Installation guide
Pressure regulating valve
KVP, KVL, KVR, KVD, KVC
Refrigerants:
R22, R1270*, R134a, R290*, R404A, R407A, R407C, R407 F,
R448A, R449A, R450A, R452A, R507A, R513A, R600*,
034R9506
R600a*
* Applicable for KVP 12 – KVP 22, KVL 12 – KVL 22,
KVR 12 – KVR 22, KVD 12 – KVD 15, KVC 12 – KVC 22
For complete list of approved refrigerants,
visit www.products.danfoss.com and search for
individual code numbers,
as part of technical data.
max.
100 °C
(212 °F)
15% Ag 15% Ag 15% Ag
© Danfoss | DCS (rja) | 2017.03
where refrigerants are listed
max.
140 °C
(285 °F)
KVP KVL KVR KVD KVC
max.
140 °C
(285 °F)
NB! Tightening torques
must be respected
especially when used
with ammable refrigerants
3Nm (nger tight
034R9506
3Nm (nger tight
+ 1/4 turn
+ 1/2 turn)
DKRCC.PI.HA0.A6.00 | 1
KVP
KVL
KVC
KVR
KVD
KVP 12
KVP 22
KVP 28
KVP 35
KVL 12
KVL 15
KVL 22
KVL 28
KVL 35
KVC 12
KVC 22
KVR 12
KVR 22
KVR 28
KVR 35
KVD 12
KVD 22
360° ~ 0.45 bar (6 psi)KVP 15
360° ~ 0.30 bar (4 psi)
360° ~ 0.45 bar (6 psi)
360° ~ 0.30 bar (4 psi)
360° ~ 0.45 bar (6 psi)KVC 15
360° ~ 2.50 bar (36 psi)KVR 15
360° ~ 1.50 bar (22 psi)
360° ~ 2.50 bar (36 psi)KVD 15
pe = 2 bar
pe = 10 bar
t
max
t
min
PS/MWP
KVP 130 °C (265 °F) -45 °C (-50 °F) 18 bar (260 psig)
KVL 130 °C (265 °F) -60 °C (-75 °F) 18 bar (260 psig)
KVR, KVD, KVC 130 °C (265 °F) -45 °C (-50 °F) 28 bar (406 psig)
3Nm
3Nm
© Danfoss | DCS (rja) | 2017.03
DKRCC.PI.HA0.A6.00 | 2