Daikin RYYQ8U7Y1B*, RYYQ10U7Y1B*, RYYQ12U7Y1B*, RYYQ14U7Y1B*, RYYQ16U7Y1B* Installer reference guide

...
Installer and user reference guide
VRV IV+ heat pump
RYYQ8U7Y1B* RYYQ10U7Y1B* RYYQ12U7Y1B* RYYQ14U7Y1B* RYYQ16U7Y1B* RYYQ18U7Y1B* RYYQ20U7Y1B*
RYMQ8U7Y1B* RYMQ10U7Y1B* RYMQ12U7Y1B* RYMQ14U7Y1B* RYMQ16U7Y1B* RYMQ18U7Y1B* RYMQ20U7Y1B*
RXYQ8U7Y1B* RXYQ10U7Y1B* RXYQ12U7Y1B* RXYQ14U7Y1B* RXYQ16U7Y1B* RXYQ18U7Y1B* RXYQ20U7Y1B*
Table of contents
1 About the documentation 6
1.1 About this document ...................................................................................................................................................... 6
1.2 Meaning of warnings and symbols................................................................................................................................. 6
2 General safety precautions 8
2.1 For the installer............................................................................................................................................................... 8
2.1.1 General ........................................................................................................................................................... 8
2.1.2 Installation site ............................................................................................................................................... 9
2.1.3 Refrigerant — in case of R410A or R32.......................................................................................................... 9
2.1.4 Electrical ......................................................................................................................................................... 11
3 Specific installer safety instructions 14
For the user 17
4 User safety instructions 18
4.1 General............................................................................................................................................................................ 18
4.2 Instructions for safe operation ....................................................................................................................................... 19
5 About the system 22
5.1 System layout.................................................................................................................................................................. 22
6 User interface 24
7 Before operation 25
8 Operation 26
8.1 Operation range.............................................................................................................................................................. 26
8.2 Operating the system ..................................................................................................................................................... 26
8.2.1 About operating the system........................................................................................................................... 26
8.2.2 About cooling, heating, fan only, and automatic operation ......................................................................... 27
8.2.3 About the heating operation.......................................................................................................................... 27
8.2.4 To operate the system (WITHOUT cool/heat changeover remote control switch)...................................... 28
8.2.5 To operate the system (WITH cool/heat changeover remote control switch) ............................................. 28
8.3 Using the dry program.................................................................................................................................................... 29
8.3.1 About the dry program................................................................................................................................... 29
8.3.2 To use the dry program (WITHOUT cool/heat changeover remote control switch) .................................... 29
8.3.3 To use the dry program (WITH cool/heat changeover remote control switch) ........................................... 30
8.4 Adjusting the air flow direction ...................................................................................................................................... 30
8.4.1 About the air flow flap.................................................................................................................................... 30
8.5 Setting the master user interface................................................................................................................................... 31
8.5.1 About setting the master user interface........................................................................................................ 31
8.5.2 To designate the master user interface (VRV DX and Hydrobox) ................................................................. 32
8.6 About control systems .................................................................................................................................................... 32
9 Energy saving and optimum operation 34
9.1 Available main operation methods ................................................................................................................................ 34
9.2 Available comfort settings .............................................................................................................................................. 35
10 Maintenance and service 36
10.1 Maintenance after a long stop period............................................................................................................................ 36
10.2 Maintenance before a long stop period......................................................................................................................... 37
10.3 About the refrigerant...................................................................................................................................................... 37
10.4 After-sales service and warranty .................................................................................................................................... 37
10.4.1 Warranty period............................................................................................................................................. 37
10.4.2 Recommended maintenance and inspection................................................................................................ 38
10.4.3 Recommended maintenance and inspection cycles ..................................................................................... 38
10.4.4 Shortened maintenance and replacement cycles......................................................................................... 39
Installer and user reference guide
2
11 Troubleshooting 40
11.1 Error codes: Overview .................................................................................................................................................... 41
11.2 Symptoms that are NOT system malfunctions............................................................................................................... 44
11.2.1 Symptom: The system does not operate....................................................................................................... 44
11.2.2 Symptom: Cool/Heat cannot be changed over ............................................................................................. 44
11.2.3 Symptom: Fan operation is possible, but cooling and heating do not work ................................................ 44
11.2.4 Symptom: The fan speed does not correspond to the setting...................................................................... 44
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
11.2.5 Symptom: The fan direction does not correspond to the setting................................................................. 44
11.2.6 Symptom: White mist comes out of a unit (Indoor unit) .............................................................................. 45
11.2.7 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)........................................................ 45
11.2.8 Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few minutes.......... 45
11.2.9 Symptom: Noise of air conditioners (Indoor unit)......................................................................................... 45
11.2.10 Symptom: Noise of air conditioners (Indoor unit, outdoor unit) .................................................................. 45
11.2.11 Symptom: Noise of air conditioners (Outdoor unit)...................................................................................... 45
11.2.12 Symptom: Dust comes out of the unit........................................................................................................... 46
11.2.13 Symptom: The units can give off odours ....................................................................................................... 46
11.2.14 Symptom: The outdoor unit fan does not spin.............................................................................................. 46
11.2.15 Symptom: The display shows "88"................................................................................................................. 46
11.2.16 Symptom: The compressor in the outdoor unit does not stop after a short heating operation ................. 46
11.2.17 Symptom: The inside of an outdoor unit is warm even when the unit has stopped.................................... 46
11.2.18 Symptom: Hot air can be felt when the indoor unit is stopped.................................................................... 46
12 Relocation 47
13 Disposal 48
14 Technical data 49
14.1 Information requirements for Eco Design...................................................................................................................... 49
For the installer 50
15 About the box 51
15.1 About LOOP BY DAIKIN ................................................................................................................................................... 51
15.2 Overview: About the box ................................................................................................................................................ 51
15.3 To unpack the outdoor unit ............................................................................................................................................ 52
15.4 To remove the accessories from the outdoor unit ........................................................................................................ 53
15.5 Accessory pipes: Diameters ............................................................................................................................................ 53
15.6 To remove the transportation stay ................................................................................................................................ 54
16 About the units and options 55
16.1 Overview: About the units and options.......................................................................................................................... 55
16.2 Identification label: Outdoor unit ................................................................................................................................... 55
16.3 About the outdoor unit................................................................................................................................................... 56
16.4 System layout .................................................................................................................................................................. 56
16.5 Combining units and options .......................................................................................................................................... 57
16.5.1 About combining units and options............................................................................................................... 57
16.5.2 Possible combinations of indoor units........................................................................................................... 57
16.5.3 Possible combinations of outdoor units ........................................................................................................ 58
16.5.4 Possible options for the outdoor unit............................................................................................................ 59
17 Unit installation 61
17.1 Preparing the installation site......................................................................................................................................... 61
17.1.1 Installation site requirements of the outdoor unit........................................................................................ 61
17.1.2 Additional installation site requirements of the outdoor unit in cold climates............................................ 63
17.1.3 Securing safety against refrigerant leaks....................................................................................................... 64
17.2 Opening the unit ............................................................................................................................................................. 66
17.2.1 About opening the units................................................................................................................................. 66
17.2.2 To open the outdoor unit............................................................................................................................... 66
17.2.3 To open the electrical component box of the outdoor unit ......................................................................... 67
17.3 Mounting the outdoor unit............................................................................................................................................. 68
17.3.1 To provide the installation structure ............................................................................................................. 68
18 Piping installation 70
18.1 Preparing refrigerant piping ........................................................................................................................................... 70
18.1.1 Refrigerant piping requirements.................................................................................................................... 70
18.1.2 Refrigerant piping insulation.......................................................................................................................... 71
18.1.3 To select the piping size ................................................................................................................................. 71
18.1.4 To select refrigerant branch kits.................................................................................................................... 74
18.1.5 About the piping length.................................................................................................................................. 76
18.1.6 Piping length: VRV DX only............................................................................................................................. 76
18.1.7 Piping length: VRV DX and Hydrobox............................................................................................................. 80
18.1.8 Piping length: VRV DX and RA DX................................................................................................................... 81
18.1.9 Multiple outdoor units: Possible layouts....................................................................................................... 82
18.2 Connecting the refrigerant piping .................................................................................................................................. 83
18.2.1 About connecting the refrigerant piping....................................................................................................... 83
18.2.2 Precautions when connecting the refrigerant piping.................................................................................... 84
18.2.3 Multiple outdoor units: Knockout holes........................................................................................................ 85
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
3
18.2.4 To route the refrigerant piping...................................................................................................................... 85
18.2.5 To connect the refrigerant piping to the outdoor unit ................................................................................. 86
18.2.6 To connect the multi connection piping kit................................................................................................... 86
18.2.7 To connect the refrigerant branching kit....................................................................................................... 87
18.2.8 To protect against contamination.................................................................................................................. 87
18.2.9 To braze the pipe end..................................................................................................................................... 88
18.2.10 Using the stop valve and service port............................................................................................................ 89
18.2.11 To remove the spun pipes.............................................................................................................................. 91
18.3 Checking the refrigerant piping ...................................................................................................................................... 92
18.3.1 About checking the refrigerant piping........................................................................................................... 92
18.3.2 Checking refrigerant piping: General guidelines ........................................................................................... 93
18.3.3 Checking refrigerant piping: Setup ................................................................................................................ 94
18.3.4 To perform a leak test.................................................................................................................................... 94
18.3.5 To perform vacuum drying............................................................................................................................. 95
18.3.6 To insulate the refrigerant piping .................................................................................................................. 96
18.4 Charging refrigerant........................................................................................................................................................ 96
18.4.1 Precautions when charging refrigerant ......................................................................................................... 96
18.4.2 About charging refrigerant............................................................................................................................. 97
18.4.3 To determine the additional refrigerant amount.......................................................................................... 98
18.4.4 To charge refrigerant: Flow chart .................................................................................................................. 101
18.4.5 To charge refrigerant...................................................................................................................................... 103
18.4.6 Step 6a: To automatically charge refrigerant................................................................................................ 106
18.4.7 Step 6b: To manually charge refrigerant....................................................................................................... 107
18.4.8 Error codes when charging refrigerant.......................................................................................................... 108
18.4.9 Checks after charging refrigerant .................................................................................................................. 109
18.4.10 To fix the fluorinated greenhouse gases label............................................................................................... 109
19 Electrical installation 110
19.1 About connecting the electrical wiring .......................................................................................................................... 110
19.1.1 Precautions when connecting the electrical wiring....................................................................................... 110
19.1.2 Field wiring: Overview.................................................................................................................................... 112
19.1.3 About the electrical wiring............................................................................................................................. 112
19.1.4 Guidelines when knocking out knockout holes............................................................................................. 113
19.1.5 About electrical compliance........................................................................................................................... 114
19.1.6 Safety device requirements ........................................................................................................................... 115
19.2 To route and fix the transmission wiring........................................................................................................................ 117
19.3 To connect the transmission wiring ............................................................................................................................... 118
19.4 To finish the transmission wiring.................................................................................................................................... 119
19.5 To route and fix the power supply ................................................................................................................................. 119
19.6 To connect the power supply ......................................................................................................................................... 120
19.7 To check the insulation resistance of the compressor .................................................................................................. 121
20 Configuration 122
20.1 Overview: Configuration ................................................................................................................................................. 122
20.2 Making field settings ....................................................................................................................................................... 122
20.2.1 About making field settings............................................................................................................................ 122
20.2.2 Field setting components............................................................................................................................... 124
20.2.3 To access the field setting components......................................................................................................... 124
20.2.4 To access mode 1 or 2.................................................................................................................................... 125
20.2.5 To use mode 1................................................................................................................................................ 126
20.2.6 To use mode 2................................................................................................................................................ 126
20.2.7 Mode 1: Monitoring settings ......................................................................................................................... 127
20.2.8 Mode 2: Field settings.................................................................................................................................... 130
20.2.9 To connect the PC configurator to the outdoor unit..................................................................................... 137
20.3 Energy saving and optimum operation .......................................................................................................................... 137
20.3.1 Available main operation methods................................................................................................................ 138
20.3.2 Available comfort settings.............................................................................................................................. 139
20.3.3 Example: Automatic mode during cooling..................................................................................................... 141
20.3.4 Example: Automatic mode during heating.................................................................................................... 142
20.4 Using the leak detection function .................................................................................................................................. 143
20.4.1 About automatic leak detection .................................................................................................................... 143
20.4.2 To manually perform a leak detection........................................................................................................... 144
Installer and user reference guide
4
21 Commissioning 146
21.1 Overview: Commissioning .............................................................................................................................................. 146
21.2 Precautions when commissioning .................................................................................................................................. 146
21.3 Checklist before commissioning ..................................................................................................................................... 147
21.4 About the test run........................................................................................................................................................... 148
21.5 To perform a test run...................................................................................................................................................... 149
21.6 Correcting after abnormal completion of the test run .................................................................................................. 150
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
21.7 Operating the unit........................................................................................................................................................... 151
22 Hand-over to the user 152
23 Maintenance and service 153
23.1 Maintenance safety precautions .................................................................................................................................... 153
23.1.1 To prevent electrical hazards......................................................................................................................... 153
23.2 About service mode operation ....................................................................................................................................... 154
23.2.1 To use vacuum mode ..................................................................................................................................... 154
23.2.2 To recover refrigerant.................................................................................................................................... 154
24 Troubleshooting 156
24.1 Solving problems based on error codes ......................................................................................................................... 156
24.2 Error codes: Overview .................................................................................................................................................... 156
25 Disposal 162
26 Technical data 163
26.1 Service space: Outdoor unit ........................................................................................................................................... 163
26.2 Piping diagram: Outdoor unit ......................................................................................................................................... 165
26.3 Wiring diagram: Outdoor unit ........................................................................................................................................ 169
27 Glossary 175
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
5
1 | About the documentation

1 About the documentation

In this chapter

1.1 About this document.............................................................................................................................................................. 6
1.2 Meaning of warnings and symbols......................................................................................................................................... 6

1.1 About this document

Target audience
Authorised installers + end users
Documentation set
This document is part of a documentation set. The complete set consists of:
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the outdoor unit)
Outdoor unit installation and operation manual:
- Installation and operation instructions
- Format: Paper (in the box of the outdoor unit)
Installer and user reference guide:
- Preparation of the installation, reference data,…
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).

1.2 Meaning of warnings and symbols

Installer and user reference guide
6
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
DANGER
Indicates a situation that results in death or serious injury.
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
1 | About the documentation
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbols used in the documentation:
Symbol Explanation
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
Installer and user reference guide
7
2 | General safety precautions

2 General safety precautions

In this chapter

2.1 For the installer....................................................................................................................................................................... 8

2.1 For the installer

2.1.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
2.1.1 General ................................................................................................................................................................... 8
2.1.2 Installation site ....................................................................................................................................................... 9
2.1.3 Refrigerant — in case of R410A or R32 ................................................................................................................. 9
2.1.4 Electrical ................................................................................................................................................................. 11
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
Installer and user reference guide
8
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
2 | General safety precautions
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.

2.1.2 Installation site

Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.

2.1.3 Refrigerant — in case of R410A or R32

If applicable. See the installation manual or installer reference guide of your application for more information.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
Installer and user reference guide
9
2 | General safety precautions
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self­combustion and explosion of the compressor because of air going into the operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
Installer and user reference guide
10
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
Charge the liquid refrigerant as follows:
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
2 | General safety precautions
If Then
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.

2.1.4 Electrical

DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
11
2 | General safety precautions
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Installer and user reference guide
12
Install power cables at least 1 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 m may not be sufficient.
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
2 | General safety precautions
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
13
3 | Specific installer safety instructions

3 Specific installer safety instructions

Always observe the following safety instructions and regulations.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
CAUTION
Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF BURNING/SCALDING
DANGER: RISK OF ELECTROCUTION
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
Installer and user reference guide
14
CAUTION
Do not vent gases into the atmosphere.
WARNING
Any gas or oil remaining inside the stop valve may blow off the spun piping.
If these instructions are NOT followed correctly it may result in property damage or personal injury, which may be serious depending on the circumstances.
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
3 | Specific installer safety instructions
WARNING
NEVER remove the spun piping by brazing.
Any gas or oil remaining inside the stop valve may blow off the spun piping.
WARNING
ONLY use R410A as refrigerant. Other substances may cause explosions and
accidents.
R410A contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 2087.5. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
CAUTION
Do NOT push or place redundant cable length in the unit.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
WARNING
ALWAYS use multicore cable for power supply cables.
Installer and user reference guide
15
3 | Specific installer safety instructions
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
CAUTION
Do NOT perform the test operation while working on the indoor units.
When performing the test operation, NOT only the outdoor unit, but the connected indoor unit will operate as well. Working on an indoor unit while performing a test operation is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.
Installer and user reference guide
16
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10

For the user

For the user
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
17
4 | User safety instructions

4 User safety instructions

Always observe the following safety instructions and regulations.

In this chapter

4.1 General.................................................................................................................................................................................... 18
4.2 Instructions for safe operation............................................................................................................................................... 19

4.1 General

WARNING
If you are NOT sure how to operate the unit, contact your installer.
WARNING
Children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge can only use this appliance if they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
Children MUST NOT play with the appliance. Cleaning and user maintenance MUST NOT be carried out
by children without supervision.
WARNING
To prevent electrical shocks or fire:
Do NOT rinse the unit.Do NOT operate the unit with wet hands.Do NOT place any objects containing water on the unit.
CAUTION
Do NOT place any objects or equipment on top of the
unit.
Do NOT sit, climb or stand on the unit.
Installer and user reference guide
18
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
4 | User safety instructions
Units are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation.
Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.

4.2 Instructions for safe operation

CAUTION
NEVER touch the internal parts of the controller.Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
Installer and user reference guide
19
4 | User safety instructions
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
WARNING
Never touch the air outlet or the horizontal blades while the swing flap is in operation. Fingers may become caught or the unit may break down.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running. Be sure to turn off the main switch before executing any
maintenance task.
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
Installer and user reference guide
20
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
4 | User safety instructions
WARNING
Do NOT modify, disassemble, remove, reinstall or repair
the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely safe, non-toxic and non-combustible, but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters, gas cookers, etc. is present. Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation.
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
WARNING
The refrigerant in the system is safe and normally does not leak. If the refrigerant leaks in the room, contact with a fire of a burner, a heater or a cooker may result in a harmful gas.
Turn off any combustible heating devices, ventilate the room and contact the dealer where you purchased the unit.
Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired.
CAUTION
NEVER expose little children, plants or animals directly to the airflow.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
CAUTION
Do NOT touch the heat exchanger fins. These fins are sharp and could result in cutting injuries.
Installer and user reference guide
21
5 | About the system

5 About the system

The indoor unit part of VRV IV heat pump system can be used for heating/cooling applications. The type of indoor unit which can be used depends on the outdoor units series.
NOTICE
Do NOT use the system for other purposes. In order to avoid any quality deterioration, do NOT use the unit for cooling precision instruments, food, plants, animals, or works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available in technical engineering data and should be consulted. Contact your installer to receive more information and professional advice.
In general following type of indoor units can be connected to a VRV IV heat pump system (not exhaustive list, depending on outdoor unit model and indoor unit model combinations):
VRV direct expansion indoor units (air to air applications).
RA direct expansion indoor units (air to air applications).
Hydrobox (air to water applications): HXY080/125 only.
AHU (air to air applications): EKEXV-kit is required.
Aircurtain -Biddle- (air to air applications).
Combination of VRV direct expansion indoor units with RA direct expansion units is allowed.
Combination of VRV direct expansion indoor units with Hydrobox units is allowed.
Combination of VRV direct expansion indoor units with RA direct expansion unit(s) and Hydrobox unit(s) is NOT allowed.
In case AHU or Aircurtain are used, no Hydrobox may be connected.
Hydrobox only connection to VRV IV heat pump outdoor unit is not allowed.
Airhandling unit connection in pair to VRV IV heat pump outdoor unit is supported.
Airhandling unit connection in multi to VRV IV heat pump outdoor unit is supported, even combined with VRV direct expansion indoor unit(s).
Single (continuous heating/non-continuous heating) unit combinations: restrictions exist.
Multi (continuous heating/non-continuous heating) unit combinations: restrictions exist.

In this chapter

5.1 System layout

Installer and user reference guide
22
For more specifications, see technical engineering data.
5.1 System layout.......................................................................................................................................................................... 22
Your VRV IV heat pump series outdoor unit can be one of following models:
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
5 | About the system
g
c
g g
h
g g
c c cd
f
eb
i
a
Model Description
RYYQ Single continuous heating model.
RYMQ Multi continuous heating model.
RXYQ Single and multi non-continuous heating model.
Depending on the type of outdoor unit which is chosen, some functionality will or will not exist. It will be indicated throughout this operation manual when certain features have exclusive model rights or not.
a VRV IV Heat pump outdoor unit
b Refrigerant piping
c VRV direct expansion (DX) indoor unit d VRV LT Hydrobox (HXY080/125) e BP box (required to connect Residential Air (RA) or Sky Air (SA) direct expansion
(DX) indoor units)
f Residential Air (RA) direct expansion (DX) indoor units) g User interface (dedicated depending on indoor unit type) h User interface (wireless, dedicated depending on indoor unit type)
i Cool/heat changeover remote control switch
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
23
6 | User interface

6 User interface

CAUTION
NEVER touch the internal parts of the controller.Do NOT remove the front panel. Some parts inside are dangerous to touch and
appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
This operation manual offers a non-exhaustive overview of the main functions of the system.
Detailed information on required actions to achieve certain functions can be found in the dedicated installation and operation manual of the indoor unit.
Refer to the operation manual of the installed user interface.
Installer and user reference guide
24
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10

7 Before operation

WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
NOTICE
NEVER inspect or service the unit by yourself. Ask a qualified service person to perform this work.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
7 | Before operation
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
NOTICE
Be sure to turn ON the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor.
This operation manual is for the following systems with standard control. Before initiating operation, contact your dealer for the operation that corresponds to your system type and mark. If your installation has a customised control system, ask your dealer for the operation that corresponds to your system.
Operation modes (depending on indoor unit type):
Heating and cooling (air to air).
Fan only operation (air to air).
Heating and cooling (air to water).
Dedicated functions exist depending on the type of indoor unit, refer to dedicated installation/operation manual for more information.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
25
8 | Operation

8 Operation

In this chapter

8.1 Operation range...................................................................................................................................................................... 26
8.2 Operating the system ............................................................................................................................................................. 26
8.2.1 About operating the system .................................................................................................................................. 26
8.2.2 About cooling, heating, fan only, and automatic operation ................................................................................. 27
8.2.3 About the heating operation ................................................................................................................................. 27
8.2.4 To operate the system (WITHOUT cool/heat changeover remote control switch) ............................................. 28
8.2.5 To operate the system (WITH cool/heat changeover remote control switch)..................................................... 28
8.3 Using the dry program............................................................................................................................................................ 29
8.3.1 About the dry program .......................................................................................................................................... 29
8.3.2 To use the dry program (WITHOUT cool/heat changeover remote control switch)............................................ 29
8.3.3 To use the dry program (WITH cool/heat changeover remote control switch) ................................................... 30
8.4 Adjusting the air flow direction.............................................................................................................................................. 30
8.4.1 About the air flow flap ........................................................................................................................................... 30
8.5 Setting the master user interface .......................................................................................................................................... 31
8.5.1 About setting the master user interface ............................................................................................................... 31
8.5.2 To designate the master user interface (VRV DX and Hydrobox) ......................................................................... 32
8.6 About control systems............................................................................................................................................................ 32

8.1 Operation range

Use the system in the following temperature and humidity ranges for safe and effective operation.
Outdoor temperature –5~43°CDB –20~21°CDB
Indoor temperature 21~32°CDB
Indoor humidity ≤80%
(a)
Above operation range is only valid in case direct expansion indoor units are connected to the VRV IV system.
Special operation ranges are valid in case of using Hydrobox units or AHU. They can be found in the installation/operation manual of the dedicated unit. Latest information can be found in the technical engineering data.
Cooling Heating
–20~15.5°C WB
15~27°CDB
14~25°C WB
(a)
To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.

8.2 Operating the system

8.2.1 About operating the system

Installer and user reference guide
26
Operation procedure varies according to the combination of outdoor unit and
user interface.
To protect the unit, turn on the main power switch 6 hours before operation.
If the main power supply is turned off during operation, operation will restart
automatically after the power turns back on again.
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10

8.2.2 About cooling, heating, fan only, and automatic operation

Changeover cannot be made with a user interface whose display shows
"change-over under centralised control" (refer to installation and operation manual of the user interface).
When the display "change-over under centralised control" flashes, refer to
"About setting the master user interface"[431].
The fan may keep on running for about 1 minute after the heating operation
stops.
The air flow rate may adjust itself depending on the room temperature or the fan
may stop immediately. This is not a malfunction.

8.2.3 About the heating operation

It may take longer to reach the set temperature for general heating operation than for cooling operation.
The following operation is performed in order to prevent the heating capacity from dropping or cold air from blowing.
Defrost operation
8 | Operation
In heating operation, freezing of the outdoor unit's air cooled coil increases over time, restricting the energy transfer to the outdoor unit's coil. Heating capability decreases and the system needs to go into defrost operation to be able to remove frost from the outdoor unit’s coil. During defrost operation the heating capacity on the indoor unit side will temporarily drop until defrosting is completed. After defrosting, the unit will regain its full heating capacity.
If Then
RYYQ or RYMQ outdoor unit is installed
The indoor unit will continue heating operation at a reduced level during defrost operation. It will guarantee a decent comfort level indoor. A heat storage element in the outdoor unit will provide the energy to de-ice the outdoor unit's air cooled coil during defrost operation.
RXYQ outdoor unit is installed
The indoor unit will stop fan operation, the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil.
The indoor unit will indicate defrost operation on the display .
Hot start
In order to prevent cold air from blowing out of an indoor unit at the start of heating operation, the indoor fan is automatically stopped. The display of the user interface shows . It may take some time before the fan starts. This is not a malfunction.
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
Installer and user reference guide
27
8 | Operation
a
b

8.2.4 To operate the system (WITHOUT cool/heat changeover remote control switch)

INFORMATION
The heating capacity drops when the outside temperature falls. If this happens,
use another heating device together with the unit. (When using together with appliances that produce open fire, ventilate the room constantly). Do not place appliances that produce open fire in places exposed to the air flow from the unit or under the unit.
It takes some time to heat up the room from the time the unit is started since the
unit uses a hot-air circulating system to heat the entire room.
If the hot air rises to the ceiling, leaving the area above the floor cold, we
recommend that you use the circulator (the indoor fan for circulating air). Contact your dealer for details.
1 Press the operation mode selector button on the user interface several times
and select the operation mode of your choice.
Cooling operation
Heating operation
Fan only operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system starts operating.

8.2.5 To operate the system (WITH cool/heat changeover remote control switch)

Overview of the changeover remote control switch
a FAN ONLY/AIR CONDITIONING SELECTOR
SWITCH
Set the switch to for fan only operation or to
for heating or cooling operation.
b COOL/HEAT CHANGEOVER SWITCH
Set the switch to for cooling or to for heating
Note: In case a cool/heat changeover remote control switch is used, the position of DIP switch 1 (DS1-1) on the main PCB needs to be switched to the ON position.
To start
1 Select operation mode with the cool/heat changeover switch as follows:
Installer and user reference guide
28
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10
8 | Operation
1
1
1
1
1
Cooling operation
Heating operation
Fan only operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system starts operating.
To stop
3 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops operating.
NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.
To adjust
For programming temperature, fan speed and air flow direction refer to the operation manual of the user interface.

8.3 Using the dry program

8.3.1 About the dry program

The function of this program is to decrease the humidity in your room with
minimal temperature decrease (minimal room cooling).
The micro computer automatically determines temperature and fan speed
(cannot be set by the user interface).
The system does not go into operation if the room temperature is low (<20°C).

8.3.2 To use the dry program (WITHOUT cool/heat changeover remote control switch)

To start
1 Press the operation mode selector button on the user interface several times
and select (program dry operation).
2 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system starts operating.
3 Press the air flow direction adjust button (only for double-flow, multi-flow,
RYYQ+RYMQ+RXYQ8~20U7Y1B VRV IV+ heat pump 4P546228-1B – 2020.10
corner, ceiling-suspended and wall-mounted). Refer to "8.4 Adjusting the air
flow direction"[430] for details.
Installer and user reference guide
29
8 | Operation
1
1

8.3.3 To use the dry program (WITH cool/heat changeover remote control switch)

To stop
4 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops operating.
NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.
To start
1 Select cooling operation mode with the cool/heat changeover remote control
switch.
2 Press the operation mode selector button on the user interface several times
and select (program dry operation).
3 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system starts operating.
4 Press the air flow direction adjust button (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted). Refer to "8.4 Adjusting the air
flow direction"[430] for details.
To stop
5 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops operating.
NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

8.4 Adjusting the air flow direction

Refer to the operation manual of the user interface.

8.4.1 About the air flow flap

Installer and user reference guide
30
Double flow+multi-flow units
Corner units
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1B – 2020.10