Daikin FXCQ80MVE user guide manual

English
Deutsch
Français
Español
Italiano
Nederlands
Português
Ελληνικά
INSTALLATION MANUAL
SYSTEM Air Conditioners
MODELS
Ceiling-mounted cassette type (Double flow model)
FXCQ20MVE FXCQ50MVE FXCQ25MVE FXCQ63MVE FXCQ32MVE FXCQ80MVE FXCQ40MVE FXCQ125MVE
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
LESEN SIE DIESE HINWEISE VOR DER INSTALLATION SORGFÄLTIG DURCH. BEWAHREN SIE DIESE ANLEITUNG AN EINEM LEICHT ZUGÄNGLICHEN ORT FÜR SPÄTERES NACHSCHLAGEN AUF.
VEUILLEZ LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT L'INSTALLATION. CONSERVEZ CE MANUEL EN LIEU SÛR POUR POUVOIR VOUS Y REPORTER ULTÉRI­EUREMENT.
LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN. CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS.
PRIMA DELL'INSTALLAZIONE, LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI. CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO.
ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ. ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ ΜΕΛΛΟΝΤΙΚΗ ΑΝΑΦΟΡΑ.
LEES DEZE INSTRUCTIES ZOGVULDIG DOOR VOORDAT MET DE INSTALLATIE WORDT BEGONNEN. BEWAAR DEZE HANDLEIDING VOOR TOEKOMSTIG GEBRUIK OP EEN GESCHIKTE PLAATS ONDER HANDBEREIK.
LEIA ATENTAMENTE ESTAS INSTRUÇÕES ANTES DA INSTALAÇÃO. MANTENHA ESTE MANUAL NUM LOCAL DE FÁCIL ACESSO PARA CONSULTA.
ПЕРЕД УСТАНОВКОЙ ВНИМАТЕЛЬНО ПРОЧИТАЙТЕ ДАННЫЕ ИНСТРУКЦИИ. ХРАНИТЕ ДАННОЕ РУКОВОДСТВО В ЛЕГКО ДОСТУПНОМ МЕСТЕ ДЛЯ ЕГО ПОСЛЕДУЮЩЕГО ИСПОЛЬЗОВАНИЯ.
FXHQ32MAVE, FXHQ63MAVE, FXHQ100MAVE
FXKQ25MAVE, FXKQ32MAVE, FXKQ40MAVE, FXKQ63MAVE
FXAQ20MAVE, FXAQ25MAVE, FXAQ32MAVE, FXAQ40MAVE
FXAQ50MAVE, FXAQ63MAVE
FXUQ71MAV1, FXUQ100MAV1, FXUQ125MAV1
BEVQ71MAVE, BEVQ100MAVE, BEVQ125MAVE
FXLQ20MHV1, FXLQ25MHV1, FXLQ32MHV1, FXLQ40MHV1, FXLQ50MHV1,
FXMQ40MAVE, FXMQ50MAVE, FXMQ63MAVE, FXMQ80MAVE
FXMQ100MAVE, FXMQ125MAVE, FXMQ200MAVE, FXMQ250MAVE
FXLQ20MAVE, FXLQ25MAVE, FXLQ32MAVE, FXLQ40MAVE
FXLQ50MAVE, FXLQ63MAVE
FXNQ20MAVE, FXNQ25MAVE, FXNQ32MAVE, FXNQ40MAVE
FXNQ50MAVE, FXNQ63MAVE
DAIKIN.TCF.022E1/10-2007
TÜV Rheinlard EPS B.V.
0305020101
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Low Voltage 2006/95/EC
Machinery Safety 98/37/EC
Electromagnetic Compatibility 2004/108/EC
FXKQ25MVE, FXKQ32MVE, FXKQ40MVE, FXKQ63MVE
FXAQ20MVE, FXAQ25MVE, FXAQ32MVE, FXAQ40MVE, FXAQ50MVE, FXAQ63MVE
FXUQ71MV1, FXUQ100MV1, FXUQ125MV1
BEVQ71MVE, BEVQ100MVE, BEVQ125MVE
FXMQ125MFV1, FXMQ200MFV1, FXMQ250MFV1
FXAQ20MHV1, FXAQ25MHV1, FXAQ32MHV1, FXAQ40MHV1, FXAQ50MHV1
BEVQ50MVE
Shinri Sada
Manager Quality Control Department
1st of May 2009
FXZQ20MVE, FXZQ25MVE, FXZQ32MVE, FXZQ40MVE, FXZQ50MVE
FXCQ20MVE, FXCQ25MVE, FXCQ32MVE, FXCQ40MVE, FXCQ50MVE, FXCQ63MVE, FXCQ80MVE, FXCQ125MVE
FXMQ40MVE, FXMQ50MVE, FXMQ63MVE, FXMQ80MVE, FXMQ100MVE, FXMQ125MVE, FXMQ200MVE, FXMQ250MVE
FXLQ20MVE, FXLQ25MVE, FXLQ32MVE, FXLQ40MVE, FXLQ50MVE, FXLQ63MVE
FXNQ20MVE, FXNQ25MVE, FXNQ32MVE, FXNQ40MVE, FXNQ50MVE, FXNQ63MVE
FXHQ32MVE, FXHQ63MVE, FXHQ100MVE
DAIKIN INDUSTRIES, LTD.
FXSQ20MVE, FXSQ25MVE, FXSQ32MVE, FXSQ40MVE, FXSQ50MVE, FXSQ63MVE, FXSQ80MVE, FXSQ100MVE, FXSQ125MVE
EN60335-2-40,
3P109591-1E
VRV SYSTEM Air Conditioners Installation manual
WARNING
CAUTION

CONTENTS

1. SAFETY PRECAUTIONS................................................ 1
2. BEFORE INSTALLATION ................................................ 2
3. SELECTING INSTALLATION SITE ................................. 3
4. PREPARATIONS BEFORE INSTALLATION.................... 4
5. INDOOR UNIT INSTALLATION ....................................... 4
6. REFRIGERANT PIPING WORK ..................................... 5
7. DRAIN PIPING WORK .................................................... 7
8. ELECTRIC WIRING WORK ............................................ 8
9. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER........................................ 9
10. DECORATION PANEL INSTALLATION ......................... 11
11. FIELD SETTINGS ......................................................... 11
12. TEST OPERATION........................................................ 11
The original instructions are written in English. All other lan­guages are translations of the original instructions.
1. SAFETY PRECAUTIONS
Be sure to follow this “SAFETY PRECAUTIONS”. This product comes under the term “appliances not accessible to the general public”. This is a class A product. In a domestic environment this prod­uct may cause radio interference in which case the user may be required to take adequate measures.
This manual classifies the precautions into WARNINGS and CAUTIONS. Be sure to follow all the precautions below: They are all impor­tant for ensuring safety.
WARNING ............. Indicates a potentially hazardous situ-
ation which, if not avoided, could result in death or serious injury.
CAUTION .............. Indicates a potentially hazardous situ-
ation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
• After the installation is completed, test the air conditioner and check if the air conditioner operates properly. Give the user adequate instructions concerning the use and cleaning of the indoor unit according to the Operation Manual. Ask the user to keep this manual and the Operation Manual together in a handy place for future reference.
• Ask your local dealer or qualified personnel to carry out installa­tion work. Improper installation may result in water leakage, electric shocks or a fire.
• Perform installation work in accordance with this installation manual. Improper installation may result in water leakage, electric shocks or a fire.
• Consult your local dealer regarding what to do in case of refrigerant leakage. When the air conditioner is installed in a small room, it is nec­essary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in
the event of a leakage. Otherwise, this may lead to an accident due to oxygen defi­ciency.
• Be sure to use only the specified parts and accessories for installation work. Failure to use the specified parts may result in the air condi­tioner falling down, water leakage, electric shocks, a fire, etc.
• Install the air conditioner on a foundation that can withstand its mass. Insufficient strength may result in the air conditioner falling down and causing injury. In addition, it may lead to vibration of indoor units and cause unpleasant chattering noise.
• Carry out the specified installation work in consideration of strong winds, typhoons, or earthquakes. Improper installa­tion may result in an accident such as air conditioner falling.
• Make certain that all electrical work is carried out by qualified personnel according to the applicable legislation (note 1) and this installation manual, using a separate circuit. In addition, even if the wiring is short, make sure to use a wir­ing that has sufficient length and never connect additional wiring to make the length sufficient. Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire. (note 1) applicable legislation means “All international,
national and local directives, laws, regulations and/ or codes which are relevant and applicable for a certain product or domain”.
• Make sure that all wiring is secure, using the specified wiring and ensuring that external forces do not act on the terminal connections or wiring. Incomplete connection or fixing may cause an overheat or a fire.
• When wiring the remote controller wiring and transmission wiring, and wiring the power supply, form the wiring orderly so that the control box cover can be securely fastened. If the control box cover is not in place, overheat of the termi­nals, electric shocks or a fire may be caused. If refrigerant gas leaks during installation work, ventilate the
• area immediately. Toxic gas may be produced if refrigerant gas comes into con­tact with a fire.
After completing the installation work, check to make sure that there is no leakage of refrigerant gas. Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of a fire, such as a fan heater, stove or cooker.
• Disconnect the power supply before touching the electric components. If you touch the live part, you may get an electric shocks.
• Earth the air conditioner. Do not connect the earth wiring to gas or water piping, light­ning conductor or telephone earth wiring. Incomplete earthing may cause electric shocks or a fire. A high surge current from lightning or other sources may cause damage to the air conditioner.
• Be sure to install an earth leakage circuit breaker. Failure to do so may cause electric shocks and a fire.
• Install drain piping according to this installation manual to ensure good drainage, and insulate the piping to prevent condensation.
English 1
Improper drain piping may cause water leakage, make the furniture get wet.
• Install the air conditioner, power supply wiring, remote con­troller wiring and transmission wiring at least 1 meter away from televisions or radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
• Install the indoor unit as far as possible from fluorescent lamps. If a wireless remote controller kit is installed, the transmission distance may be shorter in a room where an electronic light­ing type (inverter or rapid start type) fluorescent lamp is installed.
• Do not install the air conditioner in places such as the follow­ing:
1. Where there is mist of oil, oil spray or vapour for example
a kitchen. Resin parts may deteriorate, and cause them to fall out or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is pro-
duced. Corrosion of copper pipings or brazed parts may cause the refrigerant to leak.
3. Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
4. Where flammable gases may leak, where carbon fibre or
ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled. If the gas should leak and remained around the air condi­tioner, it may cause ignition.
• The air conditioner is not intended for use in a potentially explosive atmosphere.
Where exposed to combustible gases and where vol-
atile flammable gas like thinner or gasoline is used. (Gas in the vicinity of the unit could ignite.)
Where machines can generate electromagnetic
waves. (Control system may malfunction.)
Where the air contains high levels of salt such as that
near the ocean and where voltage fluctuates greatly such as that in factories. Also in vehicles or vessels.
This unit, both indoor and outdoor, is suitable for installation in
• a commercial and light industrial environment. If installed as a household appliance it could cause electro­magnetic interference.
2-1 PRECAUTIONS
• Be sure to read this manual before installing the indoor unit.
• Entrust installation to the place of purchase or a qualified ser­viceman. Improper installation could lead to leaks and, in worse cases, electric shock of fire.
• Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could cause the unit to fall out of place, or could lead to leaks and, in worse cases, electric shock or fire.
2-2 ACCESSORIES
Check the following accessories are included with your unit.
Name Metal clamp
Quantity 1 pc. 1 pc.
Shape
Name Drain hose
Quantity 1 pc. 1 each
Paper pattern for
installation
Insulation for fitting

2. BEFORE INSTALLATION

When moving the unit while removing it from the carton
box, be sure to lift it by holding on to the four lifting lugs without exerting any pressure on other parts, especially, the refrigerant piping, drain piping, and other resin parts.
• Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect refrigerant will prevent normal operation of the unit.)
• The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them!
• Decide upon a line of transport.
• Leave the unit inside its packaging while moving, until reach­ing the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
• When moving the unit at or after opening, hold the unit by the hanger brackets (×4). Do not apply force to the refrigerant piping, drain piping or plastic parts.
• When selecting installation site, refer to the paper pattern.
• For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.
• Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or filled with oil vapor or spray
like in kitchens. (Plastic parts may deteriorate which could eventually cause the unit to fall out of place, or could lead to leaks.)
Where corrosive gas like sulfurous gas exists. (Cop-
per tubing and brazed spots may corrode, which could eventually lead to refrigerant leaks.)
Shape
Name Washer fixing plate Sealing pad
Quantity 4 pcs. 1 each
Shape
Name
Quantity 8 pcs. 8 pcs.
Shape
Name Screws (M5)
Quantity 4 pcs.
Shape
Washer for hanging
bracket
For paper pattern for installation
for gas pipe
for liquid pipe
Large
Small
Clamp
(Other)
• Operation manual
• Installation manual
• Screws for fixing panels are attached to decoration panel.
2 English
2-3 OPTIONAL ACCESSORIES
NOTE
The items with WARNING and CAUTION marks in the instruction manual are the items pertaining to possibilities for bodily injury and material damage in addition to the general usage of the product. Accordingly, it is necessary that you make a full explanation about the described contents and also ask your customers to read the instruction manual.
• The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1)
• These are two types of remote controllers: wired and wire­less. Select a remote controller from Table 2 according to customer request and install in an appropriate place.
Tabl e 1
Model
FXCQ20 · 25 · 32MVE BYBC32GJW1 · BYBC32G-W1 FXCQ40 · 50MVE BYBC50GJW1 · BYBC50G-W1 FXCQ63MVE BYBC63GJW1 · BYBC63G-W1 FXCQ80 · 125MVE BYBC125GJW1 · BYBC125G-W1
Optional decoration panel
White
Tabl e 2
Remote controller
Wired type
Wireless type
Heat pump type Cooling only type
• If the you wishes to use a remote controller that is not listed above, select a suitable remote controller after consulting catalogs and technical materials.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checked
Are the indoor and outdoor unit fixed firmly?
Is the gas leak test finished?
Is the unit fully insulated? Condensate water may drip. Does drainage flow
smoothly? Does the power supply volt-
age correspond to that shown on the name plate?
Are wiring and piping cor­rect?
Is the unit safely grounded?
Is wiring size according to specifications?
Is something blocking the air outlet or inlet of either the indoor or outdoor units?
Are refrigerant piping length and additional refrigerant charge noted down?
If not properly done, what is likely to occur
The units may drop, vibrate or make noise.
It may result in insufficient cooling.
Condensate water may drip.
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
Dangerous at electric leak­age.
The unit may malfunction or the components burn out.
It may result in insufficient cooling.
The refrigerant charge in the system is not clear.
Check
c. Points for explanation about operations
2-4 NOTES TO INSTALLER
Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different functions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.

3. SELECTING INSTALLATION SITE

Please attach additional thermal insulation material to the unit body when it is believed that the relative humidity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 10 mm or more as thermal insulation mate­rial.
(1) Select an installation site where the following condi-
tions are fulfilled and that meets with your customer’s approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• In the upper space of the indoor unit where there is no possible dripping of water from the refrigerant pipe, drain pipe, water pipe, etc.
• If supporting structural members are not strong enough to take the unit’s weight, the unit could fall out of place and cause serious injury.
• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service can be ensured.
• Where piping between indoor and outdoor units is possi­ble within the allowable limit. (Refer to the installation manual for the outdoor unit.)
• Any vents, light fixtures, or other appliances which may disturb the airflow might cause the top side to become dirty if located too nearby, so follow the figure below when installing.
• Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televi­sions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
b. Items to be checked at time of delivery
Also review the “SAFETY PRECAUTIONS”
Items to be checked Check Did you explain about operations while showing the
instruction manual to your customer? Did you hand the instruction manual over to your cus-
tomer?
English 3
2500 or more
Decoration panel
Ceiling opening
Indoor unit
Suspension bolt (× 4)
D (Panel outside dimensions)
A (Ceiling opening)
B (Suspension pitch)
C (Unit outside dimensions)
20
20
20
20
680 (Panel outside dimensions)
640 (Ceiling opening)
600 (Unit outside dimensions)
520 (Suspension pitch)
(length:mm)
160
[ Relative positioning of ceiling and unit ]
Hanger
Ceiling surface
(length:mm)
For installation
in high places
[ Space required for installation ]
350
1000
100 100
15001500
(length:mm)
Model A (mm) B (mm) C (mm) D (mm) FXCQ20 · 25 · 32MVE 990 820 775 1030 FXCQ40 · 50MVE 1205 1035 990 1245 FXCQ63MVE 1390 1220 1175 1430 FXCQ80 · 125MVE 1880 1710 1665 1920
(2) Make the ceiling opening needed for installation, where
applicable.
[ Installation example ]
Ceiling slab
Anchor
Long nut or turn-buckle
100mm
Suspension bolt
[ PRECAUTION ]
If installing the wireless kit in a room with electronic fluores­cent lighting (inverter or rapid start type), the remote con­troller’s transmission distance may be shortened. Indoor units should be installed as far away from fluorescent light­ing as possible.
(2) Ceiling height
These units can be installed with ceilings up to 3 m in height. Install this unit where the height of bottom panel is more than 2.5 m so that the user cannot easily touch.
(3) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the paper pattern for instal­lation. Refer to it to check for points requiring reinforcing.)

4. PREPARATIONS BEFORE INSTALLATION

(1) Relation of ceiling opening to units and suspension
bolt position
False ceiling
Note: All the above parts are eld supplied.
• Refer to the paper pattern for installation for ceiling open­ing dimension.
• Create the ceiling opening required for installation. From the side of the opening to the casing outlet, implement the refrigerant and drain piping and wiring for remote con­troller (unnecessary for wireless type) and indoor-out­door unit casing outlet. Refer to each PIPING or WIRING section.
• After making an opening in the ceiling, it may be neces­sary to reinforce ceiling beams to keep the ceiling level and to prevent it from vibrating. Consult the builder for details.
(3) Install the suspension bolts. (Use either a W3/8 or M10
size bolt.)
Use a hole-in-anchor for existing ceilings, and a sunken insert, sunken anchor or other part to be procured in the field for new ceilings to reinforce the ceiling to bearing the weight of the unit. Adjust clearance from the ceiling before proceeding further.

5. INDOOR UNIT INSTALLATION

Installing optional accessories (except for the decoration panel) before installing the indoor unit is easier. However, for existing ceilings, install branch duct before installing the unit.
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts designated by our company.
4 English
(1) Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and washer from the upper and lower sides of the hanger bracket. The washer fixing plate will prevent the washer from falling.
CAUTION
CAUTION
Part to be procured in the eld
Cut-out section
Paper pattern for installation
Screws (× 4 accessory)
(accessory)
[ Installation of paper pattern for installation ]
Guide section (4 corners)
Paper pattern for installation
Ceiling
Lower surface of the ceiling
[ Unit height adjustment ]
(accessory)
The unit body
Ceiling
Lower surface of the ceiling
The guide portion
[ Unit height adjustment ]
Washer (accessory)
Hanger bracket
(4) Check the unit is horizontally level.
Tighten (double nut)
[ Securing the hanger bracket ]
Insert
Washer xing plate
(accessory)
[ Securing the washer ]
[ For new ceilings ]
(2) Refer to the paper pattern for installation for ceiling
opening dimension. Consult the builder or carpenter for details.
• The center of the ceiling opening is indicated on the paper pattern for installation.
• After cutting out a slit for the unit in the center of the paper pattern for installation (accessory), install with the 4 screws (accessory).
• Fold the guide section of paper pattern for installation and adjust the height of the unit so the notch in the guide is at the position where you expect the ceiling surface to be.
Level
Vinyl tube
The indoor unit is equipped with a built-in drain pump and float switch. At each of the unit’s 4 corners, verify that it is level by using a level or a water-filled vinyl tube. (If the unit is inclined against condensate flow, the float switch may malfunction and cause water to drip.)
(5) Remove the washer fixing plate used for preventing the
washer from falling and tighten the upper nut.
(6) Remove the paper pattern for installation.
[ For existing ceilings ]
(2) Adjust the height of the unit.
Cut out the guide section of the paper pattern for installation attached, place on the bottom surface of the unit, and adjust the height of the unit so that the notch of the guide matches the lower surface of the ceiling.
Ceiling work
(3) Adjust the unit to the right position for installation.
English 5
(Refer to “
PREPARATIONS BEFORE INSTALLATION-(1)
”.)
(3) Perform steps (3), (4), (5) in For new ceilings.

6. REFRIGERANT PIPING WORK

• For the outdoor unit refrigerant piping, refer to the installation manual attached to the outdoor unit.
• Carry out insulation of both gas and liquid refrigerant piping securely. If not insulated, it may cause water leakage. For gas piping, use insulation material of which heat resistant temperature is not less than 120°C. For use under high humidity, strengthen the insulation mate­rial for refrigerant piping. If not strengthened, the surface of insulation material may sweat.
• Before installation work, make sure that the refrigerant is R410A. (Unless the refrigerant is R410A, the normal opera­tion cannot be expected.)
This air conditioner is a dedicated model for new refrig­erant R410A. Make sure to meet the requirements shown below and carry out installation work.
Use dedicated piping cutters and flaring tools for
R410A.
When making a flare connection, coat the flared inner
surface only with ether oil or ester oil.
Use only the flare nuts attached to the air conditioner.
If other flare nuts are used, it may cause refrigerant leakage.
To prevent contamination or moisture from getting
NOTE
CAUTION
CAUTION
CAUTION
Coat the flared inner surface only with ether oil or ester oil.
Fig. 1
Torque wrench
Spanner
Piping union
Flare nut
Fig. 2
Insulation for tting (accessory)
Small sealing pad
Insulation for tting (accessory)
(for gas line)
Clamp (×4) (accessory)
(for liquid line)
Liquid pipe
Fig. 3
(accessory)
Gas pipe
into the piping, take measures such as pinching or
taping the pipings. Do not mix substance other than the specified refriger­ant such as air into the refrigeration circuit. If the refrigerant leaks during the work, ventilate the room.
• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make sure to use a spanner and a torque wrench as shown in Fig. 1.
• For the dimension of flared part and the tightening torque, refer to the Table 3.
• When making a flare connection, coat the flared inner sur­face only with ether oil or ester oil.
(Refer to Fig. 2)
Then, turn the flare nut 3 to 4 times with your hand and screw in the nut.
• Refer to Table 3 for tightening torque.
Tabl e 3
Pipe
gauge
6.4
(1/4”)
9.5
(3/8”)
12.7
(1/2”)
15.9
(5/8”)
Tightening torque
(N·m)
15.7 ± 1.5 8.9 ± 0.2
36.3 ± 3.6 13.0 ± 0.2
54.9 ± 5.4 16.4 ± 0.2
68.6 ± 6.8 19.5 ± 0.2
Flare
dimension A
(mm)
Flare shape
0
±
0
0
2
±
45
0
90
2
R0.4-0.8
A
• Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas leakage by thor­oughly studying the following figure and using the attached heat insulating materials for fitting. (Fasten both ends with the clamps (accessory).) (Refer to Fig. 3)
• Wrap the sealing pad (accessory) only around the insulation for the joints on the gas piping side.
Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause condensation or burns if touched.
CAUTION TO BE TAKEN WHEN BRAZING REFRIGER­ANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal (BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux. (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains flu­orine, it will damage the refrigerant oil.)
The flare nuts used must be those included with the main body.
Over-tightening may damage the flare and cause a refriger­ant leakage.
Use “ Table 4 ” as a reference if a torque wrench is not available. Once work is complete, make sure there is no gas leaking. As the flare nut is tightened with the wrench, the torque will sud­denly increase. From that position, tighten the nut to the angle shown on “ Table 4 ”.
6 English
• Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the piping. If your brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, and could cause system malfunction.
• When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or while inserting nitrogen into the refrigerant piping. Once this is done, con­nect the indoor unit with a flared or a flanged connection.
• Nitrogen should be set to 0.02 MPa with a pressure-reducing valve if brazing while inserting nitrogen into the piping.
Pressure-
Refrigerant piping
Part to be brazed
Nitrogen
Taping
hands valve
reducing valve
Nitrogen
Not recommendable but in case of emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installa­tion method mentioned below.
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown below:
Tabl e 4
CAUTION
1-1.5m
1-1.5m
Hanger bracket
Ceiling slab
600
mm
310mm)
290
mm
1-1.5m
300mm
Hanger bracket
Adjustable
Drain raising pipe
Drain hose (accessory)
Metal clamp (accessory)
Portable pump
Water inlet lid
Close
Open
Bucket
Refrigerant piping
Water inlet
Pipe size Further tightening angle
6.4 (1/4”) 60 to 90 degrees Approx. 150mm
9.5 (3/8”) 60 to 90 degrees Approx. 200mm 12.7 (1/2”) 30 to 60 degrees Approx. 250mm 15.9 (5/8”) 30 to 60 degrees Approx. 300mm
Recommended arm length
of tool
Metal clamp (accessory)
Large sealing pad (accessory)
4mm

7. DRAIN PIPING WORK

Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings.
(1) Carry out the drain piping
• The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe (vinyl tube; pipe size: 25 mm; outer dimension: 32 mm).
• Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from forming.
• If the drain hose cannot be sufficiently set on a slope, exe­cute the drain raising piping.
• To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
PRECAUTIONS FOR DRAIN RAISING PIPING
• Install the drain raising pipes at a height of less than 310 mm.
• Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
If converging multiple drain pipes, install according to the procedure shown below.
100mm
T-joint converging drain pipes
Setting the unit at an angle opposite to the drain piping might cause leaks.
• Use the drain hose and the metal clamp. Insert the drain hose into the drain socket, up to the tape. Tighten the clamp until the screw head is less than 4 mm from the hose.
• Wrap the attached sealing pad over the clamp and drain hose to insulate.
• Insulate the drain hose inside the building.
English 7
Tape
Metal clamp
Drain hose
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) After piping work is finished, check drainage flows
smoothly.
• Open the water inlet lid, add approximately 2.5 liter of water gradually and check drainage flow.
[ WHEN ELECTRIC WIRING WORK IS FINISHED ]
• Check drainage flow during COOL running, explained under “TEST OPERATION.”
[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED ]
CAUTION
NOTE
Terminal block
220V-240V single phase power supply
Electric parts box lid
TEST
• Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground during lighting storms.
8-2 ELECTRICAL CHARACTERISTICS
• Remove the electric parts box lid, connect a power supply and remote controller to the terminals. (Refer to the “HOW TO CONNECT WIRINGS”) Be sure attach the electric parts box lid before turning on the power. Next, press the inspection/test operation button “ ” on the
TEST
remote controller. The unit will engage the test operation mode. Press the operation mode selector button “ ” until selecting FAN OPERATION “ ”. Then, press the ON/OFF button “ ”. The indoor unit fan and drain pump will start up. Check that the water has drained from the unit. Press “ ” to go back to the first mode.
Be careful when doing so because the fan is turning at
the same time.
• Attach the electric parts box lid as before.
• Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
• Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

8. ELECTRIC WIRING WORK

8-1 GENERAL INSTRUCTIONS
• All field supplied parts and materials and electric works must conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also attached to the electric parts box lid.
• For remote controller wiring details, refer to the installation manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched. If wiring and piping between the outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
• A circuit breaker capable of shutting down power supply to the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, light­ning rods, or telephone ground wires.
• Gas pipes
: might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is used.
Wiring diagram label
Units
220-
240
Voltage
range
Max. 264 Min. 198
Max. 242 Min. 198
Model
FXCQ20MVE FXCQ25 · 32MVE 0.5 15 0.015 0.4 FXCQ40 · 50MVE 0.8 15 0.020 0.6 FXCQ63MVE 0.9 15 0.030 0.7 FXCQ80MVE 1.1 15 0.050 0.9 FXCQ125MVE 1.3 15 0.085 1.0 FXCQ20MVE FXCQ25 · 32MVE 0.5 15 0.015 0.4 FXCQ40 · 50MVE 0.8 15 0.020 0.6 FXCQ63MVE 0.9 15 0.030 0.7 FXCQ80MVE 1.3 15 0.050 1.0 FXCQ125MVE 1.5 15 0.085 1.2
Hz Volts
50
60 220
Power supply
MCA MFA kW FLA
0.5 15 0.010 0.4
0.5 15 0.010 0.4
Fan motor
MCA:Min. Circuit Amps (A); MFA:Max. Fuse Amps (A) kW: Fan Motor Rated Output (kW); FLA:Full Load Amps (A)
8-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
Remote controller
Power supply wiring
Model
FXCQ20MVE FXCQ25 · 32MVE FXCQ40 · 50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE
Field
fuses
Wire Size Wire Size
Wiring size
H05VV
15A
-U3G
NOTE 1)
and length must comply with local codes.
Allowable length of transmission wiring between indoor/outdoor units and between the indoor unit and the remote controller is as follows. (1) Outdoor unit – Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit – Remote controller:
Max. 500 m
1. Shows only in case of protected piping. Use H07RN-F in case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
wiring
Transmission wiring
Sheathed wire
(2 wire)
NOTE 2)
0.75
-
1.25 mm
2
8 English
9. WIRING EXAMPLE AND HOW TO SET
CAUTION
CAUTION FOR WIRING
WARNING
Insulation sleeve
Ring type crimp style terminals
Wiring
Fig. 4
Fig. 5
Use wires the same in size (if the air conditioner is in simultaneous multi operation)
P
1
P
2
F
1
F
2
T
1
T
2
Terminal block for unit transmission wirings
Clamp
(accessory)
Transmission wiring between units
Remote controller wiring (*)
Power supply wiring (*)
Ground terminal
Power supply terminal block
Field supplied wire
Ground wiring (*)
THE REMOTE CONTROLLER
9-1 HOW TO CONNECT WIRINGS
Methods of wiring power supply, connecting transmission and remote controller wiring
• Do not carry out soldering finish when stranded wires are used. (Otherwise, the loosening of wires may result in abnor­mal heat radiation.)
Remote controller wiring Transmission wiring
Terminal block for remote controller wiring
Electric parts box
Electric parts box lid
Guide plate
Power supply wiring
Ground wiring
Terminal block for power supply
• Power supply wiring Remove the electric parts box lid shown in the figure, and connect to the terminal block (power supply) inside. At this time, run the wiring from the power supply side of the guide plate to inside the machine.
• Transmission wiring and remote controller wiring Connect the terminal block (remote controller / transmission wiring) so there is no mistake. At this time, run the remote controller / transmission wiring from the transmission wiring side of the guide plate to inside the machine.
• Be sure to attach the sealing material or putty (field supplied) to hole of wiring to prevent the infiltration of water as well as any insects and other small creatures from outside. Other­wise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps. Also, when wiring, make sure the lid on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box lid firmly. When attaching the electric parts box lid, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the same locations outside of the unit, separating them by at least 50mm, otherwise electrical noise (external static) could cause mistaken operation or breakage.
(Abnormal heating may occur if the wirings are not tightened securely.)
• Use the required wirings, connect them securely and fix these wirings securely so that external force may not apply to the terminals.
• Use a proper screw driver for tightening the terminal screws. If an improper screw driver is used, it may damage the screw head and a proper tightening cannot be carried out. If a terminal is over tightened, it may be damaged.
• Refer to the table shown below for tightening torque of terminals
Tabl e 5
Tightening torque (N · m)
Terminal block for remote controller and transmission wiring
Terminal for power supply 1.47 ± 0.14 Earth terminal 1.69 ± 0.25
0.88 ± 0.08
• Do not carry out soldering finish when stranded wirings are used.
• When wiring, form the wirings orderly so that the control box lid can be securely fastened. If the control box lid is not in place, the wirings may come out or be sandwiched by the box and the lid and cause electric shocks or a fire.
• Use only specified wire and tightly connect wires to termi­nals. Be careful wires do not place external stress on termi­nals. Keep wiring in neat order and so as not to obstruct other equipment such as popping open the electric parts box lid. Make sure the lid closes tight. Incomplete connections could result in overheating, and in worse case, electric shock or fire.
.
• For connection to the terminal block, use ring type crimp style terminals with insulation sleeve or insulate the wirings prop­erly.
• Connect the terminal as shown in Fig. 5.
English 9
9-2 WIRING EXAMPLE
NOTE
Power supply wiring Transmission wiring
Switch
Fuse
Power supply
Main switch
Remote controller
Indoor unit
BS unit (Only for Heat recovery system)
LN
IN/D OUT/D
F
1 F2 F1 F2
Control box
LN
P1P
2
P1P
2
F1F2T1T
2
P1P
2
P1P
2
F1F2T1T
2
LN
P1P
2
P1P
2
F1F2T1T
2
LN LN
P1P
2
P1P
2
F1F2T1T
2
Outdoor unit
No. 1 System
Indoor unit A
Indoor unit B
Indoor unit C
Most downstream Indoor unit
Power supply
220-240V
50Hz
or
220V
60Hz
• Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 systems)
3. When including BS unit
Power supply
220-240V
50Hz
or
220V
60Hz
LN
Outdoor unit
Control box
IN/D OUT/D
F
1F2F1F2
No. 3 System
BS unit
Control box
IN/DOUT/D
F
1F2F1F2
BS unit
Control box
IN/DOUT/D
F
1F2F1F2
1. When using 1 remote controller for 1 indoor unit. (Nor­mal operation)
2. For group control or use with 2 remote controllers
Power supply
220-240V
50Hz
or
220V
60Hz
Outdoor unit
LN
Indoor unit A
Control box
IN/D OUT/D
F
1 F2 F1 F2
No. 2 System
Indoor unit B
LN
P1P
2
F1F2T1T
2 LNP1P2F1F2T1T2 LNP1P2F1F2T1T2 LNP1P2F1F2T1T2
Indoor unit C
Most downstream indoor unit
Indoor unit A
LN LN
P1P2F1F2T1T
2
P1P2F1F2T1T
Most
2
downstream indoor unit
P1P
2
P1P
2
• It is not necessary to designate indoor unit address when using group control. The address is automatically set when power is activated.
[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the same system. However, branch switches and branch circuit breakers must be selected carefully.
2. Do not ground the equipment on gas pipes, water pipes or lightning rods, or crossground with telephones. Improper grounding could result in electric shock.
9-3
CONTROL BY 2 REMOTE CONTROLLERS (Con­trolling 1 indoor unit by 2 remote controllers)
• When using 2 remote controllers, one must be set to “MAIN” and the other to “SUB”.
MAIN/SUB CHANGEOVER
(1) Insert a screw driver into the recess between the
upper and lower part of remote controller and, working from the 2 positions, pry off the upper part.
The remote controller PC board is attached to the upper part of remote controller.
Upper part of remote controller
10 English
Lower part of
P1P
2
P1P
P1P
2
For use with 2
Fig. 6
remote controllers
2
Insert the screwdriver here and gently work off the upper part of remote controller.
remote controller
(2) Turn the MAIN/SUB changeover switch on one of the
Only one remote controller needs to be changed if factory settings have remained untouched.
(Factory setting)
S
M
S
S
M
Remote controller PC board
SETTING
MODE NO.
SECOND CODE NO.
FIELD SET MODE
FIRST CODE NO.
two remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to “M”.)
Wiring Method (See ‘‘ELECTRIC WIRING WORK’’)
(3) Remove the electric parts box lid (4) Add remote control 2 (slave) to the terminal block for
remote controller (P
, P2) in the electric parts box.
1
(There is no polarity.) (Refer to Fig. 6 and 8-3.)
9-4 COMPUTERISED CONTROL (FORCED OFF
AND ON/OFF OPERATION)
(1) Wire specifications and how to perform wiring
• Connect input from outside to terminals T1 and T2 of the terminal block for remote controller.
2. Slide the insulation tube according to the arrow as shown in fig. so that the connector can be completely covered.
3. Bind the opening of insulation tube with the attached clamp material.
Clamp (accessory)

11. FIELD SETTINGS

Make sure the electric parts box lids are closed on the indoor and outdoor units. Field setting must be made from the remote controller in accordance with the installation condition.
• Setting can be made by changing the “Mode No.”, “FIRST CODE NO.”, and “SECOND CODE NO.”.
• The “Field Settings” included with the remote control lists the order of the settings and method of operation. Setting is made in all units in a group. To set for individual indoor units or to check the setting, use the mode Nos. (with “2” in upper digit) in parentheses ( ).
Wire specification Sheathed vinyl cord or cable (2 wire) Gauge Length Max. 100 m
External terminal
(2) Actuation
• The following table explains FORCED OFF and ON/OFF
FORCED OFF ON/OFF OPERATION Input “ON” stops operation (impossible
by remote controllers.) Input OFF enables control by remote
controller.
(3) How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to
9-5 CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the group No. For details, refer to the manual of each optional control­lers for centralized control.

10. DECORATION PANEL INSTALLATION

Refer to the installation manual of the panels.
[ CAUTION ]
SWING FLAP MOTOR WIRING METHOD
1. Connect two lead wires of swing flap motor mounted on the
decoration panel to the connectors of main body.
English 11
F2 T1 T2
FORCED OFF
Input A
0.75 - 1.25 mm
Contact that can ensure the minimum applica­ble load of 15 V DC, 10 mA.
OPERATIONS in response to Input A.
select operation.
Input OFF
Input ON
2
ON turns ON unit.
OFF turns OFF unit.
• Set the remote controller to the field set mode. For details, refer to the “HOW TO SET IN THE FIELD”, in the remote controller manual.
• When in the field set mode, select mode No. 12, then set the first code (switch) No. to “1”. Then set second code (position) No. to “01” for FORCED OFF and “02” for ON/ OFF OPERATION. (FORCED OFF at factory set)

12. TEST OPERATION

Refer to the installation manual of the outdoor unit.
• The operation lamp of the remote controller will flash when an malfunction occurs. Check the malfunction code on the liquid crystal display to identify the point of trouble. An expla­nation of malfunction codes and the corresponding trouble is provided in “CAUTION FOR SERVICING” of the outdoor unit. If any of the items in Table 6 are displayed, there may be a problem with the wiring or power, so check the wiring again.
Tabl e 6
Remote control display Content
“Concentrated Manage­ment” is lit up
“U4” is lit up
“UH” is lit up
No display
• There is a short circuit at the FORCED OFF terminals (T1, T2)
• The power on the outdoor unit is off.
• The outdoor unit has not been wired for power supply.
• Incorrect wiring for the transmission wiring and / or FORCED OFF wiring.
• The power on the indoor unit is off.
• The indoor unit has not been wired for power supply.
• Incorrect wiring for the remote control­ler wiring, the transmission wiring and / or the FORCED OFF wiring.
3P258319-5K EM02A084C
(1511) HT
Loading...