Danfoss MCI 25B Data sheet

Data sheet
CI-tronic™ Soft Start Motor Controller
Type MCI 25B with Brake
MCI 25B motor controller with brake is designed for soft starting and braking of 3 phase AC motors.
The MCI 25B controller is typically applied on demanding braking applications such as saws, cranes, automatic doors, etc.
Features
y Adjustable acceleration time, 0 – 10 seconds
y Initial torque adjustable from 0 – 85%, with or
without kick start (break-away)
y Adjustable DC injection brake, 0 – 50 A DC
y Fast acting brake mode with automatic motor
field reduction
y Automatic stop detection
y Universal control voltage 24 – 480 V AC/DC
y Slow speed function, 7.5% or 10% of nom.
speed
y SCR aux. contacts for external control of
by-pass, I-O and mechanical brake
y Automatic detection of missing phase(s)
y Automatic adaptation to 50/60 Hz
y Unlimited start and stop per hour
y IP 20 protection
y Compact DIN rail mountable design
y EN 60947-4-2
y CE, C-tick
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 1
Data sheet | Soft Start Motor Controller, Type MCI 25B
Adjustments
Motor torque (voltage)
Ramp-up time 0 – 10 sec.
Danfoss
A37-217.20
Selection guide
Kick Start selectable
Slow speed
7.5% or 10%
Initial torque up to 85% of nom. torque
Braking torque 0 – 50 A
Operational
voltage
[V AC] [A] [kW/HP] [V AC/DC] [mm]
208 – 240 25 7.5/10 24 – 480 90 037N0061 380 – 480 25 1/15 25 – 480 90 037N0062
Motor
current
Motor power
Control voltage
Module
dimensions
Code no.
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 2
Data sheet | Soft Start Motor Controller, Type MCI 25B
Technical data Control circuit specifications
Control voltage range 24 – 480 V AC/DC Pick-up voltage max. 20.4 V AC/DC Drop-out voltage min. 5 V AC/DC Max. control current for no operation 1 mA Control current / power max. 15 mA / 2 VA Response time max. 70 ms Ramp-up time Adjustable from 0 to 10 Sec. Brake current Adjustable from 0 to 50 A
Initial torque
SCR aux. contacts, voltage/current max. 24 – 480 V AC / 0.5 A (AC-14, AC-15) SCR aux. contacts, max. fuse 10 A gL/gG, I2t max. 72 A2s Design standard CE marked according to EN 60947-4-2 EMC immunity Meets requirements of EN 50082-1 and EN 50082-2
Output Specifications
Operational current max. (AC-3, AC-53a) 25 A Motor size at:
208 – 240 V AC 380 – 480 V AC
Leakage current max. 5 mA Minimum operational current 50 mA Overload relay trip class Class 10 Semiconductor protection fusing
Type 1 co-ordination Type 2 co-ordination I2t (t = 10 ms)
Rating index Slip ring motors: 25A: AC-52a: 4-13: 100-3000
Adjustable from 0 to 85 % of nominal torque with optional kick start
0.7 – 7.5 kW (1 – 10 HP) 1 – 11 kW (1.5 – 15 HP)
80 A gL/gG 6300 A2 S
Asynchronous motors: 25A: AC-53a: 8-3: 100-3000
Insulation
Rated insulation voltage, U Rated impulse withstand voltage, U Installation category III
i
imp
660 V AC 4 kV
Thermal Specification
Power dissipation for continuous duty Pd max. 2 W/A Power dissipation for Intermittent duty Pd max. 2 W/A x Duty cycle Ambient temperature range -5 °C – 40 °C Cooling method Natural convection Mounting Vertical +/- 30 °C Max. ambient temperature with limited rating 60 °C, see derating for high temperatures in chart below Storage temp. range -20 °C – 80 °C Protection degree/pollution degree IP 20 / 3
Materials
Housing Self extinguishing PPO UL94V1 Heatsink Aluminum black anodized Base Electroplated steel
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 3
Data sheet | Soft Start Motor Controller, Type MCI 25B
Functions
Control inputs
Operating mode selector, select slow speed and auxiliary contact function
Ramp up setting, accurately adjustable from 0 – 10 seconds
Initial torque setting, adjustable from 0 – 85%, with or without kick start
Brake torque setting, adjustable on a relative scale from 0 – 15
LED for status and error indication
Auxiliary contacts (SCR)
Functional diagram
Line voltage L1, L2, L3 Run command Slow speed command Brake command
Motor voltage T1, T2, T3 Brake on
Aux. contacts: 23-24 by-pass 13-14 I-O 13-14 ( M )
1. When line voltage is applied the brake will automatically stop a rotating motor.
2. The function of auxiliary contact 13-14 is selectable; “start - stop” or “mechanical brake”
Soft start function Ramp up
During ramp-up the controller will gradually increase the voltage to the motor until it reach full line voltage. The motor speed will depend on the actual load on the motor shaft. A motor with little or no load will reach full speed before the voltage has reached its maximum value.
The actual ramp time is digitally calculated and will not be influenced by other settings, net frequency or load variations.
Initial torque
The initial torque is used to set the initial starting voltage. This way it is possible to adapt the controller to an application requiring a higher starting torque. In some cases on application with very high break-away torque the initial torque can be combined with a kick start function. The kick start is a period of 200 ms where the motor receives full voltage.
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 4
Data sheet | Soft Start Motor Controller, Type MCI 25B
Brake function Braking is achieved by injecting a DC current,
adjustable from 0 – 50 A, onto all the windings of the motor. The brake can be used on both star and delta connected motors, but is most efficient if the motor is connected in star.
Adjustment
The actual braking torque is controlled indirectly by adjusting the braking voltage. The braking voltage can be set for 0 – 15. For small motors a relatively high braking voltage is necessary contrary to larger motors where a relatively low voltage is sufficient. For this reason the braking voltage must be adjusted to the actual application. Before starting up a new application set the Braking torque to 1. Increase incrementally until desired braking time is reached.
Automatic stop detection
When the brake function is applied the MCI-B will bring the motor to a stop before releasing the brake current.
Note: If a contactor is placed between motor and the MCI-B, do not open during braking as it can cause the contactor to fail.
If the motor does not stop within 30 seconds the DC brake will disengage and the controller will show a “brake failure” condition.
The automatic stop detection is accomplished by sensing the DC brake current on the motor, and as so the accuracy of the stop detection will depend on a correctly adjusted brake. The point of “no rotation” depends on the motor size and the brake voltage setting. If the motor voltage is set to low the brake will be switched off before the motor has come to a complete stop. However, if the brake voltage is set to high, out of detection range, it will not switch off the motor before the brake failure conditions occurs after 30 seconds.
Slow speed function The slow speed function is intended for short
time operation in applications where an exact positioning is needed, for example cranes. The function has two selectable slow speeds: 7.5% or 10% of nominal speed.
Auxiliary contacts The auxiliary contacts are made possible by
means of SCR technology and will only switch correctly on AC current.
Contact 13-14
The contact 13-14 is selectable for two different functions; “I-O” or “Mechanical brake”. If the “I-O” is selected, the contact will be closed as long as a RUN command is given, see functional diagram
LED status indication
LED status indication:
The torque level will depend on the motor and selected slow speed, typically 25 – 40% of nominal torque. During slow speed the motor current will increase, typically 2 – 2.5 times the nominal current.
If “Mechanical brake” is selected, the contact will be closed as long as the motor is rotating. The “Mechanical brake” setting is intended for operating an external mechanical brake.
Contact 23-24
The contact 23-24 is intended for operating an external by-pass contactor. The contact will close when the controller is in steady state operation, see functional diagram.
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 5
Data sheet | Soft Start Motor Controller, Type MCI 25B
Wiring
Overload and short circuit protection
Run / brake command Slow speed command Forced brake command
MCI 25B
By-pass
I-O or mechanical brake
Common
Overload and short circuit protection is easily achieved by installing a circuit breaker on the line side of the motor controller. Select circuit breaker from the table according to motor full load current.
380 – 415 V AC
Type
CTI 25M
CTI 25M
CTI 25M
CTI 25M
CTI 25M
1
) Values based on let-through curves for appropriate circuit breaker
Motor full load current
[A] [kA]
4.0 – 6.3
6.3 – 10 10 – 16
14.5 – 20 18 – 25
Code number 037N0061 037N0062
Mains L1, L2, L3
Inputs (C, R, S, B)
Outputs (13/14, 23/24)
208 – 240 V AC 380 – 480 V AC
24 – 480 V AC/DC
24 – 480 V AC
max. 0.5 A
Be aware of the maxium prospective short circuit current breaking capacity. For further information please refer to data sheet for the circuit breaker.
Max. prospective short-circuit current Icc
100
100
40
1.8
1.5
24 – 480 V AC/DC
24 – 480 V AC
max. 0.5 A
Code no.Co-ordination 1)
047B3148 047B3149 047B3150 047B3151 047B3152
Dimensions mm (inches)
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 6
Data sheet | Soft Start Motor Controller, Type MCI 25B
Operating at high temperatures
Operating on heavy loads
Overheat protection
Operation in temperatures from 40 °C up to 60 °C is possible if the power dissipation is limited
Ambient temperature Continuous operation
[°C] [A]
50 20 25 A with 80% duty cycle, max. on-time 15 min 60 15 25 A with 65% duty cycle, max. on-time 15 min
Load data is given for normal starts. If applied on heavy starts please derate according to table.
If required the controller can be protected against overheating by inserting a thermostat in the slot on the right-hand side of the controller.
Order: UP 62 thermostat 037N0050
either by reducing the current or by reducing the ON-time of the controller. Refer to table.
Duty-cycle rating
Overload relay trip class
10 (Light starts) 25
10 (Normal starts) 25
20 (Heavy starts) 20
30 (Very Heavy starts) 15
Max. current
[A]
For wiring connections see application examples.
Mounting instructions The controller is designed for vertical mounting.
If the controller is mounted horizontally the load current must be reduced by 50%.
The controller needs no side clearance.
Clearance between two vertical mounted controller must be minimum 80 mm (3.15”).
Clearance between controller and top and bottom walls must be minimum 30 mm (1.2”).
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 7
37-218.20
Data sheet | Soft Start Motor Controller, Type MCI 25B
Application examples Overheat protection
Example 1
The thermostat can be connected in series with the control input of the Motor Controller. When the temperature of the heat sink exceeds 100 °C the Motor Controller will be switched OFF.
Note: when the temp. has dropped approx. 30 °C the Controller will automatically be switched ON again. This is not acceptable in some applications
Example 2
The thermostat is connected in series with the control circuit of the main contactor. When the temp. of the heat sink exceeds 100 °C the main contactor will be switched OFF. This circuit requires manual reset to restart the motor.
Standard start – brake wiring
If only the soft start and braking function is required it is easily achieved by wiring the control voltage to “R”. When control voltage is applied the controller will begin the soft start procedure. To brake the load the control voltage is disconnected.
Danfoss circuit breaker CTI 25M is in this example providing overload and short circuit protection.
MCI 25B
Danfoss CTI 25M
Danfoss
24 – 480 V AC
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 8
A37-220.20
Application examples
(continued)
Direct wired start-stop with bypass
By wiring the auxiliary contact function 13-14 into the control circuit start and stop can be achieved by means of push buttons.
Note that the operating mode selector must be set for “I-0” control.
Auxiliary contact 23-24 is used to control and external by-pass contactor during steady state operation.
Danfoss circuit breaker CTI 25M is in this example providing overload and short circuit protection.
Wired for control of mechanical brake and bypass
The auxiliary contact function 13-14 is in this example used to control a mechanical brake. The brake is released when the controller is applying voltage to the motor.
MCI 25B
Danfoss CTI 25M
Danfoss CTI 25M
24 – 480 V AC
Danfoss
A37-219.20
Danfoss
Note that the operating mode selector must be set for “mechanical brake” control.
Auxiliary contact 23-24 is used to control an external by-pass contactor during steady state operation.
Danfoss circuit breaker CTI 25M is in this example providing overload and short circuit protection.
MCI 25B
24 – 480 V AC
24 – 480 V AC
­Max. 0.5 A
© Danfoss | DCS (az) | 2018.02
IC.PD.C50.H3.02 | 9
Loading...