONTROLLER
OUTPUT
3017
K28400 UNIT SPEC
2 OF 2