Daikin FXCQ40M7, FXCQ20M7, FXCQ50M7, FXCQ63M7, FXCQ80M7 Service Manual

...
SiBE39-402A
Service
Manual
R-410A Heat Pump 50Hz
SiBE39-402A
Table of Contents i
50Hz
1. Introduction ............................................................................................vi
1.1 Safety Cautions....................................................................................... vi
Part 1 General Information ........................................................... 1
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................3
2.1 Indoor Units..............................................................................................3
3. Capacity Range.......................................................................................4
Part 2 Specifications .................................................................... 5
1. Specifications ..........................................................................................6
1.1 Outdoor Units ...........................................................................................6
1.2 Indoor Units..............................................................................................8
Part 3 List of Electrical and Functional Parts ............................27
1. List of Electrical and Functional Parts...................................................28
1.1 Outdoor Unit...........................................................................................28
1.2 Indoor Unit..............................................................................................29
Part 4 Refrigerant Circuit ........................................................... 33
1. Refrigerant Circuit .................................................................................34
1.1 RXYSQ4·5·6M........................................................................................34
2. Functional Parts Layout ........................................................................36
2.1 RXYSQ4·5·6M........................................................................................36
Part 5 Function............................................................................ 37
1. Operation Mode ....................................................................................38
2. Basic Control.........................................................................................39
2.1 Normal Operation...................................................................................39
2.2 Compressor PI Control...........................................................................40
2.3 Electronic Expansion Valve PI Control...................................................41
2.4 Cooling Operation Fan Control...............................................................42
3. Special Control......................................................................................43
3.1 Startup Control .......................................................................................43
3.2 Oil Return Operation ..............................................................................44
3.3 Defrosting Operation ..............................................................................46
3.4 Pump-down Residual Operation ............................................................47
3.5 Restart Standby......................................................................................48
3.6 Stopping Operation ................................................................................49
3.7 Pressure Equalization Prior to Startup ...................................................50
4. Protection Control .................................................................................51
4.1 High Pressure Protection Control...........................................................51
4.2 Low Pressure Protection Control............................................................52
SiBE39-402A
ii Table of Contents
4.3 Discharge Pipe Protection Control .........................................................53
4.4 Inverter Protection Control .....................................................................54
5. Other Control.........................................................................................55
5.1 Demand Operation.................................................................................55
5.2 Heating Operation Prohibition ................................................................55
6. Outline of Control (Indoor Unit) .............................................................56
6.1 Drain Pump Control................................................................................56
6.2 Louver Control for Preventing Ceiling Dirt..............................................58
6.3 Thermostat Sensor in Remote Controller...............................................59
6.4 Freeze Prevention..................................................................................61
6.5 View of Operations of Swing Flaps ........................................................62
Part 6 Test Operation ................................................................. 63
1. Test Operation ......................................................................................64
1.1 Procedure and Outline ...........................................................................64
1.2 Operation When Power is Turned On ....................................................67
2. Outdoor Unit PC Board Layout .............................................................68
3. Field Setting ..........................................................................................69
3.1 Field Setting from Remote Controller.....................................................69
3.2 Field Setting from Outdoor Unit..............................................................81
3.3 Detail of Setting Mode............................................................................87
Part 7 Troubleshooting ...............................................................97
1. Troubleshooting by Remote Controller .................................................99
1.1 The INSPECTION / TEST Button...........................................................99
1.2 Self-Diagnosis by Wired Remote Controller.........................................100
1.3 Self-Diagnosis by Wireless Remote Controller ....................................101
1.4 Operation of the Remote Controller’s Inspection / Test Operation Button. 103
1.5 Remote Controller Service Mode .........................................................104
2. List of Malfunction Code......................................................................106
3. Malfunction Code Indication by Outdoor Unit PCB .............................108
4. Troubleshooting by Indication on the Remote Controller ....................110
4.1 “A0” Indoor Unit: Error of External Protection Device ...........................110
4.2 “A1” Indoor Unit: PC Board Defect.........................................................111
4.3 “A3” Indoor Unit: Malfunction of Drain Level Control System (33H)......112
4.4 “A6” Indoor Unit: Fan Motor (M1F) Lock, Overload...............................114
4.5 “A7” Indoor Unit: Malfunction of Swing Flap Motor (MA).......................115
4.6 “A9” Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (20E)........................................................117
4.7 “AF” Indoor Unit: Drain Level above Limit..............................................119
4.8 “AJ” Indoor Unit: Malfunction of Capacity Determination Device ..........120
4.9 “C4” Indoor Unit: Malfunction of Thermistor (R2T) for Heat Exchanger 121
4.10 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes..........122
4.11 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air.........123
4.12 “CA” Indoor Unit: Malfunction of Thermistor for Discharge Air...............124
4.13 “CJ” Indoor Unit: Malfunction of Thermostat Sensor in Remote Controller. 125
4.14 “E1” Outdoor Unit: PC Board Defect ......................................................126
4.15 “E3” Outdoor Unit: Actuation of High Pressure Switch ..........................127
4.16 “E4” Outdoor Unit: Actuation of Low Pressure Switch...........................128
4.17 “E5” Compressor Motor Lock ................................................................129
SiBE39-402A
Table of Contents iii
4.18 “E7” Malfunction of Outdoor Unit Fan Motor..........................................130
4.19 “E9” Outdoor Unit: Malfunction of Moving Part of Electronic Expansion Valve132
4.20 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature ..................134
4.21 “H9” Outdoor Unit: Malfunction of Thermistor for Outdoor Air (R1T).....135
4.22 “J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R3T) ....136
4.23 “J5” Outdoor Unit: Malfunction of Thermistor (R2T) for Suction Pipe ...137
4.24 “J6” Outdoor Unit: Malfunction of Thermistor
(R4T) for Outdoor Unit Heat Exchanger...............................................138
4.25 “J9” Malfunction of Receiver Gas Pipe Thermistor (R5T).....................139
4.26 “JA” Outdoor Unit: Malfunction of High Pressure Sensor......................140
4.27 “JC” Outdoor Unit: Malfunction of Low Pressure Sensor.......................141
4.28 “L4” Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise.................................................................................142
4.29 “L5” Outdoor Unit: Inverter Compressor Abnormal ...............................143
4.30 “L8” Outdoor Unit: Inverter Current Abnormal.......................................144
4.31 “L9” Outdoor Unit: Inverter Start up Error..............................................145
4.32 “LC” Outdoor Unit: Malfunction of Transmission between Inverter and
Control PC Board .................................................................................146
4.33 “P4” Outdoor Unit: Malfunction of Inverter Radiating Fin Temperature
Rise Sensor..........................................................................................148
4.34 “PJ” Outdoor Unit: Faulty Combination of Inverter and Fan Driver .......149
4.35 “UO” Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................150
4.36 “U2” Power Supply Insufficient or Instantaneous Failure ......................151
4.37 “U3” Check Operation not Executed......................................................153
4.38 “
U4
” Malfunction of Transmission between Indoor Units and Outdoor Units 154
4.39 “U5” Malfunction of Transmission between Remote Controller and
Indoor Unit............................................................................................156
4.40 “U8” Malfunction of Transmission between Master and Slave
Remote Controllers ..............................................................................157
4.41 “U9” Malfunction of Transmission between Indoor and Outdoor Units
in the Same System .............................................................................158
4.42 “UA” Excessive Number of Indoor Units ................................................160
4.43 “UC” Address Duplication of Central Remote Controller ........................161
4.44 “UE” Malfunction of Transmission between Central Remote Controller
and Indoor Unit.....................................................................................162
4.45 “UF” Refrigerant System not Set, Incompatible Wiring/Piping ...............164
4.46 “UH” Malfunction of System, Refrigerant System Address Undefined...165
5. Troubleshooting by Indication on the Centralized Remote Controller.166
5.1 “UE” Malfunction of Transmission between Centralized Remote
Controller and Indoor Unit ....................................................................166
5.2 “M1” PC Board Defect ............................................................................167
5.3 “M8” Malfunction of Transmission between Optional Controllers for
Centralized Control...............................................................................168
5.4 “MA” Improper Combination of Optional Controllers for Centralized Control169
5.5 “MC” Address Duplication, Improper Setting ..........................................171
6. Troubleshooting by Indication on the Unified ON/OFF Controller.......172
6.1 Operation Lamp Blinks .........................................................................172
6.2 Display “Under Host Computer Integrate Control” Blinks
(Repeats Single Blink)..........................................................................174
SiBE39-402A
iv Table of Contents
6.3 Display “Under Host Computer Integrate Control” Blinks
(Repeats Double Blink) ........................................................................177
7. Troubleshooting (OP: Schedule Timer)...............................................178
7.1 “UE” Malfunction of Transmission between Central Remote Controller
and Indoor Unit.....................................................................................178
7.2 “M1” PC Board Defect ............................................................................180
7.3 “M8” Malfunction of Transmission between Optional Controllers for
Centralized Control...............................................................................181
7.4 “MA” Improper Combination of Optional Controllers for Centralized Control182
7.5 “MC” Address Duplication, Improper Setting ..........................................184
8. Check..................................................................................................185
Part 8 Appendix......................................................................... 187
1. Piping Diagrams..................................................................................188
1.1 Outdoor Unit.........................................................................................188
1.2 Indoor Unit............................................................................................189
2. Wiring Diagrams for Reference...........................................................192
2.1 Outdoor Unit.........................................................................................192
2.2 Indoor Unit............................................................................................193
3. Thermistor Resistance / Temperature Characteristics........................198
4. Pressure Sensor .................................................................................200
Part 9 Precautions for New Refrigerant (R410A) ..................... 201
1. Precautions for New Refrigerant (R410A)...........................................202
1.1 Outline..................................................................................................202
1.2 Service Tools........................................................................................204
Index .............................................................................................i
Drawings & Flow Charts ...............................................................iii
Introduction SiBE39-402A
vi
1. Introduction
1.1 Safety Cautions
Cautions and Warnings
! Be sure to read the following safety cautions before conducting repair work. ! The caution items are classified into “ Warning” and “ Caution”. The “ Warning
items are especially important since they can lead to death or serious injury if they are not followed closely. The “ Caution” items can also lead to serious accidents under some conditions if they are not followed. Therefore, be sure to observe all the safety caution items described below.
! About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction. The instruction is shown inside or near the symbol. ! After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the customer
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before disassembling the equipment for a repair. Working on the equipment that is connected to a power supply can cause an electrical shook. If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits, do not touch any electrically charged sections of the equipment.
If the refrigerant gas discharges during the repair work, do not touch the discharging refrigerant gas. The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded section, release the refrigerant gas completely at a well-ventilated place first. If there is a gas remaining inside the compressor, the refrigerant gas or refrigerating machine oil discharges when the pipe is disconnected, and it can cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Be sure to discharge the capacitor completely before conducting repair work. A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the power cable plug. Plugging or unplugging the power cable plug to operate the equipment can cause an electrical shock or fire.
SiBE39-402A Introduction
vii
1.1.2 Cautions Regarding Products after Repair
Caution
Do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock.
Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the equipment. The internal fan rotates at a high speed, and cause injury.
Do not tilt the unit when removing it. The water inside the unit can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled down sufficiently before conducting repair work. Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place. Using the welder in an enclosed room can cause oxygen deficiency.
Warning
Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock, excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment. If the installation site does not have sufficient strength and if the installation work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard installation frame. Incorrect use of the installation frame and improper installation can cause the equipment to fall, resulting in injury.
For integral units only
Be sure to install the product securely in the installation frame mounted on a window frame. If the unit is not securely mounted, it can fall and cause injury.
For integral units only
Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
Introduction SiBE39-402A
viii
1.1.3 Inspection after Repair
Be sure to use the specified cable to connect between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals. Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable. If the cover is not mounted properly, the terminal connection section can cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable. Damaged or modified power cable can cause an electrical shock or fire. Placing heavy items on the power cable, and heating or pulling the power cable can damage the cable.
Do not mix air or gas other than the specified refrigerant in the refrigerant system. If air enters the refrigerating system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before charging the refrigerant. After charging refrigerant, make sure that there is no refrigerant leak. If the leak cannot be located and the repair work must be stopped, be sure to perform pump-down and close the service valve, to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself is harmless, but it can generate toxic gases when it contacts flames, such as fan and other heaters, stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed of the old battery to prevent children from swallowing it. If a child swallows the coin battery, see a doctor immediately.
Warning
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. If the packing and seal are not installed properly, water can enter the room and wet the furniture and floor.
For integral units only
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet all the way. If the plug has dust or loose connection, it can cause an electrical shock or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to replace them. Damaged cable and wires can cause an electrical shock, excessive heat generation or fire.
Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it can cause an electrical shock, excessive heat generation or fire.
SiBE39-402A Introduction
ix
1.1.4 Using Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each icon is described in the table below:
1.1.5 Using Icons List
Caution
Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it. Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Check the grounding, and repair it if the equipment is not properly grounded. Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 Mohm or higher. Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair. Faulty drainage can cause the water to enter the room and wet the furniture and floor.
Icon Type of
Information
Description
Note:
Note A “note” provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Caution
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an unexpected result or has to restart (part of) a procedure.
Warning
Warning A “warning” is used when there is danger of personal injury.
Reference A “reference” guides the reader to other places in this binder or
in this manual, where he/she will find additional information on a specific topic.
Introduction SiBE39-402A
x
SiBE39-402A
General Information 1
Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................3
2.1 Indoor Units..............................................................................................3
3. Capacity Range.......................................................................................4
Model Names of Indoor/Outdoor Units SiBE39-402A
2 General Information
1. Model Names of Indoor/Outdoor Units
Indoor Units
Indoor Units (Connection Unit Series)
Note: BEV unit is required for each indoor unit.
Outdoor Units (Inverter Series)
Power Supply Symbol
V1: 1φ, 220~240V, 50Hz VE: 1φ, 220~240V, 50Hz / 1φ, 220V, 60Hz V3: 1φ, 230V, 50Hz
Type Model Name
Power
Supply
Ceiling mounted cassette type (Double flow)
FXCQ 20M7 25M7 32M7 40M7 50M7 63M7 80M7
125M7
VE
Ceiling mounted cassette type (Multi flow) 600×600
FXZQ 20M 25M 32M 40M 50M
Ceiling mounted cassette type (Multi flow)
FXFQ 20M7 25M7 32M7 40M7 50M7 63M7 80M7
125M7
V1
Ceiling mounted cassette corner
FXKQ 25M 32M 40M 63M
VE
Slim ceiling mounted built-in type (L.S.P)
FXDQ 20N 25N 32N 40N 50N 63N
Ceiling mounted built-in type (L.S.P)
FXDQ 20M7 25M7
V1
Ceiling mounted built-in type (M.S.P)
FXSQ 20M7 25M7 32M7 40M7 50M7 63M7 80M7
100M7 125M7
Ceiling mounted duct type
FXMQ 40M 50M 63M 80M 100M 125M
VE
Ceiling suspended type
FXHQ 32M 63M 100M
Wall mounted type
FXAQ 20M 25M 32M 40M 50M 63M
Floor standing type
FXLQ 20M 25M 32M 40M 50M 63M
Concealed Floor standing
FXNQ 20M 25M 32M 40M 50M 63M
Type Model Name
Power
Supply
Wall Mounted Type
FXAQ
-MH
20MH 25MH 32MH 40MH 50MH
————
V1
Floor Standing Type
FXLQ
-MH
20MH 25MH 32MH 40MH 50MH
————
Connection Unit
BEVQ
-M
50M 50M 50M 50M 50M VE
Series Model Name
Power
Supply
Inverter Heat Pump RXYSQ 4M 5M 6M V3
SiBE39-402A External Appearance
General Information 3
2. External Appearance
2.1 Indoor Units
Ceiling mounted cassette type (Double flow)
FXCQ20M7 FXCQ25M7 FXCQ32M7 FXCQ40M7 FXCQ50M7 FXCQ63M7 FXCQ80M7 FXCQ125M7
Ceiling mounted duct type
FXMQ40M FXMQ50M FXMQ63M FXMQ80M FXMQ100M FXMQ125M
Ceiling mounted cassette type (Multi flow)
600×600
FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M
Ceiling suspended type
FXHQ32M FXHQ63M FXHQ100M
Ceiling mounted cassette type (Multi flow)
FXFQ20M7 FXFQ25M7 FXFQ32M7 FXFQ40M7 FXFQ50M7 FXFQ63M7 FXFQ80M7 FXFQ125M7
Wall mounted type
FXAQ20M FXAQ25M FXAQ32M FXAQ40M FXAQ50M FXAQ63M
Ceiling mounted cassette corner type
FXKQ25M FXKQ32M FXKQ40M FXKQ63M
Floor standing type
FXLQ20M FXLQ25M FXLQ32M FXLQ40M FXLQ50M FXLQ63M
Slim ceiling mounted built-in type
FXDQ20N FXDQ25N FXDQ32N FXDQ40N FXDQ50N FXDQ63N
Concealed floor standing type
FXNQ20M FXNQ25M FXNQ32M FXNQ40M FXNQ50M FXNQ63M
Ceiling mounted built-in type
FXDQ20M7 FXDQ25M7
Wall Mounted Type (Connection Unit Series)
FXAQ20MH FXAQ25MH FXAQ32MH +BEVQ50M FXAQ40MH FXAQ50MH
Ceiling mounted built-in type
FXSQ20M7 FXSQ25M7 FXSQ32M7 FXSQ40M7 FXSQ50M7 FXSQ63M7 FXSQ80M7 FXSQ100M7 FXSQ125M7
Floor Standing Type (Connection Unit Series)
FXLQ20MH FXLQ25MH FXLQ32MH +BEVQ50M FXLQ40MH FXLQ50MH
Capacity Range SiBE39-402A
4 General Information
3. Capacity Range
Outdoor Units
Indoor Units
Capacity Range 4HP 5HP 6HP
RXYSQ 4M7 5M7 6M7
No of Indoor Units to be Connected
689
Total Capacity Index of Indoor Units to be Connected
50~130 62.5~162.5 70~182
Capacity Range
0.8 HP
1
HP
1.25HP1.6 HP2HP
2.5HP3.2 HP
4
HP
5
HP
Capacity Index 20 25 31.25 40 50 62.5 80 100 125
Ceiling Mounted Cassette Type (Double Flow)
FXCQ 20M7 25M7 32M7 40M7 50M7 63M7 80M7 125M7
Ceiling Mounted Cassette Type (Multi Flow) 600
×
600
FXZQ 20M 25M 32M 40M 50M
Ceiling Mounted Cassette Type (Multi Flow)
FXFQ 20M7 25M7 32M7 40M7 50M7 63M7 80M7 125M7
Ceiling Mounted Cassette Corner Type
FXKQ 25M 32M 40M 63M
Slim Ceiling Mounted Built-in Type
FXDQ 20N 25N 32N 40N 50N 63N
Ceiling Mounted Built-in Type
FXDQ20M725M7———————
Ceiling Mounted Built-in Type
FXSQ 20M7 25M7 32M7 40M7 50M7 63M7 80M7 100M7 125M7
Ceiling Mounted Duct Type
FXMQ 40M 50M 63M 80M 100M 125M
Ceiling Suspended Type
FXHQ 32M 63M 100M
Wall Mounted Type
FXAQ 20M 25M 32M 40M 50M 63M
Floor Standing Type
FXLQ 20M 25M 32M 40M 50M 63M
Concealed Floor Standing Type
FXNQ 20M 25M 32M 40M 50M 63M
Wall Mounted Type
FXAQ
-MH
20MH 25MH 32MH 40MH 50MH
Floor Standing Type
FXLQ
-MH
20MH 25MH 32MH 40MH 50MH
SiBE39-402A
Specifications 5
Part 2
Specifications
1. Specifications ..........................................................................................6
1.1 Outdoor Units ...........................................................................................6
1.2 Indoor Units..............................................................................................8
Specifications SiBE39-402A
6 Specifications
1. Specifications
1.1 Outdoor Units
Notes: H1 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m,
level difference : 0m.
H2 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB or 6°CWB / Equivalent piping length : 7.5m,
level difference : 0m.
Model Name RXYSQ4M7V3B RXYSQ5M7V3B
H1 Cooling Capacity
kcal / h 9,600 12,000
Btu / h 38,200 47,700
kW 11.2 14.0
H2 Heating Capacity
kcal / h 10,700 13,700
Btu / h 42,600 54,600
kW 12.5 16.0 Casing Color Ivory White Ivory White Dimensions: (H×W×D) mm 1,345×900×320 1,345×900×320 Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Piston Displacement m³/h 19.36 19.36 Number of Revolutions r.p.m 6,480 6,480 Motor Output×Number
of Units
kW 2.5×1 3.0×1
Starting Method Direct on line Direct on line
Fan
Type Propeller Fan Propeller Fan Motor Output W 70×2 70×2 Air Flow Rate m³/min 106 106 Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm φ9.5 (Flare Connection) φ9.5 (Flare Connection) Gas Pipe mm φ15.9 (Flare Connection) φ15.9 (Flare Connection)
Machine Weight kg 127 127
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Inverter Overload Protector, Fusible Plugs, Fuse
High Pressure Switch, Fan Driver Overload Protector,
Inverter Overload Protector, Fusible Plugs, Fuse Defrost Method Reverse cycle defrosting Reverse cycle defrosting Capacity Control % 24~100 24~100
Refrigerant
Refrigerant Name R410A R410A Charge kg 5.8 5.8 Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil
DAPHNE FVC68D DAPHNE FVC68D
Charge Volume L 1.6 1.6 Standard Accessories Installation Manual, Operation Manual, Clamps Installation Manual, Operation Manual, Clamps Drawing No. 4D045796
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 7
Notes: H1 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m,
level difference : 0m.
H2 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB or 6°CWB / Equivalent piping length : 7.5m,
level difference : 0m.
Model Name RXYSQ6M7V3B
H1 Cooling Capacity
kcal / h 13,300
Btu / h 52,900
kW 15.5
H2 Heating Capacity
kcal / h 15,400
Btu / h 61,400
kW 18.0 Casing Color Ivory White Dimensions: (H×W×D) mm 1,345×900×320 Heat Exchanger Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Piston Displacement m³/h 19.36 Number of Revolutions r.p.m 6,480 Motor Output×Number
of Units
kW 3.5×1
Starting Method Direct on line
Fan
Type Propeller Fan Motor Output W 70×2 Air Flow Rate m³/min 106 Drive Direct Drive
Connecting Pipes
Liquid Pipe mm φ9.5 (Flare Connection) Gas Pipe mm φ19.1 (Brazing Connection)
Machine Weight kg 127
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Inverter
Overload Protector, Fusible Plugs, Fuse Defrost Method Reverse cycle defrosting Capacity Control % 24~100
Refrigerant
Refrigerant Name R410A Charge kg 5.8 Control Electronic Expansion Valve
Refrigerator Oil
DAPHNE FVC68D
Charge Volume L 1.6 Standard Accessories Installation Manual, Operation Manual, Clamps, Auxiliary Piping Drawing No. 4D045796
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
8 Specifications
1.2 Indoor Units
Ceiling Mounted Cassette Type (Multi Flow) 600×600
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model FXZQ20MVE FXZQ25MVE FXZQ32MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,150
Btu/h 7,900 9,900 12,500
kW 2.3 2.9 3.7
H2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
H3 Heating Capacity
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm
260 (286)×575×575
( ): Include Control Box
260 (286)×575×575
( ): Include Control Box
260 (286)×575×575
( ): Include Control Box
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×10×1.5 2×10×1.5 2×10×1.5 Face Area 0.269 0.269 0.269
Fan
Model QTS32C15M QTS32C15M QTS32C15M Type Turbo Fan Turbo Fan Turbo Fan Motor Output × Number
of Units
W 55×1 55×1 55×1
Air Flow Rate (H/L)
m³/min 9/7 9/7 9.5/7.5
cfm 318/247 318/247 335/265
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene/
Foamed Polyethylene
Foamed Polystyrene/ Foamed Polyethylene
Foamed Polystyrene/
Foamed Polyethylene
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Drain Pipe mm
VP20
External Dia. 26
Internal Dia. 20
VP20
External Dia. 26
Internal Dia. 20
VP20
External Dia. 26
Internal Dia. 20 Machine Weight kg 18 18 18 H5 Sound Level (H/L) (230V) dBA 30/25 30/25 32/26 Safety Devices Fuse Fuse Fuse Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series R410A M Series
Decoration Panels (Option)
Model BYFQ60BW1 BYFQ60BW1 BYFQ60BW1 Panel Color White (Ral 9010) White (Ral 9010) White (Ral 9010) Dimensions: (H×W×D) mm 55×700×700 55×700×700 55×700×700
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Weight kg 2.7 2.7 2.7
Standard Accessories
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Sealing Pads, Clamps, Screws, Washer for Hanging Bracket, Insulation for Fitting.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Sealing Pads, Clamps, Screws, Washer for Hanging Bracket, Insulation for Fitting.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Sealing Pads, Clamps, Screws, Washer for Hanging Bracket, Insulation for Fitting.
Drawing No. 3D038929A
() () ()
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 9
Ceiling Mounted Cassette Type (Multi Flow) 600×600
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model FXZQ40MVE FXZQ50MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 4,000 5,000
Btu/h 15,900 19,900
kW 4.7 5.8
H2 Cooling Capacity (19.0°CWB) kW 4.5 5.6
H3 Heating Capacity
kcal/h 4,300 5,400
Btu/h 17,000 21,500
kW 5.0 6.3
Casing Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm
260 (286)×575×575
( ): Include Control Box
260 (286)×575×575
( ): Include Control Box
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×10×1.5 2×10×1.5 Face Area 0.269 0.269
Fan
Model QTS32C15M QTS32C15M Type Turbo Fan Turbo Fan Motor Output × Number
of Units
W 55×1 55×1
Air Flow Rate (H/L)
m³/min 11/8 14/10
cfm 388/282 494/353
Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene/Foamed
Polyethylene
Foamed Polystyrene/Foamed
Polyethylene
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Drain Pipe mm
VP20
External Dia. 26
Internal Dia. 20
VP20
External Dia. 26
Internal Dia. 20 Machine Weight kg 18 18 H5 Sound Level (H/L) (230V) dBA 36/28 41/33 Safety Devices Fuse Fuse, Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series
Decoration Panels (Option)
Model BYFQ60BW1 BYFQ60BW1 Panel Color White (Ral 9010) White (Ral 9010) Dimensions: (H×W×D) mm 55×700×700 55×700×700
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Weight kg 2.7 2.7
Standard Accessories
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Sealing Pads, Clamps, Screws, Washer for Hanging Bracket, Insulation for Fitting.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Sealing Pads, Clamps, Screws, Washer for Hanging Bracket, Insulation for Fitting.
Drawing No. 3D038929A
() ()
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
10 Specifications
Ceiling Mounted Cassette Corner Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward.
During actual operation, these values are normally somewhat higher as a result of installation conditions.
Model FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,500 3,150 4,000 6,300
Btu/h 9,900 12,500 15,900 25,000
kW 2.9 3.7 4.7 7.3
H2 Cooling Capacity (19.0°CWB) kW 2.8 3.6 4.5 7.1
H3 Heating Capacity
kcal/h 2,800 3,400 4,300 6,900
Btu/h 10,900 13,600 17,000 27,300
kW 3.2 4.0 5.0 8.0 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) mm 215×1,110×710 215×1,110×710 215×1,110×710 215×1,310×710
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×11×1.75 2×11×1.75 2×11×1.75 3×11×1.75 Face Area 0.180 0.180 0.180 0.226
Fan
Model 3D12H1AN1V1 3D12H1AN1V1 3D12H1AP1V1 4D12H1AJ1V1 Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 15×1 15×1 20×1 45×1
Air Flow Rate (H/L)
m³/min 11/9 11/9 13/10 18/15
cfm 388/318 388/318 459/353 635/530
Drive Direct Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material Polyethylene Foam Polyethylene Foam Polyethylene Foam Polyethylene Foam
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection)
Drain Pipe mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25 Machine Weight kg 31 31 31 34 H5 Sound Level (H/L) (220V) dBA 38/33 38/33 40/34 42/37
Safety Devices
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable Outdoor Units R410A M Series R410A M Series R410A M Series R410A M Series
Decoration Panels (Option)
Model BYK45FJW1 BYK45FJW1 BYK45FJW1 BYK71FJW1 Panel Color White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) Dimensions: (H×W×D) mm 70×1,240×800 70×1,240×800 70×1,240×800 70×1,440×800
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Weight kg 8.5 8.5 8.5 9.5
Standard Accessories
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws, Washers, Positioning Jig for Installation, Insulation for Hanger Bracket, Air Outlet Blocking Pad.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws, Washers, Positioning Jig for Installation, Insulation for Hanger Bracket, Air Outlet Blocking Pad.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws, Washers, Positioning Jig for Installation, Insulation for Hanger Bracket, Air Outlet Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad. Drawing No. 3D038813
()()()()
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 11
Slim Ceiling Mounted Built-in Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
H4 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
H5 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections. When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
Model FXDQ20NVE FXDQ25NVE FXDQ32NVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,150
Btu/h 7,900 9,900 12,500
kW 2.3 2.9 3.7
H2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
H3 Heating Capacity
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) mm 200×900×620 200×900×620 200×900×620
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×12×1.5 2×12×1.5 2×12×1.5 Face Area 0.176 0.176 0.176
Fan
Model — Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 62×1 62×1 62×1
Air Flow Rate (H/L) m³/min 9.5/7.5 9.5/7.5 10.5/8.5 External Static Pressure Pa 44-15 H4 44-15 H4 44-15 H4 Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene Air Filter Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Drain Pipe mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20) Machine Weight kg 26 26 26 H5 Sound Level (H/L) dBA 33/29 33/29 33/29 Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard Accessories
Operation Manual, Installation Manual, Warranty, Drain Hose, Sealing Pads, Clamps, Washers, Insulation for Fitting, Clamp Metal, Washer Fixing Plate, Screws for Duct Flanges, Air Filter
Operation Manual, Installation Manual, Warranty, Drain Hose, Sealing Pads, Clamps, Washers, Insulation for Fitting, Clamp Metal, Washer Fixing Plate, Screws for Duct Flanges, Air Filter
Operation Manual, Installation Manual, Warranty, Drain Hose, Sealing Pads, Clamps, Washers, Insulation for Fitting, Clamp Metal, Washer Fixing Plate, Screws for Duct Flanges, Air Filter
Drawing No. 3D045744
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
12 Specifications
Slim Ceiling Mounted Built-in Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
H4 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
H5 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections. When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
Model FXDQ40NVE FXDQ50NVE FXDQ63NVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 4,000 5,000 6,300
Btu/h 15,900 19,900 25,000
kW 4.7 5.8 7.3
H2 Cooling Capacity (19.0°CWB) kW 4.5 5.6 7.1
H3 Heating Capacity
kcal/h 4,300 5,400 6,900
Btu/h 17,000 21,500 27,300
kW 5.0 6.3 8.0 Casing Color Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) mm 200×900×620 200×900×620 200×1100×620
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 3×12×1.5 3×12×1.5 3×12×1.5 Face Area 0.176 0.176 0.227
Fan
Model — Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 62×1 130×1 130×1
Air Flow Rate (H/L) m³/min 10.5/8.5 12.5/10.0 16.5/13.0 External Static Pressure Pa 44-15 H4 44-15 H4 44-15 H4 Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene Air Filter Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection)
Drain Pipe mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20) Machine Weight kg 27 28 31 H5 Sound Level (H/L) dBA 34/30 35/31 36/32 Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard Accessories
Operation Manual, Installation Manual, Warranty, Drain Hose, Sealing Pads, Clamps, Washers, Insulation for Fitting, Clamp Metal, Washer Fixing Plate, Screws for Duct Flanges, Air Filter
Operation Manual, Installation Manual, Warranty, Drain Hose, Sealing Pads, Clamps, Washers, Insulation for Fitting, Clamp Metal, Washer Fixing Plate, Screws for Duct Flanges, Air Filter
Operation Manual, Installation Manual, Warranty, Drain Hose, Sealing Pads, Clamps, Washers, Insulation for Fitting, Clamp Metal, Washer Fixing Plate, Screws for Duct Flanges, Air Filter
Drawing No. 3D045744
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 13
Ceiling Mounted Duct Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means "High static pressure-Standard".
H5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of installation conditions.
Model FXMQ40MVE FXMQ50MVE FXMQ63MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 4,000 5,000 6,300
Btu/h 15,900 19,900 25,000
kW 4.7 5.8 7.3
H2 Cooling Capacity (19.0°CWB) kW 4.5 5.6 7.1
H3 Heating Capacity
kcal/h 4,300 5,400 6,900
Btu/h 17,000 21,500 27,300
kW 5.0 6.3 8.0 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) mm 390×720×690 390×720×690 390×720×690
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 3×16×2.0 3×16×2.0 3×16×2.0 Face Area 0.181 0.181 0.181
Fan
Model D11/2D3AB1VE D11/2D3AB1VE D11/2D3AB1VE Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 100×1 100×1 100×1
Air Flow Rate (H/L)
m³/min 14/11.5 14/11.5 14/11.5
cfm 494/406 494/406 494/406 External Static Pressure Pa 157/157-118/108 H4 157/157-118/108 H4 157/157-118/108 H 4 Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber Air Filter H5 H5 H5
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection)
Drain Pipe mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25 Machine Weight kg 44 44 44 H7 Sound Level (H/L) dBA 39/35 39/35 39/35
Safety Devices
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
Drawing No. 3D038814
() () ()
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
14 Specifications
Ceiling Mounted Duct Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means "High static pressure-Standard".
H5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of installation conditions.
Model FXMQ80MVE FXMQ100MVE FXMQ125MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 8,000 10,000 12,500
Btu/h 31,800 39,700 49,600
kW 9.3 11.6 14.5
H2 Cooling Capacity (19.0°CWB) kW 9.0 11.2 14.0
H3 Heating Capacity
kcal/h 8,600 10,800 13,800
Btu/h 34,100 42,700 54,600
kW10.012.516.0 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) mm 390×720×690 390×1,110×690 390×1,110×690
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 3×16×2.0 3×16×2.0 3×16×2.0 Face Area 0.181 0.319 0.319
Fan
Model D11/2D3AA1VE 2D11/2D3AG1VE 2D11/2D3AF1VE Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 160×1 270×1 430×1
Air Flow Rate (H/L)
m³/min 19.5/16 29/23 36/29
cfm 688/565 1,024/812 1,271/1,024 External Static Pressure Pa 157/160-108/98 H4 157/172-98/98 H4 191/245-152/172 H4 Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber Air Filter H5 H5 H5
Piping Connections
Liquid Pipes mm φ9.5 (Flare Connection) φ9.5 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ15.9 (Flare Connection) φ15.9 (Flare Connection) φ15.9 (Flare Connection)
Drain Pipe mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25 Machine Weight kg 45 63 65 H7 Sound Level (H/L) dBA 42/38 43/39 45/42
Safety Devices
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.
Drawing No. 3D038814
() () ()
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 15
Ceiling Suspended Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model FXHQ32MVE FXHQ63MVE FXHQ100MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 3,150 6,300 10,000
Btu/h 12,500 25,000 39,700
kW 3.7 7.3 11.6
H2 Cooling Capacity (19.0°CWB) kW 3.6 7.1 11.2
H3 Heating Capacity
kcal/h 3,400 6,900 10,800
Btu/h 13,600 27,300 42,700
kW 4.0 8.0 12.5 Casing Color White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) Dimensions: (H×W×D) mm 195×960×680 195×1,160×680 195×1,400×680
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×12×1.75 3×12×1.75 3×12×1.75 Face Area 0.182 0.233 0.293
Fan
Model 3D12K1AA1 4D12K1AA1 3D12K2AA1 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 62×1 62×1 130×1
Air Flow Rate (H/L)
m³/min 12/10 17.5/14 25/19.5
cfm 424/353 618/494 883/688
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Wool Glass Wool Glass Wool Air Filter Resin Net (with Mold Resistant) Resin Net (with Mold Resistant) Resin Net (with Mold Resistant)
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ9.5 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ15.9 (Flare Connection) φ15.9 (Flare Connection)
Drain Pipe mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20) Machine Weight kg 24 28 33 H5 Sound Level (H/L) dBA 36/31 39/34 45/37
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Insulation for Fitting, Clamps, Washers.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Insulation for Fitting, Clamps, Washers.
Operation Manual, Installation Manual, Paper Pattern for Installation, Drain Hose, Clamp Metal, Insulation for Fitting, Clamps, Washers.
Drawing No. 3D035297
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
16 Specifications
Wall Mounted Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length:7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model FXAQ20MVE FXAQ25MVE FXAQ32MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,150
Btu/h 7,900 9,900 12,500
kW 2.3 2.9 3.7
H2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
H3 Heating Capacity
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0 Casing Color White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) Dimensions: (H×W×D) mm 290×795×230 290×795×230 290×795×230
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×14×1.4 2×14×1.4 2×14×1.4 Face Area 0.161 0.161 0.161
Fan
Model — Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Motor Output × Number
of Units
W 40×1 40×1 40×1
Air Flow Rate (H/L)
m³/min 7.5/4.5 8/5 9/5.5
cfm 265/159 282/177 318/194
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene / Foamed Polyethylene
Foamed Polystyrene / Foamed Polyethylene
Foamed Polystyrene / Foamed Polyethylene
Air Filter Resin Net (Washable) Resin Net (Washable) Resin Net (Washable)
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Drain Pipe mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13) Machine Weight kg 11 11 11 H5 Sound Level (H/L) dBA 35/29 36/29 37/29 Safety Devices Fuse Fuse Fuse Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Installation Panel, Paper Pattern for Installation, Insulation Tape, Clamps, screws.
Operation Manual, Installation Manual, Installation Panel, Paper Pattern for Installation, Insulation Tape, Clamps, screws.
Operation Manual, Installation Manual, Installation Panel, Paper Pattern for Installation, Insulation Tape, Clamps, screws.
Drawing No.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 17
Wall Mounted Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model FXAQ40MVE FXAQ50MVE FXAQ63MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 4,000 5,000 6,300
Btu/h 15,900 19,900 25,000
kW 4.7 5.8 7.3
H2 Cooling Capacity (19.0°CWB) kW 4.5 5.6 7.1
H3 Heating Capacity
kcal/h 4,300 5,400 6,900
Btu/h 17,000 21,500 27,300
kW 5.0 6.3 8.0 Casing Color White (B-272) White (B-272) White (B-272) Dimensions: (H×W×D) mm 290×1,050×230 290×1,050×230 290×1,050×230
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 2×14×1.4 2×14×1.4 2×14×1.4 Face Area 0.161 0.161 0.161
Fan
Model — Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Motor Output × Number
of Units
W 43×1 43×1 43×1
Air Flow Rate (H/L)
m³/min 12/9 15/12 19/14
cfm 424/318 530/424 671/494
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene / Foamed Polyethylene
Foamed Polystyrene / Foamed Polyethylene
Foamed Polystyrene / Foamed Polyethylene
Air Filter Resin Net (Washable) Resin Net (Washable) Resin Net (Washable)
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection)
Drain Pipe mm VP13 VP13 VP13 Machine Weight kg 14 14 14 H5 Sound Level (H/L) dBA 39/34 42/36 46/39 Safety Devices Fuse Fuse Fuse Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable outdoor unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Installation Panel, Paper Pattern for Installation, Insulation Tape, Clamps, screws.
Operation Manual, Installation Manual, Installation Panel, Paper Pattern for Installation, Insulation Tape, Clamps, screws.
Operation Manual, Installation Manual, Installation Panel, Paper Pattern for Installation, Insulation Tape, Clamps, screws.
Drawing No.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
18 Specifications
Floor Standing Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of installation conditions.
Model FXLQ20MVE FXLQ25MVE FXLQ32MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,150
Btu/h 7,900 9,900 12,500
kW 2.3 2.9 3.7
H2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
H3 Heating Capacity
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0 Casing Color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Dimensions: (H×W×D) mm 600×1,000×222 600×1,000×222 600×1,140×222
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 3×14×1.5 3×14×1.5 3×14×1.5 Face Area 0.159 0.159 0.200
Fan
Model D14B20 D14B20 2D14B13 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 15×1 15×1 25×1
Air Flow Rate (H/L)
m³/min 7/6 7/6 8/6
cfm 247/212 247/212 282/212
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber/ Urethane Foam Glass Fiber/ Urethane Foam Glass Fiber/ Urethane Foam Air Filter Resin Net (with Mold Resistant) Resin Net (with Mold Resistant) Resin Net (with Mold Resistant)
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection) Drain Pipe mm φ21 O.D (Vinyl Chloride) φ21 O.D (Vinyl Chloride) φ21 O.D (Vinyl Chloride)
Machine Weight kg 25 25 30 H5 Sound Level (H/L) dBA 35/32 35/32 35/32
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable Outdoor Unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Drawing No. 3D038816
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiBE39-402A Specifications
Specifications 19
Floor Standing Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of installation conditions.
Model FXLQ40MVE FXLQ50MVE FXLQ63MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 4,000 5,000 6,300
Btu/h 15,900 19,900 25,000
kW 4.7 5.8 7.3
H2 Cooling Capacity (19.0°CWB) kW 4.5 5.6 7.1
H3 Heating Capacity
kcal/h 4,300 5,400 6,900
Btu/h 17,000 21,500 27,300
kW 5.0 6.3 8.0 Casing Color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Dimensions: (H×W×D) mm 600×1,140×222 600×1,420×222 600×1,420×222
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 3×14×1.5 3×14×1.5 3×14×1.5 Face Area 0.200 0.282 0.282
Fan
Model 2D14B13 2D14B20 2D14B20 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 25×1 35×1 35×1
Air Flow Rate (H/L)
m³/min 11/8.5 14/11 16/12
cfm 388/300 494/388 565/424
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber/ Urethane Foam Glass Fiber/ Urethane Foam Glass Fiber/ Urethane Foam Air Filter Resin Net (with Mold Resistant) Resin Net (with Mold Resistant) Resin Net (with Mold Resistant)
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection) Drain Pipe mm φ21 O.D (Vinyl Chloride) φ21 O.D (Vinyl Chloride) φ21 O.D (Vinyl Chloride)
Machine Weight kg 30 36 36 H5 Sound Level (H/L) dBA 38/33 39/34 40/35
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable Outdoor Unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Drawing No. 3D038816
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiBE39-402A
20 Specifications
Concealed Floor Standing Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of installation conditions.
Model FXNQ20MVE FXNQ25MVE FXNQ32MVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,150
Btu/h 7,900 9,900 12,500
kW 2.3 2.9 3.7
H2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
H3 Heating Capacity
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0 Casing Color Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) mm 610×930×220 610×930×220 610×1,070×220
Coil (Cross Fin Coil)
Rows×Stages×Fin Pitch mm 3×14×1.5 3×14×1.5 3×14×1.5 Face Area 0.159 0.159 0.200
Fan
Model D14B20 D14B20 2D14B13 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output × Number
of Units
W 15×1 15×1 25×1
Air Flow Rate (H/L)
m³/min 7/6 7/6 8/6
cfm 247/212 247/212 282/212
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating Sound Absorbing Thermal Insulation Material Glass Fiber/ Urethane Foam Glass Fiber/ Urethane Foam Glass Fiber/ Urethane Foam Air Filter Resin Net (with Mold Resistant) Resin Net (with Mold Resistant) Resin Net (with Mold Resistant)
Piping Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection) Drain Pipe mm φ21 O.D (Vinyl Chloride) φ21 O.D (Vinyl Chloride) φ21 O.D (Vinyl Chloride)
Machine Weight kg 19 19 23 H5 Sound Level (H/L) dBA 35/32 35/32 35/32
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Connectable Outdoor Unit R410A M Series R410A M Series R410A M Series
Standard Accessories
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Operation Manual, Installation Manual, Insulation for Fitting, Drain Hose, Clamps, Screws, Washers, Level Adjustment Screw.
Drawing No. 3D038817
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3