Data sheet
Actuators for three point control
AMV 01, AMV 02, AMV-H 01, AMV-H 02
Description AMV 01/02 and AMV-H 01/02 actuators are used
with VZ, VZL, VRBZ or with AB-QM valves (AMV
version only). The actuator can be used with
fan coil units, induction units, small reheaters,
recoolers, and zone applications in which hot/
cold water is the controlled medium.
Main data:
• 3-point versions
• The advanced design incorporates no-force
switch-off at stem up position, which enables
AMV 01, AMV 02
use of the actuator on valves with different
nominal strokes and improves the controller
response
• Force switch-off at stem down position
prevents overload of actuator and valve
• No tools required for mounting
• Maintenance free during the lifetime
• Low noise operation
• Supplied with 1.5 m cable.
Ordering
Technical data
AMV-H 01, AMV-H 02
Type
AMV 01
AMV 02 12 s/mm 082H8004
AMV-H 01 24 s/mm 082H8021
AMV-H 02 12 s/mm 082H8024
AMV 01
AMV 02 12 s/mm 082H8005
AMV-H 01 24 s/mm 082H8022
AMV-H 02 12 s/mm 082H8025
Type AMV 01, AMV-H 01 AMV 02, AMV-H 02
Power supply 24 Vac, 230 Vac; +10 to –15%
Power consumption 1 VA - 24 Vac; 7 VA-230 Vac
Frequency 50 Hz/60 Hz
Close of force 200 N
Max. stroke 5.5 mm
Speed 24 s/mm 12 s/mm
Max. medium temperature inside the pipe 120 °C
Ambient temperature 0 to 55 °C
Storage and transport temperature –40 to +70 °C
Protection code IP 42
Weight 0.34 kg
Supply
voltage
24 V~
230 V~
- marking in accordance with standards
Speed Code No.
24 s/mm 082H8001
24 s/mm 082H8002
Spare parts
Type Code No.
1.5 m cable for AMV, AMV-H - 24 V 082H8007
1.5 m cable for AMV, AMV-H - 230 V 082H8008
EMC- Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN 50081-1 and EN 50082-1
Low voltage Directive 73/23/EEC and 93/68/EEC,
EN 60730/2/14
SIBC VD.JC.M2.02 © Danfoss 08/05 1

Data sheet Actuators for three point control AMV 01, AMV 02, AMV-H 01, AMV-H 02
Installation Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring which requires no tools for
mounting. The ring should be tightened by hand.
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Each actuator is supplied with the connecting
cable for the controller.
Wiring
AMV/AMV-H 01, AMV/AMV-H 02 - 24V
AMV/AMV-H 01, AMV/AMV-H 02 - 230V
Disposal The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
Commissioning All actuators are factory tested prior to shipment.
The factory setting of the spindle is the fully
stem up position because of easier mechanical
connection of actuator on valve.
Important: Uninstalled actuator will operated
properly only in stem down direction!
If uninstalled actuator is tested than use Allen key
size 4 mm (or knob for AMV-H version) in order to
drive actuator on it's top position.
2 VD.JC.M2.02 © Danfoss 08/05 SIBC