Upgrade to new software version. Support of Multiple Drive Handling, Wireless Direct, and Condition-based Monitoring.
5.3
VLT® Motion Control Tool MCT 10
Operating Guide
Introduction
1 Introduction
1.1 Purpose of this Operating Guide
This manual provides basic knowledge required to use the MCT 10 Set-up Software with Danfoss drives. Familiarity with the following is assumed:
•
MS®-Windows™ at user level.
•
Set-up, process knowledge, and operation of drive.
•
Use of and linkage with communication equipment.
The manual does not provide any detailed information regarding specific applications or possible solutions and related parameter
combinations in the set-up and use of a drive. Refer to the operating guide and design guide of the drive. Any update of the manual
and instructions related to the MCT 10 Set-up Software is available at www.danfoss.com.
Familiarity with the PC or PLC master of the system is assumed. Issues regarding hardware or software produced by other manufacturers are beyond the scope of this manual and are not the responsibility of Danfoss.
Refer to the appropriate manuals for more information about master-to-master communication, or communication to a non-Danfoss slave.
1.2 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
The original language of this manual is English.
1.3 Intended Use
The MCT 10 Set-up Software enables full system configuration and control. With MCT 10, it is possible to monitor the entire system
more efficiently for faster diagnosis and better preventive maintenance.
MCT 10 is designed as an interactive commissioning tool for quick and easy commissioning of the following drive series:
For planning a new communication network offline. The MCT 10 contains a complete database with all Danfoss Drives products.
•
For commissioning drives online.
•
For easy replacement of drives.
•
For easy expansion of networks with more drives.
•
For back-up of parameter settings of drives in a communication network.
•
The MCT 10 supports PROFIBUS DP-V1 communication via a master class 2 connection. This connection eliminates the need for
an extra communication network.
The communication framework part of MCT 10 is handling the control of the fieldbuses. It provides enhanced capabilities allowing
multiple concurrent fieldbus communication. Several fieldbuses can be configured and combined in the same network within MCT
10.
Introduction
N O T I C E
If several fieldbuses are created with the same type, make sure that they are configured with different scan ranges.
1.4 System Requirements
To use the VLT® Motion Control Tool MCT 10, the IBM-compatible computer must meet the following minimum system requirements:
4 GB of available space on the hard drive.
•
MCT 10 runs on Windows™ 10 32/64-bit editions.
1.5 Software Modules
The VLT® Motion Control Tool MCT 10 Set-up Software is supplied in 2 modules:
•
MCT 10 Set-up Software for:
-
Setting the drive parameters.
-
Copying parameter sets to and from a drive.
-
Documentation/printout of set-up, including diagrams.
-
Servicing and fault analysis.
•
APoss program for creating APoss programs.
1.5.1 Features of the VLT® Motion Control Tool MCT 10
•
Project-oriented PC tool, 1 tool for all drive series.
•
Links to all Windows applications possible.
•
Supports Siemens CP PCMCIA-and PCI cards for PROFIBUS DP-V1 master class 2 connection.
•
Supports standard interfaces: COMx, USB, RS232 (Flux).
•
Siemens PG/Field PGs already have the required hardware.
•
View is highly individually configurable.
•
Downwards compatibility with Dos-Dialog (*.mnu) and WinDialog (*.vlt).
•
Windows™ Explorer-like interface for quick and easy start-up and navigation.
The following manuals related to VLT® Motion Control Tool MCT 10 are available:
•
VLT® PROFIBUS DP-V1 MCA 101 Installation Guide.
•
Design guides for the relevant drives.
Refer to www.danfoss.com/en/about-danfoss/our-businesses/drives/ for more information.
It is also possible to find video training material on this site for operating the MCT 10.
Drives in the VLT® HVAC Drive FC 102, VLT® AQUA Drive FC 202, and VLT® AutomationDrive FC 302 series are equipped with a USB
port. Communication from a PC can be established using a standard A–B male-to-male USB cable connected to the drive. No extra
hardware or bus configuration is required. If the PC is equipped with more than 1 USB port, several drives can be connected. The
USB bus is automatically added to the network bus list.
Establish a hardwired connection through:
•
Standard built-in RS485, or
•
USB port.
The USB interface socket allows devices to be connected and disconnected using hot swapping. When connecting a drive using
USB, MCT 10 Set-up Software automatically adds on to the bus list.
If the VLT® PROFIBUS DP-V1 MCA 101 or the VLT® EtherNet/IP MCA 121 option is mounted in the drive, establish the connection
through:
•
PROFIBUS master class 2 connection (MSAC 2), or
•
Ethernet-based network.
N O T I C E
Connect soft starters either via a USB cable or via ethernet.
N O T I C E
RISK OF DAMAGE TO PC USB HOST CONTROLLER
When connecting the PC to the drive through the USB cable, there is a risk of damaging the PC USB host controller.
Follow the recommendations for grounding described in the Operating Guide for the relevant drive.
-
Use a USB isolator with galvanic isolation to protect the PC USB host controller from ground potential differences when con-
-
necting the PC to a drive through a USB cable.
Do NOT use a PC power cable with a ground plug when the PC is connected to the drive through a USB cable.
-
Communication from a PC can be established via RS232 to RS485 converters or via USB to RS485 converters.
Illustration 3: Communication from a PC
4.2 Manual Fieldbus Configuration
After installation, configure the non-plug-and-play networks via the fieldbus configuration dialog.
Right-click Network and select Add/Remove/Configure Buses.
Illustration 4: Refreshing the Fieldbus List
4.
Add, remove, or configure the properties for the connected buses.
Set-up of Communication
Illustration 5: Fieldbus Configuration
5.
Scan the network for active drives to make MCT 10 indicate available drives on the non-plug-and-play fieldbuses.
4.3 Automatic Scan
Only the USB fieldbus is scanned automatically when a drive is connected to the PC. For non-plug-and-play fieldbuses, scan manually for active drives.
4.3.1 Scan Range Configuration
Enter the preferred scan setting by right-clicking SerialCom and then selecting Configure Driver.
Adding a standard bus RS485 or PROFIBUS to the network tree configures the scan range to scan the entire address range. The
Ethernet-TSC bus is added using the current IP address settings.
The fieldbus scan range can be configured in several ways:
•
Right-click the Fieldbus icon in the network tree and select Configure Bus.
•
Mark the Fieldbus icon in the network tree and select Configure under Communication in the main menu bar.
•
Open the Fieldbus Configuration dialog, right-click the Network icon, and select Add/Remove/Configure Buses.
Right-click the Fieldbus icon in the network tree and select Scan Bus for active drives.
•
Mark the Fieldbus icon in the network tree and select Scan/Refresh under Communication in the main menu bar.
•
Mark the Fieldbus icon in the network tree and select the Scan icon on the toolbar.
The Scanning for Drives window appears and indicates the progress of the scan.
Illustration 7: Progress of Network Scanning
4.4 Set Up the Drive with RS485 Data Communication
All drives can be configured to 300, 1200, 4800, 9600 (default), 19200, 38400, 57600, or 115200 baud. The serial configuration is
always configured with:
•
8 data bits.
•
1 stop bit.
•
Even parity.
4.4.1 Configuring the Fieldbus
When using an RS485 converter as the Advantech ADAM converter, MCT 10 Set-up Software indicates online drives available on the
fieldbus after scanning the bus.
N O T I C E
Protocol and advanced settings are for performance optimization and should normally not be changed.
Open the Serial Fieldbus Configuration dialog box or right-click the appropriate fieldbus.
Illustration 8: Serial Fieldbus Configuration
2.
Set the COM port number.
Set-up of Communication
When using USB to RS485 converters, the actual COM port number can be identified from the device manager part of the
Windows control panel.
3.
Set the baud rate, parity, and the number of stop bits (must match the settings in the drive).
4.
Set the fieldbus scanning range to the available address to limit the time scanning for active drives.
5.
Press OK to activate settings or select to restore the default settings.
4.4.2 USB Data Communication
Illustration 9: Network Bus List
When the USB cable is disconnected, the drive connected via the USB port is removed from the network bus list.
4.5 Set-up of Soft Starter
Setting up connectivity to the VLT® Soft Starter MCD 500 and VLT® Soft Starter MCD 600 requires that the USB communication module is mounted on the soft starter. Communication from a PC can be established using a standard A–B male-to-male USB cable
connected to the USB communication module. If the PC is equipped with more than 1 USB port or a USB HUB, several soft starters
can be connected.
All soft starters can be configured to 300, 1200, 4800, 9600 (default), 19200, 38400, 57600, or 115200 baud. The serial configuration
is always configured with:
•
8 data bits.
•
1 stop bit.
•
No parity.
Illustration 10: Serial Configuration of Soft Starters
4.5.1.1 Configuring the Fieldbus
Procedure
1.
Add and configure the bus from the Fieldbus Configuration dialog.
If the bus is already added to the network, it can be reconfigured by right-clicking on the appropriate soft starter fieldbus.
2.
Set the COM port number. The actual COM port number can be identified from the device manager part of the control
panel.
3.
Set the baud rate, parity, and the number of stop bits (must match the setting in the soft starter).
4.
Reset to Default restores the general settings and fieldbus scanning to factory configuration values.
4.5.1.2 Using the Hilscher NetIdent Protocol
Use the tool for searching for devices and for identifying and changing IP addresses. The tool also has a filtering function.
With VLT® Soft Starter MCD 600, a parameter file (PAR file) can be exported from the soft starter to a USB stick and copied into VLT®
Motion Control Tool MCT 10. After changing the file in MCT 10, the PAR file can be copied back to the USB stick and applied to the
soft starter.
Procedure
Create an MCD 600 project soft starter.
1.
Right-click the project folder.
2.
3.
Select Import parameters.
From the dialog, select the file to import.
4.
A dialog opens showing information about the selected file.
Setting up PROFIBUS DP-V1 communication requires a VLT® PROFIBUS DP-V1 MCA 101 option module. Communication from a PC
using PROFIBUS DP-V1 can be established using a PROFIBUS PCMCIA card or a card installed in the PC. The PROFIBUS cable from the
drive is connected to the 9-pin sub D socket connector on the card.
Illustration 12: PROFIBS DP-V1 Communication
Consult Siemens www.siemens.com for the latest supported cards for PCs.
N O T I C E
Connectivity via PROFIBUS DP-V1 to a VLT® AutomationDrive FC 302 utilizing the VLT® PROFIBUS Converter MCA 114 with option
firmware version 2.03 is not possible from MCT 10 Set-up Software. Use the fieldbus or USB bus instead.
4.6.1 Configuring PROFIBUS DP-V1
When using a PROFIBUS interface card with the associated driver installed, MCT 10 Set-up Software indicates online drives available
on the specific PROFIBUS after scanning the bus for active drives.
Configure the bus from the Fieldbus Configuration dialog or by right-clicking the appropriate PROFIBUS bus.
Illustration 13: PROFIBUS Fieldbus Configuration
2.
Set the board number.
3.
Set the fieldbus scanning range to the available addresses only to limit the time used for scanning active drives.
4.
Press OK to activate or reset to restore factory default settings.
Set-up of Communication
4.6.2 DP-V1 Connection and PG/PC Interface
The MCT 10 Set-up Software PROFIBUS DP-V1 fieldbus plug-in utilizes the Siemens SoftNet driver available from Step7, or alternatively Simatic NET, to establish connectivity via the supported master class 2 cards such as CP5511 or CP5512.
N O T I C E
STEP7 Lite version does not support the SoftNet driver.
4.6.2.1 Setting Up the PG/PC Interface
This procedure explains how to set up the PG/PC Interface from default configuration to open the PROFIBUS connection from MCT
10.
Cabling and terminations must be in accordance with wiring and cabling requirements for PROFIBUS.
Configure Access Point of the Application to CP_L2_1 pointing to the master class 2 card used.
3.
Set Interface Parameter Assignment Used corresponding to the master class 2 card used.
4.
Select Properties to configure the station- and network parameters.
Station parameters:
-
Set PG/PC is the only master on the bus to Active if no PLC is active on the bus. Use the Diagnostics described later to
select a valid PROFIBUS address.
Network parameters:
-
Set the Transmission rate to the same baud rate as the PLC if it is active.
5.
Use DP as Profile and click OK to close the Properties dialog.
Select Test to verify the access path and network configuration. If a sharing violation is detected, the test results in an error
message. When the test result is successful, select Read to identify the active PROFIBUS nodes available on the network.
Make sure that the address defined for the PG/PC interface does not conflict with an active node.
Right-click a PROFIBUS and select Scan for active drives. MCT 10 Set-up Software identifies the same node IDs, except PLCs.
Set-up of Communication
4.6.3 PROFIBUS Multitelegrams
With the Parameters allowed per telegram drop-down list, it is possible to configure the number of requests to be associated within a
multitelegram. The standard allows up to 40 telegrams to be associated.
The following options are available:
•
Maximum speed (default configuration). Handles the association automatically and adapts the number of telegrams for each
drive according to the series. Can be used in PROFIBUS networks containing both old and new Danfoss drives.
•
Conservative. Always associates 10 telegrams within a multitelegram. This option is useful when communicating only with old
products such as the VLT® Decentral Drives FCD 300, VLT® DriveMotor FCM 300, series derived from VLT® HVAC Drive FC 102,
VLT® AQUA Drive FC 202, and VLT® AutomationDrive FC 302.
•
Single request. Only 1 request per telegram.
4.7 Ethernet-TSC Data Communication
To set up an Ethernet-TSC (transparent socket channel) communication, the VLT® EtherNet/IP MCA 121 option module is required
within the drive. Communication from a PC can be established using a standard Ethernet cable connected to the drive.
4.7.1 Ethernet-TSC Configuration
An Ethernet-TSC bus is scanned using DDP (drive discovery protocol). The protocol does not require an IP port number and IP scan
range. It identifies drives based on the MAC addresses.
N O T I C E
When scanning through different subnets or remotely via a VPN tunnel, it is advised not to utilize the ADDP protocol but to use
an IP range.
Click Refresh to generate a list of all active drives in the Ethernet. The list appears in the Ethernet Fieldbus Settings dialog when the
scan is complete.
Drive types without any IP configuration use their Auto IP Class B address, which is 169.254.yy.xx, with yy.xx corresponding to the
last 2 segments in the MAC address. Several uncommissioned drives without any IP configuration can be scanned on the same network.
Select a device from the Discovered Drives list to;
•
Get more information about the device.
•
Assign a static IP address, a subnet mask, or default value to the drive.
•
Set up DHCP (dynamic host configuration protocol) look-up.
When scanning using an IP range, the Ethernet telegrams are transmitted as traditional TCP/IP packages routed out in a router,
switch, or manage switch without requiring any changes. The disadvantage is an increased scanning time, and drives without IP
address configured are not identified.
N O T I C E
Identification of drives using the VLT® EtherNet/IP MCA 121 option is possible only from option firmware version 1.03 or newer. If
using options with firmware versions earlier than 1.03, configure parameter 12-89 Transparent Socket Channel Power to 0 to pre-
Configure the IP start address and the transparent socket channel port (parameter 12-89 Transparent Socket Channel Port),
which is factory default 4000 in the drive.
Set-up of Communication
Illustration 19: Scan Range
After the scan, all active drives are identified.
2.
Use a corresponding drive to read or write to a single drive instead of waiting for MCT 10 to scan and identify all drives.
a.
Open the project file and create offline drives manually.
b.
Configure the connection properties.
c.
Right-click the offline drive.
d.
Read and write to the drive without scanning the bus.
4.7.1.2 Filtering
When using multicast, it is possible to filter a range of IP addresses.
Also, use filtering for boosting scan performance.
During a commissioning process of a system containing several drives, it can be time-consuming physically to locate a drive based
on the MCT 10 project. This is especially the case if the drive is not equipped with an LCP.
Through the Ethernet_TSC fieldbus, it is possible via MCT 10 to use a wink function. This function blinks with the MS, NS1, and NS2
LEDs on all Danfoss Ethernet-based fieldbus options.
On the Ethernet-based fieldbus option, the winking is recognized with all 3 LEDs blinking orange with 1-Hz interval. There is no limit
to the number of drives winking and the duration of winking.
4.7.2.1 Start Winking
N O T I C E
It can take up to 30 s from starting or stopping the winking, until the option responds.
To configure Port Number For Range Scan. The default value is 4000.
•
To define the TSC Connection Allocation/Sharing.
The drive has limited simultaneous connections, and with this function it is possible to define if the connections should be released
or not. If selecting Release Idling Connections, the MCT 10 releases unused connections and makes them available to other users in
the network after idle timeout.
This chapter explains how to control a drive using the MCT 10 Set-up Software. After starting the MCT 10, the main window looks
like the example shown in Illustration 23.
Illustration 23: MCT 10 Set-up Software Main Window
5.2 User Interface
5.2.1 Display
The MCT 10 Set-up Software has 2 views:
•
Left view.
•
Right view.
Left view
The left view shows the network view (real, online) and the project view (simulated, offline) of the drive network.
Use the left view to:
•
Add or delete folders and elements.
•
Store changes into the Project folder.
Store changes made to the real online set-up into the Project folder in the simulated, offline set-up for later use.
For more information on saving data, refer to 6.8.1.1 Saving a Project.
The left view is organized in a tree structure and contents can be expanded or collapsed as required. Click +/- to expand/collapse
the folder.
Right view
The right view shows details of the element highlighted in the left view. In the right view, the elements of the drive network can be
programmed.
A toolbar shows icons for the most commonly used functions.
Illustration 25: Toolbar
Activate the toolbar under View in the main menu bar, where the toolbar is tick-marked when it is active. To deactivate the toolbar,
select View⇒Toolbar. Check that the toolbar is no longer tick-marked.
5.2.2 Network and Project Folders
The Network folder gives access to physical devices operating in the field. Use Network to configure the physical drive as with the
LCP. Configuration changes made in the Network folder are therefore saved only in the physical device in the field. The Network
folder contains online data.
The Project folder contains offline data.
N O T I C E
Changes made in the Network folder are not saved automatically to the Project folder.
Network mode - online
The Network folder contains the drives, low harmonic drives, active filters, and/or soft starters online connected to the PC. Monitor
and change the parameter settings exactly as if operating on the control panel.
Data entered online is stored in the drive, low harmonic drive, active filter, or soft starter only, not on the hard disk. For information
on saving data to the hard disk, refer to
Project mode - offline
The Project folder contains the user-defined network of drive, low harmonic drive, active filter, and/or soft starter.
Data entered offline is stored on hard disk.
Use the Project folder to:
Organize drive and/or soft starters that are part of a machine or system.
e30bt713.12
File folder
Organize files belonging to a project. Any file format can be used.
e30bt714.11
Parameter folder
Store parameter settings temporarily or for documentation purposes. The folder can
contain a single parameter, subgroup, parameter group, or the entire parameter database.
e30bt523.12
Scope folder
Analyze the behavior of 1 or several parameters for diagnostic purposes by visualizing
them as a curve.
e30bt715.11
e30bt516.14
VLT® Motion Control Tool MCT 10
Operating Guide
•
Open a project file.
•
Insert folders.
•
Store project-related files in any format, for example Word or PDF.
5.2.3 Other Folders
Four folder types are available for organizing a large system into several smaller systems.
Table 2: Available Folder Types
Parameter Set-up
Insert any folder type in an offline project in 1 of 2 ways:
•
Right-click the project or an existing folder and select New Folder/New File Folder, as shown in Illustration 26.
•
Alternatively, mark the project or an existing folder and select New Folder/New File Folder under Insert in the main menu bar.
Sometimes, it is necessary to insert a new folder before setting up new drives. See 5.3.1 Inserting a New Folder for instructions.
The way to set up drives depends on the drive type. The methods are described in 5.3.2 Setting Up Drives, Active Filters, or Soft
Starters and 5.3.3 Setting Up Low Harmonic Drives.
5.3.1 Inserting a New Folder
Procedure
1.
Right-click the Project folder or selectInsert in the main menu bar.
2.
Select New.
3.
Select Folder or File Folder.
5.3.2 Setting Up Drives, Active Filters, or Soft Starters
Insert the drive, the active filter, or the soft starter in a project folder as follows:
Procedure
1.
Right-click in the left view or click Insert in the main menu bar.
Enter a unique name for the drive. Any text/number combination is allowed. Also specify with software version
and the voltage in this section.
Select Drive
Type
Information about the drive series and power size. A PUD file (power unit data information) is also available. The
default file is always preselected.
Options
Various information about the installed options.
Connection
The fieldbus used between the PC and the drive associated with the address to communicate. The specific fieldbus type is available from the drop-down menu.
e30bt636.12
VLT® Motion Control Tool MCT 10
Operating Guide
It is mandatory to fill in all fields. The different selections are available from the drop-down menus.
Once the new drive is added to the Project folder, the drive data is stored in the offline Project folder. To view the data, click the
drive icon.
Parameter Set-up
Illustration 28: View the Drive Data
To change the stored drive data, right-click the specific drive icon and select Properties.
5.3.3 Setting Up Low Harmonic Drives
Insert a low harmonic drive in a project folder as follows:
Procedure
1.
Right-click in the left view or select Insert in the main menu bar.
Enter all relevant data in the New Drive dialog and click Make LHD.
Parameter Set-up
Illustration 29: Entering Data for a New Low Harmonic Drive
N O T I C E
The Make LHD option is only available when power size and voltage ranges of the drive correspond to the supported low
harmonic drive.
5.
Enter all active filter data in the New filter dialog. Ensure that the fieldbus address used for the active filter is not used for
other components.
The low harmonic drive is visible in the project as a composition of the drive and the active filter.
Illustration 30: Low Harmonic Drive Shown in the Project Folder
5.3.4 All Parameters Folders
A new Drive folder contains an All Parameters folder. This folder comprises a series of subfolders with generic names. There is no
rename function for these folders. The generic folders within most drives consist of the following subfolders:
The generic folders can vary according to the type of drive selected.
Parameter Set-up
Illustration 31: Subfolders in the All Parameters Folder
The generic folders comprise parameters relevant to the drive type selected.
Illustration 32: Data Example in a Generic Folder
5.3.5 Array Parameters
Parameters containing array data are shown as a matrix in the right view, where the rows of the matrix are defined as ID.1, ID.2, and
so on. For example, array parameters parameter 9-15 PCD Write Configuration and parameter 9-16 PCD Read Configuration are shown
over several entries as 915.1, 915.2, 915.3, and 916.1, 916.2, 916.3 in the right view.
Apply the selected parameter view settings to subfolders, to an entire project, or to the entire application, that is all MCT 10 Set-up
Software folders in network or project mode.
Procedure
1.
Right-click the parameter cell or set-up column.
2.
Select Apply Parameter View Settings.
Illustration 36: Applying Parameter View Settings
3.
Select the relevant option and click OK.
5.4.2 Customize Background Color
To customize the background color of the views, go to Options⇒Online Parameter Grid Settings.
Removed columns are still stored in the memory and can be retrieved into the right view by highlighting the relevant
field name and selecting Add.
5.5 Parameter Edit
The parameter structures in the MCT 10 and in the drive are the same. Modify the parameter by double-clicking the relevant parameter entry. If an entry cell is shaded, the parameter is read-only and cannot be modified.
Change parameter set-up by manually entering new values in the cells in the right view. Alternatively, change the parameter set-up
by importing values from an active drive using the Read From Drive function.
If a parameter value is set to an illegal value, an error is shown. Parameters can be edited in 2 different modes:
In inline edit mode, the available setting options are shown without any detailed descriptions of the options. Inline edit is only recommended for experienced users.
Dialog-based edit
To have details of parameters available while editing, use dialog-based edit. The parameter details are:
•
Parameter options.
•
Ranges.
•
Functions.
Enter dialog-based edit by deselecting inline edit.
Parameter Set-up
5.6 Comparison of Parameters
Parameter settings can be compared to the parameter settings in another drive. Comparisons can be made either to another drive
inside the project or to an online drive. The comparison function evaluates whether settings inside the drive have been changed, or
checks if 2 or more drives have the same settings.
Procedure
1.
Activate the function by highlighting the base drive for comparison and select Compare.
Illustration 45: Comparison
2.
Select the drive to compare with.
This drive can be an online drive from the network, or it can be a drive in the offline folder (Project folder).
The result of a comparison can be stored in an ASCII text file for documentation or for subsequent import into a spreadsheet.
It is possible to compare all set-ups, or to compare 1 set-up to another.
Comparing multiple drives is done via the menu. The project drive has to have the correct addresses. If necessary, the addresses can
be changed in the project properties by right-clicking the project and selecting Drive's Properties.
Illustration 47: Drive's Properties
Only drives from the same product series can be compared and written. If the series do not match, a status message is shown.
When the read is complete, the comparison window appears.
Illustration 51: Comparison Window
The parameters in the red block are those which are set differently in the compared drives.
The parameters in the yellow block have not been compared.
The parameters in the green block have the same settings in the compared drives.
For common setup parameters, only setup 1 is compared. The result is shown as All Setups.
Exceptions
There are some parameters that, for technical reasons, are not written/compared. These parameters include some communication
parameters (8-31, 9-18, and 12-01). Trying to write these parameters would cause loss of communication.
Furthermore, safety parameters are not written.
5.8 View Change Log
When configuring a drive, active filter, or soft starter from the project, it is possible to view the change log containing the changes
made by the user only, or the changes made including the dependent parameters.
User-defined changes can be read out by right-clicking All Parameters and selecting Minimal Changeset.
Changes made including the dependent parameters can be read out by right-clicking All Parameters and selecting Compare parameters with default values.
Illustration 53: Compare Parameters with Default Values
5.9 Read Drive Operation Status
The drive can be in 2 different operating conditions:
•
Auto On
•
Off
The operation status can be monitored via the LCP or MCT 10. Use MCT 10 to monitor the actual operation status by clicking a drive
located in the network. Select Refresh Status to update the status information. Parameters can only be written to drives in operation
status Off.
Parameter settings can be read from or written to an online connected drive.
Most parameters are read/write and can thus be configured. Other parameters are read-only and cannot be configured. Use the
filter function to view which parameters are read/write or read-only.
Select the values to be read/written and then select the Read From Drive or Write To Drive menu.
The following options are available:
•
A single parameter in the right view.
•
All parameters in the left view.
•
A parameter group in the left view, for example the Load and Motor group.
The read-from-drive and write-to-drive functions apply to the whole section.
Select Options in the menu bar to access a range of functions.
Illustration 54: Select Options
6.1.1 Read From Drive Settings
Select the required options for reading from an active drive.
Setups
Select to read visible set-ups only or to read all set-ups.
Drive differences
If field device software and MCT 10 Set-up Software versions are not identical, specify the acceptable level of compatibility errors.
Select Allow drive differences to ignore all compatibility errors.
Select Allow drive version difference to restrict the acceptable compatibility errors to those occurring in different software versions
but same drive series. Select Do not allow drive differences not to accept differences between online devices and offline devices.
Save as default settings
Activate Read From Drive settings for all reads from the drive.
To read or write between online and offline drives, configure the connection properties in the offline project. If the fieldbus does
not refer to an available drive in the network tree, MCT 10 Set-up Software is not able to identify the online drive.
Reconfigure the fieldbus by right-clicking the offline project and select Properties⇒Connection.
Configure the fieldbuses added to the network tree in the Fieldbus drop-down list.
6.3 Read from Drive
Values can be read from an active drive by right-clicking a selection and then selecting Read from drive.
Illustration 58: Read from Drive
Once Read from drive is selected, the software accesses the online device and shows the Drives Check window. This window contains
a list of drives with detected compatibility issues.
Select Details to view details on the different properties between project device (based on database information) and online device
(the connected drive).
Illustration 60: Details
The color codes indicate the level of compatibility between the project drive and the connected drive for each property.
To continue the reading process, define an action in the Drives Check dialog. The default action is Continue. Other available selections are:
Add addresses in the Address field and in the Secondary Addresses field. Secondary Addresses in the right view is enabled for DP-V1,
Ethernet, Serial, and Dummy.
Illustration 63: New Drive Dialog
Write parameter values to the main address and to secondary addresses. If the drive is not available on the configured address, it
must be skipped.
If a drive is configured with secondary addresses, the Write to Multiple Drives context menu is enabled on the right-view parameters
and on the parameter headers context menu on the left-view group and on the drive menu.
Illustration 65: Examples, Write to Multiple Drives, Parameter Headers Context Menu, and Drive Menu
6.6 Poll
When in network mode, MCT 10 Set-up Software automatically polls the parameters in the right view to update their status continuously to reflect live operation.
6.6.1 Stop Polling
To stop polling, for example to freeze and analyze a particular moment:
Procedure
1.
Click Communication in the main menu bar.
2.
Select Stop polling.
Alternatively, click the Stop polling icon in the toolbar.
Alternatively, click the Resume polling icon in the toolbar.
Illustration 67: Resume Polling Icon
6.6.3 Using Smart Polling (Intelligent Scan Frequency)
While the MCT 10 Set-up Software is polling the parameter grid, the LCP becomes slow. To improve LCP usability, configure MCT 10
to enable smart polling. Enabling smart polling slows down the polling when the LCP is connected.
Tick the checkbox Enable Smart Polling (slow down the polling when the LCP is connected).
Illustration 69: Ticking the Checkbox
Operation
6.7 Changing the Set-up of a Field Device
Procedure
1.
Open the Network folder.
2.
Select the relevant device.
3.
Select Stop on the toolbar to stop polling.
Change the settings in the set-up columns in the right view.
4.
The changes are implemented online in the field device, but are not recorded.
6.8 Save Changes to a Hard Disk
6.8.1 Recoding Online Changes
Procedure
Select the relevant device in the Network folder.
1.
2.
Right-click the device and select Copy.
Select the Project folder.
3.
4.
Right-click and select Paste.
5.
Select File from the main menu bar.
6.
Select Save As.
Save the device file into a directory in the storage location.
7.
6.8.1.1 Saving a Project
Procedure
1.
Click File in the main menu bar.
2.
Select Save.
Alternatively, click the Save icon in the toolbar.
6.8.1.1.1 Including Drive Information
It is not possible to open a project file including a firmware version not supported by MCT 10 Set-up Software. Including the drive
information in the project file makes it possible to open in other installations with MCT 10 without having the firmware installed.
By opening the project file, the drive information is updated similarly to:
Selecting Update Drive Support under Tools in the main menu bar.
•
Downloading the drive information from an online drive.
The drive information is saved in the project file.
6.8.1.1.2 Excluding Drive Information
Procedure
1.
Click Options in the main menu bar.
2.
Select Project properties.
3.
Click Include drive supprt in project.
Operation
Illustration 70: Save Drive Information
6.8.2 Archive/Unarchive
Projects that include links to other documents can store the linked files.
By selecting the Archive function, the MCT 10 Set-up Software generates a file that contains all drives and the linked files into a *.ssa
file. If this file is sent to other computers, the user gets a copy of the linked files on the computer.
6.9 Import of Older Dialog Files
For users working with VLT set-up software dialog, the files generated with these software packages can be imported into the MCT
10 Set-up Software.
Files from DOS versions and Windows versions can be imported to the MCT 10 Set-up Software. Following a successful import, the
MCT 10 places the imported files in an imported files folder.
Due to limitations in some of the former PC tools, some functionalities cannot be imported, for example, functions such as showing
changed values only.
6.10 Printing
There are 2 print options in MCT 10 Set-up Software:
•
Print project.
•
Print selected folders.
Both options are in the File menu in the main menu bar. Alternatively, right-click the Project icon and select Print project.
To print a folder, right-click a folder icon within the project and select Print selected folders.
Select Print project to print parameter settings for an entire project. Select Print selected folders to print parameter settings for part of
a project.
Illustration 72: Print Options
Select the desired print language from the drop-down list.
Changed parameters
Print either parameters that have been changed from factory default or all parameters.
Click More to be able to print selected parameter groups only.
Operation
Illustration 73: Example of Print Selection
6.11 Update Database Information
If the MCT 10 Set-up Software database information is outdated, updates are available either by download from the Internet or,
when this is not possible, by reading from the drive itself.
When the MCT 10 Set-up Software database for a drive is outdated, the drive icon is shown with a red line through it and the
Database information fields show the message Not supported.
When reading from the drive is complete, the drive icon no longer has a red line through it, and the Database information shows
settings identical to the Connected drive information.
Also, the parameter settings are shown in capital letters.
6.12 Update Drives Firmware Support in MCT 10 Set-up Software
The MCT 10 Set-up Software can be updated regardless of the firmware of the drive.
Download upgrades from the Danfoss website
Software versions of MCT 10 Set-up Software and drive in existing project file
Software versions of Danfoss Set-up
Software
Compatible ✓/✗
2.00 and 2.01
2.02✓2.02 and 2.51
2.00
✗
e30bt574.12
VLT® Motion Control Tool MCT 10
Operating Guide
Operation
N O T I C E
The update files can be installed without administrator rights in Microsoft operating systems.
6.13 Software Compatibility
The MCT 10 Set-up Software project files can open legacy version project files.
Table 4: Opening Legacy Versions
When MCT 10 Set-up Software has been updated, project files saved with a newer firmware version can be opened and used. Refer
to Illustration 77 for an example.
Illustration 77: Use Updated MCT 10 Set-up Software
6.13.1 Mapping to Compatible Firmware
To establish connectivity to a drive with firmware version 1.10, it is required to modify the MCT 10 Set-up Software drive database
mapping to firmware version 1.05 as reference.
Procedure
1.
Start the MS Explorer and open the path C:\Program Files\Common Files\Danfoss Drives\SharedSource\.
2.
Open the text file ss_version_mapping.txt in Notepad by right-clicking the file and selecting Edit.
3.
Change "Series="FC-202",AOC="01.10",Database="01.10" to Series="FC-202",AOC="01.10",Database="01.03".
4.
Save and close the file.
To find out if the MCT 10 Set-up Software has been updated, check the information in the About box. This box shows the
actual MCT 10 Set-up Software version.
System information can be copied directly to the Windows clipboard.
It is required that database versions, power size, voltage range, and option configuration of the source match the destination drive.
Differences can be converted using 1 of the conversion wizards available in the MCT 10 Set-up Software:
•
VLT to FC series conversion.
•
FC to FC series conversion.
N O T I C E
If the parameter database of a source drive is different from the database on the destination drive, it cannot be written without
errors signaled during write to drive.
6.14.2 VLT to FC Series Converter Function
It is possible to convert, for example, a VLT® 5000 drive to a VLT® AutomationDrive FC 302 via the conversion matrix in the MCT 10
Set-up Software.
Select the Tools menu and activate Drive Conversion Wizard.
2.
In the subsequent dialogs, select the drives for conversion.
When converted, a new VLT® AutomationDrive FC 302 drive is created in the Project folder.
Illustration 80: Conversion of Multiple Drives
6.14.2.2 Import Drive from Excel
Use this function to create a VLT® AutomatonDrive project based on an Excel sheet. For example, import of VLT® 3000 settings from
an Excel sheet into a new FC 302.
An example file is attached in the MCT 10 Set-up Software (vlt3000conversion.xls). This example file can be edited and used for
converting from VLT® 3000 to FC 302.
N O T I C E
Detailed knowledge of Microsoft Excel formula editing is required.
The converter tool can convert projects within the same drive series, regardless of software versions, power size, voltage range, and
option configuration. It covers:
•
VLT® HVAC Drive FC 102.
•
VLT® Refrigeration Drive FC 103.
•
VLT® AQUA Drive FC 202.
•
VLT® AutomationDrive FC 301/FC 302.
•
VLT® Lift Drive LD 302.
•
All OEM versions based on the FC xxx series.
Differences can be matched by using the Conversion Tables Manager.
A conversion table enables conversion from:
•
Online to online drive.
•
Online to offline drive.
•
Offline to online drive.
•
Offline to offline drive.
Two user profiles are available:
•
Administrator - qualifies and manages the conversion tables through access to the Conversion Tables Manager. From the Conversion Tables Manager, new conversion tables can be created and deployed to other MCT 10 Set-up Software installations.
•
User - writes projects to the destination using the conversion tables transparently. The user cannot access the Conversion Tables Manager. Conversion tables can be imported to the database.
MCT 10 Set-up Software is installed with user rights. Enabling the Conversion Tables Manager is done from the checkbox in the
Converter Tool Settings dialog.
The conversion tables are stored locally on the hard disk. Using the database non-distributed, the path to the network location can
be reconfigured from the Converter Tool Settings dialog.
6.14.4 Conversion Tables Manager
Access the Conversion Tables Manager via the Tools menu in the MCT 10 Set-up Software.
A conversion table containing the list of conversion tables in the database.
•
A preview pane.
Conversion tables can be created or imported, edited, exported, or deleted.
Exporting tables
Distribute to other MCT 10 Set-up Software installations by exporting the relevant tables to a *.cvt file. The preview pane lists the
conversion table source and destination drive information.
The conversion can be as follows:
•
Drive series based on the FC 102/FC 202/FC 3xx platform.
•
Software version (major and minor).
•
Power size.
•
Voltage range.
•
Option A.
•
Option B.
•
Option C0.
•
Option C1.
Create conversion tables
To create a conversion table, open the Conversion Tables Manager or right-click the source drive and select Convert drive.
Operation
N O T I C E
When using the right-click option, it is only possible to configure the information of the destination drive. Furthermore, parame-
ter group 19-** User-defined Parameters is not converted. These settings are configured when writing from source to destination.
Difference between source database and drive. A formula is required before changes can be applied to the drive.
Blue
Difference between source database and drive. The formula is ignored and changes can be applied to the drive.
VLT® Motion Control Tool MCT 10
Operating Guide
Illustration 83: Drive Conversion
Editing tables
In the Drive conversion view, enter the information for source and destination drives. Click OK to open the conversion table editor
listing the parameter database differences.
Use the conversion table editor to create or load a conversion table. Ensure that the conversion table matches the drive series, software version, power size, voltage range, and option configuration. The MCT 10 Set-up Software is not able to find and load incompatible conversion tables. After loading or creating the conversion table, it is possible to re-edit the table or to convert the source
drive and store the converted drive in an offline folder.
Formulas
The parameter database is listed and sorted according to the parameter ID. To simplify the conversion process, filter the database to
list alerts or applied changes only.
Operation
Table 5: Alert Coding
N O T I C E
If a formula is applied to all alerts, the source parameter database can be converted to the destination parameter database with-
When a formula is applied to all red alerts, assign a name to save the conversion table in the database.
If differences are detected when writing from source to destination drive, MCT 10 Set-up Software uses the following as search crite-
ria:
•
The drive series.
•
Major software version.
•
Power size.
•
Voltage range.
•
Option configuration.
With the proper conversion table in the database, any drive can be written transparently to a destination even if the minor software
version does not match. If several conversion tables are found matching the criteria, MCT 10 Set-up Software uses the minor software version to find the closest match. Only 1 drive can be written transparently to the destination.
If parameter group 19-** User-defined Parameters is available, the settings are written transparently to the destination drive.
6.14.4.1 Converting Offline to Offline/Online to Online
Procedure
1.
Mark the appropriate number of set-ups from All Parameters.
Reading out alarms, warnings, and fault logs of the online drives.
•
Quick location of alarms and warnings in the connected drive system.
•
Investigation of the fault log for previous trips.
•
Gathering and storing events in the project file for later evaluation.
•
Sending the project file to a remote specialist for further investigation.
7.2 Localization of Alarms and Warnings
After a complete scanning of a drive network, the MCT 10 Set-up Software indicates if the connected drives have active warnings
and alarms. An exclamation mark in front of the drive icon indicates a warning or an alarm.
Illustration 88: Drive with Active Alarm or Warning
Expand the drive and click the alarm/warning icon.
Illustration 89: Fault Log View for Control Cards Marked MKI
Illustration 90: Fault Log View for Control Cards Marked MKII
For a more detailed description of the code, refer to the Operating Guide for the particular drive. If the drive trips, it stores the cause
for the trip in a fault log buffer. The log consists of 3 values:
•
Code.
•
Value.
•
Time.
When the MCT 10 Set-up Software reads the fault log, it shows the time and date when the log was read.
Diagnostics
N O T I C E
The actual time when a fault occurs is not indicated.
7.3 Storing Alarms/Warnings in Project Files
Alarms/warnings and the fault loggings are stored into the Project file. The MCT 10 Set-up Software automatically reads alarms,
warnings, and fault loggings at every read from/write to the drive.
7.4 Handling the Alarms and Warnings Loggings
The MCT 10 Set-up Software allows more than 200 alarms and warnings for each drive in the project. The loggings can be cleared
individually. This is done by entering the loggings to clear and then right-clicking. Clearing the log only clears the PC log while the
information in the drive is unaffected by this handling.
N O T I C E
There are redundant alarm entries in the log.
The MCT 10 Set-up Software stores active alarms and warnings in the Project file at each read/write command. No alarm is lost, but
an alarm can have multiple entries in the log.
Illustration 91: Loggings
7.5 The Scope Function
The scope function supports monitoring and diagnosing of parameters. The function polls parameter data and dynamically shows
the polled data as a curve graph.
The scope function provides 2 different channel types to sample parameters:
••PC polling channel - Channel selected when the PC SW requests the parameters from the drive. The channel does not have any
time limitation, the buffer size is user-configurable and corresponds to the number of samples. Fast sampling with accurate
sampling rate cannot be obtained because the Windows operating system does not support real-time extension.
Drive real-time channel - Only available in the FC 102, FC 202, and FC 300 series - uses an internal 16-kByte buffer located in the
drive. Recommended for continuously monitored applications requiring high and precise sampling rates. It is required to set up
a trigger event for the drive to start filling up the buffer with samples.
Diagnostics
7.5.1 Activating the Scope - MCT 10 Set-up Software
Insert a new scope from the Insert menu or by right-clicking the Project folder, Drive folder, Regular folder, or Drive.
Illustration 92: New Scope
Rename the Scope folder via the Edit menu or by right-clicking the icon and select Rename.
The 1st time that the Scope folder is selected, the Add Channel dialog pops up. From this dialog, select the drive to monitor. Then,
depending on the drive series, select the type of channel to collect samples from.
Insert additional text for later usage to each scope folder such as the type of drive monitored and diagnostic help text. Text notes
are added by right-clicking the Scope folder and selecting New⇒Text note. The default text can be changed by right-clicking the
text note and selecting Rename. Several text notes can be added to the same Scope folder.
Illustration 94: Text Notes
7.5.2 Configuring the PC Polling Channel
PC polling channel is enabled by default when a drive is selected within the Network folder or Project folder. All parameters available in the list are visible by ID name and are automatically updated according to the product.
Select a parameter in the parameter list and click Next to update the Add Channel dialog.
2.
Configure A/div (value/division).
3.
Define the position number (vertical zero line on the Y axis). If there are several signals on top of each other, it is useful to
have them plotted apart.
4.
Set color and tick Marker to differentiate the different curves in a black and white printout. Each curve gets a marker as box,
triangle, cross, and so on.
N O T I C E
MCT 10 Set-up Software stores the values even if they are not shown within the visible area of the curve.
Year, month, date, hour, seconds, and milliseconds
–
Buffer size
Number of data sets in the buffer
0–1.000.000
Polling rate
Time in milliseconds between 2 samples
–
VLT® Motion Control Tool MCT 10
Operating Guide
General parameter sample settings
The General tab holds 4 basic settings for the Scope Properties:
•
Seconds per division (SEC/DIV).
•
Time format.
•
Buffer size in samples.
•
Polling rate in milliseconds.
Diagnostics
Illustration 99: Basic Scope Settings
Table 6: Format and Range of the Basic Scope Settings
N O T I C E
For systems with large inertia, a low sampling rate may be used since the value changes slowly. For systems with low inertia, a
high sampling rate is needed.
N O T I C E
Setting Polling Rate to As fast as possible means that MCT 10 Set-up Software does not control the actual time between each sam-
ple. This can lead to a high jitter between 2 samples.
Trigger
The trigger function starts the sampling of values only when a certain value is reached. This reduces the need for large buffer sizes.
A trigger is also a valuable tool to see if values cross borders where the drive does not store any warnings.
Auto starts the trigger automatically when Resume All is pressed. The trigger line is set to the time when Re-sume was pressed. Normal (Norm) activates the trigger when level and slope settings are fulfilled.
Slope
Sets if the value must rise (source value goes from low values to high values) or the slope must fall (source
value goes from high values to low values).
Cursor
e30bu985.10
Inserts cursor in scope
VLT® Motion Control Tool MCT 10
Operating Guide
Illustration 100: Trigger Functions
Table 7: Descriptions of the Trigger Functions
Diagnostics
Cursor
Style defines the functionality of the cursor. The style contains 5 different possibilities:
•
Value XY - Shows the time and value of each signal at the cursor location.
•
Value X - Shows the time only.
•
Value Y - Shows the value only.
•
Delta X - Shows 2 cursors, and the time between the 2 cursors is calculated.
•
Delta Y - Works like Delta X, but this time the difference between 2 levels is calculated.
The pointer position defines the default position when a cursor is inserted in Scope.
7.5.4 Reuse of PC Polling Channel Settings
Often, the same settings are used when measuring with the PC polling channel on more than 1 drive. These settings can be reused
either by copying an existing scope folder or by reusing an existing one.
Reconfigure the scope folder connection properties for another drive in the network by double-clicking an added channel. In the
Reconfigure Channel dialog, another drive on the same or a different fieldbus can be selected.
The following example explains the set-up of a trigger, which triggers the collection of data in the drive when the motor speed
exceeds a certain limit.
Set up a comparator in the smart logic control to get a trigger signal when the motor speed exceeds a certain limit:
Procedure
1.
Select the smart logic group.
2.
Select a comparator not in use, 1310.0, and set it up to motor speed.
More settings can be configured by right-clicking the Scope window and selecting Properties.
It is possible to reconfigure all drive real-time channel settings and also to configure:
MCT 10 Set-up Software scope starts collecting the requested data from the drive network.
Stop Data Acquisition
e30bt561.12
MCT 10 Set-up Software stops collecting data and there is no communication to the
drive network while the scope part is active on the screen.
Resume All (Tracking)
e30bt562.12
Activates the tracking mechanism. MCT 10 Set-up Software starts the readout of variables to the screen and to the buffer. Variables are checked against the trigger settings. If
the buffer has been partially filled (use of the Pause All Tracking function), MCT 10 Set-up
Software continues to fill data into the buffer.
Pause All (Tracking)
e30bu986.10
Deactivates the tracking. The buffer remains at its current state, no new data is shown.
The buffer pointer keeps its current position.
e30bt469.12
VLT® Motion Control Tool MCT 10
Operating Guide
The Units/Div, Position, Marker, and Color functionalities are similar to the PC polling channel functionality.
Cursor
The functionality is similar to the PC polling channel functionality.
7.5.8 Communication Control
The Scope toolbar has 4 main buttons for communication control.
Table 8: Functions of the Control Buttons
Diagnostics
7.5.9 Additional Functionality
Select Resume poll to start tracking. To stop tracking, click Stop poll or Pause all tracking. The tracking continues until the buffer is
filled (default 1000 samples). If the tracking stops due to a filled buffer, the buffer has to be emptied before a new track can be
activated. Clear the buffer and reset the scope in 1 step by clicking the icon shown in
Illustration 108: Clear all Buffer for the Channel
Alternatively, the buffer can be cleared individually.
Clears all buffers for the channel at once. This is more convenient if many channels are activated
at the same time, or if a new channel is added to an existing track. Before new values can be
added to a track, all channel buffers must be emptied, since MCT 10 Set-up Software requires
that all buffers have the same amount of data.
Export to Excel
e30bt568.12
Enables storing scope data in a file which Microsoft Excel can open. A Save file dialog appears,
making it possible to store the file in an appropriate location.
Scope storage
e30bt858.11
Enables storing scope data in a file on the hard disk. Save to the hard disk to avoid the limitation
of 1 million points in the project file.
Open scope
history viewer
e30bt859.11
Open scope data saved on the hard disk.
VLT® Motion Control Tool MCT 10
Operating Guide
Illustration 109: Individually Clearing the Buffer
Table 9: Functions of the Main Buttons
Diagnostics
7.5.10 Scope Storage
Enable scope storage or persistent data storage in Scope Properties. In Scope Properties, it is also possible to change and select where
data should be saved.
If polling data in scope when scope storage is selected, data is saved in both the project file and on the hard disk. However, the
project file is limited to 1 million points. When the limit is exceeded, MCT 10 Set-up Software replaces the oldest point with the
latest point.
7.6 Export Log Files
All log files can be exported to the desktop in 1 compressed .zip file.
From version 2.13, VLT® Motion Control Tool MCT 10 supports the smart logic controller plug-in. This feature enables quick set-up of
logical sequence programs.
The smart logic controller monitors a predetermined event. When the specified event occurs, it performs a predetermined act and
starts monitoring the next predetermined event. The smart logic controller continues like this in up to 20 different steps until it
returns to step 1 – monitoring the 1st specified event.
The smart logic controller can monitor any parameter that can be characterized as true or false. This includes digital commands and
logic expressions, which allow sensor outputs to determine the operation. Temperature, pressure, flow, time, load, frequency, voltage, and other parameters combined with the operators >, <, =, AND, and OR form logic expressions that control the drive logically
in any application.
The smart logic controller supports multiple controllers. The basic functionality is the same, but the appearance differs slightly due
to multiple controllers being available in different tabs.
Refer to the relevant Design Guide for a full overview of the smart logic controller features.
8.2 Time-based Actions and Preventive Maintenance Plug-ins
For the VLT® HVAC Drive FC 102, VLT® AQUA Drive FC 202, and VLT® AutomationDrive FC 301/FC 302, the MCT 10 Set-up Software
provides the following plug-ins:
•
Clock features.
•
Preventive maintenance.
•
Time-based actions.
N O T I C E
Consult the relevant Design Guide for detailed information about the drive.
8.2.1 Clock Functions
The MCT 10 Set-up Software enables set-up of the clock functions.
The clock functions are grouped in 2 sublevels:
•
Date and time.
•
Working days.
8.2.1.1 Date and Time
In the Date and time dialog, the following groups of settings are available:
•
Display format.
•
Set date and time.
•
Daylight saving time.
•
Enable clock fault.
Display format in LCP
Select how date and time are presented in the LCP on the drive. In MCT 10 Set-up Software parameters, date and time format depends on PC regional options (date and time format).
Set date and time
Change the date and time in the drive from the PC. Normally, it should be set to use the connected PC’s date and time. When the
connected PC’s time is in another time zone, it is beneficial to set the date and time manually. Date and time are changed in the
MCT 10 Set-up Software project file or in the drive only when the Change checkbox is ticked.
Daylight saving time
Set the date and time for daylight saving.
Daylight saving time begins for most of the United States at 2:00 a.m. on the first Sunday of April. Time reverts to standard time at
2:00 a.m. on the last Sunday of October. In the U.S., each time zone switches at a different time. In the European Union, summer
time begins and ends at 1:00 a.m. Universal Time (Greenwich Mean Time). It begins the last Sunday in March and ends the last
Sunday in October. In the EU, all time zones change at the same moment.
Enable clock fault
If the clock is not set up, the drive shows a specific warning. Enable or disable the clock fault function.
Additional working days and non-working days include the year and must be updated every year.
Procedure
1.
Select First day of the week (Monday or Sunday).
2.
Select working days and non-working days.
3.
Set additional working days (maximum 5).
4.
Set additional non-working days (maximum 15).
Plug-ins
Illustration 111: Define Working Days
8.2.2 Preventive Maintenance
The preventive maintenance feature supports the planning of periodic maintenance of both the drive and other technical equipment. If the defined date and time of preventive maintenance is passed, the item is marked red.
Program the clock parameters (parameters in the Clock functions folder) for preventive maintenance to function correctly.
Procedure
1.
Double-click the cells in the right view to specify application item, action, and interval.
2.
Reset Maintenance Word (in parameter 23-15 Reset Maintenance Word) and write to the drive.
8.2.3 Timed Actions
The time-based actions function enables automation of real-time controlled events.
Actions, which can be programmed, are the same as known from the SLC (smart logic controller), see 8.1 Smart Logic Controller
Plug-in.
N O T I C E
The clock parameters (parameters in the Clock functions folder) must be correctly programmed for timed actions to function cor-