Danfoss MCT 10 Operating guide

Operating Guide
VLT® Motion Control Tool MCT 10
vlt-drives.danfoss.com
VLT® Motion Control Tool MCT 10
Operating Guide

Contents

1
Introduction 10
1.1
1.2
1.3
1.4
System Requirements 11
1.5
1.5.1
Features of the VLT® Motion Control Tool MCT 10 11
1.6
1.7
Safety 14
2
2.1
2.2
Contents
Installation and De-installation 16
3
3.1
3.1.1
Starting the Installation Program 16
3.1.2
Selecting the Software Language 16
3.1.3
Uninstalling the Software 16
4
Set-up of Communication 17
4.1
4.2
4.3
4.3.1
Scan Range Configuration 18
4.3.2
Scan Network 19
4.4
Set Up the Drive with RS485 Data Communication 19
4.4.1
Configuring the Fieldbus 19
4.4.2
USB Data Communication 20
4.5
4.5.1
Serial Configuration 21
4.5.2
Importing/Exporting Parameter Files, MCD 600 22
4.6
PROFIBUS DP-V1 Communication 24
4.6.1
Configuring PROFIBUS DP-V1 24
4.6.2
DP-V1 Connection and PG/PC Interface 25
4.6.3
PROFIBUS Multitelegrams 28
4.7
4.7.1
Ethernet-TSC Configuration 28
AQ283728700891en-000201/130R0466 | 3Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
4.7.2
Wink Drive 32
4.7.3
Advanced 33
5
Parameter Set-up 35
5.1
Introduction 35
5.2
User Interface 35
5.2.1
Display 35
5.2.2
Network and Project Folders 36
5.2.3
Other Folders 37
5.3
Setting Up Drives and Folders 38
5.3.1
Inserting a New Folder 38
5.3.2
Setting Up Drives, Active Filters, or Soft Starters 38
5.3.3
Setting Up Low Harmonic Drives 39
5.3.4
All Parameters Folders 40
5.3.5
Array Parameters 41
Contents
5.3.6
Sorting 42
5.4
Customized Views 42
5.4.1
Customize Parameter View Settings 43
5.4.2
Customize Background Color 43
5.4.3
Customize Parameter View 44
5.4.4
Filtering Parameters 45
5.4.5
Customize Columns 45
5.5
Parameter Edit 46
5.6
Comparison of Parameters 48
5.7
Compare Multiple Drives 49
5.8
View Change Log 51
5.9
Read Drive Operation Status 53
6
Operation 54
6.1
Reading and Writing Parameters 54
6.1.1
Read From Drive Settings 54
6.1.2
Write to Drive Settings 55
6.1.3
Communication Fault Tolerance 55
6.2
Connection Properties 56
6.3
Read from Drive 56
6.3.1
Changing the PROFINET Host Name 58
6.4
Write to Drive 59
6.5
Write to Multiple Drives 60
6.6
Poll 62
AQ283728700891en-000201/130R04664 | Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
6.6.1
6.6.2
6.6.3
6.7
6.8
6.8.1
6.8.2
6.9
Import of Older Dialog Files 65
6.10
6.11
6.12
Update Drives Firmware Support in MCT 10 Set-up Software 69
6.13
6.13.1
6.14
Contents
Stop Polling 62
Resume Polling 63
Using Smart Polling (Intelligent Scan Frequency) 63
Recoding Online Changes 64
Archive/Unarchive 65
Mapping to Compatible Firmware 70
6.14.1
Conversion 71
6.14.2
VLT to FC Series Converter Function 71
6.14.3
FC to FC Conversion 73
6.14.4
Conversion Tables Manager 73
7
Diagnostics 80
7.1
7.2
7.3
Storing Alarms/Warnings in Project Files 81
7.4
Handling the Alarms and Warnings Loggings 81
7.5
7.5.1
Activating the Scope - MCT 10 Set-up Software 82
7.5.2
Configuring the PC Polling Channel 83
7.5.3
PC Polling Channel Properties 85
7.5.4
Reuse of PC Polling Channel Settings 87
7.5.5
Configuring the Drive Real-time Channel 88
7.5.6
Using Advanced Triggers 90
7.5.7
Drive Real-time Channel Properties 92
7.5.8
Communication Control 93
7.5.9
Additional Functionality 93
7.5.10
Scope Storage 94
7.6
8
Plug-ins 97
8.1
AQ283728700891en-000201/130R0466 | 5Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
8.2
Time-based Actions and Preventive Maintenance Plug-ins 97
8.2.1
8.2.2
8.2.3
8.3
Motor Plug-in 100
8.3.1
8.3.2
8.3.3
8.3.4
8.4
Multi-motor Plug-in 105
8.4.1
8.4.2
8.4.3
8.4.4
Contents
Clock Functions 97
Preventive Maintenance 98
Timed Actions 99
Asynchronous Motors 102
PM Non-salient SPM 102
PM Salient IPM 103
SynRM 105
Defining Normal Operation Curve 106
Threshold 106
Coefficients 107
Modified Curves 107
8.5
8.5.1
The Preconditions Tab 108
8.5.2
The Set-up Tab 111
8.5.3
The System Optimizing Tab 116
8.5.4
The Service Tab 117
8.5.5
Extended Cascade Controller Options 120
8.6
8.6.1
Customer-specific Initialization Values - CSIV 125
8.6.2
Creating New CSIV Files 126
8.6.3
Configuration of CSIV Files 127
8.6.4
Drive File Manager 129
8.7
Functional Safety Configuration Plug-in 131
8.7.1
Introduction 131
8.7.2
Access 132
8.7.3
Safe Plug-in Interface 133
8.7.4
Configuration 147
8.7.5
Commissioning 152
8.7.6
Operation 154
8.8
8.9
Drive Control Plug-in 158
8.9.1
Launching the Drive Control Plug-in 160
8.9.2
Setting the Control Word 161
8.9.3
Start Drive Control 162
8.9.4
Changing Control Word Bits 165
AQ283728700891en-000201/130R04666 | Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
8.9.5
8.9.6
8.10
8.10.1
8.11
Condition-based Monitoring (CBM) Plug-in 168
8.11.1
8.11.2
8.11.3
8.11.4
8.11.5
8.11.6
Contents
Changing the Reference 166
Open Drive Control Plug-in 166
Starting the Decoder Plug-in 167
Home Page 171
Speed Range Page 172
Speed Steps Configuration Page 175
8.11.3.1
8.11.3.2
8.11.3.3
Sensor Configuration Page 179
Auto-configuration Setup Page 184
Baseline Progress Page 185
Baseline Run 175
Online Baseline 176
All Baseline Types 177
8.11.6.1
8.11.6.2
8.11.6.3
8.11.7
Thresholds Page 188
8.11.7.1
8.11.7.2
8.11.7.3
8.11.7.4
8.11.8
Monitoring Page 205
8.12
9
Support of VLT® Wireless Communication Panel LCP 103 214
9.1
Introduction 214
9.1.1
Using LCP 103 with MCT 10 Set-up Software Basic Version 214
9.1.2
Using LCP 103 with MCT 10 Set-up Software Advanced Version 214
10
VLT® Software Customizer 216
Baseline Run 185
Online Baseline 186
All Baseline Types 187
Thresholds Generation 198
Numeric Parameters Editing 202
Choice List Parameters Editing 203
Thresholds Page when Auto-configuration is Selected 204
10.1
10.1.1
Activation Key 217
10.1.2
Disclaimer 218
10.2
10.2.1
Creating New from Blank 219
10.2.2
Selecting from Library 220
10.2.3
Import 220
10.3
LanguageChanger 223
AQ283728700891en-000201/130R0466 | 7Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
10.3.1
10.3.2
10.3.3
10.3.4
10.3.5
10.4
InitialValues 229
10.4.1
10.4.2
10.4.3
10.4.4
10.5
SmartStart 233
10.5.1
10.5.2
10.5.3
Contents
New from Blank 224
Search Filter 227
Advanced Settings 228
Audit 229
Markings 229
Creating New from Blank 230
Removing Parameters 232
Saving the CSIV File 232
Validation of Parameters During Import 233
Creating New from Blank 235
Create Diagram 239
Create Parameter Screen 240
10.5.4
Link Screens 243
10.5.5
Branching 246
10.5.6
Junction 248
10.6
Writing to Drive 248
10.6.1
Preserve Original vs. Wipe Original 249
10.7
Testing in Simulator 250
10.7.1
Installing the Simulator 251
11
Tool Calling Interface (TCI) 253
11.1
Introduction 253
11.2
Installing the GSD/GSDML File 253
11.3
Creating a Project in TIA 253
11.4
Use Cases 254
11.4.1
Doing the Initial Connection 254
11.4.2
Configuring the TCI 255
12
SyncPos 257
12.1
SyncPos Handling 257
12.2
Programs and Configuration File 257
12.2.1
Programs 257
12.2.2
Viewing the Configuration File 257
12.2.3
Importing and Exporting a Configuration File 257
12.2.4
Editing and Saving a Configuration File 258
12.2.5
Importing Program Files 259
12.2.6
Setting a Program to Auto Start 260
AQ283728700891en-000201/130R04668 | Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
12.2.7
Editing Source Code 261
12.2.8
Saving and Exiting Program 261
12.3
SyncPos Read From Drive 262
12.4
SyncPos Write to Drive 263
13
Troubleshooting 265
13.1
Save Error Dialog 265
13.2
Common Problems and Solutions 266
13.2.1
Changes are not Saved to PC 266
13.2.2
Error Message While Installing MCT 10 Set-up Software 266
13.2.3
Error Message Communication Failed 266
13.2.4
Communication Errors 267
13.2.5
Help 268
13.3
Safe Plug-in 268
13.3.1
Troubleshooting Communication Errors 268
Contents
13.3.2
Troubleshooting CRC Errors 268
13.3.3
Warnings and Alarms 269
AQ283728700891en-000201/130R0466 | 9Danfoss A/S © 2021.09
Edition
Remarks
Software ver­sion
AQ283728700891, version 0201
Upgrade to new software version. Support of Multiple Drive Handling, Wire­less Direct, and Condition-based Monitoring.
5.3
VLT® Motion Control Tool MCT 10
Operating Guide
Introduction

1 Introduction

1.1 Purpose of this Operating Guide

This manual provides basic knowledge required to use the MCT 10 Set-up Software with Danfoss drives. Familiarity with the follow­ing is assumed:
MS®-Windows™ at user level.
Set-up, process knowledge, and operation of drive.
Use of and linkage with communication equipment.
The manual does not provide any detailed information regarding specific applications or possible solutions and related parameter combinations in the set-up and use of a drive. Refer to the operating guide and design guide of the drive. Any update of the manual and instructions related to the MCT 10 Set-up Software is available at www.danfoss.com.
Familiarity with the PC or PLC master of the system is assumed. Issues regarding hardware or software produced by other manufac­turers are beyond the scope of this manual and are not the responsibility of Danfoss.
Refer to the appropriate manuals for more information about master-to-master communication, or communication to a non-Dan­foss slave.

1.2 Manual and Software Version

This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
The original language of this manual is English.

1.3 Intended Use

The MCT 10 Set-up Software enables full system configuration and control. With MCT 10, it is possible to monitor the entire system more efficiently for faster diagnosis and better preventive maintenance.
MCT 10 is designed as an interactive commissioning tool for quick and easy commissioning of the following drive series:
VLT® 2800.
VLT® 4000.
VLT® 5000.
VLT® 6000.
VLT® 8000.
VLT® Micro Drive FC 51.
VLT® HVAC Basic Drive FC 101.
VLT® HVAC Drive FC 102.
VLT® Refrigeration Drive FC 103.
VLT® AQUA Drive FC 202.
VLT® Midi Drive FC 280.
VLT® AutomationDrive FC 301/FC 302.
VLT® AutomationDrive FC 360.
VLT® Decentral Drive FCD 302.
VLT® DriveMotor FCM Series.
VLT® Compressor Drive CD 302.
VLT® Compressor Drive CDS 302.
VLT® Compressor Drive CDS 303.
VLT® Soft Starter MCD 500.
VLT® Soft Starter MCD 600.
AQ283728700891en-000201 / 130R046610 | Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
VLT® Advanced Active Filter AAF 005.
VLT® Advanced Active Filter AAF 006.
Use cases of the MCT 10:
For planning a new communication network offline. The MCT 10 contains a complete database with all Danfoss Drives products.
For commissioning drives online.
For easy replacement of drives.
For easy expansion of networks with more drives.
For back-up of parameter settings of drives in a communication network.
The MCT 10 supports PROFIBUS DP-V1 communication via a master class 2 connection. This connection eliminates the need for an extra communication network.
The communication framework part of MCT 10 is handling the control of the fieldbuses. It provides enhanced capabilities allowing multiple concurrent fieldbus communication. Several fieldbuses can be configured and combined in the same network within MCT
10.
Introduction
N O T I C E
If several fieldbuses are created with the same type, make sure that they are configured with different scan ranges.

1.4 System Requirements

To use the VLT® Motion Control Tool MCT 10, the IBM-compatible computer must meet the following minimum system require­ments:
4 GB of available space on the hard drive.
MCT 10 runs on Windows™ 10 32/64-bit editions.

1.5 Software Modules

The VLT® Motion Control Tool MCT 10 Set-up Software is supplied in 2 modules:
MCT 10 Set-up Software for:
-
Setting the drive parameters.
-
Copying parameter sets to and from a drive.
-
Documentation/printout of set-up, including diagrams.
-
Servicing and fault analysis.
APoss program for creating APoss programs.
1.5.1 Features of the VLT® Motion Control Tool MCT 10
Project-oriented PC tool, 1 tool for all drive series.
Links to all Windows applications possible.
Supports Siemens CP PCMCIA-and PCI cards for PROFIBUS DP-V1 master class 2 connection.
Supports standard interfaces: COMx, USB, RS232 (Flux).
Siemens PG/Field PGs already have the required hardware.
View is highly individually configurable.
Downwards compatibility with Dos-Dialog (*.mnu) and WinDialog (*.vlt).
Windows™ Explorer-like interface for quick and easy start-up and navigation.
Wireless Direct.
AQ283728700891en-000201 / 130R0466 | 11Danfoss A/S © 2021.09
e30bt513.12
PC (Master)
USB to RS485 converter
#1
#2
#3 #126
Version supports
MCT 10 Set-up Software Advanced
MCT 10 Set-up Soft­ware Basic
Drives per project
Unlimited
4
FC protocol
Functional safety
USB
PROFIBUS DP-V1
PROFIBUS DP-V1 handling multiple Danfoss nodes concurrently
(limited performance)
Ethernet-TSC
Logging and scope function
8 channels
2 channels
Real-time logging from a drive
4 channels
Alarm display
View only
VLT® Motion Control Option MCO 305
Graphical smart logic control
VLT® 5000 to FC 302, VLT® 6000 to FC 102, and VLT® 2800 to FC 280 conver­sion wizards
VLT® Motion Control Tool MCT 10
Operating Guide
Introduction
Illustration 1: Connect up to 126 Nodes with a Repeater and up to 31 Nodes without Repeater

1.6 Versions

VLT® Motion Control Tool MCT 10 is available in 2 versions:
MCT 10 Set-up Software Basic is available free of charge. Download the program from www.danfoss.com - select VLT® Motion Control Tool MCT 10.
MCT 10 Set-up Software Advanced can be purchased using ordering number 130B1000.
Table 1: Features of the Basic and Advanced Versions
AQ283728700891en-000201 / 130R046612 | Danfoss A/S © 2021.09
Version supports
MCT 10 Set-up Software Advanced
MCT 10 Set-up Soft­ware Basic
FC to FC conversion wizard
Import 3000.XLS to FC 302
Motor database
VLT® Extended Cascade Controller MCO 101
Drive file system
VLT® Wireless Control Panel LCP 103
Status plug-in
Drive plug-in
VLT® Software Customizer
VLT® Motion Control Tool MCT 10
Operating Guide

1.7 Further Information

The following manuals related to VLT® Motion Control Tool MCT 10 are available:
VLT® PROFIBUS DP-V1 MCA 101 Installation Guide.
Design guides for the relevant drives.
Refer to www.danfoss.com/en/about-danfoss/our-businesses/drives/ for more information. It is also possible to find video training material on this site for operating the MCT 10.
Introduction
AQ283728700891en-000201 / 130R0466 | 13Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide

2 Safety

2.1 Safety Symbols

The following symbols are used in this manual:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for example messages relating to property damage).
Safety

2.2 Safety Precautions

W A R N I N G
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input , DC supply , or load sharing. Failure to perform installation,
start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
-
W A R N I N G
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death,
serious injury, and equipment, or property damage. The motor may start by activation of an external switch, a fieldbus command,
an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condi-
tion.
Press [Off] on the LCP before programming parameters.
-
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor
-
start.
Check that the drive, motor, and any driven equipment is in operational readiness.
-
AQ283728700891en-000201 / 130R046614 | Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
Safety
W A R N I N G
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or
serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives.
Wait for the capacitors to discharge fully before performing any service or repair work. The discharge time is specified in the
-
drive operating guides.
Use a measuring device to make sure that there is no voltage, before opening the drive or performing any work on the ca-
-
bles.
AQ283728700891en-000201 / 130R0466 | 15Danfoss A/S © 2021.09
e30bt514.14
VLT® Motion Control Tool MCT 10
Operating Guide
Installation and De-installation

3 Installation and De-installation

3.1 Introduction

The VLT® Motion Control Tool MCT 10 Software and SyncPos modules are installed via a multilingual, self-explanatory installation program.
3.1.1 Starting the Installation Program
Procedure
1.
Run VLT_MCT10_Vx.xx.msi.
2.
Follow the instructions of the installation program.
When the installation process is complete, the MCT 10 Set-up Software can be found on the following path:
Illustration 2: Path for MCT 10 Set-up Software
3.1.2 Selecting the Software Language
The Danfoss default language is English. If another language is selected, it becomes the new default.
Procedure
1.
Select Options from the main menu, then select Select Language.
2.
Select the wanted language from the scrollbar and click OK.
N O T I C E
Changing the language affects the parameter language. If an external LCP is connected to the drive, the change of lan-
guage version does not affect the language in the display.
3.
Close and restart MCT 10 to activate the language setting.
3.1.3 Uninstalling the Software
N O T I C E
The following procedure is only valid for Windows operating systems.
Procedure
1.
Select Start.
2.
Select Settings.
3.
Select Control Panel.
4.
Double-click Remove/Add Programs.
5.
Select Remove.
AQ283728700891en-000201 / 130R046616 | Danfoss A/S © 2021.09
e30bt631.11
VLT® Motion Control Tool MCT 10
Operating Guide
Set-up of Communication

4 Set-up of Communication

4.1 Communication Options

Drives in the VLT® HVAC Drive FC 102, VLT® AQUA Drive FC 202, and VLT® AutomationDrive FC 302 series are equipped with a USB port. Communication from a PC can be established using a standard A–B male-to-male USB cable connected to the drive. No extra hardware or bus configuration is required. If the PC is equipped with more than 1 USB port, several drives can be connected. The USB bus is automatically added to the network bus list.
Establish a hardwired connection through:
Standard built-in RS485, or
USB port.
The USB interface socket allows devices to be connected and disconnected using hot swapping. When connecting a drive using USB, MCT 10 Set-up Software automatically adds on to the bus list.
If the VLT® PROFIBUS DP-V1 MCA 101 or the VLT® EtherNet/IP MCA 121 option is mounted in the drive, establish the connection through:
PROFIBUS master class 2 connection (MSAC 2), or
Ethernet-based network.
N O T I C E
Connect soft starters either via a USB cable or via ethernet.
N O T I C E
RISK OF DAMAGE TO PC USB HOST CONTROLLER
When connecting the PC to the drive through the USB cable, there is a risk of damaging the PC USB host controller.
Follow the recommendations for grounding described in the Operating Guide for the relevant drive.
-
Use a USB isolator with galvanic isolation to protect the PC USB host controller from ground potential differences when con-
-
necting the PC to a drive through a USB cable.
Do NOT use a PC power cable with a ground plug when the PC is connected to the drive through a USB cable.
-
Communication from a PC can be established via RS232 to RS485 converters or via USB to RS485 converters.
Illustration 3: Communication from a PC

4.2 Manual Fieldbus Configuration

After installation, configure the non-plug-and-play networks via the fieldbus configuration dialog.
Procedure
1.
Start the MCT 10 Set-up Software.
2.
Select Network.
AQ283728700891en-000201 / 130R0466 | 17Danfoss A/S © 2021.09
e30bt622.12
e30bt630.13
VLT® Motion Control Tool MCT 10
Operating Guide
3.
Right-click Network and select Add/Remove/Configure Buses.
Illustration 4: Refreshing the Fieldbus List
4.
Add, remove, or configure the properties for the connected buses.
Set-up of Communication
Illustration 5: Fieldbus Configuration
5.
Scan the network for active drives to make MCT 10 indicate available drives on the non-plug-and-play fieldbuses.

4.3 Automatic Scan

Only the USB fieldbus is scanned automatically when a drive is connected to the PC. For non-plug-and-play fieldbuses, scan manual­ly for active drives.
4.3.1 Scan Range Configuration
Enter the preferred scan setting by right-clicking SerialCom and then selecting Configure Driver. Adding a standard bus RS485 or PROFIBUS to the network tree configures the scan range to scan the entire address range. The
Ethernet-TSC bus is added using the current IP address settings. The fieldbus scan range can be configured in several ways:
Right-click the Fieldbus icon in the network tree and select Configure Bus.
Mark the Fieldbus icon in the network tree and select Configure under Communication in the main menu bar.
Open the Fieldbus Configuration dialog, right-click the Network icon, and select Add/Remove/Configure Buses.
Open from the Windows panel.
AQ283728700891en-000201 / 130R046618 | Danfoss A/S © 2021.09
e30bt495.14
Scan network icon
e30bt496.12
VLT® Motion Control Tool MCT 10
Operating Guide
Illustration 6: Scan Network Icon
Set-up of Communication
4.3.2 Scan Network
Scan a fieldbus in 3 ways:
Right-click the Fieldbus icon in the network tree and select Scan Bus for active drives.
Mark the Fieldbus icon in the network tree and select Scan/Refresh under Communication in the main menu bar.
Mark the Fieldbus icon in the network tree and select the Scan icon on the toolbar.
The Scanning for Drives window appears and indicates the progress of the scan.
Illustration 7: Progress of Network Scanning

4.4 Set Up the Drive with RS485 Data Communication

All drives can be configured to 300, 1200, 4800, 9600 (default), 19200, 38400, 57600, or 115200 baud. The serial configuration is always configured with:
8 data bits.
1 stop bit.
Even parity.
4.4.1 Configuring the Fieldbus
When using an RS485 converter as the Advantech ADAM converter, MCT 10 Set-up Software indicates online drives available on the fieldbus after scanning the bus.
N O T I C E
Protocol and advanced settings are for performance optimization and should normally not be changed.
Procedure
AQ283728700891en-000201 / 130R0466 | 19Danfoss A/S © 2021.09
e30bt629.12
e30bt623.12
VLT® Motion Control Tool MCT 10
Operating Guide
1.
Open the Serial Fieldbus Configuration dialog box or right-click the appropriate fieldbus.
Illustration 8: Serial Fieldbus Configuration
2.
Set the COM port number.
Set-up of Communication
When using USB to RS485 converters, the actual COM port number can be identified from the device manager part of the Windows control panel.
3.
Set the baud rate, parity, and the number of stop bits (must match the settings in the drive).
4.
Set the fieldbus scanning range to the available address to limit the time scanning for active drives.
5.
Press OK to activate settings or select to restore the default settings.
4.4.2 USB Data Communication
Illustration 9: Network Bus List
When the USB cable is disconnected, the drive connected via the USB port is removed from the network bus list.

4.5 Set-up of Soft Starter

Setting up connectivity to the VLT® Soft Starter MCD 500 and VLT® Soft Starter MCD 600 requires that the USB communication mod­ule is mounted on the soft starter. Communication from a PC can be established using a standard A–B male-to-male USB cable connected to the USB communication module. If the PC is equipped with more than 1 USB port or a USB HUB, several soft starters can be connected.
AQ283728700891en-000201 / 130R046620 | Danfoss A/S © 2021.09
e30bt758.12
VLT® Motion Control Tool MCT 10
Operating Guide
Set-up of Communication
4.5.1 Serial Configuration
All soft starters can be configured to 300, 1200, 4800, 9600 (default), 19200, 38400, 57600, or 115200 baud. The serial configuration is always configured with:
8 data bits.
1 stop bit.
No parity.
Illustration 10: Serial Configuration of Soft Starters
4.5.1.1 Configuring the Fieldbus
Procedure
1.
Add and configure the bus from the Fieldbus Configuration dialog.
If the bus is already added to the network, it can be reconfigured by right-clicking on the appropriate soft starter fieldbus.
2.
Set the COM port number. The actual COM port number can be identified from the device manager part of the control panel.
3.
Set the baud rate, parity, and the number of stop bits (must match the setting in the soft starter).
4.
Reset to Default restores the general settings and fieldbus scanning to factory configuration values.
4.5.1.2 Using the Hilscher NetIdent Protocol
Use the tool for searching for devices and for identifying and changing IP addresses. The tool also has a filtering function.
Procedure
1.
Click the Tools menu.
AQ283728700891en-000201 / 130R0466 | 21Danfoss A/S © 2021.09
e30bt980.12
VLT® Motion Control Tool MCT 10
Operating Guide
2.
Select Soft Starter Discover and Configuration Tool.
Set-up of Communication
Illustration 11: Selecting the Hilscher NetIdent Tool
3.
Select the soft starter for which the IP address should be configured.
4.
Click Configure.
4.5.2 Importing/Exporting Parameter Files, MCD 600
With VLT® Soft Starter MCD 600, a parameter file (PAR file) can be exported from the soft starter to a USB stick and copied into VLT® Motion Control Tool MCT 10. After changing the file in MCT 10, the PAR file can be copied back to the USB stick and applied to the soft starter.
Procedure
Create an MCD 600 project soft starter.
1.
Right-click the project folder.
2.
3.
Select Import parameters. From the dialog, select the file to import.
4.
A dialog opens showing information about the selected file.
AQ283728700891en-000201 / 130R046622 | Danfoss A/S © 2021.09
e30bu310.12
e30bu311.12
VLT® Motion Control Tool MCT 10
Operating Guide
If the soft starter differs from the project, it shows up as an error or warning in this view, depending on the differ­ence.
5.
Press Continue to apply the file.
A view, which shows all changed parameters, appears.
Set-up of Communication
6.
Click Ok to close the window.
7.
Right-click the project to export from MCT 10.
8.
Select the parameters to export.
9.
In the file selection dialog, select where to export the file to.
A dialog appears when the export is completed.
AQ283728700891en-000201 / 130R0466 | 23Danfoss A/S © 2021.09
e30bu312.11
e30bt634.11
PCMCIA DP-V1 card
DP-V1
#1
#2 #N
DP-V1
#1
#2 #N
Insertable DP-V1 card
VLT® Motion Control Tool MCT 10
Operating Guide
Set-up of Communication

4.6 PROFIBUS DP-V1 Communication

Setting up PROFIBUS DP-V1 communication requires a VLT® PROFIBUS DP-V1 MCA 101 option module. Communication from a PC using PROFIBUS DP-V1 can be established using a PROFIBUS PCMCIA card or a card installed in the PC. The PROFIBUS cable from the drive is connected to the 9-pin sub D socket connector on the card.
Illustration 12: PROFIBS DP-V1 Communication
Consult Siemens www.siemens.com for the latest supported cards for PCs.
N O T I C E
Connectivity via PROFIBUS DP-V1 to a VLT® AutomationDrive FC 302 utilizing the VLT® PROFIBUS Converter MCA 114 with option
firmware version 2.03 is not possible from MCT 10 Set-up Software. Use the fieldbus or USB bus instead.
4.6.1 Configuring PROFIBUS DP-V1
When using a PROFIBUS interface card with the associated driver installed, MCT 10 Set-up Software indicates online drives available on the specific PROFIBUS after scanning the bus for active drives.
Procedure
AQ283728700891en-000201 / 130R046624 | Danfoss A/S © 2021.09
e30bt625.14
VLT® Motion Control Tool MCT 10
Operating Guide
1.
Configure the bus from the Fieldbus Configuration dialog or by right-clicking the appropriate PROFIBUS bus.
Illustration 13: PROFIBUS Fieldbus Configuration
2.
Set the board number.
3.
Set the fieldbus scanning range to the available addresses only to limit the time used for scanning active drives.
4.
Press OK to activate or reset to restore factory default settings.
Set-up of Communication
4.6.2 DP-V1 Connection and PG/PC Interface
The MCT 10 Set-up Software PROFIBUS DP-V1 fieldbus plug-in utilizes the Siemens SoftNet driver available from Step7, or alterna­tively Simatic NET, to establish connectivity via the supported master class 2 cards such as CP5511 or CP5512.
N O T I C E
STEP7 Lite version does not support the SoftNet driver.
4.6.2.1 Setting Up the PG/PC Interface
This procedure explains how to set up the PG/PC Interface from default configuration to open the PROFIBUS connection from MCT
10. Cabling and terminations must be in accordance with wiring and cabling requirements for PROFIBUS.
Procedure
AQ283728700891en-000201 / 130R0466 | 25Danfoss A/S © 2021.09
e30bt789.10
VLT® Motion Control Tool MCT 10
Operating Guide
1.
Open the PG/PC Interface.
Set-up of Communication
Illustration 14: Set PG/PC Interface
2.
Configure Access Point of the Application to CP_L2_1 pointing to the master class 2 card used.
3.
Set Interface Parameter Assignment Used corresponding to the master class 2 card used.
4.
Select Properties to configure the station- and network parameters.
Station parameters:
-
Set PG/PC is the only master on the bus to Active if no PLC is active on the bus. Use the Diagnostics described later to select a valid PROFIBUS address.
Network parameters:
-
Set the Transmission rate to the same baud rate as the PLC if it is active.
5.
Use DP as Profile and click OK to close the Properties dialog.
AQ283728700891en-000201 / 130R046626 | Danfoss A/S © 2021.09
e30bt790.11
130BT791.10
VLT® Motion Control Tool MCT 10
Operating Guide
6.
Select Diagnostics in the Set PG/PC Interface to verify network- and bus communication.
Set-up of Communication
Illustration 15: Properties Dialog
Illustration 16: Simatic Network Diagnostics Dialog
7.
Select Test to verify the access path and network configuration. If a sharing violation is detected, the test results in an error message. When the test result is successful, select Read to identify the active PROFIBUS nodes available on the network. Make sure that the address defined for the PG/PC interface does not conflict with an active node.
AQ283728700891en-000201 / 130R0466 | 27Danfoss A/S © 2021.09
VLT® Motion Control Tool MCT 10
Operating Guide
8.
Close the PG/PC interface and start MCT 10.
9.
Right-click a PROFIBUS and select Scan for active drives. MCT 10 Set-up Software identifies the same node IDs, except PLCs.
Set-up of Communication
4.6.3 PROFIBUS Multitelegrams
With the Parameters allowed per telegram drop-down list, it is possible to configure the number of requests to be associated within a multitelegram. The standard allows up to 40 telegrams to be associated.
The following options are available:
Maximum speed (default configuration). Handles the association automatically and adapts the number of telegrams for each drive according to the series. Can be used in PROFIBUS networks containing both old and new Danfoss drives.
Conservative. Always associates 10 telegrams within a multitelegram. This option is useful when communicating only with old products such as the VLT® Decentral Drives FCD 300, VLT® DriveMotor FCM 300, series derived from VLT® HVAC Drive FC 102, VLT® AQUA Drive FC 202, and VLT® AutomationDrive FC 302.
Single request. Only 1 request per telegram.

4.7 Ethernet-TSC Data Communication

To set up an Ethernet-TSC (transparent socket channel) communication, the VLT® EtherNet/IP MCA 121 option module is required within the drive. Communication from a PC can be established using a standard Ethernet cable connected to the drive.
4.7.1 Ethernet-TSC Configuration
An Ethernet-TSC bus is scanned using DDP (drive discovery protocol). The protocol does not require an IP port number and IP scan range. It identifies drives based on the MAC addresses.
N O T I C E
When scanning through different subnets or remotely via a VPN tunnel, it is advised not to utilize the ADDP protocol but to use
an IP range.
Click Refresh to generate a list of all active drives in the Ethernet. The list appears in the Ethernet Fieldbus Settings dialog when the scan is complete.
AQ283728700891en-000201 / 130R046628 | Danfoss A/S © 2021.09
e30bt775.13
VLT® Motion Control Tool MCT 10
Operating Guide
Set-up of Communication
Illustration 17: ADDP Configuration
Drive types without any IP configuration use their Auto IP Class B address, which is 169.254.yy.xx, with yy.xx corresponding to the last 2 segments in the MAC address. Several uncommissioned drives without any IP configuration can be scanned on the same net­work.
Select a device from the Discovered Drives list to;
Get more information about the device.
Assign a static IP address, a subnet mask, or default value to the drive.
Set up DHCP (dynamic host configuration protocol) look-up.
AQ283728700891en-000201 / 130R0466 | 29Danfoss A/S © 2021.09
e30bt857.11
VLT® Motion Control Tool MCT 10
Operating Guide
Set-up of Communication
Illustration 18: TSC Configure
4.7.1.1 Scanning with IP Range
When scanning using an IP range, the Ethernet telegrams are transmitted as traditional TCP/IP packages routed out in a router, switch, or manage switch without requiring any changes. The disadvantage is an increased scanning time, and drives without IP address configured are not identified.
N O T I C E
Identification of drives using the VLT® EtherNet/IP MCA 121 option is possible only from option firmware version 1.03 or newer. If
using options with firmware versions earlier than 1.03, configure parameter 12-89 Transparent Socket Channel Power to 0 to pre-
vent the option from failing to operate.
Procedure
AQ283728700891en-000201 / 130R046630 | Danfoss A/S © 2021.09
Loading...
+ 252 hidden pages