MCI 25B motor controller with brake is designed
for soft starting and braking of 3 phase AC
motors.
The digital controlled soft starter features
accurate settings and several monitoring
functions. Acceleration time and initial torque are
along with the braking torque easily adjusted.
During braking the MCI 25B will apply a DC
current to all the windings of the motor,
thus providing a powerful brake function.
The automatic stop detection ensures a safe
operation. For positioning applications the
unique slow speed function can be applied.
The MCI 25B controller is typically applied on
demanding braking applications such as saws,
cranes, automatic doors, etc.
Data sheet | Soft Start Motor Controller, Type MCI 25B
Technical dataControl circuit specifications
Control voltage range24 – 480 V AC/DC
Pick-up voltage max.20.4 V AC/DC
Drop-out voltage min.5 V AC/DC
Max. control current for no operation1 mA
Control current / power max.15 mA / 2 VA
Response time max.70 ms
Ramp-up time Adjustable from 0 to 10 Sec.
Brake currentAdjustable from 0 to 50 A
Initial torque
SCR aux. contacts, voltage/current max. 24 – 480 V AC / 0.5 A (AC-14, AC-15)
SCR aux. contacts, max. fuse10 A gL/gG, I2t max. 72 A2s
Design standardCE marked according to EN 60947-4-2
EMC immunityMeets requirements of EN 50082-1 and EN 50082-2
Output Specifications
Operational current max. (AC-3, AC-53a)25 A
Motor size at:
208 – 240 V AC
380 – 480 V AC
Leakage current max.5 mA
Minimum operational current50 mA
Overload relay trip classClass 10
Semiconductor protection fusing
Type 1 co-ordination
Type 2 co-ordination I2t (t = 10 ms)
Rating indexSlip ring motors: 25A: AC-52a: 4-13: 100-3000
Adjustable from 0 to 85 % of nominal torque with
optional kick start
0.7 – 7.5 kW (1 – 10 HP)
1 – 11 kW (1.5 – 15 HP)
80 A gL/gG
6300 A2 S
Asynchronous motors: 25A: AC-53a: 8-3: 100-3000
Insulation
Rated insulation voltage, U
Rated impulse withstand voltage, U
Installation categoryIII
i
imp
660 V AC
4 kV
Thermal Specification
Power dissipation for continuous duty Pd max.2 W/A
Power dissipation for Intermittent duty Pd max.2 W/A x Duty cycle
Ambient temperature range-5 °C – 40 °C
Cooling methodNatural convection
MountingVertical +/- 30 °C
Max. ambient temperature with limited rating 60 °C, see derating for high temperatures in chart below
Storage temp. range-20 °C – 80 °C
Protection degree/pollution degreeIP 20 / 3
Materials
HousingSelf extinguishing PPO UL94V1
HeatsinkAluminum black anodized
BaseElectroplated steel
Data sheet | Soft Start Motor Controller, Type MCI 25B
Functions
Control inputs
Operating mode selector,
select slow speed and auxiliary
contact function
Ramp up setting, accurately
adjustable from 0 – 10 seconds
Initial torque setting, adjustable from
0 – 85%, with or without kick start
Brake torque setting, adjustable on a
relative scale from 0 – 15
LED for status and error indication
Auxiliary contacts (SCR)
Functional diagram
Line voltage L1, L2, L3
Run command
Slow speed command
Brake command
Motor voltage T1, T2, T3
Brake on
Aux. contacts:
23-24 by-pass
13-14 I-O
13-14 ( M )
1. When line voltage is applied the brake will automatically stop a rotating motor.
2. The function of auxiliary contact 13-14 is selectable; “start - stop” or “mechanical brake”
Soft start functionRamp up
During ramp-up the controller will gradually
increase the voltage to the motor until it reach
full line voltage. The motor speed will depend on
the actual load on the motor shaft.
A motor with little or no load will reach full speed
before the voltage has reached its maximum
value.
The actual ramp time is digitally calculated and
will not be influenced by other settings, net
frequency or load variations.
Initial torque
The initial torque is used to set the initial starting
voltage. This way it is possible to adapt the
controller to an application requiring a higher
starting torque. In some cases on application
with very high break-away torque the initial
torque can be combined with a kick start
function. The kick start is a period of 200 ms
where the motor receives full voltage.
Data sheet | Soft Start Motor Controller, Type MCI 25B
Brake functionBraking is achieved by injecting a DC current,
adjustable from 0 – 50 A, onto all the windings
of the motor. The brake can be used on both star
and delta connected motors, but is most efficient
if the motor is connected in star.
Adjustment
The actual braking torque is controlled
indirectly by adjusting the braking voltage. The
braking voltage can be set for 0 – 15. For small
motors a relatively high braking voltage is
necessary contrary to larger motors where a
relatively low voltage is sufficient. For this
reason the braking voltage must be adjusted to
the actual application. Before starting up a new
application set the Braking torque to 1.
Increase incrementally until desired braking time
is reached.
Automatic stop detection
When the brake function is applied the MCI-B will
bring the motor to a stop before releasing the
brake current.
Note: If a contactor is placed between motor
and the MCI-B, do not open during braking as it
can cause the contactor to fail.
If the motor does not stop within 30 seconds the
DC brake will disengage and the controller will
show a “brake failure” condition.
The automatic stop detection is accomplished
by sensing the DC brake current on the motor,
and as so the accuracy of the stop detection will
depend on a correctly adjusted brake. The point
of “no rotation” depends on the motor size and
the brake voltage setting. If the motor voltage
is set to low the brake will be switched off
before the motor has come to a complete stop.
However, if the brake voltage is set to high, out of
detection range, it will not switch off the motor
before the brake failure conditions occurs after
30 seconds.
Slow speed functionThe slow speed function is intended for short
time operation in applications where an exact
positioning is needed, for example cranes. The
function has two selectable slow speeds: 7.5% or
10% of nominal speed.
Auxiliary contactsThe auxiliary contacts are made possible by
means of SCR technology and will only switch
correctly on AC current.
Contact 13-14
The contact 13-14 is selectable for two different
functions; “I-O” or “Mechanical brake”. If the “I-O”
is selected, the contact will be closed as long as a
RUN command is given, see functional diagram
LED status indication
LED status indication:
The torque level will depend on the motor
and selected slow speed, typically 25 – 40% of
nominal torque. During slow speed the motor
current will increase, typically 2 – 2.5 times the
nominal current.
If “Mechanical brake” is selected, the contact
will be closed as long as the motor is rotating.
The “Mechanical brake” setting is intended for
operating an external mechanical brake.
Contact 23-24
The contact 23-24 is intended for operating an
external by-pass contactor. The contact will close
when the controller is in steady state operation,
see functional diagram.
Data sheet | Soft Start Motor Controller, Type MCI 25B
Wiring
Overload and short
circuit protection
Run / brake command
Slow speed command
Forced brake command
MCI 25B
By-pass
I-O or mechanical brake
Common
Overload and short circuit protection is easily
achieved by installing a circuit breaker on the
line side of the motor controller. Select circuit
breaker from the table according to motor full
load current.
380 – 415 V AC
Type
CTI 25M
CTI 25M
CTI 25M
CTI 25M
CTI 25M
1
) Values based on let-through curves for appropriate circuit breaker
Motor full load current
[A][kA]
4.0 – 6.3
6.3 – 10
10 – 16
14.5 – 20
18 – 25
Code number037N0061037N0062
Mains
L1, L2, L3
Inputs
(C, R, S, B)
Outputs
(13/14, 23/24)
208 – 240 V AC380 – 480 V AC
24 – 480
V AC/DC
24 – 480 V AC
max. 0.5 A
Be aware of the maxium prospective short
circuit current breaking capacity. For further
information please refer to data sheet for the
circuit breaker.
Data sheet | Soft Start Motor Controller, Type MCI 25B
Application examplesOverheat protection
Example 1
The thermostat can be connected in series
with the control input of the Motor Controller.
When the temperature of the heat sink
exceeds 100 °C the Motor Controller will be
switched OFF.
Note: when the temp. has dropped approx.
30 °C the Controller will automatically be
switched ON again. This is not acceptable in
some applications
Example 2
The thermostat is connected in series with the
control circuit of the main contactor. When the
temp. of the heat sink exceeds 100 °C the main
contactor will be switched OFF. This circuit
requires manual reset to restart the motor.
Standard start – brake wiring
If only the soft start and braking function is
required it is easily achieved by wiring the
control voltage to “R”. When control voltage
is applied the controller will begin the soft
start procedure. To brake the load the control
voltage is disconnected.
Danfoss circuit breaker CTI 25M is in this
example providing overload and short circuit
protection.
By wiring the auxiliary contact function
13-14 into the control circuit start and stop
can be achieved by means of push buttons.
Note that the operating mode selector must
be set for “I-0” control.
Auxiliary contact 23-24 is used to control and
external by-pass contactor during steady state
operation.
Danfoss circuit breaker CTI 25M is in this
example providing overload and short circuit
protection.
Wired for control of mechanical brake and bypass
The auxiliary contact function 13-14 is in this
example used to control a mechanical brake.
The brake is released when the
controller is applying voltage to the motor.
MCI 25B
Danfoss
CTI 25M
Danfoss
CTI 25M
24 – 480 V AC
Danfoss
A37-219.20
Danfoss
Note that the operating mode selector must
be set for “mechanical brake” control.
Auxiliary contact 23-24 is used to control an
external by-pass contactor during steady state
operation.
Danfoss circuit breaker CTI 25M is in this
example providing overload and short circuit
protection.