Danfoss KPU 74B, KPU 74, KPU 75, KPU 77, KPU Data sheet

...
Data sheet
Thermostat KPU
The KPU Thermostats are temperature controlled electrical switches, which are applied for regulation and safety monitoring of refrigeration and air conditioning systems.
All KPU Thermostats have a single pole double throw (SPDT) contact system. Theposition of the switch depends on the thermostat setting and the bulb temperature.
Features
Approvals
© Danfoss | DCS (jmn) | 2016.08 DKRCC.PD.CA0.F6.22 | 520H11320 | 1
• Wide temperature regulating range allows use in low, medium, and high temperature refrigeration application and air-conditioningsystems
• Snap-action electrical contacts minimize chatter, bounce and wear, and ensure long-term electrical and mechanical reliability
• Fingertip manual trip feature allows contact function testing without tools
• Easily replaces other manufacturers’ thermostats
• Ultra-short bounce time
UL listed for USA and Canada, le E31024
• Long operating lifetime
• Vibration and shock resistant
• SPDT switch allows NC or NO function option as well as alarm capability
• Automatic and manual reset versions available
Data sheet | Thermostat, KPU
Technical data
Regulating ranges in [°F]
Ambient temperature -40 – 122 °F, 175 °F up to 2 hours
Cable entry
⁄ in cable entry for ½ in male pipe thread connection (conduit boss)
Maximum wire dimension 10 AWG
Enclosure ~NEMA 1
Switch SPDT – single pole double throw
FLA = 24 A at 120 V AC
24 A at 240 V AC
NAM rating
Alternating current
1
) = 144 A at 120 V AC
LRA
144 A at 240 V AC
Contact load
Direct current 12 W pilot duty at 240 V DC
AC1: 16 A, 400 VA
European rating (acc. to EN 60947)
Alternating current
AC3: 16 A, 400 VA
Direct current DC13: 12 W, 220 V control current
1)
LRA is rated for make only
KPU 61
KPU 62 (room sensor) Vapor charge
KPU 63
KPU 68 (room sensor)
KPU 69
KPU 62
KPU 71
KPU 73 Adsorption charge
KP U 74
KPU 75
KPU 77
-50 0 50 100 150
© Danfoss | DCS (jmn) | 2016.082 | 520H11320 | DKRCC.PD.CA0.F6.22
Data sheet | Thermostat, KPU
Ordering
Typ e
Bulb type
Range
Dierential
at lowest
temperature
setting
at highest
temperature
setting
Max. bulb
temp.
Reset
function
Capillary
tube length
Code no.
[°F] [°F] [°F] [°F] [in]
Vapour 1)
KPU 61 A -20 – 60 10 – 40 2.5 – 13 250 auto. 80 060L5201
KPU 61 B -20 – 60 10 – 40 2.5 – 13 250 auto. 80 060L5203
3
KPU 61B B -20 – 60 fix e d 11 fixed 3.5 250 man.
KPU 61B B -20 – 60 fix e d 11 fixed 3.5 250 man.
) 80 060L5204
3
) 200 060L5205
KPU 62 C1 -20 – 60 10 – 40 2.5 – 13 250 auto. room sensor 060L5206
4
KPU 61 B -20 – 60 10 – 40 2.5 – 13 250 auto.
) 80 060L5210
KPU 63 A -60 – 15 18 – 125 5 – 15 250 auto. 80 060L5213
KPU 63 B -60 – 15 18 – 125 5 – 15 250 auto. 80 06 0L5214
KPU 68 C1 25 – 95 8 – 45 3 – 13 250 auto. room sensor 060 L5215
KPU 69 B 25 – 95 8 – 45 3 – 13 250 auto. 80 060 L5217
Adsorption 2)
KPU 62 C2 -20 – 60 9 – 36 3 – 14 175 auto. 4) room sensor 060L5207
Contact system
KPU 73 E3 -15 – 60 6.5 – 32 5 – 50 175 auto. 80 060L5208
KPU 73 E1 -15 – 60 22 – 125 15 – 45 175 auto. 80 060L5209
3
KPU 73B E3 -15 – 60 fixed 6 fixed 6 175 man.
) 80 060 L52 11
KPU 73 D -15 – 60 6 – 35 5 – 32 175 auto. 80 060L 5212
KPU 71 E2 25 – 70 5.5 – 18 4 – 16 175 auto. 80 06 0L5218
3
KPU 71B E2 25 – 70 fixed 5 fixed 5 175 man.
) 80 060L 5216
KP U 74 E1 0 – 80 9 – 35 9 – 35 175 auto. 80 06 0L5219
3
KP U 74 B E1 0 – 80 fixed 10 fi xe d 10 175 man.
) 80 060L5220
KPU 75 F 30 – 95 6 – 29 4.5 – 21.5 230 auto. 80 06 0L 5221
KPU 77 E3 60 – 140 6 – 18 6.3 – 18 265 auto. 80 060L5223
1)
Bulb must be installed in colder position than thermostat
housing and capillary tube.
2
) Bulb can be placed warmer or colder than thermostat housing and capillary tube, but variations from 70 °F ambienttemperature will inuence the scale accuracy.
3
) Manual minimum reset. Marked with letter B. Fixed dierential.
These controls have no hand knob.
4
) With manual switch and top plate.
Switch type – singlepoledoublethrow Switch action Applicaton
1. Terminals 1 – 4 close high and open low Terminals 1 – 2 can be used as
1. Low temperature cut-out
low temperature alarm
2. Terminals 1 – 2 open high and close low Terminals 1 – 4 can be used as
2. High temperature cut-out
high temperature alarm
© Danfoss | DCS (jmn) | 2016.08 DKRCC.PD.CA0.F6.22 | 520H11320 | 3
Data sheet | Thermostat, KPU
Design / Function
1. Temperature setting spindle
2. Dierential setting spindle
3. Main spring
4. Dierential spring
5. Bellows
6. Capillary tube
7. Main arm
8. Switch
9. Cable entry
11. Temperature sensor
12. Setting knob
13. Dierential setting screw
14. Control terminals
15. Ground terminal
16. Contact housing
Key sketch of KPU Thermostat KPU Thermostat without front cover
Switches in KPU Thermostats have a snap-action function, triggered when cut-in or cut-out temperature is reached.
Snap-action creates anumber of advantages:
• High contact load capability
• Ultra-short bounce time
• Long mechanical and electrical life
• High resistance to pulsation and vibration
• Vibration resistance up to 4 g in range 0 – 1000 Hz
• Long mechanical and electrical service life
© Danfoss | DCS (jmn) | 2016.08 DKRCC.PD.CA0.F6.22 | 520H11320 | 4
Data sheet | Thermostat, KPU
Terminology Set point
A predetermined value to which a thermostat is adjusted and at which it performs its intendedfunction.
Dierential
The dierential is the dierence between the cutin and cut-out temperatures. The dierential is necessary for satisfactory automatic operation of the controlled system.
Mechanical dierential (intrinsic dierential)
The mechanical dierential is the dierential set by the dierential spindle.
Snap function
A specic contact force is maintained until snap is initiated. The time over which contact force reaches zero is a few milliseconds; therefore, contact bounce due to vibration, for example, cannot occur at cut-out. The snap-action contact system will continue to function even when micro-welds are created between the contacts during cut-in. The force created to separate the contacts is strong enough to instantly shear o all contact surface welds that may have been created by cut-in action. These design features ensure that the cut-out setting of the KPU thermostat remains highly accurate and completely independent of the magnitude of the current load.
Reset
1. Manual reset: A unit with manual reset can only be restored to operational mode by activating the external reset button. On min. reset units the set value is equal to the cut-out value for falling temperature. On max. reset units the set value is equal to cut-out value for rising temperature.
2. Automatic reset: A unit with automatic reset is restored tooperational mode automatically.
FLA – Motor Full Load Amperes
FLA is the largest current that a motor or other device is designed to carry at rated voltage and other specic conditions. Also often called current at rated conditions.
LRA – Locked Rotor Amperes
LRA is the largest current that the motor is designed to carry with shaft or rotor immobilized.
Setting and resets Thermostats with automatic reset
Set the cut-in temperature on the “RANGE” scale. Set the dierential on the “DIFF” scale. Thecontrolled system will start at the temperature set on the RANGE scale and will be stopped when the temperature falls the number of degrees set on the DIFF scale.
Please note that the dierential scale is only areference. The exact value of distances on thescale depends on where in its range thecontrol cut-in is set. Use the dierential scale asaguide, and if precise function is required, establish the dierential setting by comparing function with an accurate thermometer in thecontrolled zone. If the compressor does not stop at the desired low temperature, check thedierential to ensure that it is not set at too high avalue.
The thermostat automatically resets and thecompressor starts once the temperature risesabove the range scale setting.
Thermostats with manual minimum reset
Set the cut-out temperature on the range scale. The dierential is xed.
Restart the compressor by pressing the reset button after the temperature of the sensor rises to a value equal to the range scale setting plus the xed dierential.
Thermostats with manual maximum reset
Set the cut-out temperature on the range scale. The dierential is xed.
Restart the compressor by pressing the reset button after the temperature of the sensor falls toa value equal to the range scale setting minus thexed dierential.
© Danfoss | DCS (jmn) | 2016.08 DKRCC.PD.CA0.F6.22 | 520H11320 | 5
Data sheet | Thermostat, KPU
Charges
1. Vapor charge 2. Adsorption charge
Bellows
Capillary tube
Sensor
The sensor contains saturated vapor with asmallquantity of liquid. When temperature rises, liquidevaporates, and pressure inside thesensorincreases. After all of the liquid has evaporated, additional heat results in only a small pressure rise inside the element. Vapor charges are appropriate for low temperature applications and others where the bellows must be protected from deformation by
As long as the sensor is the coldest part of the thermostat, ambient temperature has no eect on regulating accuracy. Sensors with adsorption charges contain asuperheated gas together with a solid having alarge adsorption surface. The sensor can be placed in zones that are warmer or colder than the control housing and capillary tube, but variations
of more than 70 °F may inuence scaleaccuracy. ambient temperature. The sensing element must be colder than the bellows at all times so that condensation of evaporated uid occurs in the element only, and not in the bellows.
Bellows
Capillary tube
Sensor
Dimensions of KPU withoutcapillary tube
All thermostats are supplied with universal mountingbracket and mounting screws asstandardaccessory.
Approximate weight of the bracket and mounting
screws: 0.615 lb
Net weight of KPU without capillary tube: ~ 0.77 lb
Net weight of 80 in capillary tube: ~ 0.17 lb
Net weight of 200 in capillary tube: ~ 0.43 lb
© Danfoss | DCS (jmn) | 2016.08 DKRCC.PD.CA0.F6.22 | 520H11320 | 6
Charges
KPU 61 KPU 63
Vapor charge
KPU 61 KPU 69
Vapor charge
KPU 62 KPU 68
Vapor charge
KPU 62
Adsorption charge
KPU 73
Adsorption charge
A
B
C
D
Straight capillary tube Sensing length: 15 in a = 3 1/8 in
Remote air coil a = ⁄ in b = 2 ¾ in
Room sensor C1 a = 1 ½ in b = 1 ¼ in Room sensor C2 a = 1 in b = 3 in
Double contact remote bulb a = ⁄ in b = 3 ⁄ in
NOTE!
Can not be used in sensor pocket!
Remote bulb
KPU 73, KPU 74
Adsorption charge
KPU 71, KPU 75
Adsorption charge
KPU 73, KPU 77
Adsorption charge
KPU 75
Adsorption charge
E
F
E1 a = ¼ in b = 3 ¾ in
E2 a = ⁄ in b = 4 ½ in
E3 a = ⁄ in b = 3 ⁄ in
Remote duct coil a = 1 in b = 3 ⁄ in
© Danfoss | DCS (jmn) | 2016.08 DKRCC.PD.CA0.F6.22 | 520H11320 | 7
Loading...