This manual provides basic knowledge required to use the
VLT® MCT 21 Factory Tool with VLT® DriveMotor FCP 106
and FCM 106 frequency converters.
Familiarity with the following is assumed:
MS®-WindowsTM at user level.
•
Set-up, process knowledge, and operation of
•
frequency converters.
Connection, set-up, and use of communication
•
equipment.
Familiarity with the PC or PLC master of the
•
system.
Issues regarding hardware or software produced by other
manufacturers are beyond the scope of this manual, and
are not the responsibility of Danfoss.
The manual does not provide detailed information
regarding:
Specific applications
•
Possible solutions
•
Related parameter combinations in the set-up
•
and use of a frequency converter.
1.3
Product Overview
1.3.1 Intended Use
The MCT 21 Factory Tool enables the creation of factory
settings and testing of the frequency converter in the
factory. The software comprises 2 tools:
Engineering Tool
•
Technician Tool
•
For details of the interaction of these tools, refer to
chapter 4.1 Interaction of Engineering Tool and Technician
Tool.
System Requirements
1.3.2
Supported operating systems:
Windows 7 (32 bit) Service Pack 1
•
Windows 7 (64 bit) Service Pack 1
•
Windows XP (32 bit) Service Pack 3
•
Additional system requirements:
Minimum screen resolution: 1024 × 768
•
Minimum physical memory: 256 MB
•
Communication bus: Danfoss FC protocol on
•
RS-485
VLT® is a registered trademark.
1.2
Further Information
Literature available:
VLT® DriveMotor FCP 106 and FCM 106 Operating
•
Instructions
VLT® DriveMotor FCP 106 and FCM 106
•
Programming Guide
VLT® DriveMotor FCP 106 and FCM 106 Design
•
Guide
The full range of manuals, instructions, and software
downloads is available at:
21 Factory Tool uses the parameter database
from MCT 10.
1.4
Document and Software Version
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version and the corresponding MCT 21
Factory Tool software version.
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only
qualified personnel are allowed to install or operate this
equipment.
Qualified personnel are defined as trained staff, who are
authorised to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in
these operating instructions.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input power. Failure to perform
installation, start up, and maintenance by qualified
personnel could result in death or serious injury.
Only qualified personnel are permitted to
•
perform installation, start up, and maintenance.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC power supply, or load sharing, the motor can start at
any time. Unintended start during programming, service,
or repair work can result in death, serious injury, or
property damage. The motor can start with an external
switch, a fieldbus command, an input reference signal
from the LCP or LOP, via remote operation using a
software tool, or after a cleared fault condition.
To prevent unintended motor start:
Disconnect the frequency converter from mains.
•
Press [Off/Reset] on the LCP before
•
programming parameters.
Ensure the frequency converter, motor, and any
•
driven equipment are fully wired and
assembled when the frequency converter is
connected to AC mains, DC power supply, or
load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work could result in death or serious
injury.
Stop the motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock the PM motor.
•
Wait for the capacitors to discharge fully before
•
performing any service or repair work. The
duration of waiting time is specified in
Table 2.1.
Minimum waiting
[kW]
1)
time
(min)
Voltage
[V]
3x4000.55–7.54
High voltage can be present even when the warning LED
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualified
•
personnel perform installation, start up, and
maintenance.
Ensure that electrical work conforms to national
•
and local electrical codes.
Follow the procedures in this manual.
•
WARNING
UNINTENDED MOTOR ROTATION
WINDMILLING
Unintended rotation of permanent magnet motors can
result in serious injury or equipment damage.
Ensure that permanent magnet motors are
•
blocked to prevent unintended rotation.
WARNING
LEAKAGE CURRENT HAZARD
Follow national and local codes regarding protective
earthing of equipment with a leakage current exceeding
3.5 mA. Frequency converter technology implies high
frequency switching at high power. This switching
generates a leakage current in the ground connection. A
fault current in the frequency converter at the output
power terminals can contain a DC component which can
charge the filter capacitors and cause a transient ground
current. The ground leakage current depends on various
system configurations including RFI filtering, screened
motor cables, and frequency converter power. EN/IEC
61800-5-1 (Power Drive System Product Standard)
requires special care because the leakage current
exceeds 3.5 mA. See EN 60364-5-54 paragraph 543.7 for
further information.
Ensure correct grounding of the equipment by
•
a certified electrical installer.
Grounding must be reinforced in one of the
•
following ways:
-Ensure the ground wire has a crosssection of at least 10 mm2, or
-Ensure 2 separate ground wires, both
complying with the dimensioning
rules, are used.
NOTICE
HIGH ALTITUDES
For installation at altitudes above 2000 m, contact
Danfoss regarding PELV.
WARNING
DC CURRENT RISK
This product can cause a DC current in the protective
conductor. Failure to follow the precautions can lead to
personal injury or property damage.
Take the following precautions:
Where a residual current device (RCD) is used
•
for extra protection, use only an RCD of Type B
(time delayed) on the supply side of this
product.
Protective earthing of the frequency converter
•
and the use of RCDs must always follow
national and local regulations.
WARNING
GROUNDING HAZARD
For operator safety, it is important to ground the
frequency converter properly in accordance with national
and local electrical codes, as well as the instructions in
this manual. Ground currents are higher than 3.5 mA.
Failure to ground the frequency converter properly could
result in death or serious injury.
It is the responsibility of the user, or certified electrical
installer, to ensure correct grounding of the equipment
according to national and local electrical codes and
standards.
Follow all local and national electrical codes to
•
ground electrical equipment properly.
Establish proper protective grounding for
•
equipment with current higher than 3.5 mA.
A dedicated ground wire is required for input
•
power, motor power, and control wiring.
Use the clamps provided on the equipment for
•
proper ground connections.
Do not ground one frequency converter to
•
another in a daisy chain fashion.
Keep the ground wire connections as short as
•
possible.
Use high-strand wire to reduce electrical noise.
Prerequisite: MCT 10 Set-up Software is installed.
To install the MCT 21 Factory Tool,
1.
Run the file MCT 21 Factory Tool Setup x.x.exe,
where “x.x” refers to the software version. No key
is required.
2.Select during installation:
2aTechnician Tool, and/or
2bEngineering Tool
3.Open the programme.
3.3.2 Serial Fieldbus Communication
To set up serial fieldbus communication with the
frequency converter, refer to chapter 5.6.2 Drive Communi-cation.
3.2 De-installation
NOTICE
De-installation procedure for a Windows operating
system:
1.
Select Start.
2.
Select Settings.
3.
Select Control Panel.
4.
Double-click Programs and Features.
5.Select MCT 21 Factory Tool software.
6.
Select Uninstall.
3.3
Set-up
3.3.1 General Settings
For detailed information regarding general settings, refer
to chapter 5.6.1 General Settings.
Open the MCT 21 Factory Tool software.
•
The first time the program runs, the New Project
•
dialog appears. For more information, see
chapter 5.1.2 New Project - Create from Database.
Go to [Settings → General Settings].
•
In the General Settings dialog:,
•
Set the application and parameter
-
languages.
Set the OEM password.
-
NOTICE
PASSWORD MATCH
Note that data can be password-protected in the
frequency converter. Set the OEM password to match the
frequency converter password. Otherwise no access is
granted.
4.1 Interaction of Engineering Tool and
Technician Tool
The MCT 21 Factory Tool software comprises 2 tools which
interact:
Engineering Tool
•
Technician Tool
•
Develop projects and tests in the Engineering Tool before
implementation in the Technician Tool.
Engineering Tool - Development
The Engineering Tool is intended for use by engineers in
developing projects and tests for planning factory
implementation of frequency converter default settings.
The engineer uses the Engineering Tool to:
Create projects.
•
Set up default parameter settings for OEM
•
production.
Create, design, and verify tests.
•
Manage passwords, motor database, general
•
settings, and communication with the frequency
converter.
Process orders received.
•
Access change and test logs.
•
For Engineering Tool workflow, refer to
chapter 4.2 Workflow Engineering Tool.
For details of Engineering Tool functions, refer to
chapter 5 Engineering Tool Functions.
Technician Tool - Implementation
The Technician Tool is intended for use by technicians
working in the production line. The technician is familiar
with how to assemble the frequency converter and motor.
The technician uses the Technician Tool to:
Create custom set-ups for the frequency
•
converter.
Configure the frequency converter with new
•
settings.
Select and run tests.
•
Manage communication with the frequency
•
converter.
The technician uses projects and tests developed in the
Engineering Tool.
For Technician Tool workflow, refer to chapter 4.3 WorkflowTechnician Tool.
For details of Technician Tool functions, refer to
chapter 6 Technician Tool Functions.
At initial startup of the Engineering Tool, the New Project
dialog opens, see Illustration 5.1. No projects have
previously been created. For details of how to create a
new project, go to chapter 5.1.1 Create a Project.
55
Illustration 5.1 New Project Dialog
A project contains a set of motors and tests available for
use by the technician. Use the Engineering Tool to create a
project.
There are 2 starting points for creating a new project:
Based on an MCT 10 database. Follow the steps
•
in chapter 5.1.2 New Project - Create from
Database.
Based on a project stored in a frequency
•
converter. Follow the steps in chapter 5.1.3 New
Project - Read from Drive.
When all the steps are completed, the new project opens
in project view. See chapter 5.1.6 Project View.
New Project - Create from Database
5.1.2
To create a new project based on the MCT 10 database:
1.
Select Projects in the menu bar.
2.Via the dropdown menu, go to [Projects → New
Project → Create from database], as shown in
Illustration 5.3.
Subsequent start
At subsequent startup of the Engineering Tool, the Search
dialog opens, see Illustration 5.2. Use the dialog to search
for existing projects. For more information go to
chapter 5.1.5 Search Project.
Illustration 5.2 Search Dialog
Illustration 5.3 Path for New Project Based on MCT 10
Database
The New Project dialog opens, see Illustration 5.4.
Illustration 5.4 New Project Dialog
4.
Enter or select project details, see Illustration 5.5:
4aProject name
4bFrequency converter (“Drive series”)
4cPower size
4dVoltage
4eBasic SW version
4fParameter language
Click on [Create Project]
5.
The Project Info dialog opens. Enter further details
of the project, as shown in the example, see
Illustration 5.6.
Illustration 5.6 Project Info Dialog
NOTICE
There are 2 dialogs containing information about the
customer and the order: Project Info (see Illustration 5.6)
and Test Drive and Motor (see Illustration 5.37). Ensure
the data in both dialogs are consistent.
NOTICE
To adapt the Project Info content subsequently, ensure
the original file is preserved, not overwritten. Use SaveAs when adapting content to a different project.
55
6.Click on [Save].
7.The new project opens.
8.A confirmation message appears, stating that the
new project is now created, see Illustration 5.7.
Illustration 5.7 Project Created
Illustration 5.5 New Project, Selection Drop Down Menu