Daikin FWF02B7TV1B, FWF03B7TV1B, FWF04B7TV1B, FWF05B7TV1B, FWF02B7FV1B Installation manuals

...
Page 1
INSTALLATION MANUAL
Fan coil units
FWF02B7TV1B FWF03B7TV1B FWF04B7TV1B FWF05B7TV1B
FWF02B7FV1B FWF03B7FV1B FWF04B7FV1B FWF05B7FV1B
Cover Cover
Type numbers
Page 2
tilizate în
e
le:
ази декларация:
CE - ATITIKTIES-DEKLARACIJA
CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - IZJAVA O SKLADNOSTI
CE - VASTAVUSDEKLARATSIOON
CE - IZJAVA-O-USKLAĐENOSTI
CE - MEGFELELŐSÉGI-NYILATKOZAT
, których dotyczy niniejsza deklaracja:
CE - VYHLÁSENIE-ZHODY
CE - UYUMLULUK-BİLDİRİSİ
, na katere se izjava nanaša:
CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
deklaruje na własną i wyłączną odpowiedzialność, że modele klimatyzatorów
declară pe proprie răspundere că aparatele de aer condiţionat la care se referă această declaraţie:
z vso odgovornostjo izjavlja, da so modeli klimatskih naprav
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
r
18
o
19
декларира на своя отговорност, че моделите климатична инсталация, за които се отнася т
x
b
20
21
m
17
CE - DEKLARACJA-ZGODNOŚCI
CE - DECLARAŢIE-DE-CONFORMITATE
19 Direktive z vsemi spremembami.
20 Direktiivid koos muudatustega.
21 Директиви, с техните изменения.
22 Direktyvose su papildymais.
23 Direktīvās un to papildinājumos.
24 Smernice, v platnom znení.
25 Değiştirilmiş halleriyle Yönetmelikler.
, na ktoré sa vzťahuje toto vyhlásenie:
Direktiivejä, sellaisina kuin ne ovat muutettuina.
irányelv(ek) és módosításaik rendelkezéseit.
14 v platném znění.
15 Smjernice, kako je izmijenjeno.
16
17 z późniejszymi poprawkami.
10 Direktiver, med senere ændringer.
11 Direktiv, med företagna ändringar.
12 Direktiver, med foretatte endringer.
13
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu klima modellerinin aşağıdaki gibi olduğunu beyan eder:
visiška savo atsakomybe skelbia, kad oro kondicionavimo prietaisų modeliai, kuriems yra taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk uzskaitīto modeĮu gaisa kondicionētāji, uz kuriem attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely
w
t
v
k
22
23
24
25
instrukcjami:
conformitate cu instrucţiunile noastre
инструкции:
16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie u
19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhendite
21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
льзования согласно нашим
a normgivande dokument, under
s našim návodom:
22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlad
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
ama:
01 Directives, as amended.
02 Direktiven, gemäß Änderung.
03 Directives, telles que modifiées.
04 Richtlijnen, zoals geamendeerd.
orutssetning av at
18 Directivelor, cu amendamentele respective.
pagal Sertifikatą <C>.
положително от <B> съгласно
Cертификата <C>.
23 Piezīmes * kā norādīts <A> un atbilstoši <B> pozitīvajam
22 Pastaba * kaip nustatyta <A> ir kaip teigiamai nuspręsta <B>
21 Забележка * както е изложено в <A> и оценено
05 Directivas, según lo enmendado.
06 Direttive, come da modifica.
07 √‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
08 Directivas, conforme alteração em.
09 Директив со всеми поправками.
*
**
<A> DAIKIN.TCF.028/10-2010
<B> KEMA (NB0344)
<C> 2134252.0551-QUA/EMC
súlade s osvedčením <C>.
<A>‘da belirtildiği gibi ve <C> Sertifikasına
göre <B> tarafından olumlu olarak
vērtējumam saskaņā ar sertifikātu <C>.
*
Not
24 Poznámka * ako bolo uvedené v <A> a pozitívne zistené <B> v
25
değerlendirildiği gibi.
.
Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehnično mapo.
Daikin Europe N.V. on volitatud koostama tehnilist dokumentatsiooni.
Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technickej konštrukcie.
**
19
**
20
Daikin Europe N.V. Teknik Yapı Dosyasını derlemeye yetkilidir
**
**
**
**
**
23
24
25
21
22
koittamat ilmastointilaitteiden mallit:
ingsmodellerna som berörs av denna deklaration innebär att:
дели кондиционеров воздуха, к которым относится настоящее заявление:
ingsmodeller som berøres av denne deklarasjon innebærer at:
ne, som denne deklaration vedrører:
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE - PROHLÁŠENÍ-O-SHODĚ
заявляет, исключительно под свою ответственность, что мо
erklærer under eneansvar, at klimaanlægmodeller
deklarerar i egenskap av huvudansvarig, att luftkonditioner
erklærer et fullstendig ansvar for at de luftkondisjoner
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tar
prohlašuje ve své plné odpovědnosti, že modely klimatizace, k nimž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da su modeli klima uređaja na koje se ova izjava odnosi:
u
q
s
n
11
12
09
10
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - DECLARAÇÃO-DE-CONFORMIDADE
СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
ation:
klärung bestimmt ist:
ation relates:
aarop deze verklaring betrekking heeft:
teljes felelőssége tudatában kijelenti, hogy a klímaberendezés modellek, melyekre e nyilatkozat vonatkozik:
j
c
y
h
13
14
15
16
declaración:
ação se refere:
referencia la
aatimuksia edellyttäen, että niitä käytetään ohjeidemme
ende dokument(er), forudsat at disse anvendes i henhold til vore
a instruktioner:
ma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
, odpovídají následujícím normám nebo normativním dokumentům:
lgende standard(er) eller andre normgivende dokument(er), under f
Machinery 2006/42/EC
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC
acordo com as nossas instruções:
инструкциям:
instrukser:
förutsättning att användning sker i överensstämmelse med vår
disse brukes i henhold til våre instrukser:
08 estão em conformidade com a(s) seguinte(s) nor
09 соответствуют следующим стандартам или другим нормативным документам, при условии их испо
10 overholder følgende standard(er) eller andet/andre retningsgiv
11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andr
h our
oraussetzung,
ormément à nos instructions:
oorwaarde dat ze worden gebruikt overeenkomstig
mukaisesti:
12 respektive utstyr er i overensstemmelse med fø
13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien v
14 za předpokladu, že jsou využívány v souladu s našimi pokyny
15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uput
19 ob upoštevanju določb:
20 vastavalt nõuetele:
21 следвайки клаузите на:
22 laikantis nuostatų, pateikiamų:
23 ievērojot prasības, kas noteiktas:
24 održiavajúc ustanovenia:
a(z) <C> tanúsítvány szerint.
<B> i Świadectwem <C>.
de <B> în conformitate cu Certificatul <C>.
skladu s certifikatom <C>.
17 Uwaga * zgodnie z dokumentacją <A>, pozytywną opinią
18 Notă * aşa cum este stabilit în <A> şi apreciat pozitiv
16 Megjegyzés * a(z) <A> alapján, a(z) <B> igazolta a megfelelést,
Certifikatet <C>.
11 Information * enligt <A> och godkänts av <B> enligt
25 bunun koşullarına uygun olarak:
da <B> secondo il Certificato <C>.
19 Opomba * kot je določeno v <A> in odobreno s strani <B> v
bedømmelse av <B> ifølge Sertifikat <C>.
hyväksynyt Sertifikaatin <C> mukaisesti.
souladu s osvědčením <C>.
12 Merk * som det fremkommer i <A> og gjennom positiv
13 Huom * jotka on esitetty asiakirjassa <A> ja jotka <B> on
14 Poznámka * jak bylo uvedeno v <A> a pozitivně zjištěno <B> v
positivo de <B> de acordo com o Certificado <C>.
·fi ÙÔ <B> Û‡Ìʈӷ Ì ÙÔ ¶ИЫЩФФИЛЩИОfi <C>.
положительным решением <B> согласно
kiidetud <B> järgi vastavalt sertifikaadile <C>.
Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan.
Společnost Daikin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce.
Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji.
A Daikin Europe N.V. jogosult a műszaki konstrukciós dokumentáció összeállítására.
**
**
**
**
14
15
16
20 Märkus * nagu on näidatud dokumendis <A> ja heaks
15 Napomena * kako je izloženo u <A> i pozitivno ocijenjeno od
Свидетельству <C>.
13
abrico.
e konstruktionsdata.
strane <B> prema Certifikatu <C>.
∏ Daikin Europe N.V. Â›Ó·È ÂÍÔ˘ÛÈÔ‰ÔÙË̤ÓË Ó· Û˘ÓÙ¿ÍÂÈ ÙÔÓ ∆¯ÓÈÎfi Ê¿ÎÂÏÔ Î·Ù·Û΢‹˜.
A Daikin Europe N.V. está autorizada a compilar a documentação técnica de f
Компания Daikin Europe N.V. уполномочена составить Комплект технической документации.
Daikin Europe N.V. er autoriseret til at udarbejde de teknisk
**
**
**
**
08
07
09
10
henhold til Certifikat <C>.
Daikin Europe N.V. ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej.
Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie.
**
**
17
18
onstruktionsfilen.
Tekniske konstruksjonsfilen.
Jean-Pierre Beuselinck
General Manager
Ostend, 2nd of November 2010
Daikin Europe N.V. är bemyndigade att sammanställa den tekniska k
Daikin Europe N.V. har tillatelse til å kompilere den
**
**
11
12
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
CE - ¢H§ø™H ™YMMOPºø™H™
declares under its sole responsibility that the air conditioning models to which this declar
erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Er
a
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
d
01
02
i modello a cui è riferita questa dichiarazione:
déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclar
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units w
declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace
dichiara sotto sua responsabilità che i condizionator
f
l
e
i
06
04
03
05
attere normativo, a patto che vengano usati in conformità alle
matif(s), pour autant qu'ils soient utilisés conf
mative document(s), provided that these are used in accordance wit
mdokument oder -dokumenten entspricht/entsprechen, unter der V
10 under iagttagelse af bestemmelserne i:
11 enligt villkoren i:
12 gitt i henhold til bestemmelsene i:
13 noudattaen määräyksiä:
14 za dodržení ustanovení předpisu:
15 prema odredbama:
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Щ· МФУЩ¤П· ЩˆУ ОПИМ·ЩИЫЩИОТУ Ы˘ЫОВ˘ТУ ЫЩ· ФФ›· ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declar
g
p
08
07
FWF02B7TV1B*, FWF03B7TV1B*, FWF04B7TV1B*, FWF05B7TV1B*,
FWF02B7FV1B*, FWF03B7FV1B*, FWF04B7FV1B*, FWF05B7FV1B*,
* = , , 1, 2, 3, ..., 9
instructions:
daß sie gemäß unseren Anweisungen eingesetzt werden:
01 are in conformity with the following standard(s) or other nor
02 der/den folgenden Norm(en) oder einem anderen Nor
nuestras instrucciones:
nostre istruzioni:
onze instructies:
03 sont conformes à la/aux norme(s) ou autre(s) document(s) nor
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a car
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op v
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) nor mativo(s), siempre que sean utilizados de acuerdo con
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
07 В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
01 following the provisions of:
02 gemäß den Vorschriften der:
03 conformément aux stipulations des:
04 overeenkomstig de bepalingen van:
EN60335-2-40,
05 siguiendo las disposiciones de:
06 secondo le prescrizioni per:
06 Nota * delineato nel <A> e giudicato positivamente
07 ™ËÌ›ˆÛË * fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ <A> Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
08 Nota * tal como estabelecido em <A> e com o parecer
09 Примечание * как указано в <A> и в соответствии с
16 követi a(z):
17 zgodnie z postanowieniami Dyrektyw:
18 în urma prevederilor:
according to the Certificate <C>.
beurteilt gemäß Zertifikat <C>.
<B> conformément au Certificat <C>.
<B> overeenkomstig Certificaat <C>.
07 Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
08 de acordo com o previsto em:
09 в соответствии с положениями:
01 Note * as set out in <A> and judged positively by <B>
02 Hinweis * wie in der <A> aufgeführt und von <B> positiv
03 Remarque * tel que défini dans <A> et évalué positivement par
04 Bemerk * zoals vermeld in <A> en positief beoordeeld door
05 Nota * como se establece en <A> y es valorado
10 Bemærk * som anført i <A> og positivt vurderet af <B> i
positivamente por <B> de acuerdo con el
Certificado <C>.
uction Technique.
uctiedossier samen te stellen.
o de Construcción Técnica.
Tecnico di Costruzione.
Daikin Europe N.V. is authorised to compile the Technical Construction File.
Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen.
Daikin Europe N.V. est autorisé à compiler le Dossier de Constr
Daikin Europe N.V. is bevoegd om het Technisch Constr
Daikin Europe N.V. está autorizado a compilar el Archiv
** 02
** 03
** 04
** 05
Daikin Europe N.V. è autorizzata a redigere il File
** 06
3PW66183-1
** 01
Page 3

Table of contents

1 Introduction
2 Precautions for installation
3 Prepare the installation of the fan coil unit
4 Install the fan coil unit
1.1 About fan coil units
1.2 About this fan coil unit
1.3 About this document
1.3.1 Meaning of warnings and symbols
3.1 Check that you have all optional equipment
3.2 Verify the appropriate installation location
3.3 Prepare the installation space
3.4 Prepare the water piping work
3.5 Prepare the electrical wiring work
3.6 Prepare the installation of optional equipment
4.1 Unpack the unit
4.2 Check if all accessories are included
4.3 Prepare the ceiling opening
4.4 Fix the unit
4.5 Perform the water piping work
4.5.1 Connect the water pipes
4.5.2 Insulate the water pipes
4.5.3 Fill the water circuit
4.6 Connect the electrical wiring
4.6.1 Connect the power supply
4.6.2 Connect the remote controller and unit transmission wiring
4.6.3 Close the control box
4.7 Perform the drain piping work
4.7.1 Install the drain piping in the building
4.7.2 Connect the drain piping to the unit
4.7.3 Test the drain piping
4.8 Install optional equipment
1
1
1
2
2
3
4
4
5
6
6
7
9
10
10
10
11
12
14
14
15
16
16
20
21
21
21
21
23
24
25
Page 4
5 Commission the fan coil unit
5.1 Verify completion of installation
5.2 Configure the unit
5.3 Test the installation
5.4 Handover to the user
27
27
28
29
30
6 Service and maintenance
7 Glossary
6.1 Maintenance tasks
6.2 Service to the unit
31
31
33
34
Page 5
1Introduction
About fan coil units

1.1 About fan coil units

A fan coil unit provides heating and cooling to individual spaces. It creates a comfortable environment in both commercial and residential applications. Fan coil units are widely used for the air conditioning of offices, hotels and houses.
The main components of fan coil units are:
a f
an,
a
coil (heat exchanger).
The heat exchanger receives hot or cold water spreads the heat or coolness in order to condition the space.
DAIKIN offers a wide range of fan coil units for both concealed Contact your DAIKIN dealer for a list of related products.
About this fan coil unit

1.2 About this fan coil unit

The model identification code means:
FW
Water fan coil unit
F
Subclass: Cassette F: 2x2

1 Introduction

from a heating or cooling source. The fan
and exposed applications.
02
To ta l cooling capacity (kW)
B
Major
7
T
V1
model change
Minor model change
Coil type: T: 2-pipe F: 4-pipe
1 phase / 50 Hz / 220-240
V
B
Produced in Europe
The following models are available:
F
F
About this document
FWF
Fan coil units 4PW64524-1 – 09.2010
WF02-03-04-05B7TV1B
2-pipe fan coil units have one supply and one return pipe. The supply pipe can supply ei
ther hot or cold water to the unit.
WF02-03-04-05B7FV1B
4-pipe fan coil units have two supply pipes and two return pipes. This allows either hot or
cold water to enter the unit which makes it possible to heat and cool different areas of
ilding at the same time. Use this type if you have a separate source for cooling and
a bu for heating.
Installation manual
1
Page 6
1 Introduction

1.3 About this document

This document is an installation manual. It is intended for the installer of this product. It describes the procedures for installing, commissioning and maintaining the unit, and it will provide help if problems occur. Carefully read the relevant parts of the manual.
How to get the manual?
A
printed version of the manual is delivered with the unit.
Conta
ct your local DAIKIN dealer for an electronic version of the manual.
For detailed instructions about how to install and operate the associated products and/or
tional equipment, refer to the relevant catalogues, technical literature or product manuals
op for those products.
The original documentation is written in English. All original documentation.
About this document

1.3.1 Meaning of warnings and symbols

Warnings in this manual are classified according to their severity and probability of happening.
Danger: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
other languages are translations of the
Warning: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Caution: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
Notice: Indicates situations that may result in damage to equipment or property.
Information: This symbol identifies useful information, but no hazardous situation
warnings.
Some types of danger are repr
Electric current
Danger of burning or scalding
esented by special symbols:
Installation manual
2
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 7
2 Precautions for installation
All instructions described in this manual shall be carried out by a licensed installer.
Install the unit according to the of the additional equipment (e.g. controller). Improper installation could result in electric shock, short-circuit, leaks, fire or other damage to the equipment.
Be sure to wear adequate personal protection eq when performing installation, maintenance or service to the unit.
If not sure of installation procedures or operatio DAIKIN dealer for advice and information.
Danger: electric shock
Switch off all power supply before removing the control box cover or before making any conn
ections or touching electrical parts.
To avoid electric shock, be sure to disconnect the power supply 1 minute or more before servicing at the terminals of main circuit capacitors or electrical parts and, before touching, be sure that those voltages are 50 V DC or less.
instructions in the included documentation and the manuals
the electrical parts. Even after 1 minute, always measure the voltage

2 Precautions for installation

uipment (protection gloves, safety glasses)
n of the unit, always contact your local
Danger: high temperature
Do not touch the water piping or internal parts during and immediately after operatio
n. The piping and internal parts may be hot or cold depending on the working
condition of the unit.
Your hand may get burned or frostbitten if you touch the piping or internal parts. To
d injury, give the piping and internal parts time to return to normal temperature
avoi or, if you must touch them, be sure to wear adequate protective gloves.
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
3
Page 8

3 Prepare the installation of the fan coil unit

3 Prepare the installation of the fan coil unit
Check that you have all optional equipment

3.1 Check that you have all optional equipment

Decoration panel
Decoration panel
Panel spacer
Controllers
Electronic remote controller -
Identification code
BYFQ60B
KDBQ44B60
Identification code
BRC7E530 wireless (cooling and heating)
Electronic remote controller -
BRC7E531 wireless (cooling only)
Electronic remote controller -
BRC315D7 wired
Central remote controller
Intelligent touch controller DCS601C51C
Unified ON/OFF controller DCS301BA51
DCS302CA51
Description
Decoration panel for the fan coil unit.
Decorative spacer to fill the gap between panel and unit when the height of the suspended ceiling is too small.
Description
Wireless remote controller to control each fan coil unit independently with cooling and heating functionality.
Wireless remote controller to control each fan coil unit independently with cooling functionality only.
Wired remote controller to control each fan coil unit with cooling and heating functionality.
Remote controller for centralized control of all connected units.
Advanced remote controller for centralized control of all connected units.
Remote controller to switch all connected units ON or OFF.
Installation manual
4
Air handling options
Sealing member of air
Identification code
KDBH44BA60 discharge outlet
Long-life replacement filter KAFQ441BA60
Fresh air intake kit
Sensor
Remote sensor
KDDQ44XA60
Identification code
KRCS01-1
Description
Blocking parts to close one or more air outlets of the fan coil unit.
High quality filter.
Kit which can be connected to the ventilation system in order to supply fresh air to the fan coil unit.
Description
Replacement sensor to measure temperature remotely from a location other than that in which the controller is installed.
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 9
3 Prepare the installation of the fan coil unit
Timer
Schedule timer
Valves
2-way valve (ON/OFF type) EKMV2C09B7
3-way valve (ON/OFF type) EKMV3C09B7
Electronic circuits
Valve control PCB
Optional PCB for MOD-bus
Identification code
DST301BA51
Identification code
Identification code
EKRP1C11
EKFCMBCB7 connection
Wiring adaptor for electrical appendices
Remote “ON/OFF” and
KRP4A(A)53
KRP2A52
EKROROA “Forced OFF” kit
Description
Controller with schedule timing functionality.
Description
Electronic 2-way valve to control the water supply.
Electronic 3-way valve to control the water supply.
Description
Mandatory electronic circuit when 2-way or 3-way valve is used.
Electronic circuit with MOD­bus interface connections.
Electronic circuit with additional connections for external input/output signals.
Connection to control the ON/OFF operation remotely.
Verify the appropriate installation location

3.2 Verify the appropriate installation location

When selecting the installation location, take into account the instructions as mentioned in the following paragraphs of this chapter.
Select an installation location where the following conditions are fulfilled:
the space around the unit is adequate for maintenance a
required for installation” on page 6.
the space around the unit allows suf
“Space required for installation” on page 6.
the un
it may be installed on ceilings up to 3.5 m. However, it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2.7 m. Install the unit where the height of the decoration panel is more than 2.5 m to avoid
dental touching.
acci
the air passage is not bl
the cond
the instal
the uni
ensate water can be properly drained.
lation location is frost-free.
t can be installed horizontally.
ocked.
ficient air circulation and air distribution. See figure
nd servicing. See figure “Space
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
5
Page 10
3 Prepare the installation of the fan coil unit
the unit must be installed as far away as possible from fluorescent lights or other sources that possibly interfere with the signal of wireless remote controllers.
295
Prepare the installation space
2500
1500
*
a
1500
a
b
1500
*
Fig. 3.1: Space required for installation
a
Air outlet
b
Air inlet
Information
Leave 200 mm or more space where marked with *,
on sides where the air outlet is
closed.
Refer to figure “Space required for installation”
on page 6.
Information
The equipment is not intended for use in a potentially explosive atmosphere.

3.3 Prepare the installation space

When preparing the installation space, use the paper pattern for installation which is delivered with the unit. More information on how to prepare the ceiling opening can be found in chapter “Prepare the ceiling opening” on page 11.
When
the conditions in the built-in space are exceeding 30°C and exceeding a relative humidity of 80%, or when fresh air is inducted into the ceiling, an additional insulation is required on the outside of the unit (minimum 10 mm thickness polyethylene foam).
Prepare the water piping work
3.4 Prepare the water piping work
The unit is equipped with a water inlet and water outlet for connection to a water circuit. The water circuit must be provided by an installer and must comply with the applicable legislation.
Notice
The unit is only to be used in a closed water system. Application circuit can lead to excessive corrosion of the water piping.
Before performing the water piping work, check the following points:
the max
the mi
the max
b
temperature,
imum water pressure is 10 bar,
nimum water temperature is 5°C,
imum water temperature is 70°C,
e sure to install components in the field piping that can withstand the water pressure and
in an open water
Installation manual
6
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 11
3 Prepare the installation of the fan coil unit
provide adequate safeguards in the water circuit to be sure that the water pressure will never exceed the maximum allowable working pressure,
provide a proper drain for the coming into contact with electrical parts,
sure that the water flow rates are according to the table below,
be
FWF02-05B7TV1B
FWF02B7FV1B
FWF03-05B7FV1B
Table 3.1: Maximum and minimum water flow
provide shut-off valves at the unit so that normal servicing can be accomplished without draining the system,
pro
vide drain taps at all low points of the system to permit complete drainage of the
circuit during maintenance or service to the unit,
provide air
purge valves at all high points of the system. The valves shall be located at points which are easily accessible for servicing. A manual air purge valve is mounted onto the unit,
ways use materials which are compatible with the water and 40% volume glycol,
al
sel
ect piping diameter in relation to required water flow and available ESP (External
Static Pressure) of the pump.
Prepare the electrical wiring work
pressure relief valve (if installed) to avoid any water
Minimum water speed
(l/min.)
2.7
2.7
2.7
Maximum water speed
(l/min.)
18
10.8
14.4
3.5 Prepare the electrical wiring work
The unit must be connected to the power supply. All field wiring and components must be installed by an installer and must comply with the applicable legislation.
Warning
A main switch or other means for disconnection, having a contact separation in all poles
, must be incorporated in the fixed wiring in accordance with the applicable
legislation.
Before connecting the electrical wirin
use
a
copper wires only,
ll field wiring must be carried out in accordance with the wiring diagram delivered with
the unit,
never sque
eze bundled cables and be sure that cables do not come in contact with the piping and sharp edges. Be sure no external pressure is applied to the terminal connections,
sure to establish an earth. Do not earth the unit to a utility pipe, surge absorber, or
be telephone earth. Incomplete earth may cause electrical shock,
be sure to install an
earth leakage detector in accordance with the applicable legislation. Failure to do so may cause electric shock or fire. The earth leakage detector is a field supplied part,
sure to install the required fuses or circuit breakers. The fuse or circuit breakers are
be field supplied parts.
g, check the following points:
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
7
Page 12
3 Prepare the installation of the fan coil unit
Information
The equipment described in this manual may cause electronic noise generated from radio-frequency ener to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation.
It is therefore recommended t proper distances away from stereo equipment, personal computers, etc.
In extreme circumstances a distance of
Electrical characteristics
Model
Phase
Frequency (Hz)
Voltage range (V)
Voltage tolerance (V)
Maximum running current (A)
Overcurrent fuse (A) (field supply)
gy. The equipment complies to specifications that are designed
o install the equipment and electric wires keeping
3 m or more is required.
FWF
1N~
50
220-240
±10%
0.9
(a)
16
Table 3.2: Electrical characteristics
(a)
In case of common power supply to more than one unit (as illustrated in figure “Group control or use with 2
remote controllers” on page 19), keep total current of interconnection
Branch the line outside the terminal block of the unit in accordance with electrical equipment standards, when using two power wires of a gauge greater than 2 mm². The branch must be sheathed in order to provide an equal
wiring between units less than 12 A.
or greater degree of insulation as power supply wiring itself.
Specifications for field wiring
Power supply wiring
Wire
H05VV-U3G
(a),(b)
Size (mm²)
According to the
Length
applicable
legislation. Max. 4.0
Remote controller and unit transmission
Sheathed wire
2 conductors
(c)
0.75-1.25
Max. 500 m
wiring
Table 3.3: Field wiring specifications
(a)
Only in case of protected pipes. Use H07RN-F in case of no protection.
(b)
Run electrical wiring through a conduit to protect against external forces.
(c)
Use double insulation wire for remote controller (sheath thickness: 1 mm) or run wires through a wall or conduit so that the user cannot come in contact with them.
(d)
This length is the total extended length in the system in case of group control. See figure “Group control or use
with 2 remote controllers” on page 19.
Prepare the installation of optional equipment
(d)
Installation manual
8
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 13
3 Prepare the installation of the fan coil unit
abc
3.6 Prepare the installation of optional equipment
Air flow directions
For this unit you can select different air flow direct blocking pad kit to limit the air discharge to 2, 3 or 4 (closed corners) directions.
Select the air flow direct
ions best suited for the room and point of installation. For air
discharge in 2 or 3 directions, it is necessary to make field settings by means of the remote controller and to close the air outlet(s) as illustrated in the figure below. (
direction)
Fig. 3.2: Air flow directions
a
Air discharge in 4 directions
b
Air discharge in 3 directions
c
Air discharge in 2 directions
ions. It is necessary to purchase an optional
air flow
Information
Air flow directions as shown merely serve
as examples of possible air flow
directions.
For other preparations related to the installation of optional equipment refer to “Install
optional equipment” on page 25.
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
9
Page 14

4 Install the fan coil unit

a
1x
b
1x
c
8x
d
4x
e
1x
1x
h
1x
i
2x
j
1x
k
1x
l
f
FWF_T 2x FWF_F 4x
g
FWF_T 2x FWF_F 4x
m
FWF_
T 2x
FWF_F 4x
4 Install the fan coil unit
Unpack the unit

4.1 Unpack the unit

When receiving the unit, please check its state. Verify if any damage occurred during transport. If the unit and/or packing are damaged at delivery, report this immediately to the carrier’s claims agent.
Identify model and version of the unit from the indications stated on the carton packing.
Leave the unit inside its packing until you reach the installation site. Where unpacking is un
avoidable, use a sling of soft material or protective plates together with a rope when lifting,
this to avoid damage or scratches to the unit.
Warning
Tear apart and throw away plastic packaging b them. Children playing with plastic bags face danger of death by suffocation.
When unpacking the unit or when moving the unit after unpacking, be sure to lift the unit by
lding on to the hanger bracket without exerting any pressure on other parts.
ho
Check if all accessories are included
ags so that children will not play with

4.2 Check if all accessories are included

An overview of the accessories included in the box:
Fig. 4.1: Accessories
a
Metal clamp
b
Drain hose
c
Washer for hanger bracket
d
Screw
e
Paper pattern for installation
f
Insulation tube
g
O-ring
h
Large sealing pad
i
Small sealing pad
j
Sealing pad
k
Installation manual
l
User manual
m
Sealing pad for piping connections
Prepare the ceiling opening
Installation manual
10
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 15

4.3 Prepare the ceiling opening

533
575
585~660
*
585
585~660
*
700
20
45
20
45
533
575
585~660
*
700
a
c
e
f
g
g
h
h
g
f
e
b
d
i
45
b a
4 Install the fan coil unit
Fig. 4.2: Opening in ceiling
a
Water inlet/outlet
b
Suspension bolt (x4) (field supply)
c
Hanger bracket
d
Suspended ceiling
e
Distance between suspension bolts
f
Unit dimensions
g
Ceiling opening dimensions
h
Decoration panel dimensions
i
Suspended ceiling frame
Information
Installation is possible with a ceiling dimension of 660 mm (marked with * in figure
“Opening in ceiling” on page 11). However, to achieve a ceiling-panel overlapping
dimension of 20 mm, the spacing between the ceiling and the unit should be 45 mm or material
less. If the spacing between ceiling and the unit is over 45 mm, attach sealing
or recovered ceiling in the area marked below.
Fig. 4.3: Ceiling spacing too large
a
Area to fit sealing material or recovered ceiling into
b
Suspended ceiling
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
11
Page 16
4 Install the fan coil unit
c
b
d
e
a
50 - 100
1 Make the ceiling opening needed for installation where applicable. (For existing
ceilings.)
Refer to the pap
opening dimensions.
Create the ceiling opening required for installation.
After making an opening in the ceiling, it may be necessary to reinforce the
suspended ceiling frame to keep the ceiling level and to prevent it from vibrating. Consult the builder for details.
2 Install the suspension bolts. (Us
Use anchors for existing ceilings, and a sunken ins supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit. The distance between the suspension bolts is marked on the paper pattern for installation (delivered with the unit). Refer to it to check for points requiring reinforcing. Adjust clearance from the ceiling before proceeding further. See installation example in figure below:
er pattern for installation (delivered with the unit) for the ceiling
e either a M8~M10 size bolt.)
ert, sunken anchors or other field
Fig. 4.4: Installing the suspension bolts
a
Ceiling slab
b
Anchor
c
Long nut or turn-buckle
d
Suspension bolt
e
Suspended ceiling
Information
All the above
For i
dealer for advice.
Fix the unit

4.4 Fix the unit

Caution
To avoid injury, do not touch the air inlet or aluminium fins of the unit.
parts are field supplied.
nstallation other than standard installation, contact your local DAIKIN
Installation manual
12
When installing optional equipment, also read
the installation manual of the optional equipment. Depending on the field conditions, it may be easier to install optional equipment before the unit is installed. However, for existing ceilings, always install fresh air intake kit before installing the unit. For more information, refer to “Install optional equipment” on
page 25.
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 17
4 Install the fan coil unit
a b
b
1 Install the unit temporarily.
Attach the hanger bracket to the suspensio and washer from the upper and lower sides of the hanger bracket as illustrated in the figure below.
a
c
b
d
Fig. 4.5: Securing the hanger bracket
a
Nut (field supply)
b
Washer (delivered with the unit)
c
Hanger bracket
d
Double nut (field supply)
2 Fix the paper pattern for installation (delivered with the unit). (For new ceilings only.)
The paper pattern for installation corresponds with the measurements of the ceiling opening. Consult the builder for details.
The centre of the ceiling opening is indicated on the paper pattern for installation. The centre of the unit is indicated on the unit casing.
Attach the paper pattern for installation to the unit with the screws as illustrated in the figure below.
n bolt. Be sure to fix it securely by using a nut
Fig. 4.6: Paper pattern for installation
a
Paper pattern for installation (delivered with the unit)
b
Screws (delivered with the unit)
3 Adjust the unit to the right position for installation.
4 Check if the unit is horizontally levelled.
Do
not install the unit tilted. The unit is equipped with a built-in drain pump and float switch. If the unit is tilted against the direction of the condensate flow (the drain piping side is raised), the float switch may malfunction and cause water to drip.
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
13
Page 18
b
b
a
4 Install the fan coil unit
a
c
b
FWF_
T
FWF_
F
FWF_
T
FWF_
F
a
e
g
f b i
i
j
h
j
d
Check if the unit is levelled at all four corners with a water level or a water-filled vinyl tube as illustrated in the figure below.
Fig. 4.7: Check if unit is levelled
a
Water level
b
Vinyl tube
5 Remove the paper pattern for installation. (For new ceilings only.)
Perform the water piping work

4.5 Perform the water piping work

Perform the water piping work

4.5.1 Connect the water pipes

The unit is equipped with water outlet and inlet connections. There is an air purge valve that is fitted along with the water inlets and outlets for air purging as illustrated in the figure below.
Fig. 4.8: Water piping connection
a
Drain pipe connection
b
Installation manual
14
Power supply entry hole
c
Water inlet (3/4" female BSP)
d
Water outlet (3/4" female BSP)
e
Cold water inlet (3/4" female BSP)
f
Cold water outlet (3/4" female BSP)
g
Hot water inlet (3/4" female BSP)
h
Hot water outlet (3/4" female BSP)
i
Transmission wiring entry
j
Air purge valve
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 19
4 Install the fan coil unit
a b
d
c
c d
Connect the water inlet and outlet connections of the fan coil unit to the water piping as illustrated below.
ba
Fig. 4.9: Connecting the water piping
a
Water piping:
3
/4" male BSP in case of direct connection to the unit,
3/4" female BSP in case of connection to an optional valve.
b
O-ring (delivered with the unit)
Notice
Do not use excessive force when connecting th piping.
Deformation of the piping can ca
use the unit to malfunction.
e piping. This could deform the unit
In case the optional valve is used, refer to the installation manual of the valve kit to install the field pi
ping.
Perform the water piping work

4.5.2 Insulate the water pipes

The complete water circuit, inclusive all piping, must be insulated to prevent condensation and reduction of the capacity.
Fig. 4.10: Water piping insulation
a
Water inlet
b
Water outlet
c
Sealing pad for piping connections (delivered with the unit)
d
Insulation tube (delivered with the unit)
If the temperature is higher than 30°C and the relati thickness of the sealing materials shall be at least 20 mm in order to avoid condensation on the surface
Perform the water piping work
of the sealing.
ve humidity is higher than 80%, then the
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
15
Page 20
4 Install the fan coil unit
ab
c

4.5.3 Fill the water circuit

Notice
Water quality must be according
Notice
Use of glycol is allowed, but the amount s higher amount of glycol may cause damage to the hydraulic components.
During filling, it might not be possible to remove all air in the system. Remaining air can be
oved during the first operating hours of the unit. The air can be removed from the unit
rem through the manual air purge valve. For the location of the air purge valve on the unit, refer to figure “Water piping connection” on page 14.
1 Open the air purge valve (refer to figure “Air purge valve” on page 16) by turning the nut
2 times.
2 Push the springy core (refer to figure “Air purge valve” on page 16) to let off superfluous
air from the unit water circuit(s).
3 Close the nut.
4 Additional filling with water afterwards might b
purge valve).
to EU directive 98/83 EC.
hall not exceed 40% of the volume. A
e required (but never through the air
Fig. 4.11: Air purge valve
a
Air purge
b
Nut
c
Connect the electrical wiring
Springy core

4.6 Connect the electrical wiring

Precautions
Observe the notes mentioned below when connecting
Do not
Do
When connecting wires
connect wires of different gauge to the same power supply terminal. Looseness in
the connection may cause overheating.
not connect wires of different gauge to the same grounding terminal. Looseness in the
connection may deteriorate the protection.
of the same gauge, connect them according to the figure below.
Fig. 4.12: Terminal wiring
the electrical wiring.
Installation manual
16
4PW64524-1 – 09.2010
FWF
Fan coil units
Page 21
4 Install the fan coil unit
Use the specified electric wire (refer to “Field wiring specifications” on page 8). Connect the wire securely to the terminal. Lock the wire down without applying excessive force
the terminal. Use the appropriate tightening torque:
to
Tightening torque (N·m)
Terminal block for remote controller
0.79~0.97
Terminal block for power supply
1.18~1.44
Table 4.1: Tightening torque
Remote controller wiring should be located at least 50 mm away from the unit transmission wiring and other wiring. Failure to observe this guideline may result in malfunction due to electrical noise.
For th
e remote controller wiring, refer to the installation manual of the remote controller
delivered with the remote controller.
Keep wiring
in neat order so that wires do not obstruct other equipment or force the control box cover to pop open. Make sure the cover closes tight. Incomplete connections could result in overheating, and in the worst case, electric shock or fire.
Notice
Never connect the unit transmission wiring to the remote controller wiring. This connection
could cause irreparable damage to the entire system.
Wiring diagram
Refer to the wiring diagram sticker on the unit
: Terminal
: Connector
: Wire connector
: Field wiring
(on the inside of the control box cover).
RED : Red
BLK : Black
WHT : White
ORG : Orange
YLW : Yellow
GRN : Green
BLU : Blue
A1P, A2P Printed circuit board
C1
F1U
HAP
KPR
M1F
M1P
M1S
Q1M
Q1D1
R1T
R2T, R3T Thermistor
S1L
T1R
V1TR
X1M, X2M Term ina l str ip
FWF
Fan coil units 4PW64524-1 – 09.2010
Capacitor (M1F)
Fuse (F5A, 250 V)
Light emitting diode (service monitor green)
Magnetic relay (M1P)
Motor (indoor fan)
Motor (drain pump)
Motor (swing flap)
Thermo switch (M1F embedded)
Field earth leak detector (Max. 300 mA)
Thermistor (air)
Float switch
Transformer (220-240 V/22 V)
Phase control circuit
Installation manual
17
Page 22
4 Install the fan coil unit
Z1F
TC
Ferrite core
Signal transmission circuit
Wired remote controller
R1T
SS1
Thermistor (air)
Selector switch (main/sub)
Wireless remote controller (Receiver/display unit)
A3P, A4P Printed circuit board
BS1
H1P
H2P
H3P
H4P
SS1
SS2
Push button (ON/OFF)
Light emitting diode (ON - red)
Light emitting diode (timer - green)
Light emitting diode (filter sign - red)
Light emitting diode (defrost - orange)
Selector switch (main/sub)
Selector switch (wireless address set)
Connector for optional parts
X24A
X33A
X35A
X40A
Connector (wireless remote controller))
Connector (valve control adaptor)
Connector (external adaptor)
Connector (ON/OFF input from outside)
Notes
1 If a remote controller is used, connect it to the unit in accordance with the controller
installation manual.
2 The remote controller model varies
according to the combination with the system.
See technical data, catalogues, etc. before connecting.
3 Ground the shield of the remote controller wire to the indoor unit.
(in case of using shield wire)
4 When using the central remote controller,
see manual for connection to the unit.
5 X24A,X33A,X35A and X40A are connected when optional accessories are being used.
6 X24A is connected when the wireless remo
te controller is being used.
7 Availability of R2T and/or R3T is depending on model type.
Installation manual
18
FWF
Fan coil units
4PW64524-1 – 09.2010
Page 23
System examples
P11
NL
a
2
P2F1F
2
P11NL2
P2F1F
2
P11NL2
P
2
P1P
2
P1P
2
P1P
2
P1P
2
F1F
2
P11NL2
P2F1F
2
c
b
P11a2
P2F1F
2
P11 2
P2F1F
2
P11NL2
P
2
P1P
2
P1P2P1P
2
F1F
2
P11 2
P2F1F
2
b
d
c
When usin
g 1 remote controller for 1 indoor unit (normal operation)
Fig. 4.13: 1 remote controller for 1 indoor unit
a
Fan coil unit
b
Remote controller (optional equipment)
c
Overcurrent fuse
For group control or use with 2 remote controllers
4 Install the fan coil unit
Fig. 4.14: Group control or use with 2 remote controllers
a
Fan coil unit
b
Remote controller (optional equipment)
c
Overcurrent fuse
d
Interconnection wiring: total current should not exceed 12 A.
Information
It is not necessary to designate indoor
unit address when using group control. The
address is automatically set when the power is activated.
For forced OFF and ON/OFF operation, connect input wires from the outside on the EKROROA option kit. For more information refer to “Install optional equipment” on
page 25.
Wire specification
Gauge
Length
External terminal
Connect the electrical wiring
Table 4.2: Forced OFF and ON/OFF wiring specifications
Sheathed vinyl cord or cable (2 wire)
0.75-1.25 mm²
100 m
Contact that can ensure the minimum applicable load of 15 V DC, 10 mA
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
19
Page 24
4 Install the fan coil unit

4.6.1 Connect the power supply

cnm m d b
a
A
C
j
m
c
10~15
j
B
e
10~15
f
123
c
el fg hi g ei
LN
k
Fig. 4.15: How to connect electrical wiring
A
Detail: connect the remote controller and unit transmission cables
B
Detail: connect the power supply cable
Do NOT connect wires to the terminal numbered 3!
C
Detail: close the cable intake holes
Stick the adhesive sealing pads onto the casing outside to close the wiring intake holes.
a
Control box cover
b
Wiring diagram sticker
c
Remote controller cable
d
Remote controller and unit transmission terminal block
e
Power supply cable
f
Power supply terminal block
g
Large clamp (field supply)
h
Small clamp (field supply)
i
Clamp holder
j
Sealing pad (delivered with the unit)
k
Ground wire
l
Power supply cable intake
m
Unit transmission cable
n
Remote controller and unit transmission cables intake
Installation manual
20
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 25
4 Install the fan coil unit
1 Remove the control box cover (a) as illustrated in figure “How to connect electrical
wiring” on page 20.
2 Pull the power supply cable (e) (or interconnection wiring in case of common power
pply) inside through the power supply cable intake (l).
su
3 Connect the power supply wires to the power supply terminal block (f).
Connect L to terminal 1 and connect N to terminal 2.
4 Connect the ground wire (k) to the grounding terminal.
5 Securely fix the wiring using a clamp (g).
6 Install an earth leakage detector and fuse in t
he power supply line (field supply). Select the earth leakage detector in accordance with the applicable legislation. To select the fuse, refer to Electrical characteristics.
Connect the remote controller and unit transmission wiring

4.6.2 Connect the remote controller and unit transmission wiring

1 Remove the control box cover (a) as illustrated in figure “How to connect electrical
wiring” on page 20.
2 Pull the cables (c, m) inside through the remote controller and unit transmission cables
e (n).
intak
3 Connect the remote controller wires to (P1, P2) terminals of the terminal block (d).
4 Connect the unit transmission wires to (F1, F2) terminals.
5 Securely fix the wiring using a clamp (g).
Connect the electrical wiring

4.6.3 Close the control box

1 After all wiring connections are executed, fill gaps in the casing cable intakes with the
small sealing pad (delivered with the unit) to prevent small animals, water or dirt from entering the unit causing short circuits in the control box.
2 Fit the control box cover (a) back in place like
illustrated in figure “How to connect
electrical wiring” on page 20. When attaching the control box cover, make sure not to
pinch any wires.
Perform the drain piping work

4.7 Perform the drain piping work

Perform the drain piping work

4.7.1 Install the drain piping in the building

1-1.5 m
Fig. 4.16: Drain pipe installation
a
Hanging bar
b
1/100 gradient
a
b
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
21
Page 26
4 Install the fan coil unit
300
0~545205
750
1~1.5 m
0~75
a
b
d
d
ce
100 0~675
a a
a a
Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that air does not remain trapped inside the pipe. Refer to “Drain pipe installation” on
page 21.
If the drain hose cannot be sufficiently set on raising piping (field supply) as illustrated in the figure below.
Fig. 4.17: How to perform drain piping
a
Ceiling slab
b
Hanger bracket
c
Drain raising pipe (nominal diameter = 20 mm)
d
Drain hose (delivered with the unit)
e
Metal clamp (delivered with the unit)
a slope, fit the drain hose with a drain
Keep pipe size equal to or greater than that of the connecting pipe (20 mm inner diameter).
Instal
Install the drain raising pipes
l the drain raising pipes at a height of less than 545 mm.
at a right angle to unit and no more than 300 mm from the
unit.
o prevent air bubbles, install the drain hose level or slightly tilted up (75 mm).
T
Insul
ate the complete drain piping inside the building.
Information
When unifying multiple drain pipes, install the pipes as illustrated in the figure belo
w. Select converging drain pipes whose size is suitable for the operating capacity
of the unit.
Fig. 4.18: Unifying multiple drain pipes
a
T-joint converging drain pipes
Perform the drain piping work
Installation manual
22
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 27

4.7.2 Connect the drain piping to the unit

ba
aebc d
4 mm
c d
b
A
A'
A-A'
a
1 Push the drain hose (delivered with the unit) as far as possible over the drain socket as
illustrated in the figure below.
Fig. 4.19: Connecting the drain hose
a
Drain socket (fixed to the unit)
b
Drain hose (delivered with the unit)
2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part
as illustrated in the figure below.
4 Install the fan coil unit
Perform the drain piping work
Fig. 4.20: Wrap sealing pad
a
Drain socket (fixed to the unit)
b
Drain hose (delivered with the unit)
c
Metal clamp (delivered with the unit)
d
Large sealing pad (delivered with the unit)
e
Drain piping (field supply)
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
23
Page 28
4 Install the fan coil unit

4.7.3 Test the drain piping

After the drain piping work is finished, check if drainage flows smoothly.
1 Add approximately 2 l of water gradually through the air outlet.
e
d
c
100
b
a
Fig. 4.21: Method of adding water
a
Plastic watering can (tube should be about 100 mm long)
b
Service drain outlet (with rubber plug) (Use this outlet to drain water from the drain pan)
c
Drain pump location
d
Drain pipe
e
Drain socket
2 Check the drainage flow.
In case the electric wiring work is finished
Check drainage flow during COOL running, explained in “Test the installation” on
page 29.
In case electric wiring work is not finished
1 Remove the control box cover. Connect the power supply (50 Hz, 220-240 V) to
connections 1 and 2 on the power supply terminal block and connect the ground wire firmly.
2 Close the control box cover and turn on the power.
Installation manual
24
Danger: electric shock
Do not touch the drain pump.
3 Confirm the drain operation looking at the drain socket.
4 After checking the drainage flow, turn off power, remove the control box cover and
disconnect the power supply from the power supply terminal block again. Fit the control box cover back in place.
Install optional equipm ent
4PW64524-1 – 09.2010
FWF
Fan coil units
Page 29

4.8 Install optional equipment

For the installation of optional equipment, refer to the installation manual which is delivered with the optional equipment and take into account the remarks mentioned in the table below.
Option
BYFQ60B
KDBQ44B60
KAFQ441BA60
KDDQ44XA60
KDBH44BA60
BRC7E530
BRC7E531
KRCS01-1
DCS302CA51
DCS601C51C
DCS301BA51
DST301BA51
KRP4A(A)53
KRP2A52
KEK26-1A
KJB212AA
KJB311A
KJB411A
KRP1BA101
BRC315D7
EKMV2C09B7
EKMV3C09B7
Description
Decoration panel
Panel spacer
Long life replacement filter —
Fresh air intake kit
Sealing member of air discharge outlet
Remote controller - wireless (cooling and heating)
Remote controller - wireless (cooling only)
Remote sensor
Central remote controller
Intelligent touch controller
Unified ON/OFF controller Installation: direct connect to
Schedule timer
Wiring adaptor for electrical appendices
Wiring adaptor for electrical appendices
Noise filter
Electrical box with earth terminal (2 blocks)
Electrical box with earth terminal (3 blocks)
Electrical box
Installation box for adaptor PCB
Wired remote controller
2-way valve (ON/OFF type) —
3-way valve (ON/OFF type) —
4 Install the fan coil unit
Remark
Not all functions are available for the FWF models.
Not all functions are available for the FWF models.
Installation: direct connect to indoor unit, no outdoor unit connection.
Not all functions are available for the FWF models.
Installation: direct connect to indoor unit, no outdoor unit connection.
It is not possible to use AIRNET or telephone connection.
Not all functions are available for the FWF models.
indoor unit, no outdoor unit connection+ EKROROA option kit is needed.
Installation: refer to FXZQ.
Connection: refer to VRV system.
Installation: refer to FXZQ.
Connection: refer to VRV system.
Installation: refer to FFQ or FXZQ.
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
25
Page 30
4 Install the fan coil unit
Option
EKRP1C11
EKFCMBCB7
EKROROA
Table 4.3: Installation of optional equipment
Description
Valve control PCB
Optional PCB for MOD-bus connection
Remote “ON/OFF” and “Forced OFF” kit
Remark
Installation: do not use the installation manual delivered with the option EKRP1C11, but refer to the installation manual of options EKMV2 and EKMV3 instead.
Installation manual
26
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 31
5 Commission the fan coil unit
Verify completion of installation

5.1 Verify completion of installation

Danger: electric shock
See “Precautions for installation” on page
After the installation of the unit, first check the following items. Once all below checks are fulfilled, the unit must be closed, only then can the unit be powered up.
Tick when checked
The unit is installed properly. If not installed properly, there may be abnormal noises and vibrations when starting up the unit.
The unit has been fully insulated. If not fully insulated, condensate water may drip.
The drainage flows smoothly. If drainage does not flow smoothly, condensate water may drip.
The power supply voltage corresponds to the voltage on the nameplate of the unit.
The wiring and piping connections are correct. In case of wrong connections, the unit may malfunction or components may burn out.
The earth wires are connected properly. The earth terminals have been tightened.
The wiring size is according to specifications. In case of wrong wiring size, the unit may malfunction or components may burn out.
The fuses, circuit breakers, or the locally installed protection devices are of the size and type specified in the chapter “Prepare the electrical wiring work” on
page 7.
None of the fuses or protection devices have been bypassed.
There are no visible loose connections or damaged electrical components in the control box or inside the unit.
There are no damaged components or squeezed pipes inside the unit.
There is no water leakage inside the unit. If there is water leakage, close the water inlet and water outlet shut-off valves and call your local DAIKIN dealer.
All air is removed from the circuit.
All options are correctly installed and connected.
The air inlet and outlet of the unit is not obstructed by paper sheets, cardboard, or any other material.

5 Commission the fan coil unit

3.
FWF
Fan coil units 4PW64524-1 – 09.2010
Table 5.1: Installation completion checklist
Installation manual
27
Page 32
5 Commission the fan coil unit
Warning
Be sure to provide for adequate measures in order to as a shelter by small animals. Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the user to keep the area around the unit clean and clear.
Configure the unit

5.2 Configure the unit

It is important that all information in this chapter is read sequentially by the installer and that the unit is configured as applicable.
Configuration of the unit is done trough the contro condition.
Setting No.”.
For set controller.
can be made by changing the “Mode No.”, “First code No.” and “Second code
ting and operation, refer to “Field setting” in the installation manual of the
prevent that the unit will be used
ller in accordance with the installation
Setting ceiling height
Adjust the Second code No. accordi
ng to the table below so that it corresponds to the ceiling
height of your installation. (Second code No. is factory set to “01”)
Ceiling height (m)
2.7
>2.7 or ≤3
>3 or ≤3.5
Table 5.2: Ceiling height setting
Mode No.
13(23)
13(23)
13(23)
First code No.
Second code No.
0
0
0
01
02
03
Setting air discharge direction
For changing air discharge direction (2, 3 or 4 directions), refer to the option handbook of the
tional blocking pad kit. (Second code No. is factory set to “01” for all-round air discharge)
op
Setting air filter sign
Remote controllers are equipped with liquid crystal air filter signs to display the time to clean
air filter. Change the Second code No. Depending on the amount of dirt or dust in the
the room. (Second code No. is factory set to “01” for air filter contamination-light)
Setting
Display interval Mode No.
First code No. Second code
No.
Light
Heavy
No display
±2500 hrs
±1250 hrs
10(20)
10(20)
10(20)
0
0
3
01
02
02
Installation manual
28
Table 5.3: Air filter contamination
When using wireless remote controllers it is necessary to use address setting. Refer to the controller installation manual for the setting instructions.
Fan coil units
4PW64524-1 – 09.2010
FWF
Page 33
5 Commission the fan coil unit
Activating forced OFF and ON/OFF operation
The following table explains “forced OFF” and “ signal.
Forced OFF
Input “ON” stops operation Input OFFON: turns on the
ON/OFF operations
unit (impossible by remote controllers)
Input “OFF” enables control Input ONOFF: turns off
the unit (by remote controller)
Table 5.4: Forced OFF and ON/OFF operation
1 Turn the power on and then use the remote controller to select operation.
2 Set the remote controller to the field set mode.
Setting
Forced OFF
ON/OFF operation 12(22)
Protective
Mode No.
12(22)
12(22)
equipment input
ON/OFF operations” in response to the input
Protective equipment input
Input ON: enables abnormal system stop (an error code will be displayed)
Input OFF: enables normal operation
First code No.
8
8
8
Second code No.
01
02
03
Table 5.5: Forced OFF and ON/OFF selection
Notice
For FWF models, the “forced OFF” setti
ON/OFF selection” on page 29 and NOT 12(22)-1-01/02 as mentioned in some
option manuals.
Test the installation

5.3 Test the installation

After installation, the installer is obliged to verify correct operation. Therefore a test run must be performed according to the procedures described below.
In case something is wrong with the unit and it does not operate, contact your local DAIKIN dealer.
Information
When using a wireless remote controller, conduct decoration panel.
ng is as indicated in table “Forced OFF and
a test operation after installing the
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
29
Page 34
5 Commission the fan coil unit
Test operation before installing decoration panel
Danger: electric shock
See “Precautions for installation” on page
1 Open the water inlet valve(s).
2 Open the water outlet valve(s).
3 Set to cooling operation with the remote controller and start operation by pushing
ON/OFF button.
4Press Inspection/Test Operation button 4 times and operate at Test Operation
mode for 3 minutes.
5Press Inspection/Test Operation button and operate normally.
6 Confirm function of unit according
7 Turn off the main power supply after operation.
Test operation after installing decoration panel
1 Open the water inlet valve(s).
2 Open the water outlet valve(s).
3 Set to cooling operation with the remote controller and start operation by pushing
ON/OFF button.
3.
to the operation manual.
4Press Inspection/Test Operation button 4 times (2 times for wireless remote
controller) and operate at Test Operation mode for 3 minutes.
5Push air flow direction adjust button to make sure the unit is in operation.
6Press Inspection/Test Operation button and operate normally.
7 Confirm function of unit according
Handover to the user

5.4 Handover to the user

Once the test run is finished and the unit operates properly, fill in the sheet “Handover of the installation to the user” which is an annex of the user manual.
to the operation manual.
Installation manual
30
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 35
6 Service and maintenance
For safety reasons, switch off the unit before carrying out any maintenance or service activities.
The service and maintenance activities which are mentioned in this paragraph may only be carried out by the installer or
Danger: electric shock
See “Precautions for installation” on page
Danger: high temperature
See “Precautions for installation” on page
Notice
Do not pour any liquid on the fan coil unit. This could damage the components inside it.
service company.

6 Service and maintenance

3.
3.
Maintenance tasks

6.1 Maintenance tasks

Cleaning the air filter
Clean the filter when necessary. Clean installed in a room where the air is extremely contaminated clean more often.
If it becomes impossible to clea
To clean the air filter:
1 Switch off the power supply.
2 Push both knobs simultaneously and carefully lower the grill.
The suction grill is now opened.
Fig. 6.1: Opening the suction grill
3 Pull the hook of the air filter out diagonally downward and remove the filter.
the filter at least once every 6 months. If the unit is
n, replace the air filter with an original spare part.
FWF
Fan coil units 4PW64524-1 – 09.2010
Fig. 6.2: Detaching the air filter
Installation manual
31
Page 36
6 Service and maintenance
4 Use a vacuum cleaner or wash the air filter with water.
When the air filter is very dirty, u
Fig. 6.3: Cleaning the air filter
5 Fix the air filter.
Attach the air filter to the suction grill by hanging it to the projected portion above the
ction grill. Press the bottom of the air filter against the projections on the bottom of the
su grill to snap the air filter into its place.
Fig. 6.4: Fixing the air filter
6 Close the suction grill.
se a soft brush and neutral detergent.
Cleaning the suction grill
1 Switch off the power supply.
2 Push both knobs simultaneously and carefully lower the grill.
The suction grill is now opened.
Fig. 6.5: Opening the suction grill
3 Open the suction grill 45 degrees and lift it upward.
The suction grill is now detached.
Fig. 6.6: Detaching the suction grill
4 Pull the hook of the air filter out diagonally downward and remove the filter.
Installation manual
32
Fig. 6.7: Detaching the air filter
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 37
6 Service and maintenance
5 Wash the suction grill with a soft brush and neutral detergent and dry thoroughly.
Fig. 6.8: Cleaning the suction grill
6 Attach the air filter to the suction grill by hanging it to the projected portion above the
suction grill. Press the bottom of the air filter against the projections on the bottom of the grill to snap the air filter into its place.
Fig. 6.9: Fixing the air filter
7 Close the suction grill.
Service to the unit

6.2 Service to the unit

For detailed instructions on reparations of the unit, refer to the service manual. Contact your local DAIKIN dealer to obtain the service manual.
If the cause of the problem can not be found or m DAIKIN dealer or the appointed service company.
In case some part is damaged and needs to be replaced, appointed service company for a list of available spare parts.
Information
Before starting the troubleshooting procedure, carry of the unit and look for obvious defects such as loose connections or defective wiring.
ore information is needed, call your local
call your local DAIKIN dealer or the
out a thorough visual inspection
FWF
Fan coil units 4PW64524-1 – 09.2010
Installation manual
33
Page 38

7 Glossary

7 Glossary
Term
Accessories:
Air filter:
Applicable legislation
Circuit breaker (fuse)
Coil (heat exchanger)
Controller:
Dealer
:
:
:
Meaning
Equipment which is delivered with the unit and which needs to be installed according to the instructions in the documentation
Device composed of fibrous materials which removes solid particulates such as dust, pollen, mould and bacteria from the air
All international, European, national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain
Safety device used in electrical installations to prevent electric shock
Main component of a fan coil unit. Receives hot or cold water from a heat source
Device to configure and operate the fan coil unit
Sales distributor for fan coil units and other DAIKIN products
Fan:
Main component of a fan coil unit. Spreads heat or coolness in a space
Fan coil unit:
Field supply:
Heating and cooling product
Equipment which needs to be installed according to instructions in this manual, but which are not supplied by DAIKIN
Air inlet/outlet:
Fan coil units have an air inlet and air outlet for providing air circulation
Installer:
Technical skilled person who is qualified to install fan coil units and other DAIKIN products
Optional equipment
Water inlet/outlet: Fan coil units have a water inlet and water outlet for connection to
:
Equipment which can optionally be combined to the fan coil unit
the water circuit.
Service company: Qualified company which can perform or coordinate the required
service to the fan coil unit
Installation manual
34
User:
Person who is owner of the fan coil unit and/or operates the product
FWF
4PW64524-1 – 09.2010
Fan coil units
Page 39
NOTES
Page 40
4PW64524-1 09.2010
Copyright 2010 Daikin
Loading...