Daikin HXY080A7V1B user guide manual

Page 1
INSTALLATION AND
OPERATION MANUAL
HXY080A7V1B HXY125A7V1B
System indoor unit
Page 2
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
CE - ∆HΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ
CE - DECLARAÇÃO-DE-CONFORMIDADE
CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OVERENSSTEMMELSESERKLÆRING
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE - PROHLÁŠENÍ-O-SHODĚ
CE - IZJAVA-O-USKLAĐENOSTI
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE - DEKLARACJA-ZGODNOŚCI
CE - DECLARAŢIE-DE-CONFORMITATE
CE - IZJAVA O SKLADNOSTI
CE - VASTAVUSDEKLARATSIOON
CE - ДЕКЛАРАЦИЯ-ЗА-ϹЪОТВЕТСТВИЕ
CE - ATITIKTIES-DEKLARACIJA
CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - VYHLÁSENIE-ZHODY
CE - UYUMLULUK-BİLDİRİSİ
01
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
02
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
daß sie gemäß unseren Anweisungen eingesetzt werden:03sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:04conform de volgende norm(en) of één of meer andere bindende documenten zjn, op voorwaarde dat ze worden gebru kt overeenkomstig
onze nstructies:05están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean ut lizados de acuerdo con
nuestras instrucciones:06sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità a le
nostre istruzioni:07είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονι σμών, υπό την προϋπόθεση ότι χρησιμοποιούνται σύμφωνα
με τ ς οδηγίες μας:
08
estão em conform dade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:09соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
инструкциям:10overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold t l vore
instrukser:11respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
förutsättning att användning sker i överensstämmelse med våra instruktoner:
12
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
disse brukes i henhold til våre instrukser:13vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
mukaisesti:14za předpokladu, že jsou využívány v souladu s našmi pokyny, odpovídají následujícím normám nebo normativním dokumentům:15u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
16
megfelelnek az a ábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:17spełniają wymogi następujących norm i nnych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
instrukcjami:
18
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
conformitate cu instrucţiunile noastre:
19
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:20on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt me e juhend tele:21съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
инструкции:
22
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:23tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:24sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym( ) dokumentom(am ), za predpokladu, že sa používajú v súlade
s našim návodom:25ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
01
Directives, as amended.02Direktiven, gemäß Änderung.
03
Directives, telles que modifiées.04Richtlijnen, zoals geamendeerd.05Directivas, según lo enmendado.06Direttive, come da modifica.07Οδηγιών, όπως έχουν τροποποιηθεί.08Directivas, conforme alteração em.09Директив со всеми поправками.
10
Direktiver, med senere ændringer.11Direktiv, med företagna ändringar.12Direktiver, med foretatte endringer.13Direktiivej ä, sellaisina ku n ne ovat muutettuina.14v platném znění.15Smjernice, kako je izmijenjeno.16irányelv(ek) és módosításaik rendelkezéseit
.
17
z późniejszymi poprawkami.18Directivelor, cu amendamentele respective.
19
D rektive z vsemi spremembami.20D rektiivid koos muudatustega.21Директиви, с техните изменения.22D rektyvose su papildymais.23D rektīvās un to papildinājumos.24Smernice, v platnom znení.25Deǧiştirilmiş halleriyle Yönetmelikler.
01
following the provis ons of:02gemäß den Vorschriften der:03conformément aux stipulations des:04overeenkomstig de bepalingen van:05siguiendo las disposiciones de:06secondo le prescrizioni per:07με τήρηση των διατάξεων των:08de acordo com o previsto em:09в соответствии с положениями:
10
under iagttagelse af bestemmelserne i:11enligt villkoren i:12gitt i henhold til bestemmelsene i:13noudattaen määräyks ä:14za dodržení ustanovení předpisu:15prema odredbama:16követi a(z):17zgodn e z postanow eniami Dyrektyw:18în urma prevederilor:
19
ob upoštevanju določb:20vastavalt nõuetele:21следвайки клаузите на:22la kantis nuostatų, pateik amų:
23
evērojot prasības, kas noteiktas:
24
održiavajúc ustanovenia:25bunun koşullarına uygun olarak:
01 Note *
as set out in
<A>
and judged positively by
<B>
according to the
Certificate <C>
.
02 Hinweis *
wie in
<A>
aufgeführt und von
<B>
positiv beurtei t
gemäß
Zertifikat <C>
.
03 Remarque *
tel que défini dans
<A>
et évalué positivement par
<B>
conformément au
Certificat <C>
.
04 Bemerk *
zoals vermeld in
<A>
en pos tief beoordeeld door
<B>
overeenkomstig
Certificaat <C>
.
05 Nota *
como se establece en
<A>
y es valorado
positivamente por
<B>
de acuerdo con el
Certificado <C>
.
06 Nota *
delineato nel
<A>
e giudicato pos tivamente
da
<B>
secondo il
Certificato <C>
.
07 Σημείωση *
όπως καθορίζεται στο
<A>
και κρίνεται θετικά από
το
<B>
σύμφωνα με το
Πιστοποιητικό <C>
.
08 Nota *
tal como estabelec do em
<A>
e com o parecer
positivo de
<B>
de acordo com o
Certificado <C>
.
09 Примечание *
как указано в
<A>
и в соответствии
с полож ительным решением
<B>
согласно
Свидетельству <C>
.
10 Bemærk *
som anført i
<A>
og pos tivt vurderet af
<B>
i henhold til
Certifikat <C>
.
11 Information *
enligt
<A>
och godkänts av
<B>
enligt
Certifikatet <C>
.
12 Merk *
som det fremkommer i
<A>
og gjennom pos tiv
bedømmelse av
<B>
ifølge
Sertifikat <C>
.
13 Huom *
jotka on esitetty asiakirjassa
<A>
ja jotka
<B>
on
hyväksynyt
Sertifikaatin <C>
mukaisesti.
14 Poznámka *
jak bylo uvedeno v
<A>
a pozitivně zjištěno
<B>
v souladu s
osvědčením <C>
.
15 Napomena *
kako je izloženo u
<A>
i pozitivno ocijenjeno
od strane
<B>
prema
Certifikatu <C>
.
16 Megjegyzés *
a(z)
<A>
alapján, a(z)
<B>
igazolta a megfelelést,
a(z)
<C> tanúsítvány
szer nt.
17 Uwaga *
zgodnie z dokumentac ą
<A>
, pozytywną opinią
<B>
i
Świadectwem <C>
.
18 Notă *
aşa cum este stabilit în
<A>
şi apreciat pozitiv
de
<B>
în conformitate cu
Certificatul <C>
.
19 Opomba *
kot je določeno v
<A>
n odobreno s strani
<B>
v skladu s
certifikatom <C>
.
20 Märkus *
nagu on näidatud dokumendis
<A>
ja heaks
kiidetud
<B>
järgi vastavalt
sertifikaadile <C>
.
21 Забележка
* както е изложено в
<A>
и оценено положително
от
<B>
съгласно
Сертификата <C>
.
22 Pastaba *
kaip nustatyta
<A>
ir kaip teigiamai nuspręsta
<B>
pagal
Sertifikatą <C>
.
23 Piezīmes *
kā norādīts
<A>
un atbilstoši
<B>
pozitīvajam
vērtējumam saskaņā ar
sertifikātu <C>
.
24 Poznámka *
ako bolo uvedené v
<A>
a poz tívne zistené
<B>
vsúlade s
osvedčením <C>
.
25 Not * <A>
’da belirtildiği gibi ve
<C> Sertifikasına
göre
<B>
tarafından olumlu olarak değerlendir ldiği gibi.
<A> DAIKIN.TCF.025E11/07-2012
<B> DEKRA (NB0344)
<C> 2082543.0551-QUA/EMC
01
a
declares under its sole responsibil ty that the equipment to which this declaration relates:
02
d
erklärt auf seine alle nge Verantwortung daß d e Ausrüstung für die diese Erklärung bestimmt ist:
03
f
déclare sous sa seule responsabilité que l équipement visé par la présente déclaration:
04
l
verklaart hierbij op eigen exclus eve verantwoordel jkheid dat de apparatuur waarop deze verklaring betrekking heeft:
05
e
declara bajo su única responsabilidad que el equipo al que hace referencia la declaración:
06
i
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
07
g
δηλώνει με αποκλειστική της ευθύνη ότι ο εξοπλισμός στον οποίο αναφ έρεται η παρούσα δήλωση:
08
p
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
09
u
заявляет, исключительно под свою ответственность, что
оборудование,
к котором
у
относи тся настоящее заявление:
10
q
erklærer under eneansvarlig, at udstyret, som er omfattet af denne erklæring:
11
s
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklarat on innebär att:
12
n
erklærer et fu lstendig ansvar for at det utstyr som berøres av denne deklarasjon innebærer at:
13
j
ilmoittaa yksinomaan omalla vastuullaan, että tämän lmoituksen tarkoittamat laitteet:
14
c
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
15
y
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
16
h
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
17
m
deklaruje na własną i wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
18
r
declară pe proprie răspundere că ech pamentele la care se referă această declaraţie:
19
o
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
20
x
kinnitab oma täiel kul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
21
b
декларира на своя отговорност, че оборудването, за коeто се отнася тази декларация:
22
t
visiška savo atsakomybe skelbia, kad įranga, kuriai takoma ši deklaracija:
23
v
ar pilnu atb ldību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attecas šī deklarācija:
24
k
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
25
w
tamamen kendi sorumluluǧunda olmak üzere bu bildir nin ilgili olduǧu donanımının aşaǧıdaki gibi olduǧunu beyan eder:
EN60335-2-40,
3P327592-1
Jean-Pierre Beuselinck
Director
Ostend, 3rd of September 2012
01 **
Daikin Europe N.V. is authorised to compile the Technical Construction File.
02 **
Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen.
03 **
Daikin Europe N.V. est autorisé à compiler le Dossier de Construction Technique.
04 **
Daikin Europe N.V. is bevoegd om het Technisch Constructiedossier samen te stellen.
05 **
Daikin Europe N.V. está autorizado a complar el Archivo de Construccón Técnica.
06 **
Daikin Europe N.V. è autorizzata a redigere il File Tecnico di Costruz one.
07 **
Η Daikin Europe N.V. είναι εξουσιοδοτημένη να συντάξει τον Τε χν ικ ό φάκελο κατασκευή ς.
08 **
A Daikin Europe N.V. está autorizada a compilar a documentação técnica de fabrico.
09 **
Компания Daikin Europe N.V. уполномочена составить Комплект технической документации.
10 **
Daikin Europe N.V. er autoriseret til at udarbejde de tekniske konstruktionsdata.
11 **
Daikin Europe N.V. är bemyndigade att sammanställa den tekniska konstruktionsfilen.
12 **
Daikin Europe N.V. har tillatelse til å kompilere den Tekniske konstruksjonsfilen.
13 **
Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan.
14 **
Společnost Da kin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce.
15 **
Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji.
16 **
A Daikin Europe N.V. jogosult a műszaki konstrukc ós dokumentáció összeállítására.
17 **
Daikin Europe N.V. ma upoważnienie do zbieran a i opracowywania dokumentacji konstrukcyjnej.
18 **
Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie.
19 **
Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehn čno mapo.
20 **
Daikin Europe N.V. on volitatud koostama tehnilist dokumentats ooni.
21 **
Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
22 **
Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
23 **
Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
24 **
Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technckej konštrukcie.
25 **
Daikin Europe N.V. Tekn k Yapı Dosyasını derlemeye yetkil dir.
Machinery 2006/42/EC
Electromagne ic Compatibility 2004/108/EC
**
*
HXY080A7V1B, HXY125A7V1B,
Page 3
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
1
Content Page
1. About the documentation...........................................................2
1.1. About this document ......................................................... 2
1.2. Scope of the manual ......................................................... 2
1.3. Documentation set ............................................................2
2. General safety precautions........................................................ 2
2.1. For the user.......................................................................2
2.2. For the installer ................................................................. 2
2.2.1. General................................................................... 2
2.2.2. Installation site........................................................ 3
2.2.3. Refrigerant .............................................................. 3
2.2.4. Water ...................................................................... 3
2.2.5. Electrical ................................................................. 3
2.2.6. Meaning of used items............................................ 4
3. About the box............................................................................. 4
3.1. Indoor unit ......................................................................... 4
3.1.1. To unpack the indoor unit........................................ 4
3.1.2. To remove the accessories from the indoor unit ..... 4
4. About the units and options .......................................................5
4.1. General information .......................................................... 5
4.1.1. Identification label: Indoor unit ................................ 5
4.2. Possible combinations of units and options ......................5
4.2.1. List of options for indoor unit................................... 5
4.2.2. Poss ble combinations of indoor unit
and outdoor unit......................................................6
5. Application guidelines ................................................................ 6
5.1. Overview: Application guidelines ...................................... 6
5.2. Setting up the space heating/cooling system....................6
5.3. Using an auxiliary heat source.......................................... 7
6. Preparation ................................................................................7
6.1. Preparing installation site.................................................. 7
6.1.1. Installation site requirements of the indoor unit ......7
6.2. Preparing water circuit ...................................................... 8
6.2.1. Selection of the type of heat emitters ..................... 8
6.2.2. Water circuit requirements......................................9
6.2.3. Formula to calculate the expansion vessel
pre-pressure ........................................................... 9
6.2.4. To check the water volume .....................................9
6.2.5. Changing the pre-pressure of the expansion
vessel.................................................................... 10
6.2.6. To check the water volume: Examples ................. 10
6.3. Preparing electrical wiring............................................... 11
6.3.1. About preparing electrical wiring........................... 11
6.3.2. Overview of electrical connections
on the indoor unit .................................................. 11
7. Installation................................................................................ 12
7.1. Mounting the indoor unit ................................................. 12
7.1.1. To install the indoor unit ........................................ 12
7.2. Connecting the water piping ........................................... 13
7.2.1. To connect the water piping .................................. 13
7.3. Connecting the electrical wiring ...................................... 14
7.3.1. Precautions on electrical wiring work.................... 14
7.4. Finishing the indoor unit installation ................................ 16
7.4.1. To fix the user interface cover to the indoor unit ... 16
7.4.2. To close the indoor unit.........................................16
8. Commissioning ........................................................................ 17
8.2. Final air purging .............................................................. 17
8.3. Field settings................................................................... 17
8.3.1. Procedure ............................................................. 17
8.3.2. Detailed description ..............................................18
8.4. Field setting list for Installation Manual ........................... 22
8.5. Final check and test run .................................................. 24
8.5.1. Final check............................................................ 24
8.5.2. System test run.....................................................24
8.5.3. Indoor unit individual test run................................24
8.6. Service and maintenance ............................................... 25
8.6.1. Maintenance activities .......................................... 25
8.6.2. Malfunction codes list ........................................... 25
8.6.3. Important information regarding
the refrigerant used............................................... 25
9. Installing the optional EKBUHAA(6V3/6W1) heater kit............26
10. Hand-over to the user .............................................................. 26
11. Operation of the unit ................................................................ 27
11.1. Introduction .....................................................................27
11.1.1. General information .............................................. 27
11.2. Quick start-up of the unit.................................................27
11.2.1. Space cooling/heating operation...........................27
11.3. Operating the unit ........................................................... 27
11.3.1. Operating the user interface ................................. 27
11.3.2. Name and function of buttons and icons...............28
11.3.3. Setting up the controller........................................ 29
11.3.4. Space cooling operation (c) ................................. 29
11.3.5. Space heating operation (h)................................. 29
11.3.6. Other operation modes.........................................31
11.3.7. Temperature read-out mode ................................. 31
11.3.8. Schedule timer operation ...................................... 32
11.3.9. Space heating ....................................................... 32
11.3.10. Programming and consulting the schedule timer..33
11.3.11. Operating the optional demand PCB .................... 37
11.3.12. Operating the optional user interface.................... 37
11.4. Field settings...................................................................37
11.4.1. Procedure ............................................................. 37
11.5. Field setting list for Operation Manual............................. 38
12. Maintenance ............................................................................ 40
12.1. Important information regarding the refrigerant used...... 40
12.2. Maintenance activities..................................................... 40
13. Troubleshooting ....................................................................... 40
13.1. Malfunction codes list...................................................... 40
14. Technical Data .........................................................................40
14.1. Piping diagram ................................................................ 40
14.2. Wiring diagram................................................................41
14.3. Electrical components box .............................................. 42
14.4. Operation range HXY(080/125) ......................................42
14.5. ESP curve ....................................................................... 42
14.6. Technical specifications table .......................................... 43
14.7. Electrical specifications table .......................................... 43
15. Disposal requirements ............................................................. 43
The English text is the original instruction. Other languages are translations of the original instructions.
HXY080A7V1B HXY125A7V1B
VRV IV System indoor unit
Installation and
operation manual
Page 4
Installation and operation manual
2
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
1. About the documentation
1.1. About this document
This document is an installation manual. It is intended for authorized installers of this product. It describes the procedures for installing, commissioning and maintaining the unit, and it will provide help if problems occur. Carefully read the relevant parts of the manual.
This document is also an operation manual. It is intended for the installer and the user of this product. It descr bes how to operate and maintain the unit, and it will provide help if problems occur. Carefully read the relevant parts of the manual.
1.2. Scope of the manual
This manual does NOT include the selection procedure and the water system design procedure. Only some precautions and tips and tricks about the design of the water circuit are given in a separate chapter of this manual.
Once the selection is done and the water system is designed, this manual describes the procedures for handling, installing and connecting the HXY080/125 units. This manual has been prepared to ensure adequate maintenance of the unit, and it will provide help if problems occur.
1.3. Documentation set
This document is part of a documentation set. The complete set consists of:
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
2. General safety precautions
2.1. For the user
If you are not sure how to operate the unit, contact your installer.The appliance is not intended for use by persons, including
children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children must be supervised to ensure that they do not play with the product.
Units are marked with the following symbol:
This means that electrical and electronic products may not be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
2.2. For the installer
2.2.1. General
If you are not sure how to install or operate the unit, contact your dealer.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an accessible place at the product:
Instructions for shutting down the system in case of an
emergency.
Name and address of fire department, police and hospital.Name, address and day and night telephone numbers for
obtaining service.
In Europe, EN378 provides the necessary guidance for this logbook.
Document Contains Format
Indoor unit installation/opera ion manual
Installation and operator instructions
Indoor unit installation/opera ion manual
Outdoor unit installation manual
See info delivered with outdoor unit.
CAUTION
Do NOT rinse the unit. This may cause electric shocks or fire.
NOTICE
Do NOT place any objects or equipment on top of the
unit.
Do NOT sit, climb or stand on the unit.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions descr bed in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
DANGER: RISK OF BURNING
Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
Page 5
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
3
2.2.2. Installation site
Provide sufficient space around the unit for servicing and air
circulation.
Make sure the installation site withstands the unit’s weight and
vibration.
Make sure the area is well ventilated.Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon f bre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
2.2.3. Refrigerant
Only use phosphoric acid deoxidised seamless copper with
annealed temper grade.
2.2.4. Water
2.2.5. Electrical
Install power cables at least 1 meter away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 meter may not be sufficient.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are not subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
Toxic gas may be produced if refrigerant gas comes
into contact with fire.
WARNING
Always recover the refrigerants. Do NOT release them directly into the environment. Use a refrigerant reclaim unit to evacuate the installation.
NOTICE
Make sure water quality complies with EU directive 98/83 EC.
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage must be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If not factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, shall be installed in the fixed wiring.
WARNING
Only use copper wires.All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the
unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
Make sure to install the required fuses or circuit
breakers.
Make sure to install an earth leakage protector.
Failure to do so may cause electric shock or fire.
WARNING
After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the
unit.
Page 6
Installation and operation manual
4
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
2.2.6. Meaning of used items
3. About the box
At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier’s claims agent.
Bring the packed unit as close as poss ble to its final installation
position to prevent damage during transport.
3.1. Indoor unit
3.1.1. To unpack the indoor unit
a Installation/operation manual
3.1.2. To remove the accessories from the indoor unit
The installation/operation manual indoor unit is located in the upper part of the box. Follow the procedure below to remove the other accessories.
1 Unfix front panel. 2 Tilt the bottom side of the front panel upwards and remove it.
Dealer:
Sales distributor for the product.
Authorized installer:
Technical skilled person who is qualified to install the product.
User:
Person who is owner of the product and/or operates the product.
Applicable legislation:
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Service company:
Qualified company which can perform or coordinate the required service to the product.
Installation manual:
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application, explaining how to operate it.
Accessories:
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment:
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field supply:
Equipment not made by Da kin that can be combined with the product according to the instructions in the accompanying documentation.
INFORMATION
Do NOT throw away the upper cardboard cover. On the inside of the cardboard cover, the installation pattern is printed.
WARNING
Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face danger of death by suffocation.
a
21
Page 7
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
5
3 Remove the accessories.
a HXY(080/125) manual b User interface kit: user interface, 4 fixing screws, 2 plugs c Shut-off valve d User interface cover e 2 fixing screws front panel
f Bottomplate g 4 fixing screws bottom plate h Top pl a te
4. About the units and options
4.1. General information
This installation manual concerns VRV IV indoor unit air to water inverter heat pump units of the Daikin HXY080/125 series.
These units are intended for indoor installation and aimed for commercial and public buildings.
The unit is designed for wall mounted installation.
HXY080/125 units have a heating capacity of 9 kW/14 kW, cooling capacity of 8.2 KW/12.5 kW.
The indoor units are designed to work at indoor ambient temperatures from 5°C to 30°C.
During heating operation, the unit can heat up water to temperatures of 25°C to 45°C, cooling operation of 5°C to 20°C.
The units are designed for indoor installation (outdoor temperatures: cooling 10°C to 43°C, heating: -20°C to 24°C) (for details see technical data book).
4.1. Identification
4.1.1. Identification label: Indoor unit
Location
Model identification
Modelname: HXY080A7V1B, HXY125A7V1B
4.2. Possible combinations of units and options
4.2.1. List of options for indoor unit
User interface (EKRUAHT)
The user interface is delivered as an accessory with the unit. An additional user interface is optionally available.
The additional user interface can be connected to have both:
Control close to the indoor unit.Room thermostat functionality in the principal space to be
heated.
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room thermostat.
Demand PCB (EKRP1AHTA)
An optional EKRP1AHTA demand PCB can be connected to the indoor unit. This PCB is needed when an external room thermostat is installed and provides the communication with the indoor unit.
Refer to the demand PCB installation manual for further details.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit and "7.3.5. To connect the electrical wiring on the
indoor unit" on page 14.
Heat pump convector (FWXV)
An optional FWXV convector for heating/cooling operation can be connected to this indoor unit.
Refer to the heat pump convector installation manual for further details.
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.
d
b c
h
e
a
1x
bcd
2x 1x
g
4x
f
1x
e
1x
2x
3
Code Description
HHydro Box
X VRV connection
Y
Reversible applications (cooling + heating)
080 Capacity class (approx.):
080 kW x 10 cooling capacity125 kW x 10 cooling capacity
A7 Series
V1 Voltage 1 P~, 220-240 V, 50 Hz
B European Market
NOTICE
An additional 230 V AC power supply is required for the EKRTR1 room thermostat.
Page 8
Installation and operation manual
6
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Drain pan kit (EKHBDPCA2)
The drain pan is required to drain accumulated condensation from the indoor unit. It is required during low temperature cooling operation of the indoor unit and when the leaving water temperature is <18°C.
For installation of this option into the indoor unit, refer to the installation manual delivered with this option kit.
Heater kit (EKBUH)
The heater kit option can be installed to assist the heat pump during heating operation or to provide primary heating during emergency situations
(1)
.
4.2.2. Possible combinations of indoor unit and outdoor unit
5. Application guidelines
5.1. Overview: Application guidelines
The purpose of the application guidelines is to give a glance of the possibilities of the Daikin heat pump system.
This chapter contains applications guidelines for:
Setting up the space heating/cooling systemSetting up an auxiliary heat source for space heating
5.2. Setting up the space heating/cooling system
The Da kin heat pump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
How many rooms are heated (or cooled) by the Daikin
heat pump system?
Which heat emitter types are used in each room and what is
their design leaving water temperature?
Once the space heating/cooling requirements are clear, Daikin recommends to follow the setup guidelines below.
5.2.1. Single room
Under floor heating or heat pump convector – Wired room thermostat
Setup
A Main leaving water temperature zone B One single room C One single room a Outdoor VRV IV heat pump b VRV Direct Expansion (DX) Indoor unit cassette c HXY(080/125) d Optional EKRUAHT user interface (master) e Refrigerant piping
f Water piping g Floor heating loop h Fan coil unit
i Bypass valve (field supply)
j User interface (slave)
The under floor heating or heat pump connection is directly
connected to the indoor unit.
The room temperature is controlled by the user interface, which
is used as room thermostat. Possible installations:
User interface (standard equipment) installed in the room and
used as room thermostat
User interface (standard equipment) installed at the indoor
unit and used for control close to the indoor unit + user interface (optional equipment EKRUAHT) installed in the room and used as room thermostat
Benefits
Cost effective. You do NOT need an additional external room
thermostat.
Highest comfort and efficiency. The smart room thermostat
functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation). This results in:
Stable room temperature matching the desired temperature
(higher comfort)
Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
Lowest possible leaving water temperature (higher efficiency)
Easy. You can easily set the desired room temperature via the
user interface:
For your daily needs, you can use preset values and
schedules.
To deviate from your daily needs, you can temporarily
overrule the preset values and schedules.
(1) More information can be found in the manual of the heater kit and on page
"9. Installing the optional EKBUHAA(6V3/6W1) heater kit" on page 26
of this manual.
Outdoor unit
Indoor unit RYYQ8~20 RYMQ RXYQ
HXY080A7V1B O X X
HXY125A7V1B O X X
O = allowed
X = not allowed
INFORMATION
For detailed information, refer to the VRV IV heat pump combination table in Technical Data. Combinations are explained depending on the system layout of the VRV IV heat pump series.
NOTICE
The illustrations in the application guidelines are
meant for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
For more information about the configuration settings
to optimize heat pump operation, see the configuration chapter.
C
B
A
d
B
A
d
b
e
c
f f
ii
j
a
g
h
Page 9
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
7
Under floor heating or heat pump convectors – External room thermostat
Setup
A Main leaving water temperature zone B One single room C One single room
a Outdoor VRV IV heat pump b VRV Direct Expansion (DX) Indoor unit cassette c HXY(080/125) d External room hermostat e Refrigerant piping
f Water piping g Floor hea ing loop h Fan coil unit
i Bypass valve (field supply)
The under floor heating or heat pump convectors are directly
connected to the indoor unit.
The room temperature is controlled by the external room
thermostat (demand PCB is needed for this option).
5.3. Using an auxiliary heat source
a Outdoor VRV IV heat pump b Floor hea ing loop (field supply) c Collector (field supply) d Auxiliary heat source (field supply) e Shut-off valve
f Aquastat valve (field supply) g Bypass valve (field supply)
Make sure the return water to the heat pump does NOT exceed
45°C. To do so:
Set the desired water temperature via the auxiliary boiler
controller to maximum 45°C.
Install an aquastat valve in the return water flow of the
heat pump.
Set the aquastat valve to close above 45°C and to open
below 45°C.
Install non-return valves.Make sure to only have one expansion vessel in the water
circuit. An expansion vessel is already premounted in the indoor unit.
Alternative option EKBUH can be considered. The heater kit option will provide additional capacity in case of heat pump capacity shortage. See "9. Installing the optional EKBUHAA(6V3/6W1) heater
kit" on page 26 for details.
6. Preparation
6.1. Preparing installation site
Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Choose the installation location with sufficient place for carrying the unit in and out of the site.
6.1.1. Installation site requirements of the indoor unit
Select an installation site that meets the following requirements: All piping lengths and distances have been taken into
consideration (for requirements of piping length for the refrigerant piping, refer to the outdoor unit installation manual):
Mind the measurement guidelines:
NOTICE
Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
C
B
A
d
B
A
d
b
e
c
f f
ii
a
g
h
g
a
cbd
e
f
e
WARNING
Be sure to provide for adequate measures in order to prevent that the unit is used as a shelter by small animals
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean and clear.
Requirement Value
Maximum refrigerant piping length between indoor unit and outdoor unit.
<135 m
(a)
(a) Refer to VRV IV piping lenght restrictions to judge the complete VRV system
integration.
Maximum height difference between indoor unit and outdoor unit.
<15 m
(a)
NOTICE
Mind the following spacing installation guidelines.
Page 10
Installation and operation manual
8
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
The space around the unit allows for sufficient air circulation.There is no danger of fire due to leakage of inflammable gas.The equipment is not intended for use in a potentially explosive
atmosphere.
Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
Be sure that sufficient precautions are taken, in accordance with
the applicable legislation, in case of refrigerant leakage.
When installing the unit in a small room, take measures in order
to keep the refrigerant concentration from exceeding allowable safety limits in the event of a refrigerant leak.
Do not climb, sit or stand on top of the unit.Do not place any objects or equipment on top of the unit (top
plate).
Do NOT install the unit in places such as: Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or water to leak.
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom and the like), so that the operation noise will cause no trouble. Note: If the sound is measured under actual installation conditions, the measured value will be higher than the sound pressure level mentioned in Sound spectrum due to environmental noise and sound reflections.
The foundation must be strong enough to bear the weight of the
unit. Make sure, in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
In places with high humidity (max. RH=85%), for example a
bathroom.
In places where frost is possible. Ambient temperature around
the indoor unit should be >5°C.
The indoor unit is designed for indoor installation only and for
indoor ambient temperatures ranging 5~35°C in cooling mode and 5~30°C in heating mode.
6.2. Preparing water circuit
6.2.1. Selection of the type of heat emitters
The selection of the heat emitter is the choice of the end customer. The choice of the heat emitter will define the needed water temperature from the unit.
Based on the needed water temperature for the heat emitters, following range can be defined:
1 Low temperature (heating leaving water temperature range from
25°C to 40°C, cooling leaving water temperature range from 25°C to 18°C). Typical example: floor heating.
2 Medium temperature (leaving water temperature range from
40°C to 45°C), cooling leaving water temperature range from 12°C to 7°C. Typical example: low temperature radiators (heating) and convectors (heating and cooling).
Once the heat emitters are chosen, the capacity of these heat emitters should be defined and from this the dimensioning and position of the heat emitters in the different rooms should be decided.
An important parameter of the heat emitters is the temperature difference between entering water and leaving water.
This will define the water flow in the system.
Finally, the piping layout from the heat source to the different heat emitters needs to be drawn.
This will finally define following important parameters:
Minimal water volume in the system.Maximal water volume in the system.Minimal and maximal water flow in system.Maximal pressure drop in the system.
WARNING
Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.



  
(mm)
Page 11
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
9
6.2.2. Water circuit requirements
Use the indoor unit only in a closed water system.
Using the system in an open water system will lead to excessive corrosion.
Maximum water temperature is 45°C (heating) and mimimum
water temperature is 5°C (cooling).
The maximum water pressure is 3 bar.
Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
All installed piping and piping accessories (valve,
connections,…) must withstand the following temperatures.
a Outdoor unit (VRV IV heat pump) b Indoor unit HXY(080/125) c Heat exchanger dPump e Shut-off valve
f Motorised 2-way valve (field supply) g Collector
FCU1...3 Fan coil unit (op ional)
FHL1...3 Floor hea ing loop (optional)
T Room thermostat (optional)
Shut-off valves delivered with the unit should be installed so that
normal servicing can be accomplished without draining the system.
Make all water piping connections in accordance with the
applicable legislation and the outlook diagram that is delivered with the unit, respecting the water inlet and outlet.
Do NOT use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the unit.
Provide drain taps at all low points of the system in order to allow
complete drainage of the water circuit.
Provide a proper drain for the pressure relief valve to avoid
water coming into contact with electrical parts.
Provide air vents at all high points of the system, which must
also be easily accessible for servicing. An automatic air purge is provided in the indoor unit. Check that the air purge is NOT tightened too much, so that automatic release of air in the water circuit is possible.
Only use materials that are compat ble with water used in the
system and with the materials used in the indoor unit.
Check that all components in the field piping can withstand the
water pressure and water temperature.
When using non-brass metallic piping, insulate the brass and
non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Never use Zn-coated parts in the water circuit. Because the
unit's internal water circuit uses copper piping, excessive corrosion may occur.
Only use appropriate tooling to handle brass, which is a soft
material. If NOT, pipes will get damaged.
Select the water piping diameter in relation to the required water
flow and the available external static pressure of the pump. See
"14. Technical Data" on page 40 for the external static pressure
curves of the indoor unit.
You can find the minimum required water flow for the indoor unit
operation in the following table. When the water flow is lower, flow malfunction A6 will be displayed and the indoor unit will be stopped.
It is strongly recommended to install an additional filter on the
heating water circuit. Especially to remove metallic particles from the field heating piping, it is advised to use a magnetic or cyclone filter, which can remove small particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump system.
If air or dust gets into the water circuit, problems may occur. To
prevent this:
Only use clean pipes
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall, to
prevent dust and/or particles entering the pipe.
Use a decent thread sealant to seal connections.
For safety reasons, it is NOT allowed to add any kind of glycol to
the water circuit.
The installation must be in compliance with the applicable
legislation and may require additional hygienic installation measures.
In accordance with the applicable
legislation, it may
be
necessary to install thermostatic mixing valves.
6.2.3. Formula to calculate the expansion vessel pre-pressure
The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)
6.2.4. To check the water volume
The indoor unit has an expansion vessel of 10 litre with a factory set pre-pressure of 1 bar.
To make sure that the unit operates properly:
You must check the minimum and maximum water volume.You might need to adjust the pre-pressure of the expansion
vessel.
INFORMATION
The following illustration is an example and may NOT match your system layout.
M
T
FCU2
FCU3
FHL1
FHL2
FHL3
abc
d e
ef
g
g
g
g
65°C
Model Minimum water flow (l/min)
HXY080A7V1B 15 HXY125A7V1B 15
Page 12
Installation and operation manual
10
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Minimum water volume
Check that the total water volume in the installation is minimum 20 liter, the internal water volume of the indoor unit NOT included.
a Outdoor unit (VRV IV heat pump) b Indoor unit HXY(080/125) c Heat exchanger dPump eShut-off valve
f Collector (field supply) g By-pass valve (field supply)
FHL1...3 Floor hea ing loop (field supply)
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control loop FHL1...3
(field supply)
Maximum water volume
Use the following graph to determine the maximum water volume for the calculated pre-pressure.
a Pre-pressure (bar) b Maximum water volume (l)
Example: Maximum water volume and expansion vessel pre­pressure
6.2.5. Changing the pre-pressure of the expansion vessel
When changing the default pre-pressure of the expansion vessel (1 bar) is required, take following guidelines into account:
Only use dry nitrogen to set the expansion vessel pre-pressure.Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder valve of the expansion vessel.
a Schräder valve
6.2.6. To check the water volume: Examples
Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100 l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l.
Actions: Because the total water volume (350 l) is more than the default
water volume (280 l), the pre-pressure must be decreased.
The required pre-pressure is:
Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar=0.3 bar.
The corresponding maximum water volume at 0.3 bar is 410 l.
(See the graph in the chapter above).
Because 350 l is lower than 410 l, the expansion vessel is
appropriate for the installation.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be required
NOTICE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
FHL1
FHL2
FHL3
M1
T1
M2T2M3
T3
fecba g
de
0
.3
0
.5
1
1
.5
2
2
.5
10050
0
20
150 200 250 300 350 400 450
a
b
Installation height difference
(a)
(a) Thi s is the height difference (m) between the highest point of the water circuit an d
the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0 m.
Water volume 280 l >280 l
7 m No pre-pressure
adjustment is required.
Do he following:
• Decrease the pre-pressure.
• Check if he water volume does NOT exceed the maximum allowed water volume.
>7 m Do the following:
• Increase the pre-pressure.
• Check if the water volume does NOT exceed the maximum allowed water volume.
The expansion vessel of the indoor unit is too small for the installation.
NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
a
Page 13
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
11
6.3. Preparing electrical wiring
6.3.1. About preparing electrical wiring
6.3.2. Overview of electrical connections on the indoor unit
The following illustration shows the required field wiring.
a Dedicated power supply for the indoor unit b HXY(080/125)
c User interface d Optional user interface e Optional heater kit
f Dedicated power supply for the external backup heater kit g Optional room hermostat h 230 VAC power supply
WARNING
Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with the piping or sharp edges, particularly on the high-pressure side
Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
All wiring must be performed by an authorized
electrician and must comply with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on the site and all electrical
construction must comply with the applicable legislation.
WARNING
The indoor unit should have a dedicated power
supply.
The optional heater kit (EKBUH) should have a
dedicated power supply.
a
b
1
a Normal power supply bFuse 1 Power supply for indoor unit
INFORMATION
The following illustration is an example and may NOT
match your system layout.
For details see "14.2. Wiring diagram" on page 41.
Item Description Wiring
Maximum running current
High voltage wiring (High voltage bundle)
1 Indoor unit power supply 2+GND
(a)
(a) Refer to name plate on the indoor unit.
2 malfunction output 2 0.3 A
(b)
(b) Minimum cable section 0.75 mm².
3 Operation ON/OFF output 2 0.3 A
(b)
4 Cooling/heating output 2 0.3 A
(b)
5 Heater kit step 1/2 output 3
(b)
6 External heater kit power supply For details refer to the
installation manual provided with the option kit.
Low voltage wiring (Low voltage bundle)
7 Indoor/outdoor transmission 2
(c)
(c) Cable section between 0.75 mm² and 1.25 mm².
8 User interface transmission 2
(c)
9 External heater kit safety 2
(b)
10 Thermostat input 1 2
(b)
11 Thermostat input 2 2
(b)
12 Operation ON signal 2
(b)
13 Operation OFF signal 2
(b)
14 230 V AC power supply (only for
wireless room thermostat EKRTR1)
2<1A
6
b
a
e
f
d
c
10
11
8
2
3
4
5
9
17
g
h
14
12
13
Page 14
Installation and operation manual
12
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
7. Installation
Before installing, first read the instructions of previous chapter.
7.1. Mounting the indoor unit
7.1.1. To install the indoor unit 1 Remove the accessories from the unit, see instructions in
chapter "3.1.2. To remove the accessories from the indoor unit"
on page 4.
2 Install indoor unit as follows.
7.1.2. To install the drainpan kit
If a drain pan kit (EKHBDPCA2) is required, install it before connecting the refrigerant and water pipes and the electrical wiring.
To install, see the installation manual of the drain pan kit.
7.1.3. To connect the refrigerant piping to the outdoor unit
a Refrigerant liquid connection Ø9.52 mm b Refrigerant gas connection Ø15.9 mm
1 Connect the liquid piping from the outdoor unit to the refrigerant
liquid connection of the indoor unit.
2 Connect the gas piping from the outdoor unit to the refrigerant
gas connection of the indoor unit.
INFORMATION
Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe the EN378 is the applicable standard that shall be used.
WARNING
Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face danger of death by suffocation.
CAUTION
Do NOT grasp the piping to lift the indoor unit.
NOTICE
Please install following the spacing installation guidelines as described in "6.1.1. Installation site requirements of the
indoor unit" on page 7.
60kg
1
2
4x
1
2
3
3
2x
43 5 6
87
2x
9
2x
10
11
1
2
2
2
4x
12 13
b
a
Page 15
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
13
For details concerning vacuuming and operating the unit during vacuuming, see installation manual of outdoor unit.
For details concerning piping sizes and refnet selection, see installation manual of the outdoor unit.
7.2. Connecting the water piping
7.2.1. To connect the water piping
To facilitate service and maintenance, 2 shut-off valves are provided. Mount the valves on the water inlet and on the water outlet. Mind their position. Orientation of the integrated drain valves is important for servicing.
1 Install the shut-off valves on the water pipes.
a Water inlet b Water outlet
2 Screw the indoor unit nuts on the shut-off valves. 3 Connect the field piping on the shut-off valves.
7.2.2. To install the bottom plate and connect safety valve drain hose
7.2.3. To fill the water circuit 1 Connect the water supply hose to the drain and fill valve.
2 Open the drain and fill valve. 3 Make sure that the automatic air purge valve is open (at least 2
turns).
4 Fill the circuit with water until the manometer indicates a
pressure of ±2.0 bar.
5 Purge as much air as poss ble from the water circuit.
6 Close the drain and fill valve. 7 Disconnect the water supply hose from the drain and fill valve.
7.2.4. To insulate the water piping
The piping in the complete water circuit must be insulated to prevent condensation during cooling operation and reduce capacity losses during heating and cooling operations.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the sealing materials should be at least 20 mm to prevent condensation on the surface of the sealing.
NOTICE
Do NOT put power on the unit before vacuuming is completed. In case this happened, refer to the instructions in the installation manual of the outdoor unit to avoid dirt, air or nitrogen to be trapped in the piping.
NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
NOTICE
It is recommended to install a pressure reducing valve on the cold water inlet in accordance with the applicable legislation.
ab
1 2
4x
3
NOTICE
Air in the water circuit can cause malfunctioning of the
flow switch. During filling, it may not be poss ble to remove all the air from the circuit. Remaining air will be removed through the automatic air purge valves during the initial operating hours of the system. Additional filling with water afterwards may be required. Pump only operation in order to purge the air of the system is possible through field settings. Refer to field settings of [E-04] in the chapter "[E] Service mode" on
page 21 for further details.
The unit might dispose some excessive water through
the pressure relief valve.
Water quality must be accordingly to EU directive
98/83 EC.
NOTICE
The water pressure needle on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure shall remain above 1 bar to avoid air entering the circuit.
Page 16
Installation and operation manual
14
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
7.3. Connecting the electrical wiring
7.3.1. Precautions on electrical wiring work
7.3.2. System overview of field wiring
Field wiring consists out of power supply, indoor-outdoor communication (= transmission F1F2) wiring, wiring of the user interface (=P1P2), wiring for connection of options and field supply accessories.
7.3.3. Requirements
A power supply (refer to the table mentioned in "6.3.2. Overview of
electrical connections on the indoor unit" on page 11) must be
provided for connection of the unit. The power supply must be protected with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leakage protector in accordance with applicable legislation.
Selection and sizing of the wiring should be done in accordance with the applicable legislation based on the information mentioned in the table "6.3.2. Overview of electrical connections on the indoor unit" on
page 11.
7.3.4. To open the switch box cover
7.3.5. To connect the electrical wiring on the indoor unit
1 Wiring should enter the unit from the bottom. 2 Routing of the wiring inside the unit and switchbox should be as
follows:
WARNING: Electrical Installation
All field wiring and components must be installed by an installer and must comply with the applicable legislation.
NOTICE
Electrical wiring work recommendations.
To persons in charge of electrical wiring work.
Do not operate the unit until the refrigerant piping is complete. Running the unit before the piping is ready will break the compressor.
WARNING
A main switch or other means for disconnection,
having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with the applicable legislation.
Use only copper wires.All field wiring must be carried out in accordance with
the wiring diagram supplied with the unit and the instructions given below.
Never squeeze bundled cables and be sure that it
does not come in contact with the non-insulated piping and sharp edges. Be sure no external pressure is applied to the terminal connections.
Power supply wires must be attached securely.Be sure to establish an earth. Do not earth the unit to
a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Be sure to install an earth leakage protector in
accordance with the applicable legislation. Failure to do so may cause electric shock or fire.
Be sure to use a dedicated power circuit, never use a
power supply shared by another appliance.
Be sure to install the required fuses or circuit
breakers.
NOTICE
The equipment described in this manual may cause electronic noise generated from radio-frequency energy. The equipment complies to specifications that are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo
equipment, personal computers, etc....
In extreme circumstances you shall keep distances of 3m or more and use conduit tubes for power and transmission lines.
INFORMATION
More information about the legend and the location of the wiring diagram of the unit can be found in "14.2. Wiring
diagram" on page 41.
The Wiring diagram on the indoor unit is only for the indoor unit.
For the outdoor unit refer to the wiring diagram of the outdoor unit.
NOTICE
Check the table in "6.3.2. Overview of electrical
connections on the indoor unit" on page 11 to know which
wiring should be routed in the high voltage cable bundle and which wiring should be routed in the low voltage cable bundle.
4x
ab
Page 17
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
15
a Low voltage cable bundle (see "6.3.2. Overview of
electrical connections on the indoor unit" on page 11
b High voltage cable bundle (see "6.3.2. Overview of
electrical connections on the indoor unit" on page 11
c Earth connec ion d Op ional
3 Fix the cable with cable ties to the cable tie mountings to ensure
strain relief and to make sure that it does NOT come in contact with the piping and sharp edges.
7.3.6. To connect the user interface
The unit is equipped with a user interface offering a user-friendly way to set up, use and maintain the unit.
Before operating the user interface, follow this installation procedure.
Procedure
Remove the front part of the user interface
Insert a slotted screwdriver into the slots (1) in the rear part of the user interface, and remove the front part of the user interface.
Fixation of the user interface to the indoor unit
1 Fix the wallplate of the user interface to the frontplate of the unit.
For installation of the frontplate, see "7.4.1. To fix the user
interface cover to the indoor unit" on page 16.
2 Cut off a 2 wire conductor. 3 Connect the wires to the user interface as shown below.
From the rear
4 Reinstall the faceplate onto the wallplate.
First begin fitting from the clips at the bottom.
5 Remove the user interface cover from its hinge.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The wiring for connection is not included.
NOTICE
The user interface, delivered in a kit, has to be mounted indoors.
NOTICE
The PCB is mounted in the faceplate of the user interface.
Be careful NOT to damage it.
INFORMATION
For connection to the switchbox see "7.3.5. To connect the
electrical wiring on the indoor unit" on page 14.
X2MX1M
X801M
A4P
b a
c
d
1
NOTICE
Be careful NOT to distort the shape of the backside of the user interface by overtightening the mounting screws..
a
b
P1P
2
a Rear part of the user interface b Front part of he user interface
1
2
1
Page 18
Installation and operation manual
16
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Fixation of the user interface to the wall in case of installation as room thermostat
1 Cut off a 2 wire conductor. 2 Fix the wallplate of the user interface to the wall. 3 Connect the wires tot the user interface as shown below.
From the bottom
4 Reinstall the faceplate onto the wallplate.
First begin fitting from the clips at the bottom.
How to connect for multi unit
7.4. Finishing the indoor unit installation
7.4.1. To fix the user interface cover to the indoor unit 1 Make sure that the front panel is removed from the indoor unit.
See To open the indoor unit.
2 Plug the hinges into the backside of the front panel.
3 Plug the user interface cover into the hinges.
4 Mount the front panel to the indoor unit.
7.4.2. To close the indoor unit 1 Close the switch box cover. 2 Install the front panel as shown below.
NOTICE
Be careful NOT to distort the shape of the backside of the user interface by overtightening the mounting screws..
INFORMATION
If next to the standard remote controller the optional remote controller is installed as well:
Connect the electrical wires of both remote controllers
in the same way l ke descr bed above.
Select a master and a slave remote controller by
switching the SS1 selector switch.
Only the remote controller set as master can work as room thermostat.
INFORMATION
For multiple unit control, connect the remote controller to the unit as instructed above. For all other units to be controlled by this controller every next unit has to be connected as shown in the figure below (meaning: make a connection from P1 of the previous unit to P1 of the next unit, and make a connection from P2 of the previous unit to P2 of the next unit, and so on...).
Limitation: 16 indoor units
a
b
P1P
2
c
a Rear part of the user interface
b Front part of the user interface
c Use rippers to notch he part for
the wiring to pass through
1
S
M
PCB
SS1
S Slave M Master
P1 P1 P1P2
P1 P2
P2 P2
remote controller
NOTICE
When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 Nm.
NOTICE
Be careful NOT to pinch the wiring when attaching the frontplate to the unit.
2x
1
2
Page 19
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
17
8. Commissioning
8.1. Pre-operation checks
After the installation of the unit, check the following:
1 Field wiring
Make sure that the field wiring has been carried out according to the instructions descr bed in the chapter "6.3. Preparing
electrical wiring" on page 11, according to the wiring diagrams
and according to European and national regulations.
2 Fuses and protection devices
Check that the fuses and other locally installed protection devices are of the size and type specified in the chapter
"Electrical specifications table" on page 43. Make sure that
neither a fuse nor a protection device has been bypassed.
3 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
4 Internal wiring
Visually check the switch box and the inside of the unit on loose connections or damaged electrical components.
5 Installation
Check that the unit is properly installed, to avoid abnormal noises and vibrations when starting up the unit.
6 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
7 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak try to repair the leak (recovery, repair, and vacuuming needed). If it is impossible to repair by yourself, call your local dealer. Do not touch any refrigerant which has leaked out of refrigerant piping connections. This may result in frostbite.
8 Vacuuming/recovery and refrigerant charging
Refer to the outdoor unit manual for more details.
9 Water leak
Check the inside of the unit on water leakage. In case there is a water leakage try to repair the leak. If it is impossible to repair by yourself, close the water inlet and water outlet shut-off valves and call your local dealer.
10 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage must correspond to the voltage on the identification label of the unit.
11 Air purge valve
Make sure the air purge valve of the heat pump is open (at least 2 turns).
12 Shut-off valves
Make sure that the shut-off valves are correctly installed and fully open.
Once all checks are fulfilled, the unit must be closed, only then can the unit be powered on. When the power supply to the indoor unit is turned on, "88" is displayed on the user interface during its initialization, which might take up to 30 seconds. During this process the user interface can not be operated.
8.2. Final air purging
To get rid of all the air in the system, the pump should be operated.
Therefore, change the field setting [E-04] as explained in the chapter
"8.3. Field settings" on page 17. More details about setting "[E-04] Pump only operation (air purge function)" can be found on page 21.
8.3. Field settings
The indoor unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user demand. Therefore, a number of so called field settings are available. These field settings are access ble and programmable through the user interface on the indoor unit.
Each field setting is assigned a 3-digit number or code, for example [5-03], which is indicated on the user interface display. The first digit [5] indicates the 'first code' or field setting group. The second and third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given in the "8.4. Field
setting list for Installation Manual" on page 22. In this list we provided
2 columns to register the date and value of altered field settings at variance with the default value.
8.3.1. Procedure
To change one or more field settings, proceed as follows.
1 Press the z button for a minimum of 5 seconds to enter FIELD
SET MODE. The $ icon (3) will be displayed. The current selected field setting code is indicated ; (2), with the set value displayed to the right - (1).
2 Press the ébi button to select the appropriate field setting
first code.
3 Press the ébj button to select the appropriate field setting
second code.
4 Press the pfi button and pfj button to change
the set value of the select field setting.
5 Save the new value by pressing the pr button.
NOTICE
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable.
WARNING
Switch off the power supply before making any connections.
NOTICE
Operating the system with closed valves will damage the pump!
Page 20
Installation and operation manual
18
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
6 Repeat step 2 through 4 to change other field settings as
required.
7 When finished, press the z button to exit FIELD SET MODE
.
8.3.2. Detailed description
For a summary of all field settings refer to "8.4. Field setting list for
Installation Manual" on page 22.
[0] Remote control setup
[0-00] User permission level
The user interface can be programmed to make certain buttons and functions unavailable for the user. There are 2 permission levels defined. Both levels (level 2 and level 3) are basically the same, the only difference is that for level 3 no water temperature settings are possible (see table below).
By default no level is defined so all buttons and functions are operable. The actual permission level is determined by field setting. For permission level 2, set field setting [0-00] to 2, for permission level 3, set field setting [0-00] to 3. Once the field setting is set, the chosen permission level is not yet active. Enabling the selected permission level is done by simultaneously pressing buttons pi and pj immediately followed by simultaneously pressing buttons s and ba, and keeping all 4 buttons pressed for at least 5 seconds. Note that no indication on the user interface is given. After the procedure the blocked buttons will not be available anymore. Deactivating the selected permission level is done in the same way.
[0-01] Room temperature compensation value
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This can be used as countermeasure for thermistor tolerances or capacity shortage. The compensated temperature (= measured temperature plus compensation value) is then used for controlling the system and will be displayed in the temperature read-out mode. See also
"[9] Automatic temperature compensation" on page 21 for
compensation values for leaving water temperature.
[0-02] Setting not applicable[0-03] Status: defines whether the ON/OFF instruction can be
used in the schedule timer for space heating. Refer to the operation manual for details how to program the schedule timer. The schedule timer for space heating can be programmed in 2 different ways: based on the temperature set point (both leaving water temperature and room temperature) and based on the ON/OFF instruction.
In the following tables both methods on how to interpret the schedule timer are shown.
INFORMATION
Changes made to a specific field setting are only
stored when the pr button is pressed. Navigating to a new field setting code or pressing the z button will discard the change made.
The field settings are grouped by their field setting first
code.
For example, field settings [0-00]; [0-01]; [0-02]; [0-03]
are defined as "Group 0".
When different values are changed within the same
group, pressing the pr button will save all the values changed within this group.
Be aware of this when changing field settings within
the same group and pressing on the pr button.
INFORMATION
Before shipping, the set values have been set as
shown under "8.4. Field setting list for Installation
Manual" on page 22.
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit initializes itself.
NOTICE
When running through the field settings you may notice that there are some more field settings as there are mentioned in the "8.4. Field setting list for Installation
Manual" on page 22. These field settings are not appli-
cable and may not be changed!
Permission
level 2 level 3
Operation ON/OFF Operable Operable
Setting the leaving water temperature Operable
Setting the room temperature Operable Operable
Weather dependent set point operation ON/OFF
Operable
Setting the clock
Programming the schedule timer
Schedule timer operation ON/OFF Operable Operable
Field settings
malfunction code display Operable Operable
Test opera ion
INFORMATION
By default space heating based on temperature set point (method 1) is enabled, so only temperature shifts are possible (no ON/OFF instruction).
Method 1 Space heating based on temperature set point
(a)
(a) For leaving water temperature and/or room temperature
During opera ion During schedule timer operation the opera ion LED is lit
continuously.
When pushing
he y button
The schedule timer for space heating will stop and will not start again. The controller will be switched off (operation LED will stop working).
When pushing
he pr button
The schedule imer for space heating will be stopped and will not start again. The schedule timer icon will not be displayed anymore.
Page 21
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
19
Operation example: Schedule timer based on temperature set points.
When setback function (refer to "[2] Automatic setback function" on
page 19) is enabled, the setback operation will have priority over the
scheduled action in the schedule timer.
Operation example: Schedule timer based on ON/OFF instruction.
When setback function (refer to "[2] Automatic setback function" on
page 19) is enabled, the setback operation will have priority over the
scheduled action in the schedule timer if ON instruction is active. If OFF instruction is active this will have priority over the setback function. At any time the OFF instruction will have the highest priority.
[0-04] Status: defines whether the ON/OFF instruction can be
used in the schedule timer for cooling. Same as for [0-03] but for cooling schedule timer. For cooling, no setback function is available.
[1] Settings are not applicable
[2] Automatic setback function
Setback function provides the possibility to lower the room temperature. The setback function can for instance be activated during the night because the temperature demands during night and day are not the same.
[2-00] Status: defines whether the setback function is turned ON
(1) or OFF (0)
[2-01] Start time: time at which setback is started[2-02] Stop time: time at which setback is stopped
Setback can be configured for both room temperature control and leaving water temperature control.
1 Schedule imer 2 Setback function 3 When both setback function and schedule timer are enabled
A Setback function
t Time
T Temperature set point
Room temperature
Leaving water temperature
Method 2 Space heating based on ON/OFF instruction
During operation When the schedule timer switches space heating OFF,
the controller will be switched off (operation LED will stop working).
When pushing the y button
The schedule timer for space hea ing will stop (when active at hat moment) and will start again at he next scheduled ON function. The "last" programmed command overrules he "preceding" programmed command and will remain active un il the "next" programmed command occurs.
Example: imagine the actual time is 17:30 and actions are programmed at 13 00, 16:00 and 19:00. The "last" programmed command (16:00) overruled the "previous" programmed command (13:00) and will remain active until the "next" programmed command (19:00)
occurs. So in order to know the actual set ing, one should consult the last programmed command. It is clear that the "last" programmed command may date from the day before. Refer to the operation manual. The controller will be switched off (operation LED will stop working). However the schedule timer icon will stay displayed.
When pushing the pr button
The schedule timer for space heating will be stopped and will not start again. The schedule imer icon will not be displayed anymore.
T
t
6:30 9:00
16:00
0:30
19C 19C 19C
22C
21C
42C 42C 42C
45C
44C
42C
19C 19C 19C
22C
21C
42C 42C
45C
44C
0:30
1
T
t
18C
37C37C
18C
A
5:0023:00 5:0023:00
2
T
t
5:00 9:00
16:00
23:00
19C
18C
19C
22C
21C
40C
42C
45C
44C
40C
19C
18C
19C
22C
21C
42C
19C
19C
42C
19C
42C
19C19C19C
42C
45C
44C
6:30
3
37C37C
40C
40C
1 Schedule timer 2 Setback function 3 When both se back func ion and schedule timer are enabled A Setback function B ON/OFF instruction
t Time
T Temperature set point
Room temperature
Leaving water temperature
INFORMATION
By default the setback function is enabled.The setback function can be combined with the
automatic weather dependent set point operation.
Setback function is an automatic daily scheduled
function.
t
18C
40C40C
18C
A
5:0023:00 5:0023:00
2
B
t
9:00
16:00
19C 19C
22C
21C
42C 42C
45C
44C
19C 19C
22C
21C
42C 42C
45C
44C
1
OFF ONON
6:300:30
B
t
6:30 9:00
16:00
23:00
19C 19C
22C
21C
42C 42C
45C
44C
19C 19C
22C
21C
42C 42C
45C
44C
3
OFF ONON
18C
40C40C
18C
Page 22
Installation and operation manual
20
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Refer to "[5] Automatic setback" on page 20 for temperature set points.
[3] Weather dependent set point (Heating)
When weather dependent operation is active, the leaving water temperature is determined automatically depending on the outdoor temperature: colder outdoor temperatures will result in warmer water and vice versa. The unit has a floating set point. Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point.
During weather dependent operation, the user has the poss bility to shift up or down the target water temperature by a maximum of 5°C. This "Shift value" is the temperature difference between the temperature set point calculated by the controller and the real set point. E.g. a positive shift value means that the real temperature set point will be higher than the calculated set point.
It is advised to use the weather dependent set point because it adjusts the water temperature to the actual needs for space heating. It will prevent the unit from switching too much between thermo ON operation and thermo OFF operation when using the user interface room thermostat or external room thermostat.
[3-00] Low ambient temperature (Lo_A): low outdoor
temperature.
[3-01] High ambient temperature (Hi_A): high outdoor
temperature.
[3-02] Set point at low ambient temperature (Lo_Ti): the target
outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature (Lo_A). Note that the Lo_Ti value should be higher than Hi_Ti, as for colder outdoor temperatures (i.e. Lo_A) warmer water is required.
[3-03] Set point at high ambient temperature (Hi_Ti): the target
outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature (Hi_A). Note that the Hi_Ti value should be lower than Lo_Ti, as for warmer outdoor temperatures (i.e. Hi_A) less warm water suffices.
[4] Settings are not applicable
[5] Automatic setback
[5-00] Setting is not applicable.[5-01] Setting is not applicable.[5-02] Leaving water setback temperature.[5-03] Room setback temperature.[5-04] Setting is not applicable.
[6] Option setup
[6-01] External room thermostat.
If the optional external room thermostat is installed, its operation must be enabled by field setting. Default [6-01]=0, which means no external room thermostat is installed.
Set [6-01]=2 if the optional external room thermostat is
installed. The external room thermostat only gives an ON/OFF signal to the heat pump based on the room temperature.
Set [6-01]=1 in case a heating thermostat ON or cooling
thermostat ON function is required (when using optional EKRTWA or EKRT1). The processing of thermostat ON will depend on the system’s operation mode. Room thermostat input 1 = heating input, room thermostat input 2 = cooling
input. Because the external room thermostat does not give continuous feedback information to the heat pump, it is supplementary to the user interface room thermostat function. To have a good control of the system and avoiding frequent ON/OFF it is advised to use the automatic weather dependent set point operation. Room thermostat input 1 = operation ON (1)/OFF (0). Room thermostat input 2 = operation ON (1)/OFF (0). See "14.2. Wiring diagram" on page 41 for connection details.
The operation mode of the unit is subject in the master VRV DX indoor remote controller.
[6-02] Heater kit option.
To activate the heater kit as an option of the HXY(080/125) heat pump, change field setting [6-02]=1 (default value is "0"). From that moment on, the heat pump system will take the heater kit into account whilst deciding operation. When the heater is actually operating, the heater symbol is shown on the remote controller of the hydrobox. Refer to "9. Installing the optional
EKBUHAA(6V3/6W1) heater kit" on page 26.
[
6-03] Settin
g is not applicable.
[8] Option setup
[8-00] User interface temperature control.
[8-00]=0 the unit operates in leaving water temperature
control. This is the default setting. [8-00]=1 the unit operates in room temperature control. This
means that the user interface is used as room thermostat, so
the user interface can be placed in the living room to control
the room temperature.
[8-01] Setting is not applicable.
A Normal room temperature set point B Room setback temperature [5-03]
t Time
T Temperature
A Normal leaving water temperature set point B Leaving water setback temperature =A–[5-02]
t Time
T Temperature
T
t
Target water temperature
T
A
Ambient (outdoor) temperature
Shift value = Shift value
[2-01] [2-02]
A
B
T
t
21°C
18°C
[2-01] [2-02]
B
A
T
t
45°C
40°C
5°C [5-02]
Lo Ti
Lo A Hi A T
A
T
t
+ 05
00
– 05
Hi Ti
Shift value
INFORMATION
If by mistake the value of [3-03] is set higher than the value of [3-02], the value of [3-03] will always be used.
Page 23
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
21
[8-02] Emergency operation.
In case of emergency, heating can be provided by the heater kit, not by hydrobox. Emergency mode can be activated by setting [8-02]=1 (default value is "0"). Activating the emergency mode will stop the heat pump operation of the hydrobox. The pump of the indoor unit will be started, but heating itself is done by the heater kit. If there are no malfunction conditions in leaving or return water thermistors of the hydrobox, the heater kit can start to follow emergency operation.
[8-03] Setting is not applicable.[8-04] Freeze-up prevention.
The unit has a freeze-up prevention functionality for which 3 levels can be selected:
[8-04]=0 prevention level 0 (default: no prevention).[8-04]=1 prevention level 1.[8-04]=2 prevention level 2.
The freeze-up prevention is only active when the unit is in thermo OFF condition. If prevention level 1 is enabled, the freeze-up prevention will start if the outdoor ambient temperature <4°C and if leaving or return water temperature <7°C. For prevention level 2, the freeze-up prevention will start as soon as the ambient temperature <4°C. For both cases the pump will operate and if leaving or return water <5°C for 5 minutes the unit will start up to prevent too low temperatures.
[9] Automatic temperature compensation
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This can be used as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then used for controlling the system and will be displayed in the temperature read-out mode.
[9-00] Leaving water temperature compensation value for
heating operation.
[9-01] Leaving water thermistor auto corrective function.
When enabled, this function will take into account the outdoor ambient conditions and correct the measured value which will be used for the logic. Eg. when the ambient temperature is high during cooling mode, the logic will correct the measured value of the leaving water thermistor to a lower value to take into account influence of high ambient temperatures in the measurement.
[9-02] Setting is not applicable.[9-03] Leaving water temperature compensation value for
cooling operation.
[9-04] Setting not applicable.
[A] Option setup
[A-00] Setting is not applicable.[A-01] Setting is not applicable.[A-02] Pump target T setting (heating).
Depending on the systems emitter type, the T over the emitter can be modified within the range 3~8°C. Default value is 5°C for fancoil units or floor heating loops.
[A-03] Leaving water temperature overshoot/undershoot value
This setting makes it poss ble to set the allowable overshoot (heating)/undershoot (cooling) when operating the unit during leaving water control.
[A-04] Setting is not applicable.
[b] Settings are not applicable
[C] Leaving water temperature limits
[C-00] Maximum leaving water set point in heating operation.
[C-01] Minimum lea
v
ing water set point in heating operation.
[C-02] Maximum leaving water set point in cooling operation.[C-03] Minimum leaving water set point in cooling operation.
If a leaving water temperature of 5°C is wanted, this limit needs to be adjusted. Be aware this can have an impact towards the efficiency of your system.
[C-04] Setting is not applicable.
[d] Settings are not applicable
[E] Service mode
[E-00] Setting is not applicable.[E-01] Setting is not applicable.[E-02] Setting is not applicable.[E-03] Setting is not applicable.[E-04] Pump only operation (air purge function)
When installing and commisioning the unit it is very important to get all air out of the water circuit. Through this field setting the pump can be operated without actual operation of the unit. By doing so this will enhance the air removal from the unit.
[E-04]=0 normal operation of the unit (default)[E-04]=1 low pump speed operation[E-04]=2 high pump speed operation
If you select [E-04]=1 or 2, the unit will activate the air
purging function. This function is a helpful feature to get all air
removed out of the system (as well in space heating as
space cooling).
[F] Option setup
[F-00] Pump target ∆T setting (cooling).
Depending on the systems emitter type, the T over the emitter can be modified within the range 3~8°C. Default value is 5°C for fancoil units or floor heating loops.
[F-01] Setting is not applicable.[F-02] Setting is not applicable.[F-03] Setting is not applicable.[F-04] Setting is not applicable.
[E-04]=1 or 2
Pump operation for 40 minutes
Page 24
Installation and operation manual
22
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
8.4. Field setting list for Installation Manual
First code
Second code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level.
22~31—
01 Room temperature compensa ion value.
0 –5~5 0 5 °C
02 Not applicable. Do not change he default value.
1———
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0.
1 (ON) 0/1
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0.
1 (ON) 0/1
1 Settings are not applicable
00 Not applicable. Do not change he default value.
1———
01 Not applicable. Do not change he default value.
1:00
02 Not applicable. Do not change he default value.
0———
03 Not applicable. Do not change he default value.
15 00
2 Automatic setback function
00 Status: se back operation.
1 (ON) 0/1
01 Setback operation start time.
23 00 0 00~23:00 1:00 hour
02 Setback operation stop time.
5:00 0 00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A).
–10 –20~5 1 °C
01 High ambient temperature (Hi_A).
15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti).
40 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti).
25 25~80 1 °C
4 Settings are not applicable
00 Not applicable. Do not change he default value.
1———
01 Not applicable. Do not change he default value.
Fri
02 Not applicable. Do not change he default value.
23 00
5 Automatic setback and disinfection set point
00 Not applicable. Do not change he default value.
70
01 Not applicable. Do not change he default value.
10
02 Leaving water setback temperature.
50~101°C
03 Room setback temperature.
18 17~23 1 °C
04 Not applicable. Do not change he default value.
0———
6 Option setup
01 External room thermostat installed.
0 (OFF) 0/2
02 Heater kit option.
0 (OFF) 0/1
03 Not applicable. Do not change he default value.
0———
8 Option setup
00 User interface temperature control.
0 (OFF) 0/1
01 Not applicable. Do not change he default value.
1———
02 Emergency opera ion.
00/1——
03 Not applicable. Do not change he default value.
1———
04 Status: freeze-up prevention.
0 0~2 1
9 Automatic temperature compensation
00 Leaving water temperature compensation value
(heating).
0 –2~2 0 2 °C
01 Leaving water thermistor auto corrective function.
1 (ON) 0/1 1
02 Not applicable. Do not change he default value.
0———
03 Leaving water temperature compensation value
(cooling).
0 –2~2 0 2 °C
04 Not applicable. Do not change he default value.
0———
Page 25
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
23
A Option setup
00 Not applicable. Do not change he default value.
0———
01 Not applicable. Do not change he default value.
0———
02 Pump target T (hea ing).
53~81—
03 Allowable overshoot on leaving water.
31~50.C
04 Not applicable. Do not change he default value.
0———
b Settings are not applicable
00 Not applicable. Do not change he default value.
35
01 Not applicable. Do not change he default value.
45
02 Not applicable. Do not change he default value.
1———
03 Not applicable. Do not change he default value.
70
04 Not applicable. Do not change he default value.
70
C Leaving water temperature limits
00 Set point: heating leaving water maximum
temperature.
45 37~45 1 °C
01 Set point: heating leaving water minimum
temperature.
25 25~37 1 °C
02 Set point: cooling leaving water maximum
temperature.
20 18~22 1 °C
03 Set point: cooling leaving water minimum
temperature.
10 5~18 1 °C
04 Not applicable. Do not change he default value.
0———
d Settings are not applicable
00 Not applicable. Do not change he default value.
10
01 Not applicable. Do not change he default value.
30
02 Not applicable. Do not change he default value.
15
03 Not applicable. Do not change he default value.
15
04 Not applicable. Do not change he default value.
40
E Service mode
00 Not applicable. Do not change he default value.
0———
01 Not applicable. Do not change he default value.
0———
02 Not applicable. Do not change he default value.
0———
03 Not applicable. Do not change he default value.
1———
04 Pump only operation.
00~251—
F Settings are not applicable
00 Pump target T (cooling).
53~81—
01 Not applicable. Do not change he default value.
0———
02 Not applicable. Do not change he default value.
1———
03 Not applicable. Do not change he default value.
10
04 Not applicable. Do not change he default value.
50
First code
Second code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Valu e Date Val ue
Page 26
Installation and operation manual
24
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
8.5. Final check and test run
8.5.1. Final check
Before switching on the unit, read the following: When the complete installation and all necessary settings have
been carried out, be sure that all panels of the unit are closed. If this is not the case, inserting your hand through the remaining openings can cause serious injury due to electrical and hot parts inside the unit.
The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.
In order to purge most of the air out of the system perform a pump operation as described below:
1 Change field setting [E-04]
The default value is 0.
When changing the setting to 1, the pump will operate at low
speed (pump only, the unit will not operate).
When changing the field setting to 2, the pump will operate at
high speed.
2 When air purging is finished, change the field setting back to 0.
It is the respons bility of the installer to make sure that the air is purged out of the unit and system.
Be sure that all stop valves are open. (Refer to vacuuming
procedure of the outdoor unit)
Be sure that all water valves are open.
8.5.2. System test run
Before you can check test operation of each indoor unit separately, you have to do the system test run. System test run is explained in the installation manual of the outdoor unit. This is an automatic test run which can take some time.
When the system test run is finished, it is poss ble to do an individual test run as described in "8.5.3. Indoor unit individual test run" on
page 24. During this test run, the installer should check indicated
items.
8.5.3. Indoor unit individual test run
The installer is obliged to verify correct operation of the indoor and outdoor unit after installation. Therefor a test run must be performed according to the procedures descr bed below. At any time it is possible to check correct operation of space heating/cooling.
Temperature read-out mode
On the user interface, the actual temperatures can be displayed.
1 Push and hold the ba button for 5 seconds.
The leaving water temperature is displayed (icons l and = and é are blinking).
2 Use the pi and pj buttons to display:
The entering water temperature (icons l and = are
blinking and the é icon is flashing slowly).
The indoor temperature (icons l and = are blinking).
The outdoor temperature (icons l and u are blinking).
3 Push the ba button again to leave this mode. If no button is
pressed, the user interface leaves the display mode after 10 seconds.
Proced
ure fo
r space heating/cooling
1 Check the leaving water and entering water temperature through
the user interface read-out mode and write down the displayed values. See "Temperature read-out mode" on page 24.
2 Push the z button 4 times so the t icon will be displayed.
3 Perform the test as follows (when no action is performed, the
user interface will return to normal mode after 10 seconds or by pressing the z button once):
To test the space heating/cooling operation push the y button to start the test run operation.
4 The test run operation will end automatically after 30 minutes or
when reaching the set temperature. The test run operation can be stopped manually by pressing the z button once. If there are misconnections or malfunctions, an malfunction code will be displayed on the user interface. Otherwise, the user interface will return to normal operation.
5 To resolve the malfunction codes, see "8.6.2. Malfunction codes
list" on page 25.
6 Check the leaving water and entering water temperature through
the user interface read-out mode and compare them with the values noted with step 1. After 20 minutes of operation an increase/decrease of the values should confirm the space heating/cooling operation.
NOTICE
When using thermostatic radiator valves, make sure to open all valves during air purging operation.
INFORMATION
When the indoor units and outdoor unit are powered on for the first time, an initialisation takes place. This will take maximum 12 minutes.
When using the user interface during the initialisation, an malfunction code (UH) can be displayed.
INFORMATION
During the first start up of the unit (the first 50 hours of
compressor running), it might happen that the noise level of the unit is higher than mentioned in the technical specifications. This is not an abnormal event.
Start up of the unit in space heating mode is only
possible when the outdoor ambient temperature is lower than 20°C.
INFORMATION
The operation mode can not be selected on the hydrobox. The hydrobox follows the operation mode of the master VRV DX Indoor Unit. Refer to outdoor unit manual for further information.
INFORMATION
To display the last resolved malfunction code, push the z button 1 time. Push the z button again 4 times to return to normal mode.
INFORMATION
It is not possible to perform a test run if a forced operation from the outdoor unit is in progress. Should forced operation be started during a test run, the test run will be aborted.
Page 27
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
25
8.6. Service and maintenance
In order to ensure optimal operation of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
This maintenance should be carried out by your local installer.
To execute maintenance first remove the panels as shown in
"7.4.2. To close the indoor unit" on page 16.
8.6.1. Maintenance activities
Checks
The described checks must be executed at least once a year by qualified personnel.
1 Pressure relief valve hose (if present)
Check that the pressure relief valve hose is positioned appropriately to drain the water.
2 Water pressure relief valve
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter-clockwise:
If you do not hear a clacking sound, contact your local dealer.
In case the water keeps running out of the unit, close both
the water inlet and outlet shut-off valves first and then contact your local dealer.
3 Switch box
Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring.
4 Water pressure
Check if the water pressure is above 1 bar. If necessary add water.
5 Water filter
Clean the water filter.
8.6.2. Malfunction codes list
A more detailed malfunction code list can be found in the installation manual of the outdoor unit.
8.6.3. Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A GWP
(1)
value: 1975
(1)
GWP = global warming potential
DANGER: ELECTRICAL SHOCK
See "7.3.1. Precautions on electrical wiring work" on
page 14.
WARNING: ELECTRIC SHOCK
Before carrying out any maintenance or repair activity,
always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit.
Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.
Please note that some sections of the electric
component box are hot.
Make sure you do not touch a conductive section.Do not rinse the unit. This may cause electric shocks
or fire.
Play it safe!
Touch a metal part by hand (such as piping sheet metal) in order to eliminate static electricity and to protect the PCB before performing service.
Malfunction
code
Failure cause Corrective action
A1
Failure of writing memory (EEPROM malfunction)
Contact your local dealer.
A6
Malfunction water circuit • Make sure waterflow is
possible (open all valves in the circuit).
• Force clean water hrough the unit.
• Malfunction of pump.
• Malfunction of flowswitch.
A9
R410A expansion valve malfunction.
• Check wiring connections.
• Contact your local dealer.
AA Heater kit malfunction • Make sure water flow is
possible.
• Contact your local dealer.
AJ
Capacity malfunction. Contact your local dealer.
C1
Bad ACS communication. Contact your local dealer.
C4
R410A liquid thermistor malfunction.
• Check wiring connections.
• Contact your local dealer.
C9
Returning water thermistor malfunction.
• Check wiring connections.
• Contact your local dealer.
CA
Heating/cooling leaving water hermistor malfunction.
• Check wiring connections.
• Contact your local dealer.
CJ
User interface hermostat thermistor malfunction.
Contact your local dealer.
E3
High pressure malfunc ion. This malfunction is outdoor unit related. Refer to outdoor unit manual.
• Make sure the circuit is filled with water (no air inside, e.g. is he air purge open?)
• Make sure water flow is possible (open all valves in the circuit).
• Make sure the water filter is not blocked.
• Make sure all refrigerant stop valves are open.
• Contact your local dealer.
E4
Low pressure malfunction. This malfunction is outdoor
unit related. Refer to outdoor unit manual.
Contact your local dealer.
J7 R410A gas thermistor
malfunction.
• Check wiring connections.
• Contact your local dealer.
U1
The phases of the power to the unit is reversed. This malfunction is outdoor unit related. Refer to outdoor
unit manual.
Exchange two of the three phases (L1, L2, L3) to make a positive phase connection.
U2
Power supply malfunction. This malfunction is outdoor unit related. Refer to outdoor unit manual.
• Check wiring connections.
• Contact your local dealer.
UA
Type connection problem. • Wait till initialisa ion
between outdoor module and hydro module finished (after power ON, wait at least 12 minutes).
• Contact your local dealer.
UH
Address malfunction. Contact your local dealer.
Page 28
Installation and operation manual
26
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
9. Installing the optional EKBUHAA(6V3/6W1) heater kit
The heater kit option can be installed to assist the heat pump during heating operation or to provide primary heating during emergency situations.
Reference is made to the heater kit's installation/operation manual for general installation information. The EKBUHAA can be used together with HXY(080/125) hydrobox unit, when below instructions are followed!
The information in this chapter provides additional information on how to connect the EKBUHAA to the HXY(080/125) hydrobox series.
Items which are mentioned within this chapter replace information which is provided in the EKBUHAA installation/operation manual. Especially information on how to connect hydraulically (general setup) and electrically (wiring) connect EKBUHAA to the HXY(080/125) should be consulted in this chapter.
Hydraulic connection example and electrical connection are explained below.
Hydraulic connection (general setup)
a Outdoor VRV IV heat pump b VRV Direct Expansion (DX) Indoor unit cassette c HXY(080/125) d Heater kit (EKBUH) e Refrigerant piping
Electric connection
The connection of EKBUHAA to HXY(080/125) hydrobox does not require any optional PCB's to be installed in the HXY(080/125) hydrobox. The EKRP1AHTA should not be used to connect the heater kit to the HXY(080/125) hydrobox.
For details of the electrical connection of the EKBUHAA optional heater kit to the HXY(080/125) hydrobox, refer to "14.2. Wiring
diagram" on page 41.
Field settings related to the backup heater
Refer to "8.3. Field settings" on page 17 how to make field settings for field settings related to the EKBUHAA heater kit.
Other field settings which are explained in the EKBUHAA manual are not applicable in combination with HXY(080/125) hydrobox. The default values should be kept as mentioned in the installation field setting list of the HXY(080/125) hydrobox.
Other information which is explained under field settings in the EKBUHAA manual is not applicable in combination with the HXY hydrobox.
10. Hand-over to the user
Once the test run is finished and the unit operates properly, please make sure the following is clear for the user:
Fill in the installer setting table (see chapter 10) with the actual
settings.
Make sure that the user has the printed documentation and ask
him/her to keep it for future reference.
Explain the user how to properly operate the system and what
he/she has to do in case of problems.
Show the user what jobs he/she has to do in relation to
maintenance of the unit.
Explain the user about energy saving tips as described in the
operation manual.
To be filled in by the installer once the test run is finished and the unit operates properly
b
e
c
a
d
Tick when checked
Explain to he user what sytem is installed on site.
Complete the fill-in below for each unit. The information may be useful for the user in future servicing.
Place of installation:
Model name (see nameplate of the unit)
Optional equipment
Ensure hat the user has a printed version of the installation and
operation manual and ask him/her to keep it for future reference.
Explain the user how to properly operate the system and what
he/she has to do in case of problems.
Show the user what jobs he/she has to do in relation to
maintenance of the unit.
Date:
Signature:
Your product was installed by:
Page 29
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
27
11. Operation of the unit
Please read chapter 1 and 2 first before consulting this chapter.
11.1. Introduction
11.1.1. General information
The unit is the indoor part of the air to water/air VRV IV heat pump. The unit is designed for wall mounted indoor installation and used for heating/cooling applications. The unit can be combined with (field supply) floor heating/cooling loops or fan coil units.
A user interface with room thermostat functionality is standard supplied with this unit to control your installation.
Refer to chapter "4. About the units and options" on page 5.
11.2. Quick start-up of the unit
In this chapter the step-by-step procedure is explained for starting up space cooling/heating.
The more detailed information of how the unit must be operated is explained in the chapter "11.3. Operating the unit" on page 27.
The quick start-up offers the user the poss bility to start up the system before reading the entire manual.
11.2.1. Space cooling/heating operation
11.3. Operating the unit
11.3.1. Operating the user interface
The user interface offers full control over your installation. It can control all heating/cooling applications which vary in capacity, electrical supply and installed equipment (options). Operating the HXY080/125 unit comes down to operating the user interface.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
If you feel unsure about the operation, contact your installer for advice and information.
Confirm the operation mode
(a)
heating h or cooling c
(a) The operation mode can not be selected on the hydrobox. The hydrobox follows
the operation mode of the master VRV DX Indoor Unit. Refer to outdoor unit manual for further information
Push the bi or bj button

Display: 88.8 starts
blinking
Display: "n"

Set desired room
temperature (e.g. 22°C)
The user interface room
thermostat function is
not active

Push the ébi or ébj
button

You have "room
temperature based"
control of your system
(user interface room
thermostat is installed)
You have "leaving water
temperature based" control of
your system
(default)
Set desired leaving water
temperature (e.g. 35°C for heating
or 18°C cooling).
If the display is blank, automatic
leaving water temperature is enabled in heating operation.
Push the y button
The 0 LED will light up and he unit
will start.
For further details and advised settings, see " Programming" on
page 34, "11.3.4. Space cooling operation (c)" on page 29 and
"11.3.5. Space heating operation (h)" on page 29
CAUTION
Do not rinse the unit. This may cause electric shock or
fire.
Do not climb, sit or stand on top of the unit.Do not place any objects or equipment on the unit top
plate.
INFORMATION
It is advised to use the user interface, which includes room thermostat function, delivered with the unit.
This will prevent excessive space heating/cooling and will stop the outdoor and indoor unit when the room temperature is above the thermostat set point. Based on the request from the user there is an immediate feedback to the compressor control which optimizes the performance.
Refer to the typical application examples in the indoor installation manual for more details.
WARNING
Never let the user interface get wet. This may cause
an electric shock or fire.
Never press the buttons of the user interface with a
hard, pointed object. This may damage the user interface.
Never inspect or service the user interface yourself,
ask a qualified service person to do this.
Do not rinse the indoor unit. This may cause electric
shock or fire.
Do not climb, sit or stand on top of the unit.Do not place any objects or equipment on the unit top
plate.
Page 30
Installation and operation manual
28
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
11.3.2. Name and function of buttons and icons
1 ON/OFF BUTTON
y
The ON/OFF button starts or stops the space cooling/heating. Pressing the ON/OFF button consecutively too many times may cause malfunction of the system (maximum 20 times per hour).
2 OPERATION LED
0
The operation LED is lit during space heating/cooling operation. The LED blinks if a malfunction occurs. When the LED is OFF, space heating/cooling is inactive while the other operation modes can still be active.
3 OPERATION MODE ICONS h, c
These icons indicate the current operation mode(s): heating (h) or cooling (c).
4 EXTERNAL CONTROL ICON
e
This icon indicates that the unit is working in a forced operation. As long as this icon is displayed, the user interface cannot be operated or has limited functionality.
5 DAY OF THE WEEK INDICATOR
1234567
This indicator shows the current day of the week. When reading or programming the schedule timer, the indicator shows the set day.
6 CLOCK DISPLAY
8
The clock display shows the current time. When reading or programming the schedule timer, the clock display shows the action time.
7 SCHEDULE TIMER ICON
p
This icon indicates that the schedule timer is enabled.
8 ACTION ICONS
Q
These icons indicate the programming actions for each day of the schedule timer.
9 OFF ICON
x
This icon indicates that the OFF action is selected when programming the schedule timer.
10 INSPECTION REQUIRED
k and l
These icons indicate that inspection is required on the installation. Consult your dealer.
11 TEMPERATURE DISPLAY
9
The display shows the current temperature of the installation either leaving water temperature or actual room temperature. When changing the room temperature set point, the set point will be flashing for 5 seconds and then return to the actual room temperature.
12 SETTING
$
This icon is displayed whenever the field setting mode is entered.
13 NOT AVAILABL E
n
This icon is displayed whenever a non-installed option is addressed or a function is not available. A function not available can mean insufficient permission level or can mean that a slave user interface is used (see installation manual).
14 DEFROST/START UP MODE ICON
d
This icon indicates that the defrost/start up mode is active.
15 COMPRESSOR ICON
ç
This icon indicates that the compressor in the outdoor unit of the system is active.
16 PUMP ICON
é
This icon indicates that the circulation pump is active.
17 OUTDOOR TEMPERATURE DISPLAY
u
When this icon is flashing, the outdoor ambient temperature is displayed. Refer to "11.3.7. Temperature read-out mode" on
page 31 for more information.
18 WEATHER DEPENDENT SET POINT ICON
a
This icon indicates that the controller will adapt the leaving water temperature set point automatically, based on the outdoor ambient temperature (during heating operation).
19 TEMPERATURE ICON
b
This icon is displayed when the actual room temperature or room temperature set point is shown. The icon is also displayed when the temperature set point is set in schedule timer programming mode. Refer to
"11.3.7. Temperature read-out mode" on page 31 for more
information.
20 TEST OPERATION ICON
t
This icon indicates that the unit runs in test mode.
21 FIELD SET CODE
;
This code represents the code from the field set list. Refer to the
"8.3. Field settings" on page 17.
22 MALFUNCTION CODE
:
This code refers to the malfunction code list and is for service purposes only. Refer to the malfunction code list
"8.6.2. Malfunction codes list" on page 25.
23 BUTTON
w
This button has no function.
24 WEATHER DEPENDENT SET POINT BUTTON
ba
This button enables or disables the weather dependent set point function which is available in space heating operation. If the controller is set to permission level 3 (refer to "Field settings" in the installation manual), the weather dependent set point button will not be operable.
25 INSPECTION/TEST OPERATION BUTTON
z
This button is used for installation purposes and changing field settings. Refer to "8.3. Field settings" on page 17.
26 PROGRAMMING BUTTON
<
This multi-purpose button is used to program the controller. The function of the button depends on the actual status of the controller or on previous actions carried out by the operator.
27 SCHEDULE TIMER BUTTON
r/p
The main function of this multi-purpose button is to enable/disable the schedule timer. The button is also used to set the clock and to program the controller. The function of the button depends on the actual status of the controller or on previous actions carried out by the operator.
135 6 228
13
32
23
11
17
19
14
4
7 9
12
10 20
31
24
25
21
18
30 29
28
26
27
21615
Master Slave
Permission
level 2 level 3
Operation ON/OFF 
Setting the leaving water temperature —
Setting the room temperature 
Weather dependent set point operation ON/OFF

Setting the clock ——
Programming the schedule timer ———
Schedule timer operation ON/OFF 
Field settings ———
malfunc ion code display 
Test operation ——
= operable
Page 31
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
29
28 TIME ADJUST BUTTONS pi and pj
These multi-purpose buttons are used to adjust the clock, to toggle between temperatures (water inlet/outlet temperature of the unit, outdoor ambient temperature, actual room temperature) and in schedule timer programming mode.
29 LEAVING WATER TEMPERATURE ADJUST BUTTONS
ébi and ébj
These buttons are used to adjust the leaving water temperature set point in normal operation mode or in schedule timer programming mode. If the controller is set to permission level 3 (refer to "Field settings" in the installation manual), the leaving water temperature adjust button will not be operable. In case the weather dependent set point operation is selected, the unit has a floating set point. In this case, the a icon as well as the shift value (in case not zero) will display.
30 ROOM TEMPERATURE ADJUST BUTTONS
bi and bj
These multi-purpose buttons are used to adjust the current room temperature set point in normal operation mode or in schedule timer programming mode. When changing the room temperature set point, the set point value on the display will be flashing. After 5 seconds the display will show to the actual room temperature.
31 BUTTON
S
This button has no function.
11.3.3. Setting up the controller
After initial installation, the user can set the clock and day of the week.
The controller is equipped with a schedule timer that enables the user to schedule operations. Setting the clock and day of the week is required to be able to use the schedule timer.
Setting the clock
1 Hold down the
pr button for 5 seconds.
The clock read-out and the day of week indicator start flashing.
2 Use the
pi and pj buttons to adjust the clock.
Each time the
pi or pj button is pressed, the time will
increase/decrease by 1 minute. Keeping the
pi or pj
button pressed will increase/decrease the time by 10 minutes.
3 Use the
ébi or ébj button to adjust the day of the week.
Each time the
ébi or ébj button is pressed the next or
previous day is displayed.
4 Press the
< button to confirm the current set time and day of the
week. To leave this procedure without saving, press the pr button.
If no button is pressed for 5 minutes the clock and day of the week will return to their previous setting.
Setting the schedule timer
To set the schedule timer, refer to chapter "11.3.10. Programming
and consulting the schedule timer" on page 33.
11.3.4. Space cooling operation (c)
Space cooling operation can be controlled in two different ways:
based on room temperature,based on leaving water temperature (default).
The purpose of each operation and how the configuration is done, is explained below.
Room temperature control
In this mode, cooling will be activated as required by the room temperature set point. The set point can be set manually or through the schedule timer.
Selecting space cooling operation
1 Use the y button to switch ON/OFF space cooling (c).
Icon c appears on the display as well as the corresponding actual room temperature. The operation LED 0 lights up.
2 Use the bi and bj buttons to set the desired room
temperature. Temperature range for cooling: 16°C~32°C (room temperature)
Refer to "11.3.10. Programming and consulting the schedule
timer" on page 33 for setup of the schedule timer function.
3 Use the ébi and ébj buttons to select the leaving
water temperature which you want to be used to cool down your system.
Leaving water temperature control (default)
In this mode, cooling will be activated as required by the water temperature set point. The set point can be set manually or through the schedule timer.
Selecting space cooling operation
1 Use the y button to switch ON/OFF space cooling (c).
Icon c appears on the display as well as the corresponding water temperature set point. The operation LED 0 lights up.
2 Use the ébi and ébj buttons to set the desired leaving
water temperature. Temperature range for cooling: 5°C~20°C (leaving water
temperature).
Refer to "Programming space cooling" on page 34, "Programming
space heating" on page 35 for setup of the schedule timer function.
11.3.5. Space heating operation (h)
Space heating operation can be controlled in two different ways:
based on room temperature,based on leaving water temperature (default).
The purpose of each operation and how the configuration is done, is explained below.
R
oom
temperature control
In this mode, heating will be activated as required by the room temperature set point. The set point can be set manually or through the schedule timer.
INFORMATION
The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and vice versa.
If the controller is set to permission level 2 or 3 (refer
to "Field settings" in the installation manual), setting the clock will not be poss ble.
A power failure exceeding 2 hours will reset the clock
and the day of the week. The schedule timer will continue operation, but with a disordered clock. Therefor it will be needed to correct the clock and the day of the week.
INFORMATION
When using room temperature control, space cooling operation based on room temperature will have priority over leaving water control.
Note that it is poss ble that the leaving water temperature becomes lower than the set point if the unit is controlled by room temperature.
INFORMATION
When an external room thermostat is installed, the
thermo ON/OFF is determined by the external room thermostat. The user interface is then operated in the leaving control mode and is not functioning as a room thermostat.
The user interface ON/OFF status always has priority
over the external room thermostat!
Setback operation and weather dependent set point
are not available in cooling operation.
Page 32
Installation and operation manual
30
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Selecting space heating operation
1 Use the y button to switch ON/OFF space heating (h).
Icon h appears on the display as well as the corresponding actual room temperature set point. The operation LED 0 lights up.
2 Use the bi and bj buttons to set the desired room
temperature. Temperature range for heating: 16°C~32°C (room temperature)
In order to avoid overheating, space heating is not operable when the outdoor ambient temperature rises above a certain temperature (see operation range). Refer to "11.3.10. Programming and consulting the schedule
timer" on page 33 for setup of the schedule timer function.
3 Use the ébi and ébj buttons to select the leaving
water temperature which you want to be used to heat up your system.
Automatic setback function
Setback function provides the poss bility to lower the room temperature. The setback function can for instance be activated during the night because the temperature demands during night and day are not the same.
The setback function is configured through field settings. Refer to the chapter "8.3. Field settings" on page 17 for a detailed description how to set one or more field settings.
[2-00] Status: defines whether the setback function is turned ON
(1) or OFF (0)
[2-01] Start time: time at which setback is started[2-02] Stop time: time at which setback is stopped[5-03] Room setback temperature
A Normal room temperature set point B Room setback temperature [5-03]
t Time
T Temperature
Leaving water temperature control (default)
In this mode, heating will be activated as required by the water temperature set point. The set point can be set manually, through the schedule timer or weather dependent (automatic).
Selecting space heating operation
1 Use the y button to switch ON/OFF space heating (h).
Icon h appears on the display as well as the corresponding water temperature set point. The operation LED 0 lights up.
2 Use the
ébi and ébj buttons to set the desired leaving
water temperature. Temperature range for heating: 25°C~45°C (leaving water
temperature) In order to avoid overheating, space heating is not operable when the outdoor ambient temperature rises above a certain temperature (see operation range).
Refer to "User interface schedule timer" for setup of the schedule timer function.
Selecting weather dependent set point operation
When weather dependent operation is active, the leaving water temperature is determined automatically depending on the outdoor temperature: colder outdoor temperatures will result in warmer water and vice versa. The unit has a floating set point. Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point.
During weather dependent operation, the user has the possibility to shift up or down the target water temperature by a maximum of 5°C. This shift value is the temperature difference between the temperature set point calculated by the controller and the real set point. E.g. a positive shift value means that the real temperature set point will be higher than the calculated set point.
It is advised to use the weather dependent set point because it adjusts the water temperature to the actual needs for space heating. It will prevent the unit from switching too much between thermo ON operation and thermo OFF operation when using the user interface room thermostat or external room thermostat.
1 Press the ba button 1 time to select weather dependent set
point operation (or 2 times when the user interface room thermostat function is used).
Icon a appears on the display as well as the shift value. The shift value is not shown in case it is 0.
2 Use the ébi and ébj buttons to set the shift value.
Range for the shift value: –5°C to +5°C Icon a will be displayed as long as the weather dependent set point operation is enabled.
3 Press the ba button to deactivate weather dependent set point
operation. The ébi and ébj buttons are used to set the leaving
water temperature.
INFORMATION
When using room temperature control, space heating operation based on room temperature will have priority over leaving water control.
Note that it is poss ble that the leaving water temperature becomes higher than the set point if the unit is controlled by room temperature.
INFORMATION
Remark that the b icon will be flashing during setback
operation.
By default the setback function is enabled.The setback function can be combined with the
automatic weather dependent set point operation.
Setback function is an automatic daily scheduled
function.
INFORMATION
While room temperature setback function is active,
leaving water setback operation is also performed.
Pay attention not to set the setback value too low,
especially during colder periods (e.g. winter time). It is possible that the room temperature can not be reached (or it will take a much longer time) because of the big temperature difference.
[2-01] [2-02]
A
B
T
t
21°C
18°C
NOTICE
When an external room thermostat is installed, the
thermo ON/OFF is determined by the external room thermostat. The user interface is then operated in the leaving control mode and is not functioning as a room thermostat.
The user interface ON/OFF status always has priority
over the external room thermostat!
INFORMATION
During this operation, instead of showing the water temperature set point, the controller shows the shift value which can be set by the user.
Page 33
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
31
Field settings define the parameters for the weather dependent operation of the unit. Refer to the chapter "8.3. Field settings" on
page 17 for a detailed description how to set one or more field
settings.
TtTarget water temperature
T
A
Ambient (outdoor) temperature
Shift value Shift value
[3-00] Low ambient temperature (Lo_A): low outdoor
temperature.
[3-01] High ambient temperature (Hi_A): high outdoor
temperature.
[3-02] Set point at low ambient temperature (Lo_Ti): the target
outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is required.
[3-03] Set point at high ambient temperature (Hi_Ti): the target
outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature (Hi_A). Note that the Hi_Ti value should be lower than Lo_Ti, as for warmer outdoor temperatures (i.e. Hi_A) less warm water suffices.
Automatic setback function
Setback function provides the poss bility to lower the room temperature. The setback function can for instance be activated during the night because the temperature demands during night and day are not the same.
The setback function is configured through field settings. Refer to the chapter "8.3. Field settings" on page 17 for a detailed description how to set one or more field settings.
[2-00] Status: defines whether the setback function is turned ON
(1) or OFF (0)
[2-01] Start time: time at which setback is started[2-02] Stop time: time at which setback is stopped[5-02] Leaving water setback temperature (temperature drop)
A Normal leaving water temperature set point B Leaving water setback temperature =A–[5-02]
t Time
T Temperature
11.3.6. Other operation modes
Start up operation (d)
During start up, the d icon displays, indicating that the heat pump is starting up and is not working in a steady state condition.
Defrost operation (d)
In space heating operation, freezing of the outdoor heat exchanger may occur due to low outdoor temperature. If this risk occurs, the system goes into defrost operation. After a maximum of 15 minutes of defrost operation, the system returns to space heating operation. During defrost operation, space heating operation is not possible.
11.3.7. Temperature read-out mode
On the user interface, the actual temperatures can be displayed.
1 Push and hold the ba button for 5 seconds.
The leaving water temperature is displayed (icons l and = and é are blinking).
2 Use the pi and pj buttons to display:
The entering water temperature (icons l and = are
blinking and the é icon is flashing slowly).
The indoor temperature (icons l and = are blinking).
The outdoor temperature (icons l and u are blinking).
3 Push the ba button again to leave this mode. If no button is
pressed, the user interface leaves the display mode after 10 seconds.
INFORMATION
If by mistake the value of [3-03] is set higher than the value of [3-02], the value of [3-03] will always be used.
INFORMATION
Remark that the b icon will be flashing during setback
operation.
By default the setback function is enabled.The setback function can be combined with the
automatic weather dependent set point operation.
Setback function is an automatic daily scheduled
function.
Lo Ti
Lo A Hi A T
A
T
t
+ 05
00
– 05
Hi Ti
Shift value
[2-01] [2-02]
B
A
T
t
45°C
40°C
5°C [5-02]
Page 34
Installation and operation manual
32
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
11.3.8. Schedule timer operation
In schedule timer operation, the installation is controlled by the schedule timer. The actions programmed in the schedule timer will be executed automatically.
The schedule timer is enabled (
p icon displayed) or disabled (p icon
not displayed) by pressing the pr button.
Space cooling
Refer to "Programming space cooling" on page 34.
4 actions can be programmed, these actions are repeated daily.
The space cooling schedule timer can be programmed in 2 different ways:
Based on the temperature set point (leaving water temperature
and room temperature).
Based on the ON/OFF instruction.
The desired method is set through field setting. Refer to "8.3. Field
settings" on page 17 for a detailed description how to set one or more
field settings. [0-04] Status: defines whether ON/OFF instruction can be used
in the schedule timer for space cooling.
The implementation and meaning of setting [0-04] and schedule settings are the same as for heating operation. See "Operation
example: Schedule timer based on temperature set points" on page 32 and "Operation example: Schedule timer based on ON/OFF instruction" on page 33.
For cooling, no setback function is available.
11.3.9. Space heating
Refer to "Programming space heating" on page 35.
Four actions per day of the week can be programmed, totalling 28 actions.
The space heating schedule timer can be programmed in 2 different ways: based on the temperature set point (both leaving water temperature and room temperature) and based on the ON/OFF instruction.
The desired method is set through field setting. Refer to the chapter
"8.3. Field settings" on page 17 for a detailed description how to set
one or more field settings. [0-03] Status: defines whether ON/OFF instruction can be used
in the schedule timer for space heating.
In the following tables both methods on how to interpret the schedule timer are shown.
Operation example: Schedule timer based on temperature set points
When setback function is enabled, the setback operation will have priority over the scheduled action in the schedule timer.
1 Schedule timer 2 Setback function 3 When both setback function and schedule timer are
enabled
A Setback function
t Time
T Temperature set point
Room temperature Leaving water temperature
INFORMATION
By default space cooling based on temperature set point (method 1) is enabled, so only temperature shifts are possible (no ON/OFF instruction).
INFORMATION
By default space heating based on temperature set point (method 1) is enabled, so only temperature shifts are possible (no ON/OFF instruction).
Method 1 [0-03]=1 (default)
Space heating based on temperature set point
(a)
(a) For leaving water temperature and/or room temperature
During operation During schedule imer operation the operation LED is lit
continuously.
When pushing the y button
The schedule imer for space hea ing will stop and will not start again. The controller will be switched off (operation LED will stop working).
When pushing the pr button
The schedule timer for space heating will be stopped and will not start again. The schedule imer icon will not be displayed anymore.
Method 2 [0-03]=0
Space heating based on ON/OFF instruction
During opera ion When the schedule timer switches space hea ing OFF,
the controller will be switched off (operation LED will stop working).
When pushing
he y button
The schedule timer for space heating will stop (when active at that moment) and will start again at the next scheduled ON function. The "last" programmed command overrules the "preceding" programmed command and will remain active until the "next" programmed command occurs.
Example: imagine he actual time is 17:30 and actions are programmed at 13:00, 16:00 and 19:00. The "last" programmed command (16:00) overruled the "previous" programmed command (13 00) and will remain active until
he "next" programmed command (19:00)
occurs. So in order to know the actual setting, one should consult the last programmed command. It is clear that he "last" programmed command may date from he day before. Refer to
" Consulting programmed actions" on
page 36
. The controller will be switched off (operation LED will stop working). However he schedule timer icon will stay displayed.
When pushing
he pr button
The schedule imer for space heating will be stopped and will not start again. The schedule timer icon will not be displayed anymore.
T
t
6:30 9:00
16:00
0:30
19C 19C 19C
22C
21C
42C 42C 42C
45C
44C
42C
19C 19C 19C
22C
21C
42C 42C
45C
44C
0:30
1
T
t
18C
37C37C
18C
A
5:0023:00 5:0023:00
2
T
t
5:00 9:00
16:00
23:00
19C
18C
19C
22C
21C
42C
40C
42C
45C
44C
40C
19C
18C
19C
22C
21C
42C
19C
19C
42C
19C
42C
19C19C19C
42C
45C
44C
6:30
3
37C37C
40C
40C
Page 35
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
33
Operation example: Schedule timer based on ON/OFF instruction
When setback function is enabled, the setback operation will have priority over the scheduled action in the schedule timer if ON instruction is active. If OFF instruction is active this will have priority over the setback function. At any time the OFF instruction will have the highest priority.
1 Schedule timer 2 Setback function 3 When both setback function and schedule timer are
enabled
A Setback function B ON/OFF instruction
t Time
T Temperature set point
Room temperature Leaving water temperature
11.3.10. Programming and consulting the schedule timer
Getting started
Programming the schedule timer is flex ble (you can add, remove or alter programmed actions whenever required) and straightforward (programming steps are limited to a minimum). However, before programming the schedule timer, remind:
Familiarise yourself with the icons and the buttons. You will need
them when programming. Refer to "11.3.2. Name and function
of buttons and icons" on page 28.
Fill out the form at the very end of this manual. This form can
help you define the required actions for each day.
Take your time to enter all data accurately.Try to program the actions in a chronological way: start with
action 1 for the first action and end with the highest number for the last action. This is not a requirement but will simplify the interpretation of the program later.
If 2 or more actions are programmed for the same day and at the
same time, only the first programmed action will be executed.
Example:
You can always alter, add or remove the programmed actions
later.
INFORMATION
When power returns after a power supply failure, the
auto restart function reapplies the user interface settings at the time of the power supply failure (if time is shorter than 2 hours). It is therefore recommended to leave the auto restart function enabled.
The programmed schedule is time driven. Therefore,
it is essential to set the clock and the day of the week correctly.
Refer to "11.3.3. Setting up the controller" on
page 29.
When the schedule timer is not enabled (p icon not
displayed), schedule timer actions will not be executed!
The programmed actions are not stored according to
their timing but according to the time of programming. This means that the action that was programmed first gets action number 1, even though it is executed after other programmed action numbers.
t
18C
40C40C
18C
A
5:0023:00 5:0023:00
2
B
t
9:00
16:00
19C 19C
22C
21C
42C 42C
45C
44C
19C 19C
22C
21C
42C 42C
45C
44C
1
OFF ONON
6:300:30
B
t
6:30 9:00
16:00
23:00
19C 19C
22C
21C
42C 42C
45C
44C
19C 19C
22C
21C
42C 42C
45C
44C
3
OFF ONON
18C
40C40C
18C
Programmed actions Executed actions
Time
(hour)
Temperature
(°C)
Time
(hour)
Temperature
(°C)
1 18:00 OFF 1 06:00 21 2 08:00 23 2 08:00 23 3 06:00 21 3 18:00 OFF 4 18:00 26
Page 36
Installation and operation manual
34
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Programming
Programming space cooling
Programming space cooling is carried out as follows:
1 Press the < button to enter the programming/consulting mode.
2 Select the operation mode you would like to program by means
of the pi and pj buttons. The actual mode is blinking.
3 Press the < button to confirm the selected mode.
The time is blinking.
4 Consult the action by means of the pi and pj buttons.
5 Hold down the < button for 5 seconds to program the detailed
actions. The first programmed action appears.
6 Use the < button to select the action number you would l ke to
program or to modify.
7 Use the pi and pj buttons to set the correct action time.
8 Use the ébi and ébj buttons to set the leaving water
temperature.
9 Use the bi and bj buttons to set the room temperature.
10 Use the ba button to select x to switch cooling and the user
interface off.
11 Repeat steps 6 to 10 to program the other actions.
When all actions have been programmed, make sure that the display shows the highest action number you would like to save.
12 Press the < button for 5 seconds to store the programmed
actions. If the < button is pressed when action number 3 is displayed,
actions 1, 2 and 3 are stored but 4 is deleted. You automatically return to step 5. By pressing the pr button several times, you return to previous steps in this procedure and finally return to normal operation.
13 You automatically return to step 5, start again to program the
following day.
5 sec
5 sec
INFORMATION
Returning to previous steps in the programming procedure without saving modified settings is done by pressing the pr button.
Page 37
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
35
Programming space heating Programming space heating is carried out as follows:
1 Press the < button to enter the programming/consulting mode.
2 Select the operation mode you would like to program by means
of the pi and pj buttons. The actual mode is blinking.
3 Press the < button to confirm the selected mode.
The actual day is blinking.
4 Select the day you would like to consult or to program by means
of the pi and pj buttons. The selected day is blinking.
5 Press the < button to confirm the selected day.
6 Hold down the < button for 5 seconds to program the detailed
actions. The first programmed action of the selected day appears.
7 Use the < button to select the action number you would l ke to
program or to modify.
8 Use the pi and pj buttons to set the correct action time.
9 Use the ébi and ébj buttons to set the leaving water
temperature.
10 Use the bi and bj buttons to set the room temperature.
11 Use the ba button to select:
- x: to switch heating and the user interface off.
- a: to select automatic temperature calculation for leaving water temperature
Use the ébi and ébj buttons to set the appropriate shift value (refer to " Setting the schedule timer" on page 29 for more information about weather dependent set point).
12 Repeat steps 7 to 11 to program the other actions of the
selected day. When all actions have been programmed, make sure that the
display shows the highest action number you would l ke to save.
13 Press the < button for 5 seconds to store the programmed
actions. If the < button is pressed when action number 3 is displayed,
actions 1, 2 and 3 are stored but 4 is deleted. You automatically return to step 6. By pressing the pr button several times, you retur
n
to previous
steps in this procedure and finally return to normal operation.
14 You automatically return to step 6, start again to program the
following day.
5 sec
5 sec
INFORMATION
Returning to previous steps in the programming procedure without saving modified settings is done by pressing the pr button.
Page 38
Installation and operation manual
36
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Consulting programmed actions
Consulting space heating/cooling actions
Consulting space cooling heating or space heating is carried out as follows.
1 Press the < button to enter the programming/consulting mode.
2 Select the operation mode you would like to consult by means of
the pi and pj buttons. The actual mode is blinking.
3 Press the < button to confirm the selected mode.
The actual day is blinking.
4 Select the day you would l ke to consult by means of the pi
and pj buttons. The selected day is blinking.
5 Press the < button to confirm the selected day.
The first programmed action of the selected day appears.
6 Use the pi and pj buttons to consult the other
programmed actions of that day. This is called the readout mode. Empty program actions (e.g. 4)
is not displayed. By pressing the pr button several times, you return to previous steps in this procedure and finally return to normal operation.
Tips and tricks
Programming the next day(s)
After confirming the programmed actions of a specific day (i.e. after pressing the < button for 5 seconds), press the pr button once. You can now select another day by using the pi and pj buttons and restart consulting and programming.
Copying programmed actions to next day
In space heating program it is possible to copy all programmed actions of a specific day to the next day (e.g. copy all programmed actions from "1" to "2").
To copy programmed actions to the next day, proceed as follows:
1 Press the < button.
The actual mode is blinking.
2 Use the pi and pj buttons to select the mode you want
to program. The selected mode is blinking.
You can leave programming by pressing the pr button.
3 Press the < button to confirm the selected mode.
The actual day is blinking.
4 Select the day you would like to copy to the next day by means
of the pi and pj buttons. The selected day is blinking.
Y
ou can retu
rn to step 2 by pressing the pr button.
5 Press the < and pr buttons simultaneously for 5 seconds.
After 5 seconds the display will show the next day (e.g. "2" if "1" was selected first). This indicates that the day has been copied. You can return to step 2 by pressing the pr button.
Deleting one or more programmed actions
Deleting one or more programmed actions is done at the same time as storing the programmed actions.
When all actions for one day have been programmed, make sure that the display shows the highest action number you would like to save. By pressing the < button for 5 seconds, you store all actions except those with a higher action number than the one that is displayed.
E.g. when the < button is pressed when action number 3 is displayed, actions 1, 2 and 3 are stored but 4 is deleted.
Deleting a mode
1 Press the
<
button.
The actual mode is blinking.
2 Use the pi and pj buttons to select the mode you want
to delete. The selected mode is blinking.
3 Press the < and ba button simultaneously for 5 seconds to
delete the selected mode.
Deleting a day of the week
1 Press the < button.
The actual mode is blinking.
2 Use the pi and pj buttons to select the mode you want
to delete. The selected mode is blinking.
3 Press the < button to confirm the selected mode.
The actual day is blinking.
4 Select the day you would l ke to delete by means of the pi
and pj buttons. The selected day is blinking.
5 Press the < and ba button simultaneously for 5 seconds to
delete the selected day.
INFORMATION
Returning to previous steps in this procedure is done by pressing the pr button.
Page 39
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
37
11.3.11. Operating the optional demand PCB
An optional PCB EKRP1AHTA can be connected to the unit and be used to remotely control the unit
There are 3 inputs that allow
Remote thermo on - off.
Remote unit on - off.
For more details about this option kit, refer to the wiring diagram of the unit
11.3.12. Operating the optional user interface
If besides the main user interface the optional user interface is installed as well, the main user interface (master) can access all settings while the second user interface (slave) can not access schedule settings and parameter settings.
Refer to the installation manual for more details.
11.4. Field settings
The unit shall be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user demand. However, the field settings mentioned in "8.3. Field settings"
on page 17 can be modified to customer preferences. Therefore, a
number of so called field settings are available. These field settings are accessible and programmable through the user interface.
Each field setting is assigned a 3-digit number or code, for example [1-03], which is indicated on the user interface display. The first digit [1] indicates the 'first code' or field setting group. The second and third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under "8.3. Field
settings" on page 17. In this same list, we provided 2 columns to
register the date and value of altered field settings at variance with the default value.
11.4.1. Procedure
To change one or more field settings, proceed as follows.
1 Press the z button for a minimum of 5 seconds to enter FIELD
SET MODE. The $ icon (3) will be displayed. The current selected
field setting code is indicated ; (2), with the set value displayed to the right - (1).
2 Press the ébi button to select the appropriate field setting
first code.
3 Press the ébj button to select the appropriate field setting
second code.
4 Press the pfi button and pfj button to change
the set value of the select field setting.
5 Save the new value by pressing the pr button.
6 Repeat step 2 through 4 to change other field settings as
required.
7 When finished, press the z button to exit FIELD SET MODE.
NOTICE
The default values mentioned in "8.3. Field settings" on
page 17 are the values from factory. The actual initial
values shall be selected according to your application. These values shall be confirmed by your installer.
NOTICE
Changes made to a specific field setting are only stored when the pr button is pressed. Navigating to a new field setting code or pressing the z button will discard the change made.
INFORMATION
Before shipping, the set values have been set as
shown under "8.3. Field settings" on page 17.
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit initialises itself.
NOTICE
When running through the field settings you may
notice that there are some more field settings as there are mentioned in the "8.3. Field settings" on page 17.
These field settings are not applicable and may not be changed!
For more information about installation related setting,
see installation manual of the unit. For settings different from the default value, contact your installer.
Page 40
Installation and operation manual
38
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
11.5. Field setting list for Operation Manual
First code
Second code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Va lue Date Value
0 Remote control setup
00
Installation related set ing
(a)
22~31—
01
Installation related set ing
(a)
0 –5~5 0 5 °C
02 Not applicable. Do not change he default value.
1———
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0.
1 (ON) 0/1
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0.
1 (ON) 0/1
1 Settings are not applicable
00 Not applicable. Do not change he default value.
1———
01 Not applicable. Do not change he default value.
1:00
02 Not applicable. Do not change he default value.
0———
03 Not applicable. Do not change he default value.
15 00
2 Automatic setback function
00 Status: se back operation.
1 (ON) 0/1
01 Setback operation start time.
23:00 0 00~23:00 1:00 hour
02 Setback operation stop time.
5:00 0 00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A).
–10 –20~5 1 °C
01 High ambient temperature (Hi_A).
15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti).
40 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti).
25 25~80 1 °C
4 Settings are not applicable
00 Not applicable. Do not change he default value.
1———
01 Not applicable. Do not change he default value.
Fri
02 Not applicable. Do not change he default value.
23 00
5 Automatic setback and disinfection set point
00 Not applicable. Do not change he default value.
70
01 Not applicable. Do not change he default value.
10
02 Leaving water setback temperature.
50~101°C
03 Room setback temperature.
18 17~23 1 °C
04 Not applicable. Do not change he default value.
0———
6 Option setup
01
Installation related set ing
(a)
0 (OFF) 0/2
02
Installation related set ing
(a)
0 (OFF) 0/1
03 Not applicable. Do not change he default value.
0———
8 Option setup
00
Installation related set ing
(a)
1 (ON) 0/1
01 Not applicable. Do not change he default value.
1———
02 Emergency opera ion.
00/1——
03 Not applicable. Do not change he default value.
1———
04
Installation related set ing
(a)
0 0~2 1
9 Automatic temperature compensation
00
Installation related set ing
(a)
0 –2~2 0 2 °C
01
Installation related set ing
(a)
1 (ON) 0/1 1
02 Not applicable. Do not change he default value.
0———
03
Installation related set ing
(a)
0 –2~2 0 2 °C
04 Not applicable. Do not change he default value.
0———
Page 41
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
39
A Option setup
00 Not applicable. Do not change he default value.
0———
01 Not applicable. Do not change he default value.
0———
02
Installation related setting
(a)
53~81—
03
Installation related setting
(a)
31~50.C
04 Not applicable. Do not change he default value.
0———
b Settings are not applicable
00 Not applicable. Do not change he default value.
35
01 Not applicable. Do not change he default value.
45
02 Not applicable. Do not change he default value.
1———
03 Not applicable. Do not change he default value.
70
04 Not applicable. Do not change he default value.
70
C Leaving water temperature limits
00
Installation related setting
(a)
45 37~45 1 °C
01
Installation related setting
(a)
25 25~37 1 °C
02
Installation related setting
(a)
20 18~22 1 °C
03
Installation related setting
(a)
10 5~18 1 °C
04 Not applicable. Do not change he default value.
0———
d Settings are not applicable
00 Not applicable. Do not change he default value.
10
01 Not applicable. Do not change he default value.
30
02 Not applicable. Do not change he default value.
15
03 Not applicable. Do not change he default value.
15
04 Not applicable. Do not change he default value.
40
E Service mode
00 Not applicable. Do not change he default value.
0———
01 Not applicable. Do not change he default value.
0———
02 Not applicable. Do not change he default value.
0———
03 Not applicable. Do not change he default value.
1———
04
Installation related setting
(a)
00~251—
F Settings are not applicable
00
Installation related setting
(a)
53~81—
01 Not applicable. Do not change he default value.
0———
02 Not applicable. Do not change he default value.
1———
03 Not applicable. Do not change he default value.
10
04 Not applicable. Do not change he default value.
50
(a) For more information about installation related settings, see Installation Manual of the indoor unit. For settings different from the default value, contact your installer.
First code
Second code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Valu e Date Val ue
Page 42
Installation and operation manual
40
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
12. Maintenance
12.1. Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Refrigerant type: R410A GWP
(1)
value: 1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required depending on the applicable legislation. Please contact your local dealer for more information.
12.2. Maintenance activities
In order to ensure optimal readiness of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals, preferably yearly. This maintenance should be carried out by your local Da kin technician (see installation manual).
The only maintenance which may be required by the operator is:
Keeping the user interface clean by means of a soft damp cloth.Checking if the water pressure indicated on the manometer is
above 1 bar.
13. Troubleshooting
The guidelines below might help to solve your problem. If you cannot solve the problem, consult your installer.
13.1. Malfunction codes list
When a safety device is activated, the user interface LED will be flashing, and a malfunction code will be displayed.
A list of malfunctions and corrective actions can be found in
"8.6.2. Malfunction codes list" on page 25.
Reset the safety by pushing the y button.
In case this procedure for resetting the safety is not successful, contact your local dealer.
For other malfunction codes which may be displayed during the system test run or operation, see the installation manual of the outdoor unit.
14. Technical Data
14.1. Piping diagram
a Shut off valve with drain/fill valve (field installed) b Expansion vessel c Water filter d Safety valve (3 bar) e Manometer
f Pump (MP1) g Plate heat exchanger h Flowswitch (S1L)
i Airpurge
j Expansion valve (K1E) k Refrigerant filter
l Liquid refrigerant piping
m Gas refrigerant piping R1T Leaving water thermistor R2T Return water thermistor R3T Liquid thermistor R4T Gas thermistor
Cooling Hea ing
WARNING
If the supply cord is damaged, it must be replaced by the manufacturer, its agent or similar qualified persons in order to avoid hazards.
Possible causes Corrective actions
No readings on the user interface (blank display)
Check if the main power is still connected to your installation.
One of the malfunction codes appears
Consult your local dealer. Refer to the installation manual or below table for a detailed list of malfunc ion codes.
The schedule timer does work but the programmed actions are executed at the wrong time. (e.g. 1 hour too late or too early)
Check if the clock and the day of the week are set correctly, correct if necessary.
The schedule timer is programmed but does not work.
In case the pr icon is not displayed, push he pr button to enable the schedule imer.
Capacity shortage Consult your local dealer.
a
R1T
R2T R3T
R4T
a b c d e f k k lj
i h g k m
g
j
R3T
c
R4T
d
k
k
k
R2T
i hb R1T
ea mlaf
Page 43
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
41
14.2. Wiring diagram
The abbreviations used are listed below:
A1P........................ Main PCB (master)
A2P........................ User interface PCB
A3P........................ Control PCB
A4P.................*..... Demand PCB
A5P.................*..... Remote user interface PCB
A6P.................*..... Thermostat PCB
A7P.................*..... Receiver PCB
C1-C3 .................... Filter capacitor
F1U (A*P) .............. Fuse (T, 3.15 A, 250 V)
HAP (A*P).............. PCB LED
K1E........................ Electronic expansion valve
K*R (A3P).............. PCB relay
M1P ....................... Pump
PC (A7P) ........*..... Power circuit
PS (A1P)................ Switching power supply
Q*D1.............. #..... Earth leakage circuit breaker
R1H (A6P) ......* ..... Humidity sensor
R1T........................ Leaving water thermistor
R1T (A6P).......* ..... Ambient sensor
R2T........................ Return water thermistor
R2T.................*..... External sensor (floor or ambient)
R3T........................ Refrigerant liquid thermistor
R4T........................ Refrigerant gas thermistor
S1L ........................ Flow switch
S1S................ #..... Thermostat input 1
S2S................ #..... Thermostat input 2
S3S................ # ..... Operation ON input
S4S................ #..... Operation OFF input
SS1 (A1P).............. Selector switch (emergency)
(EMG. = emergency, NORM. = normal)
SS1 (A2P).............. Selector switch (main (M)/sub (S))
SS1 (A5P)...... * ..... Selector switch (main (M)/sub (S))
T1R........................ Diode bridge
V1C-V2C ............... Ferrite core noise filter
X*A (A*P)............... PCB connector
X1M ....................... Terminal strip for high voltage field wiring
X2M ....................... Terminal strip for low voltage field wiring
X*M (A*P) ...... *..... PCB terminal strip
Z1F (A1P ............... Noise filter
* Field installed option
# Field supplied
Colours
BLK........................ Black
BLU........................ Blue
BRN ....................... Brown
ORG ...................... Orange
RED ....................... Red
WHT ...................... White
YLW....................... Yellow
Notes
PC
LNX2M C
COM
X1M H
%H20 R1H
X1M
X1M
only for EKRTR* only for EKRTETS
only for EKRTW*
1
C
COM
H
1
A6P
A6P
A7P
X801M 4 5123
A4P
1
A1P
WHT
YLW
ORG
BLU
RED
BRN
BLU
BRN
RED
BLK
WHT
T1R
Z1F PS
HAP
SS1
NORM
EMG
HAP
3 4
X1M
5 6
X1M
X1M
11 12
Cooling / heating output: max 0 3A, 230V AC
Operation on/off output: max 0 3A, 230V AC
Error output: max 0 3A, 230V AC
LX1M N
5
X2M
6
A3P
only for EKBUH*
X2M 4 5 123
NL
1~50Hz 220 240 VAC
power supply
User interface
P1 P2
F1 F2
X2M
P1
X2M
P2
Remote user interface
P1 P2
only for EKRUAHT*
V2C N 2
V1C N 1
SS1 S M
SS1
S
M
A2P
A5P
F1F2 communication: see outdoor unit for more details
only for EKRP1AHT*
X2M
7
X1M
8 9
X1M
10
NL
1~50Hz 220 240 VAC
power supply
R1T
R1T
R2T
X80A:1
2 3 4 5 6 7 8 9 10 11 12
S1S S2S S3S S4S
X18A:1
2
X12A:1
2
X17A:1
2
X7A 1 2 3
4
5
K1E
M
X20A:1 2 3
4
6
M1P
MS
3~
6
7
3
NE
X27A:(L) 1
(N) 3
5
5
8
F1U
R3T
R2T
R1T
C3
X16A:1
2 3
R4T
4
C1
C2
X8A:1 2
K6R
S1L
X1A:1
2 3
4
F1U
X23A:1
2
3
4
X7A:1
2
K5R
K7R
2
K2R
X4A:1
Q1DI
X30A:1
2
3
4
5
6
7
8
X70A:1
2
2
X35A:1
X15A:1
2
2
X10A:1
2
X16A:1
X14A:1
2
X15A:1
2
2
K3R
X5A:1
2
K1R
X3A:1
3 4
Q2DI
X85A:1 2 3 4 5 6
only for *** only for ***
power supply power supply
Cooling/heating output: Cooling/heating output:
Operation on/off output: Operation on/off output:
Error output: Error output:
F1F2 communication: see outdoor unit for more details
F1F2 communication: see outdoor unit for more details
User interface User interface
Remote user interface Remote user interface
Page 44
Installation and operation manual
42
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
14.3. Electrical components box
a A1P: main PCB b A3P: control PCB c A4P: optional demand PCB d X2M: terminal strip e X1M: terminal strip
14.4. Operation range HXY(080/125)
Cooling operation
a Outdoor Ta (°CDB/WB) b Indoor (LWE°C) c Pull down area d Normal opera ion range
(*) Depending on opera ion conditions and only possible after field setting
activa ion (influence on DX cooling (cold draft) and total efficiency).
Heating operation
a Outdoor Ta (°CDB/WB) b Indoor (LWC°C) c Warming up zone d Normal operation range
14.5. ESP curve
ESP External Static Pressure
Flow Waterflow through the unit
Unit ESP at 4000 rpm (∆T=5°C) Unit ESP at 3800 rpm (∆T=8°C) Maximum ESP if T=5°C (heating nominal) Maximum ESP if T=5°C (cooling nominal)
NOTICE
When LWE is selected <18°C; optional drain pan has to be used for Hydrobox.
a
c
b
d e
ae
cd
b
10/8
(5*) 10 20 25
35/30
43/(37)
20/16
7/6
2/1
7/ 8
20/X
4525
a
b
5
c d
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 40
ESP (kPa)
Flow (l/min)
Page 45
HXY080+125A7V1B
VRV IV System indoor unit
4P325971-1B – 2012.07
Installation and operation manual
43
14.6. Technical specifications table 14.7. Electrical specifications table
15. Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with the applicable legislation.
Do not try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and other parts must be done by a qualified installer in accordance with the applicable legislation.
Units must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed off correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.
HXY080A7V1B HXY125A7V1B
Nominal cooling capacity
•Heating
(a)
(a) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
kW 9 14
• Cooling
(b)
(b) Tamb 35°C - LWE 18°C (DT=5°C)
kW 8 12 5
Casing
• Colour White
• Material Pre-coated sheetmetal
Dimensions
• Packing (height x wid h x depth)
mm 415 x 650 x 1016
•Unit (height x wid h x depth)
mm 890 x 480 x 344
Weight of unit
• Machine net weight kg 44
• Packed machine weight kg 47
Packing materials
• Material Carton / EPS / PP (straps)
• Weight kg 2,8
PED
• Category of unit Art 3§3
(c)
(c) Excluded from scope of PED due article 1, item 3.6 of 97/23/EC
Pump
Type DC motor Number of speed Inverter controlled Nominal ESP unit
• Cooling
(b)
kPa 83 55
•Heating
(a)
kPa 79 43
Power input W 110 135
Water side Heat exchanger
Type Brazed plate Quantity 1 Minimal water flow rate
(d)
(d) Flow switch setting
l/min 15
Nominal water flow rate
• Cooling
(a)
l/min 22.9 35 8
•Heating
(e)
(e) The sound pressure level is measured at 1 m from the unit. It is a relative value,
depending on the distance and acoustic environment.
l/min 25.8 40.1
Insula ion material Elastomeric foam
Expansion vessel
Volume l10 Maximum water pressure bar 3 Pre-pressure bar 1
Water filter
Diameter perforations mm 1 Material
• Body Copper and brass
• Filter element Stainless steel
Water circuit
• Piping connections diameter
(f)
(f) Value mentioned is connection after ball valves. Connection at unit is
G 1-1/4” female.
inch G 1-1/4” (female)
• Safety valve bar 3
• Manometer Yes
• Drain/fill valve Yes
• Shut off valves Yes
• Flow switch Yes
• Air purge valve Yes
Refrigerant circuit
• Gas side diameter mm 15.9
• Liquid side diameter mm 9.52
• Piping length restrictions See installation manual of the outdoor
unit and technical engeneering data
Sound level
• Sound power
(b)
dBA
• Sound pressure
(e)
dBA
Operation range
• Ambient space cooling °C 10~43
• Ambient space heating °C –20~20
• Waterside space cooling °C (5)10~20
• Waterside space heating °C 25~45
HXY080A7V1B HXY125A7V1B
Power supply
• Phase 1
• Frequency Hz 50
• Voltage V 220~240
Current
• Running current A2.5
•Z
max
• Minimum Ssc value kVA
Fuse
• Recommended fuse A6~16
Voltage range
• Minimum V 198
•Maximum V 264
Wiring connections
• For power supply
• Quantity of wires
3G
• Type of wires Wire type/size has to be selected
according to applicable legislation
• Communication cable (F1F2)
• Quantity of wires
2
• Type of wires 0.75~1.25 mm
2
• User interface (P1P2)
• Quantity of wires
2
• Type of wires 0.75~1.25 mm
2
Page 46
Page 47
Page 48
4P325971-1B 2012.07
Copyright 2012 Daikin
Loading...