Danfoss APP series, APP 16/1200, APP 19/1500, APP 19/1200, APP 21/1200 User Manual

...
APP 16-22
User manual
Installation, Operation and Maintenance Manual
APP pumps (APP 16-22)
MAKING MODERN LIVING POSSIBLE
Lenntech
LQIR#OHQQWHFKFRP Tel. +31-152-610-900 ZZZOHQQWHFKFRP Fax. +31-152-616-289
Lenntech
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
2
180R9265 / IOM APP Pumps - v01 / 01.2013
Table of Contents Validity .........................................................................................4
EC Declaration of Conformity
.......................................................................5
1. Introduction ............................................................................6
1.1 General.................................................................................6
1.2 Symbols ................................................................................6
1.3 Manufacturer and customer service address:............................................. 6
2. Safety ..................................................................................7
2.1 General information.....................................................................7
2.2 Preferred system design.................................................................7
2.3 Commissioning and servicing the unit ...................................................7
2.4 Adhere to the following important points ............................................... 7
2.5 In case of doubt .........................................................................7
3. Technical data ..........................................................................8
3.1 Approved applications and operational limits for the pumps .............................8
3.2 Application range .......................................................................8
3.3 Electric motor data...................................................................... 8
3.4 Noise and vibration .....................................................................8
3.5 General arrangement ................................................................... 8
3.6 Space requirement ......................................................................8
3.7 Filtration ................................................................................8
3.8 Properties of water ......................................................................8
3.9 Air bubbles .............................................................................8
3.10 Chemicals...............................................................................8
4. Arrival inspection, transportation, handling, lifting and storage .......................... 9
4.1 Arrival inspection .......................................................................9
4.2 Warning ................................................................................9
4.3 General safety information ..............................................................9
4.4 Transport and handling .................................................................9
4.5 Return to supplier ......................................................................10
4.6 Storage ................................................................................10
5. Installation and commissioning......................................................... 11
5.1 Important dimensions .................................................................11
5.2 Cleanliness............................................................................. 11
5.3 Fluid temperature......................................................................11
5.4 Electrical data.......................................................................... 11
5.5 Local regulations.......................................................................11
5.6 Pre mounting checklist, based on Danfoss preferred system design ..................... 12
5.7 Lifting and positioning .................................................................12
5.8 Mount the dierent equipment ........................................................12
5.9 Electrics ...............................................................................12
5.10 Instrumentation .......................................................................12
5.11 Connections ........................................................................... 12
5.12 Ensure free ow .......................................................................13
5.13 Verify setting of safety/relief valves .....................................................13
5.14 Flush the pump ........................................................................13
5.15 Bleed and remove air from the pump...................................................13
5.16 Verify direction of rotation .............................................................13
5.17 Commissioning ........................................................................13
5.18 Check the lter condition...............................................................13
5.19 Instruct operator and maintenance personnel .......................................... 13
6. Operation of motor pump unit .........................................................14
6.1 General safety information .............................................................14
6.2 What to listen and look for .............................................................14
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
3
180R9265 / IOM APP Pumps - v01 / 01.2013
7. Maintenance and service of the pump unit .............................................15
7.1 General safety information .............................................................15
7.2 Service and inspection interval for the pump ...........................................15
7.3 Shut down of the system ...............................................................15
7.4 Disassembling and assembling the pump unit ..........................................15
7.5 Assembling the pump unit .............................................................16
7.6 Procedure for mounting pump back onto electric motor ................................16
7.7 Getting the pump unit back into operation .............................................16
7.8 Storage of the pump ...................................................................16
8. Troubleshooting and scrapping criteria .................................................17
8.1 General safety information .............................................................17
8.2 Operational conditions which can cause pump failures..................................17
8.3 Mechanical failure...................................................................... 17
8.4 Electrical failure........................................................................17
8.5 Responsibility ..........................................................................17
8.6 Scrapping criteria ......................................................................17
Subject index .....................................................................................18
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
4
180R9265 / IOM APP Pumps - v01 / 01.2013
This manual is valid for APP pumps with the following code numbers/serial numbers:Validity
APP 16/1200 Code no. 180 B325 4
Serial no. 01
APP 16/1500 Code no. 180 B3250
Serial no. 01
APP 17/1200 Code no. 180 B3255
Serial no. 01
APP 17/1500 Code no. 180 B3251
Serial no. 01
APP 19/1200 Code no. 18 0B32 56
Serial no. 01
APP 19/1500 Code no. 180 B3252
Serial no. 01
APP 21/1200 Code no. 180B3051
Serial no. 05
APP 21/1500 Code no. 180B3052
Serial no. 03
APP 22/1200 Code no. 180 B3257
Serial no. 01
APP 22/1500 Code no. 180 B3253
Serial no. 01
5
180R9265 / IOM APP Pumps - v01 / 01.2013
EU Declaration of Conform- ity
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
6
180R9265 / IOM APP Pumps - v01 / 01.2013
1.1 General
The APP pumps and pump units are manufac­tured by Danfoss A/S, and are sold and marketed by a net of authorized distributors world wide.
This manual contains the necessary instructions for the installation, operation and service of the pumps used in a Sea Water Reverse Osmosis (SWRO) or Brackish Water Reverse Osmosis (BWRO) system.
The APP pumps must not be used for other purposes than those recommended and specied without rst consulting your local pump distributor.
Use of the pump in other applications not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
All personnel being responsible for operation and maintenance of the pump unit must read and fully understand these instructions, especially the section “Safety” before:
tTransportation of the motor pump unit
tLifting the unit
tInstalling the pump unit
t
Connecting the motor pump unit to the water system
t
Connecting the electric motor and instru­mentation
tCommissioning the unit
t
Servicing the motor pump unit, mechanic and electric parts
tDecommissioning the motor pump unit
The pump must always be installed and used in accordance with existing national/local sanitary, safety regulations and laws.
It is the responsibility of the safety ocer or the chief operator to assure compliance with all local regulations that are not taken into account in this manual.
Changing the pumps’ or motor pump units’ operational limits and hardware:
t
Changes to the delivered pump or motor pump system may only be done with a written approval from Danfoss RO Solutions.
t Operation outside the Danfoss specications
requires a written approval from Danfoss RO Solutions.
t If any changes are made without written
approval the warranty will automatically become void.
Ensure that these instructions are always readily available to all personnel concerned.
1.2 Symbols
Indicates something to be noted by the
reader
Indicates a situation which will or could
result in damage to the pump and its function
Indicates a situation which will or could
result in personal injury and/or damage to the pump
Electrical hazard - Indicates a high-
voltage warning
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
1.3 Manufacturer and customer service address:
Danfoss A/S RO Solutions
Nordborgvej 81, D25 DK-6430 Nordborg Denmark
Tel ep hon e: +45 7488 4024 Fax: +45 7445 3831 Email: ro-solutions@danfoss.com Homepage: www.ro-solutions.com
Your local Danfoss pump distributor can be found on our homepage.
Data sheets and instructions on all accessories are available on www.ro-solutions.danfoss.com
CE Declaration of Conformity can be found on page 5.
1. Introduction
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
7
180R9265 / IOM APP Pumps - v01 / 01.2013
2.1 General information
Dangers that can arise from not following the instructions:
When the pump or pump system is managed by untrained personal, there is a danger of:
tDeath or fatal injuries
tCostly damages and claims
Electrical
hazard
All electrical installation work must only be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
Install a lockable circuit breaker to avoid inadvertent starting.
Protect the motor and other electrical equip­ment from overloads with suitable equipment.
!
Protective garments must be wor n
It is recommended to place a local safety switch near by the pump, enabling service personal to cut power for the electric motor. This prevents unintentionally starting the unit during servicing.
Always wear suitable safety clothing when handling the pump.
When working near the pump system, safety proof boot/shoes, safety glasses, ear protection and safety helmet must always be worn.
Under certain operational conditions the surface of the pump can be above 60°C / 140°F. Under these conditions the pump must be labelled with a “Danger Hot” sign.
When using an electric motor, the motor must always be supplied with adequate cooling ventilation.
When using an electric motor together with a VFD, the motor must be designed for operation with VFD. VFD operation may increase the temperature inside the electric motor if the motor is not designed for VFD operation.
Before start-up, the settings for all protective devices, for example, sensors/switches and safety valves must be veried and free ow from safety valves must be ensured.
All pipe and hose connections must be stress­free mounted, securely fastened to the pumps and well supported. Improper installation will or could result in personal injury and/or damage to the pump.
Use of this manual does not relieve operation and maintenance personnel of the responsibil­ity of applying normal good judgment in the operation and care of the pump and its components.
2.2 Preferred system design
Danfoss recommends building systems with a high degree of safety. See Danfoss preferred system design and PI&D in Data sheet and Instruction which are found in appendix 1 (Data sheet) and 2 (APP pump instruction).
It is always the system builders responsibility that the system design does not cause any kind of hazard and is adapted to local regulations and standards.
Proper installation, care of start up and shut­down devices and over-pressure protection equipment is essential.
2.3 Commissioning and servicing the unit
It is recommended that commissioning and servicing are carried out by a minimum of two people, where one is acting as a supervisor.
2.4 Adhere to the following important points
t
Before using the pump/pump unit it is very important to read and understand this user manual.
t Do not try to lift the pump unit manually;
most of the pumps weight more than 20 kilos, see specic weight for the pump in the Data sheet, which is found in appendix 1.
t Do not run the pump if it is completely dry
and not bleeded.
t Do not mount the pump without the bell
housing and a exible coupling.
t Do not try to start the unit before the
system components are mounted, bleeded and adjusted.
2.5 In case of doubt
Please contact Danfoss A/S in case of doubt. Contact information are listed in section 1.3, Manufacturer and customer service address.
2. Safety
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
8
180R9265 / IOM APP Pumps - v01 / 01.2013
3.1 Approved applications and operational limits for the pumps
The pump and the pump units are designed for the use in a Sea Water Reverse Osmosis (SWRO) or Brackish Water Reverse Osmosis (BWRO) systems.
The APP pumps must not be used for other purposes than those recommended and specied without rst consulting your local pump distributor.
Use of the pump in other applications not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
For system integration of the pumps, please see Data sheet and Instruction which are found in appendix 1 (Data sheet) and 2 (APP pump instruction).
3.2 Application range
See Data sheet in appendix 1.
3.3 Electric motor data
See recommended motor in Data sheet, appendix 1 or IOM for motors, appendix 3. The motors mentioned are the most common used motors by Danfoss High Pressure Pumps.
3.4 Noise and vibration
Noise level for a motor pump unit with a ”standard” motor measured according to EN ISO 3744:2010, see Data sheet in appendix 1. Possibilities to reduce noise and vibration are described in the same Data sheet.
3.5 General arrangement
Dimensions for the dierent pumps, see Data sheet in appendix 1.
3. Technical data
3.6 Space requirement
For service and replacement of the complete motor pump unit, it is recommended having sucient space around the unit.
For easy access to the unit, at least 1 meter/ 40 inches available space should be kept free around the pump. When working with high pressures, space demands should reect the required safety requirements.
3.7 Filtration
(10µm absolute [ß10 =5000]) Requirements are specied in Data sheet, appendix 1 and APP pump instruction, appendix
2.
Danfoss recommends not to build a lter bypass function or use lters with an integrated bypass. If the above recommendation is not followed the warranty for the pump will automatically become void.
It should be possible to monitor the condition of the lter via the dierential/delta pressure across the lter.
Using insucient ltration or a lter bypass can cause a failure or decreased service life of the pumps.
3.8 Properties of water
It is recommended NOT to use the pumps in feed water concentrations higher than 50,000 ppm TDS without consulting your local Danfoss pump distributor.
3.9 Air bubbles
Large bubbles in a pressurised RO system can result in damage to piping, equipment and the pumps.
All air must be bleeded from both the low­pressure and high-pressure side before the RO system is pressurised. Special consideration should also be given to air bubbles in feed ow and continuously feed into the pumps as it else can give cavitation.
3.10 Chemicals
The pumps should not be exposed to any chemicals that can result in damage to piping, equipment and internal parts of the pumps.
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
9
180R9265 / IOM APP Pumps - v01 / 01.2013
4.1 Arrival inspection
The pump is packed in a cardboard or wood box with plugs in the port connections to protect the pumps from damage during transportation.
Immediately check the shipment for damage on arrival and make sure that the name plate/type designation is in accordance with the packing slip and your order.
Remove all packing materials immediately after delivery. In case of damage and/or missing parts, a report should be drawn up and presented to the carrier at once.
4.2 Warning
Before any lifting operation is performed, environmental conditions must be taken into consideration (Ex-rated areas, wind speed, wet/ dry conditions, lifting height, etc.).
4.3 General safety information
Personnel involved in lifting and transporting the equipment (see Safety, chapter 2) must be trained in handling and safety procedures when lifting heavy loads. Many of the pumps and pump units weigh more than 20 kilos, which requires lifting slings and suitable lifting devices; e.g. an overhead crane or industrial truck to be used as minimum.
4.4 Transport and handling
Small pumps which have a weight below 20 kilos (weight can be found in the Data sheet in appendix 1) can be handled by hand if they are not mounted together with an electric motor. The weight of a small pump with a motor will be above 20 kilos.
Pumps which have a weight above 20 kilos (see Data sheet, appendix 1) must be handled by using lifting eyes and slings.
Never use only one sling and make sure the slings does not slip o the pump.
When the pump is mounted together with an electric motor, the pump unit always weight more than 20 kilos and must be handled by using slings around the pump unit.
4. Arrival inspection, transportation, handling, lifting and storage
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
10
180R9265 / IOM APP Pumps - v01 / 01.2013
See below examples of where to/not to attach the lifting slings on the pump unit:
Correct lifting with 2 separate slings:
When lifting the pump unit, one sling must be attached to the electric motor and one sling around the pump.
Only some motors and pumps have specic lifting eyes.
Do not use connections/nozzles for lifting! Do not use only one sling!
Make sure that the unit/load is balanced before attempting to lift, as the centre of the mass is dierent from pump to pump and pump unit to pump unit.
How to mount the pump and the electric motor correctly together, see Data sheet in appendix 1 or APP pump instruction in appendix 2.
Wrong lifting:
Incorrect lifting can result in personally injury and/or damage to the pump unit.
4.5 Return to supplier
Please see maintenance chapter 7.
4.6 Storage
Each pump is tested before shipment and therefore holds water, so for storage tempera­ture and frost protection see Data sheet in appendix 1 or APP pump instruction in appendix
2.
The pumps are NOT delivered frost protected from the factory.
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
11
180R9265 / IOM APP Pumps - v01 / 01.2013
5.1 Important dimensions
Physical dimensions and connections for the pump unit are described in Data sheet, appendix 1.
5.2 Cleanliness
It is very important that the tubes and pipes are completely clean: no dirt, chips or burrs are allowed. Flush all piping before connecting the high pressure pump to ensure the system is clean. Internal surfaces of the piping must not be corroded. If dirt or rust is not removed, the pump and the valves can be damaged and in the worst case damaged beyond repair!
5.3 Fluid temperature
Before start-up, the uid and pump housing temperature must be above the minimum start-up temperature, see Data sheet, appendix 1.
5.4 Electrical data
Check voltage, current frequency and rated power on the electric motor and VFD setting name plate on both the motor and the VFD.
5.5 Local regulations
Commissioning must always be done in accordance with valid regulations and local standards.
5.6 Pre mounting checklist, based on Danfoss preferred system design
Schematic 1: Recommended system design
5. Installation and commissioning
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
12
180R9265 / IOM APP Pumps - v01 / 01.2013
Table 1: Check points when assembling and commissioning system
Check points Comment OK ?
CP1 Ensure that the environmental conditions are safe. See Arrival inspection,
transportation, handling, lifting and storage, chapter 4.
CP2 Minimum and maximum start-up temperature for uid and
pump.
See Data sheet or Instruction, appendices 1 and 2.
CP3 Filtration condition (10µm absolute (ß10 = 5000) See Danfoss requirements in
Data sheet and Instruction, appendices 1 and 2
CP4 Power supply for electric motor and VFD. See Data sheet for the used
motor and VFD, appendix 1.
CP5 Safety circuit / breaker must be sized for the motor and
environment (corrosion and humidity)
See Data sheet for the used safety circuit.
CP6 Bolts and screws must conform to environmental conditions
as well as uid and torque requirements.
CP7 Instrumentation, pressure switch should be designed to
conform to the environment (corrosion and humidity).
See Data sheet for the used equipment.
CP8 Check the factory settings of the safety/relief valves or
pressure relief valves (8 & 9).
See Data sheets for the used valves.
CP9 Check the settings of the pressure transmitter/switch (3) set
at min. inlet pressure.
See Data sheet or Instruction, appendices 1 and 2.
CP10 Check that all pressure indicators (PI) are selected to be able
to measure the system pressure range.
Scaling should at least be 1 Bar or more precise.
CP11 Check coupling distance ( air gab – movement of the spider ) 3 – 5 mm
CP12 Check correct connections on the pump ( in & outlet)
CP13 Check piping for possible air gaps.
5.7 Lifting and positioning
Lift the pump unit onto base (Remember vibration dampers, if needed). Fasten the motor to the base.
See also chapter 4, Arrival inspection, transporta­tion, handling, lifting and storage.
5.8 Mount the dierent equipment
(connections, pipes, tubes, check and safety/relief valves, etc.)
t
The hard piping and exible hoses used must be of proper design and must be installed in accordance with the manufacturer’s recom­mendations. (see also Data sheet for Hose and hose ttings and Instruction for Assembling Hose kit - both available on www.ro-solutions.danfoss.com).
t Misalignment of the hard pipes may place
stress on the pump port connection and may damage the pump.
tPrevent excessive external pipe load.
t Do not connect piping by applying external
force (use of wrenches, crane, etc.) Piping must be aligned without residual stress.
t Do not mount expansion joints so that their
force applies internal pressure on the pump connections.
5.9 Electrics
All electrical installation work must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations. (see also Safety, chapter 2)
Mount the safety circuit breaker, turn the circuit o and lock it in the o position.
Mount the power cable on the electric motor.
If a VFD is used, adjust the protective motor switch/VFD to the current limits found on name plate of the electric motor.
5.10 Instrumentation
The pressure switch/sensor should be mounted as close to the pump as possible. It is recom­mended to test the pressure/sensor switch via an instrumentation manifold.
Mount the pressure switch/sensors according to the manufacturer’s instructions.
5.11 Connections
Mount connections and maybe check valve(s). Mount and tighten as specied.
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
13
180R9265 / IOM APP Pumps - v01 / 01.2013
5.12 Ensure free ow
Ensure that the ow from safety/relief valves 8 and 9 is completely unhindered. A blocked safety/relief valve can cause excessive build-up of pressure and thereby cause dangerous situations and damage to the whole system.
5.13 Verify setting of safety/relief valves
Make sure, the safety/relief valves 8 and 9 are placed correctly.
Check the pressure settings on the name plates of the safety/relief valves. If they are OK, continue. Otherwise replace the safety/relief valves.
5.14 Flush the pump
Fully open the pressure valve at the brine site.
Close all the bleeding and draining plugs on the high pressure pump.
Start the feed pump and ensure that the ow from the feed pump to the high pressure pump is unhindered.
5.15 Bleed and remove air from the pump
Open bleeding plugs. Keep the plugs open until only water leaves the high pressure pump.
5.16 Verify direction of rotation
An arrow can be found on the pump or pump unit. The direction of rotation must always follow the arrow.
Unlock the safety circuit breaker. Start the motor for 1 second and observe the direction of rotation either looking on the fan of the motor or on the coupling true the hole in the bell housing (not available on all bell houses). If the motor is turning the wrong direction, switch two phases in the connection box of the motor or reprogram the direction in VFD.
5.17 Commissioning
tClose all the bleeding and draining plugs.
tOpen the pressure valve at the brine site.
t Switch the safety circuit breaker on for both
motor(s) and VFD(s).
tStart the feed pump.
tStart the high pressure pump.
t If a VFD or a soft starter is used a ramp up
time of minimum 10 second is required to avoid damage of internal pump parts.
t Monitor the inlet pressure and outlet
pressure of the high pressure pump and look for leakages.
t Check the pressure indicator function by
slowly closing the valves. The pump unit should stop when the minimum inlet pressure and maximum outlet pressure has been reached.
t Adjust the pressures to the specied inlet
and outlet pressure for the system and let the pump unit run until the electric motor and pump temperature is stable.
t If the system is running within the system
design limits, the system is released for operation.
5.18 Check the lter condition
Evaluate dirt found in lter, replace lter elements, if necessary.
5.19 Instruct operator and maintenance personnel
Before using the pump/pump unit, the personnel must be instructed in using the pump/pump unit, its function, components, documentation and safety.
Danfoss oers commissioning and service at system manufacturer’s location. Rate quotes are oered upon request.
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
14
180R9265 / IOM APP Pumps - v01 / 01.2013
6.1 General safety information
Before inspecting the pump unit, read the Safety chapter 2 in this user manual.
6.2 What to listen and look for
If the following is observed, please act as indicated:
A) Re-check all bolts and, if necessary, contact
the maintenance department in order to have all bolts tighten to the specied levels.
B) Leakage – if a small leak dripping from the
bell housing is observed, contact the maintenance department.
C) Leakage – if there is a large leak, the unit
should be stopped as soon as possible. Contact the maintenance department.
D) High frequency tones – safety/relief valves
are either damaged or running very close to their cracking pressure, stop the unit immediately. Contact the maintenance department.
E) Non-standard noise or vibration from the
pump requires the unit to be stopped immediately. Contact the maintenance department.
F) Very high temperatures – can indicate one
or more damaged parts inside the pump. The pump then needs to be stopped immediately and inspected before running again. Contact the maintenance depart­ment.
G) Drop in ow and/or pressure - can indicate
wear on one or more parts inside the pump. The pump needs to be stopped immediately and inspected before running again. Contact the maintenance depart­ment.
H) Other observations or troubles, please see
appendix 7, Right and Wrong or the Trouble shooting guide, appendix 6. Both appendices give good advises on design, installation, wiring and trouble­shooting.
If the pump is not stopped for inspection, it can lead to damage of the pump. See also service and warranty section in the Data sheet, appendix 1; APP pump instruction or Instruction for recommended service intervals in appendix 2 and 4.
Danfoss oers service of the pump at the system manufacturer’s location as well as training in servicing the pump. Quotes are oered upon request.
Danfoss recommends at the same time also to check the lter and membrane condition and evaluate dirt found, replace lter and membrane elements if necessary.
6. Operation of motor pump unit
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
15
180R9265 / IOM APP Pumps - v01 / 01.2013
7. Maintenance and service of the pump unit
7.1 General safety information
Before servicing the pump unit, it is necessary to read and understand this user manual, especially the Safety, chapter 2. Remember to wear suitable safety equipment according to Safety, chapter 2.
7. 2 Service and inspection interval for the pump
Maintenance and service intervals are depending on the cleanness level of the water, hydraulic load and temperature of the pump unit. The most important parameter is the cleanness of the water.
See the section Service and warranty in the Data sheet, appendix 1, APP pump instruction and Instruction for recommended service intervals in appendix 2 and 4.
For spare parts and service tools, please see Parts list, appendix 5.
Danfoss oers service of the pump at the system manufacturer’s location and training in servicing the pump. Quotes are oered upon request.
7. 3 Shut down of the system
A) Open the pressure valves at the brine site
to release the pressure.
B) Stop the high pressure pump.
C) Stop the feed pump.
D) Turn on the motor safety circuit breaker for
both the high pressure pump, the feed pump and the VDF if used and lock them. Only the employees servicing the pump unit should be able to unlock/activate the switch again.
E) Open bleeding and drain plugs. Wait until
the pump and system are emptied for water.
F) Slowly unscrew and remove the bolts and
gaskets from the in/out hoses or pipes, be careful about jets of water. Be aware that there still can be pressure in the system, which will be released when unscrewing and removing the bolts and gaskets.
G) Attach the lifting equipment to the pump
unit. For instructions on lifting the complete pump unit, see chapter 4, Arrival inspection, transportation, handling, lifting and storage.
H) For the small pumps unscrew the bolts
holding the pump to the bell housing and for the bigger pumps, unscrew the bolts holding the pump and bell housing to the
motor and afterwards unscrew the bolts/ nuts holding the pump and bell housing together.
I) Carefully pull the pump out of the bell
housing by using lifting equipment, if necessary.
J) Hold the pump in dierent positions above
a drip tray; this should allow most of the left-over water trapped in the pump to drip out. Clean and dry the pump surface and plug the bleeding and draining plugs.
K) Move the pump to a clean and safe location
where the pump can be inspected/ serviced.
7. 4 Disassembling and assembling the pump unit
A) Remove all connections from the pump.
B) Disassemble the pump according to the
Disassembling and Assembling Instruction (availabl e at w ww.ro-solutions.danfoss.com At the website you can also nd the Changing pistons instructions for APP 11-13 and APP 16-22 as well as for APP 21-38). Clean all the parts and surfaces with a uid compatible with the materials found in the pump. Wipe the parts clean and dry with a dry and lint-free cloth.
C) Inspect all parts including shaft seal and if
necessary, replace them; see Parts list, appendix 5 and APP pump instruction, appendix 2 or general instruction for Recommended service intervals, appendix
4.
D) If the pump is going to be returned to
Danfoss for repair or a warranty claim, it is important that Danfoss, besides your contact information and reason for returning, gets the below information before shipping.
After Danfoss has been informed about the return, you will receive a return number and a template to ll out. One copy should be attached to the shipment and one copy should be sent to the E-mail address on the template.
Returns without a return number will be
rejected !!!
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
16
180R9265 / IOM APP Pumps - v01 / 01.2013
7. 5 Assembling the pump unit
Assemble the pump according to the Dis­assembling and Assembling Instruction (availabl e at w ww.ro-solutions.danfoss.com).
7. 6 Procedure for mounting pump back onto electric motor
Do always follow the procedure delivered with the instructions from the coupling manufacturer!
Mount the exible coupling and bell housing according to the Data sheet, appendix 1 and APP pump instruction, appendix 2.
7.7 Getting the pump unit back into operation
Find instructions of how to put the pump unit back into operation in chapter 4, Arrival inspec­tion, transportation, handling, lifting and storage and Installation and commissioning, chapter 5.
7. 8 Storage of the pump
If the pump has to be shut down for a longer period or put on the shelf, instructions can be found in Storage-chapter in Data Sheet, appen­dix 1 or APP pump instruction, appendix 2.
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
17
180R9265 / IOM APP Pumps - v01 / 01.2013
8. Troubleshooting and scrapping criteria
8.1 General safety information
Before inspecting the pump unit, it is necessary to read and understand this user manual, especially the Safety chapter 2.
Remember to wear suitable safety equipment according to Safety chapter 2.
8.2 Operational conditions which can cause pump failures
The following conditions can cause a pump failure :
t5IFQVNQJTSVOOJOHESZ
t5IFJOMFUQSFTTVSFJTUPPIJHI
t5IFJOMFUQSFTTVSFJTUPPMPX
t5IFWJTDPTJUZPGUIFøVJEJTUPPIJHI
t5IFUFNQFSBUVSFPGUIFøVJECFJOH
pumped is too high.
t5IFBNCJFOUUFNQFSBUVSFJTUPPIJHI
t5IFQVNQJTSVOOJOHBHBJOTUBCMPDLFE
port/closed manual valve.
t5IFQVNQJTPQFSBUJOHBUBQSFTTVSFBCPWF
the operational specication.
t5IFQVNQJTSVOOJOHXJUIBOPOTQFDJöFE
approved uid.
t5IFQVNQJTSVOOJOHJOUIFXSPOH
direction.
t5IFöMUSBUJPOJTJOTVóDJFOU
t5IFQVNQJTOPUCFJOHTFSWJDFEBDDPSEJOH
to Danfoss specications (end of life).
t5IFSFJTFYDFTTJWFNFDIBOJDBMMPBEPOUIF
shaft coupling and piping.
8.3 Mechanical failure
If the pump is running dry, the temperature will quickly increase which can be dangerous, depending on how long time the pump is running dry.
If there is any leaking at start up or leaking arises during operation, the high pressure can lead to eye or skin damage.
Leaking can result in ooding, which again can cause a risk of slipping, tripping or falling.
If water is dripping into the electric motor; it can lead to electric shock, re, short of circuit or even death. In order to avoid water dripping into the electric motor, see Installation and commission­ing, chapter 5 and Operation, chapter 6.
Electrical
hazard
8.4 Electrical failure
If the wiring/connection of the electric motor is not correct or the earth connection is missing, it can lead to electric shock, burn damages, re or even death.
If a VFD is used and wrongly programmed, it can damage the pump and lead to high tempera­tures or other dangers.
Therefore all electrical installation work must only be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
8.5 Responsibility
Danfoss takes no responsibility for any other abnormal injuries, risks or damages that could arise caused by abnormal conditions, vibrations, corrosion, abrasives, foreign objects or excessive temperatures and shall not be liable for any consequential or incidental damages.
8.6 Scrapping criteria
Whether the pump can be repaired or need to be scrapped depends on how damaged the internal parts are or how damaged the whole unit is. Please use appendix 6, Trouble shooting guide as guideline or send the pump to Danfoss head­quarter in Denmark for evaluation.
For other observations or troubles, please see appendix 7, Right and Wrong which gives good advises in design, installation, wiring and troubleshooting.
User manual Installation, Operation and Maintenance APP Pumps (APP 16-22)
18
180R9265 / IOM APP Pumps - v01 / 01.2013
Danfoss ca n accept no responsi bility for pos sible errors in ca talogues, bro chures and other pr inted material. D anfoss reserve s the right to alter it s products wit hout notice. This also ap plies to produc ts already on orde r provided that su ch alterations ca n be made without su bsequential cha nges being nece ssary in speci cations alread y agreed. All trade marks in this mater ial are proper ty of the respec tive companies . Danfoss and the Danf oss logotyp e are trademark s of Danfoss A/S. Al l rights reser ved.
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
A
Address
. . . . . . . . . . . . . . . . . . . 6, 7, 15
Air bubbles . . . . . . . . . . . . . . . . . . . . . 8
Appendix
. . . .7, 8, 9, 10, 11, 12, 14, 15, 16, 17
Application range
. . . . . . . . . . . . . . . . . 8
Approval . . . . . . . . . . . . . . . . . . . . . . . 6
Arrival
. . . . . . . . . . . . . . . . . 9, 12, 15, 16
Assembling
. . . . . . . . . . . . . . . . 12, 15, 16
B
Bleed
. . . . . . . . . . . . . . . . . . . 7, 8, 13, 15
C
Checklist . . . . . . . . . . . . . . . . . . . . . . 11
Check points
. . . . . . . . . . . . . . . . . . . 12
Chemicals . . . . . . . . . . . . . . . . . . . . . . 8
Cleanliness
. . . . . . . . . . . . . . . . . . . . 11
Commissioning . . . . . .6, 7, 11, 12, 13, 16, 17
Connections
. . . . . . . . . . 7, 9, 10, 11, 12, 15
Coupling . . . . . . . . . . . . . . 7, 12, 13, 16, 17
D
Danger
. . . . . . . . . . . . . . . . . . . .7, 13, 17
Data sheet . . . . . . 7, 8, 9, 10, 11, 12, 14, 15, 16
Declaration of Conformity
. . . . . . . . . 5, 6
Design
. . . . . . . . . . . . 7, 8, 9, 11, 12, 14, 17
Distributor. . . . . . . . . . . . . . . . . . . . 6, 8
Dimensions
. . . . . . . . . . . . . . . . . . . 8, 11
Disassembling . . . . . . . . . . . . . . . . 15, 16
E
Electric motor
. 6, 7, 8, 9, 10, 11, 12, 13, 16, 17
Electrical failure
. . . . . . . . . . . . . . . . . 17
Electrical hazard . . . . . . . . . . . . . . . . . . 6
Electrics
. . . . . . . . . . . . . . . . . . . . . . 12
EU Declaration of Conformity
. . . . . . . . . 5
F
Fail ure
. . . . . . . . . . . . . . . . . . . . . .8, 17
Filter condition . . . . . . . . . . . . . . . . . . 13
Filtration . . . . . . . . . . . . . . . . . . 8, 12, 17
Flow
. . . . . . . . . . . . . . . . . . . 7, 8, 13, 14
Fluid
. . . . . . . . . . . . . . . . . . .11, 12, 15, 17
Flush
. . . . . . . . . . . . . . . . . . . . . . 11, 13
G
General information
. . . . . . . . . . . . . . . 7
Guideline . . . . . . . . . . . . . . . . . . . . . 17
H
Handling. . . . . . . . . . . . . . . 7, 9, 12, 15, 16
I
Inspection. . . . . . . . . . . . . 9, 12, 14, 15, 16
Installation
. . . . . . . . .6, 7, 11, 12, 14, 16, 17
Instruction. . . . . . . . 6, 7, 8, 10, 12, 14, 15, 16
Instrumentation
. . . . . . . . . . . . . . . .6, 12
Introduction . . . . . . . . . . . . . . . . . . . .6
M
Maintenance
. . . . . . . . . .6, 7, 10, 13, 14, 15
Mechanical failure. . . . . . . . . . . . . . . . 17
Mounting
. . . . . . . . . . . . . . . . . . . . . 16
N
Name plate
. . . . . . . . . . . . . . 9, 11, 12, 13
Noise
. . . . . . . . . . . . . . . . . . . . . . . . 14
L
Leaking. . . . . . . . . . . . . . . . . . . . . . . 17
Lifting
. . . . . . . . . . . . . 6, 9, 10, 12, 15, 16
Local regulations . . . . . . . . . 6, 7, 11, 12, 17
O
Operation
. . . . . . . . .6, 7, 8, 9, 13, 14, 16, 17
Operational conditions . . . . . . . . . . .7, 17
P
Piping. . . . . . . . . . . . . . . . . . 8, 11, 12, 17
Positioning
. . . . . . . . . . . . . . . . . . . . 12
Preferred system design
. . . . . . . . . . . 7, 11
Pre mounting . . . . . . . . . . . . . . . . . . . 11
Protection . . . . . . . . . . . . . . . . . . 6, 7, 10
R
Relief valve
. . . . . . . . . . . . . . . .12, 13, 14
Responsibility . . . . . . . . . . . . . . . 6, 7, 17
Return
. . . . . . . . . . . . . . . . . . . . . 10, 15
Rotation
. . . . . . . . . . . . . . . . . . . . . . 13
S
Safety
. . . . . . . . . .6, 7, 8, 9, 12, 13, 14, 15, 17
Safety valve . . . . . . . . . . . . . . . . . . . . .7
Scrapping criteria
. . . . . . . . . . . . . . . . 17
Serial number
. . . . . . . . . . . . . . . . . . . 4
Servicing. . . . . . . . . . . . . . . . . 6, 7, 14, 15
Shut down. . . . . . . . . . . . . . . . . . . 15, 16
Space requirement
. . . . . . . . . . . . . . . . 8
Spare part . . . . . . . . . . . . . . . . . . . . . 15
Start up
. . . . . . . . . . . . . . . . . . . . . . 7, 17
Storage . . . . . . . . . . . . . . . 9, 10, 12, 15, 16
Symbols
. . . . . . . . . . . . . . . . . . . . . . . 6
System . . . . . . . . . . 6, 7, 8, 11, 12, 13, 14, 15
Systems
. . . . . . . . . . . . . . . . . . . . . 7, 8
T
Table of content
. . . . . . . . . . . . . . . . . . 2
Technical data . . . . . . . . . . . . . . . . . . . 8
Tem pe rat ure
. . . . .7, 10, 11, 12, 13, 14, 15, 17
Transportation
. . . . . . . . . . . 6, 9, 12, 15, 16
Trouble shooting . . . . . . . . . . . . . . 14, 17
V
Valve
. . . . . . . . . . . . 7, 11, 12, 13, 14, 15, 17
W
Warning
. . . . . . . . . . . . . . . . . . . . . 6, 9
Subject index
Front page for Appendices
APP 16-22
User manual
Appendices for Installation, Operation and Maintenance Manual
APP pumps (APP 16-22)
MAKING MODERN LIVING POSSIBLE
User manual Appendices for IOM Manual for APP Pumps (APP 16-22)
2
180R9265 / IOM APP 16-22 Append ices - v02 / 01.2013
Table of Contents 1. Data sheet for APP 16-22 pumps (521B1183)..............................................3
2. APP pump instruction APP 11-13 and APP 16-22 (180R9223) .............................15
3. IOM Electric motors (180R9230)..........................................................27
4. Recommended service intervals for APP pumps (180R9199) . . .. . . . . . .. . . . .. . . . . . .. . . . .. .31
5. APP parts list (521B0941)................................................................35
6. Trouble shooting guide .. ... .. ... .. ..... ..... .. ... .. ..... ..... .. ... .. ..... ..... .. ... .. .41
7. Right and wrong (180R9042) ...........................................................51
1. Data sheet for APP 16-22 pumps (521B1183)
ro-solutions.com
Data sheet
Data sheet
APP 16-22
MAKING MODERN LIVING POSSIBLE
4
180R9265 / IOM APP 16-22 Append ices - v02 / 01.2013
Data sheet APP 16-22
APP 16-22 pumps are designed to supply low viscosity and corrosive uids under high pressure, e.g. in seawater reverse osmosis ltration applications and for high pressure salt water pumping.
The pumps are based on the positive displace­ment principle (axial piston design) which enables a very light and compact design, and
they are designed so that the lubrication of the moving parts in the pumps is provided by the uid itself. No oil lubrication is thus required.
The pumps are supplied with an integrated ushing valve that allows the salt water to ow from inlet to the outlet, when the pump is not running.
1. General information
1: Shaf t Sealing 2: Bolts for bell housing 3: Flushing valve 4: Port plate 5: Bleeding plug 6: Valve/thrust plate 7: Piston/shoe 8: Cylinder barrel 9: Retainer ring 10: Swash plate with bearing 11: Port ange with bearing 12: Drain plug 13: Housing 14: Springs
1. General information
2. Benets
3. Technical data
4. Variants
5. Flow at dierent rpm
6. Flushing valve
7. Power requirements
8. Temperature and corrosion
8.1 Operation
8.2 Storage
9. Noise level
10. Filtration
11. Dimensions
12. Dimensions, complete unit
13. Installation
13.1 Mounting
13. 2 Open-ended system with direct water supply
13. 3 RO system with APP pump
14. Service
14.1 Warranty
14. 2 Maintenance
14. 3 Repair
Data sheet for APP 16-22 pumps (521B1183)
Table of Contents
5
180R9265 / IOM APP 16-22 Append ices - v02 / 01.2013
Data sheet APP 16-22
t One of the smallest and lightest pumps on
the market
t Can be powered by a combustion engine
provided that a special coupling is used.
t Long service life / No preventive mainte-
nance required in the warranty period.
t Generates insignicant pulsations in the
pressure line.
tNo oil lubricant required
tIntegrated ushing valve
t All parts of the pump are made of non-
corrosive materials, e.g. Duplex (EN1.4462/ UNS S31803-S32205) and Super Duplex (EN1.4410/UNS S32750) stainless steel and carbon reinforced PEEK
tHigh eciency
2. Benets
3. Technical data
APP Pumps APP 16
120 0
APP 16 150 0
APP 17 120 0
APP 17 150 0
APP 19 120 0
APP 19 150 0
APP 22 120 0
APP 22 150 0
Code number 180 B325 4 18 0B325 0 18 0B32 55 180 B3251 180B 3256 18 0B32 52 180 B3257 180B 3253
Geometric displacement cm³/rpm 235 18 5 252 19 8 272 220 311 252
in³/rpm 14. 3 11 . 3 15. 4 12 .1 16 .6 13. 4 19 .0 15. 4
Rated ow at max speed
1)
m³/h 16 15. 8 17. 2 16 .9 18. 8 18. 8 21.5 21.7
gpm 70.4 69.6 75.7 74 .4 82.8 82.8 94.7 95.5
Outlet min. Pressure
2)
bar 30 30 30 30 30 30 30 30
psi 435 435 435 435 435 435 435 435
Outlet max. Pressure, continuous
3)
bar 80 70 80 70 80 70 80 70
psi 116 0 1015 116 0 1015 1160 1015 116 0 1015
Inlet min. Pressure bar 2 2 2 2 2 2 2 2
psi 29 29 29 29 29 29 29 29
Inlet max. Pressure, continuous bar 5 5 5 5 5 5 5 5
psi 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
Inlet max. Pressure, peak bar 10 10 10 10 10 10 10 10
psi 145 145 145 145 145 145 145 145
Max. Speed continuous rpm 120 0 15 00 1200 150 0 120 0 15 00 1200 150 0
Min. Speed continuous rpm 700 70 0 700 700 700 700 700 700
Power requirement at max. speed and 60 bar outlet pressure
kW 32 31 35 33 38 37 43 43
hp 42 .9 41.6 46.9 44.3 51.0 49.6 57.7 57.7
Torque at 60 bar outlet pressure
Nm 258 196 276 210 299 236 341 273
lbf-ft 190 .3 14 4.6 203.6 15 4.9 220.5 174.1 251.5 201.4
Weight kg 78 78 78 78 78 78 78 78
lb 172 17 2 17 2 17 2 172 17 2 17 2 172
Integrated ushing valve Yes Yes Ye s Yes Yes Yes Ye s Yes
1)
Typical average ow at 60 bar (870 psi)
2)
For lower pressure, please contact Danfoss
RO Sales Organization
3)
For higher pressure, please contact Danfoss
RO Sales Organization
The pump is designed according to EN809.
All parts included in the pumps are designed to provide long service life, i.e. long service life with a constantly high eciency and minimum service required.
The pumps are xed displacement pumps in which the ow is proportional to the number of revolutions of the input shaft and the pump displacement.
Loading...
+ 53 hidden pages