max.
100 °C
(212 °F)
max.
140 °C
(285 °F)
max.
140 °C
(285 °F)
3Nm (nger tight
+ 1/4 turn
3Nm (nger tight
+ 1/2 turn)
NB! Tightening torques
must be respected
especially when used
with ammable refrigerants
15% Ag 15% Ag 15% Ag
KVP KVL KVR KVD KVC
Refrigerants:
R22, R1270*, R134a, R290*, R404A, R407A, R407C, R407F,
R448A, R449A, R450A, R452A, R507A, R513A, R600*,
R600a*
* Applicable for KVP 12 – KVP 22, KVL 12 – KVL 22,
KVR 12 – KVR 22, KVD 12 – KVD 15, KVC 12 – KVC 22
For complete list of approved refrigerants,
visit www.products.danfoss.com and search for
individual code numbers,
where refrigerants are listed
as part of technical data.
Installation guide
Pressure regulating valve
KVP, KVL, KVR, KVD, KVC
034R9506
034R9506
© Danfoss | DCS (rja) | 2017.03

pe = 2 bar
pe = 10 bar
3Nm
3Nm
t
max
t
min
PS/MWP
KVP 130 °C (265 °F) -45 °C (-50 °F) 18 bar (260 psig)
KVL 130 °C (265 °F) -60 °C (-75 °F) 18 bar (260 psig)
KVR, KVD, KVC 130 °C (265 °F) -45 °C (-50 °F) 28 bar (406 psig)
KVP
KVP 12
360° ~ 0.45 bar (6 psi)KVP 15
KVP 22
KVP 28
360° ~ 0.30 bar (4 psi)
KVP 35
KVL
KVL 12
360° ~ 0.45 bar (6 psi)
KVL 15
KVL 22
KVL 28
360° ~ 0.30 bar (4 psi)
KVL 35
KVC
KVC 12
360° ~ 0.45 bar (6 psi)KVC 15
KVC 22
KVR
KVR 12
360° ~ 2.50 bar (36 psi)KVR 15
KVR 22
KVR 28
360° ~ 1.50 bar (22 psi)
KVR 35
KVD
KVD 12
360° ~ 2.50 bar (36 psi)KVD 15
KVD 22
© Danfoss | DCS (rja) | 2017.03