This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.
Special adjustment may be necessary to suit local requirement.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay
persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
! WARNING! CAUTION
Only qualified personnel must carry out the installation
•
work. Installation must be done in accordance with this
installation manual. Improper installation may result in water
leakage, electric shock, or fire.
When installing the unit in a small room, take measures to
•
keep the refrigerant concentration from exceeding allowable
safety limits. Excessive refrigerant leaks, in the event of
an accident in a closed ambient space, can lead to oxygen
deficiency.
Use only specified accessories and parts for installation
•
work. Failure to use specified parts may result in water
leakage, electric shock, fire, or the unit falling.
Install the air conditioner or heat pump on a foundation
•
strong enough to withstand the weight of the unit. A
foundation of insufficient strength may result in the unit
falling and causing injuries.
Take into account strong winds, typhoons, or earthquakes
•
when installing. Improper installation may result in the unit
falling and causing accidents.
Make sure that a separate power supply circuit is provided for
•
this unit and that all electrical work is carried out by qualified
personnel according to local, state, and national regulations.
An insufficient power supply capacity or improper electrical
construction may lead to electric shock or fire.
Make sure that all wiring is secured, that specified wires
•
are used, and that no external forces act on the terminal
connections or wires. Improper connections or installation
may result in fire.
When wiring, position the wires so that the electrical wiring
•
box cover can be securely fastened. Improper positioning of
the electrical wiring box cover may result in electric shock,
fire, or the terminals overheating.
Before touching electrical parts, turn off the unit.
•
It is recommended to install a ground fault circuit interrupter
•
if one is not already available. This helps prevent electric
shock or fire.
Securely fasten the outdoor unit terminal cover (panel). If the
•
terminal cover/panel is not installed properly, dust or water
may enter the outdoor unit causing fire or electric shock.
When installing or relocating the system, keep the refrigerant
•
circuit free from substances other than the specified
refrigerant (R410A) such as air. Any presence of air or other
foreign substance in the refrigerant circuit can cause an
abnormal pressure rise or rupture, resulting in injury.
Do not change the setting of the protection devices. If the
•
pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those
specified by Daikin are used, fire or explosion may occur.
Do not touch the switch with wet fingers. Touching a switch
•
with wet fingers can cause electric shock.
Do not allow children to play on or around the unit to
•
prevent injury.
The heat exchanger fins are sharp enough to cut. To avoid
•
injury wear gloves or cover the fins while working around
them.
Do not touch the refrigerant pipes during and immediately
•
after operation as the refrigerant pipes may be hot or cold,
depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant
cycle parts. Your hands may suffer burns or frostbite if you
touch the refrigerant pipes. To avoid injury, give the pipes
time to return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
Install drain piping to proper drainage. Improper drain piping
•
may result in water leakage and property damage.
Insulate piping to prevent condensation.
•
•
Be careful when transporting the product.
•
Do not turn off the power immediately after stopping
operation. Always wait for at least 5 minutes before turning
off the power. Otherwise, water leakage may occur.
•
Do not use a charging cylinder. Using a charging cylinder
may cause the refrigerant to deteriorate.
•
Refrigerant R410A in the system must be kept clean, dry,
and tight.
(a) Clean and Dry -- Foreign materials (including mineral
oils such as SUNISO oil or moisture) should be
prevented from getting into the system
(b) Tight -- R410A does not contain any chlorine, does not
destroy the ozone layer, and does not reduce the earth’s
protection again harmful ultraviolet radiation. R410A
can contribute to the greenhouse effect if it is released.
Therefore, take proper measures to check for the
tightness of the refrigerant piping installation. Read the
chapter Refrigerant Piping and follow the procedures.
•
Since R410A is a blend, the required additional refrigerant
must be charged in its liquid state. If the refrigerant is charged
in a state of gas, its composition can change and the system
will not work properly.
•
The indoor unit is for R410A. See the catalog for indoor
models that can be connected. Normal operation is not
possible when connected to other units.
1-4
Remote controller (wireless kit) transmitting distance can be
•
shorter than expected in rooms with electronic fluorescent
lamps (inverter or rapid start types). Install the indoor unit
far away from fluorescent lamps as much as possible.
Indoor units are for indoor installation only. Outdoor units
•
can be installed either outdoors or indoors. This unit is for
indoor use.
Do not install the air conditioner or heat pump in the
•
following locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen. Plastic parts may
deteriorate and fall off or result in water leakage.
(b) Where corrosive gas, such as sulfurous acid gas, is
produced. Corroding copper pipes or soldered parts
may result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of
the control system and cause the unit to malfunction.
(d) Where flammable gas may leak, where there is carbon
fiber, or ignitable dust suspension in the air, or where
volatile flammables such as thinner or gasoline are
handled. Operating the unit in such conditions can cause
a fire.
Take adequate measures to prevent the outdoor unit from
•
being used as a shelter by small animals. Small animals
making contact with electrical parts can cause malfunctions,
smoke, or fire. Instruct the user to keep the area around the
unit clean.
! DANGER
Refrigerant gas is heavier than air and replaces oxygen. A
•
massive leak can lead to oxygen depletion, especially in
basements, and an asphyxiation hazard could occur leading
to serious injury or death.
Do not ground units to water pipes, gas pipes, telephone
•
wires, or lightning rods as incomplete grounding can cause
a severe shock hazard resulting in severe injury or death.
Additionally, grounding to gas pipes could cause a gas leak
and potential explosion causing severe injury or death.
If refrigerant gas leaks during installation, ventilate the
•
area immediately. Refrigerant gas may produce toxic gas if
it comes into contact with fire. Exposure to this gas could
cause severe injury or death.
After completing the installation work, check that the
•
refrigerant gas does not leak throughout the system.
Do not install unit in an area where flammable materials
•
are present due to risk of explosions that can cause serious
injury or death.
Safely dispose all packing and transportation materials
•
in accordance with federal/state/local laws or ordinances.
Packing materials such as nails and other metal or wood parts,
including plastic packing materials used for transportation
may cause injuries or death by suffocation.
English
! NOTE
Install the power supply and inter-unit wires for the indoor
•
and outdoor units at least 3.5ft away from televisions or
radios to prevent image interference or noise. Depending
on the radio waves, a distance of 3.5ft may not be sufficient
to eliminate the noise.
Dismantling the unit, treatment of the refrigerant, oil and
•
additional parts must be done in accordance with the relevant
local, state, and national regulations.
Do not use the following tools that are used with conventional
If the conventional refrigerant and refrigerator oil are mixed
•
in R410A, the refrigerant may deteriorate.
This air conditioner or heat pump is an appliance that should
•
not be accessible to the general public.
As design pressure is 536 psi, the wall thickness field-
•
installed pipes should be selected in accordance with the
relevant local, state, and national regulations.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with
unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of
other parts must be done by a qualifi ed installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is
disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact
the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national
legislation.
1-5
INSTALLATION DIAGRAM
Indoor Unit
1-15/16" (50mm) or more
from walls (on both sides)
Front panel
Air filter
Outdoor Unit
M4 x 12L
2-3/16" (55mm) or more from ceiling
Service lid
n Opening service lid
Service lid is removeable.
n Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.
Caulk pipe
hole gap
with putty.
19-11/16" (500mm) from wall
Cut thermal insulation pipe to an
appropriate length and wrap it with
tape, making sure that no gap is left
in the insulation pipe’s cut line.
Wrap the insulation pipe
with the finishing tape
from bottom to top.
INSTALLATION OF THE OUTDOOR UNIT (09/12)
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines
•
below.
For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200mm) or less.
•
Wall facing one side
More than 1-15/16 (50)
More than 3-15/16 (100)
47-1/4
(1200)
or less
Side View
Wall facing two sides
More than
More than
5-7/8 (150)
3-15/16 (100)
More than 1-15/16 (50)More than 1-15/16 (50)
Top View
Wall facing three sides
More than 5-15/16 (150)
More than 1-15/16 (50)
1-6
More than 11-13/16 (300)
Top View
Unit : Inch (mm)
Drain work. (Heat Pump Unit Only)
1) Use drain elbow for drainage.
2) If the drain port is covered by a mounting base or floor
surface, place additional foot bases of at least 1-3/16"
(30mm) in height under the outdoor unit’s feet.
3) In cold areas, do not use a drain elbow, drain plugs and a
drain hose with the outdoor unit. (Otherwise, drain water
may freeze, impairing heating performance.)
The outdoor unit must be installed in such a way, so as to prevent
short circuit of the hot discharged air or obstruction to the
smooth air flow. Please follow the installation clearances shown
in the figure. Select the coolest possible place where intake air
temperature is not greater than the outside air temperature (Refer
to operating range).
Installation clearances
Dimension
Minimum Distance,
Inch (mm)
ABCD
11-13/16
(300)
39-3/8
(1000)
11-13/16
(300)
19-11/16
(500)
Note: If there is any obstacle higher than half, of the unit’s
height (H), please allow more space than the figure indicated in
the above table.
Condensed Water Disposal Of Outdoor Unit
(Heat Pump Unit Only)
There are 10 holes on the base of Outdoor Unit for condensed
•
water to flow out. Insert the drain elbow to one of the holes.
To install the drain elbow, first insert one portion of the hook to
•
the base (portion A), then pull the drain elbow in the direction
shown by the arrow while inserting the other portion to the
base. After installation, check to ensure that the drain elbow
clings to base firmly.
If the unit is installed in a snowy and chilly area, condensed
•
water may freeze in the base. In such case, please remove plug
at the bottom of unit to smooth the drainage.
Obstacle
C
Obstacle
Return air
A
Return air
B
H
Discharge air
H/2
Obstacle
D
Obstacle
Service access
BASE
A
Drain elbow
DRAIN ELBOW
DRAIN ELBOW
Drain plug
Air outlet side
Drain plug
1-7
09/12
18/24
Please remove
side plate when
connecting
the piping and
connecting cord
PUSH & PULL UP
Please remove
side plate when
connecting
the piping and
connecting cord
PUSH & PULL UP
INSTALLATION OF THE OUTDOOR UNIT
1. Precautions for Selecting a Location
Choose a place solid enough to bear the weight and vibration of the unit, where the operating sound will not be
1)
amplified.
Choose a location where the hot air discharged from the unit or the operating sound will not cause a nuisance to the
2)
neighbors of the user.
Avoid locations, such as near bedrooms, where the operating sound may cause disturbance.
3)
There must be sufficient space to carry the unit into and out of the site.
4)
There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
5)
The site must not be prone to flammable gas leaks in the surrounding area.
6)
Install units, power cords and inter-unit wire at least 10ft (3m) away from television and radio sets. (This is to prevent
7)
interference to images and sounds. Noise may be produced even if they are more than 10ft (3m) away depending on radio
wave conditions.)
In coastal areas or other places with a salty atmosphere or one containing sulfate gas, corrosion may shorten the life of
8)
the air conditioner.
Since water will flow from the drain of the outdoor unit, do not place under the unit anything which must be kept away
9)
from moisture.
NOTE
Cannot be installed suspended from a ceiling or stacked.
! CAUTION
When operating the air conditioner in a low outdoor ambient temperature, be sure to follow the
instructions described below.
To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.
•
Never install the outdoor unit at a site where the suction side may be exposed directly to
•
wind.
To prevent exposure to wind, it is recommended to install a baffle plate on the air discharge
•
side of the outdoor unit.
In heavy snow areas, select an installation site where the snow will not affect the unit.
•
If there is a likelihood of snow accumulating on the outdoor unit, attach a snow protection
•
hood.
In high humidity areas or heavy snow areas, it is recommended to attach a drain pan heater to
•
prevent ice build-up from the bottom frame.
Construct a large canopy.
•
Construct a pedestal.
•
Install the unit high enough off the
ground to prevent burying in snow
1-8
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a way so as to prevent
short circuit of the cool discharged air with the hot return air.
Please follow the installation clearance shown in the figure. Do
not place the indoor unit where there could be direct sunlight
shining on it. Also, this location must be suitable for piping
and drainage, and be away from doors or windows.
Air flow
(Indoor)
min. 2-3/16" (55)
(Space for
performance)
min. 2" (50)
(Space for
maintenance)
Required space
min. 2" (50)
(Space for
maintenance)
All dimensions are in Inch (mm)
! CAUTION
• Must be mounted with the lowest moving parts at
least 8ft (2.4m) above floor or grade level.
The refrigerant piping can be routed to the unit in a number
of ways (left or right from the back of the unit), by using the
cut-out holes on the casing of the unit. Bend the pipes carefully
to the required position in order to align it with the holes. For
the side and bottom out, hold the bottom of the piping and
then position it to the required direction. The condensation
drain hose can be taped to the pipes.
Right-side, right-back or right-bottom piping
Right-side piping
Remove pipe port cover
here for right-side piping
Remove pipe port cover here
for right-bottom piping
Right-bottom
piping
Right-back piping
Bind coolant pipe
and drain hose
together with
insulating tape.
Left-side, left-back or left-bottom piping
Remove pipe port cover
here for left-side piping
Left-side piping
Remove pipe port cover here
for left-bottom piping
Left-bottom piping
Left-back piping
English
Bottom or side piping
Cut off pipe port cover with a copping saw.
1)
For bottom piping: On the bottom of the front grille
ü
For side piping: On the side cover (front grille side and unit side)
ü
Apply the blade of the copping saw to the notch, and cut off the pipe port cover along the uneven inner surface.
Front grille side
The figure shows the case of left bottom piping
Side cover
(front grille side)
After cutting off the pipe cover, perform filing.
2)
Remove the burrs along the cut section using a half round needle file.
Wrap the inter-unit wire, refrigerant pipes and drain hose together with insulation tape.
3)
Then, insert the drain hose and refrigerant pipes into the wall hole after inserting them into the cut out piping hole
opened.
Bind refrigerant pipe and drain hose
together with adhesive vinyl tape.
NOTE
Be careful not to let chips enter the driving section of the arm.
ü
Be careful not to put pressure on the lower front panel.
ü
1-9
Right-side
piping
Right-bottom piping
Left-side
piping
Left-bottom piping
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the weight
of the unit. Otherwise, it is necessary to reinforce the wall
with plates, beams or pillars.
Use the level gauge for horizontal mounting, and fix it with 5
suitable screws for FTXB/FTKB 09/12 and 7 suitable screws
for FTXB/FTKB 18/24.
In case the rear piping draws out, drill a hole 2-9/16" (65mm)
in diameter with a cone drill, slightly lower on the outside
wall (see figure).
FTXB/FTKB 09/12
Mounting plate
Mounting plate
fixing screw
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the installation
plate (Engage the two hooks at the rear top of the indoor unit
with the upper edge of the installation plate). Ensure that the
hooks are properly seated on the installation plate by moving
it to the left and right.
How To Attach The Indoor Unit
Hook the claws of the bottom frame to the mounting plate.
How To Remove The Indoor Unit
Push up the marked area (at the lower part of the front
grille) to release the claws.
Mounting plate
Clip
FTXB/FTKB 18/24
Mounting plate
Mounting plate
fixing screw
Drilling a Wall Hole and Installing Wall Embedded
Pipe
Hole With Cone Drill
Wall embedded pipe
Inside
(Field supply)
Wall hole cover
(Field supply)
Outside
Caulking
Ø
2-9/16" (65mm)
Wall embedded pipe
(Field supply)
Front grille
When stripping the ends
of interconnecting wires in
advance, bind right ends of
wires with insulating tape.
Bottom frame
Mark (Rear side)
Hand indoor unit’s hook here.
Mounting plate
Interconnecting
wires
Wire guide
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for
smooth drainage. Avoid situations that are likely to cause
water to leak.
Water Drainage
Water
Water
leaking
Water
leaking
retention
Water
leaking
End
dipped
into
water
Drain
CorrectWrong
WrongWrong
! CAUTION
• Do not install the unit at altitude over 6560ft (2000m)
for both indoor & outdoor.
1-10
REFRIGERANT PIPING
Allowable Piping Length
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
1. Equivalent piping length is obtained with actual length of gas piping.
2. 90° bend of piping is equivalent to L joint.
Bending must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe where possible.
1-11
REFRIGERANT PIPING
Piping Works And Flaring Technique
Do not use contaminated or damaged copper tubing. If
•
any piping, evaporator or condenser had been exposed or
had been opened for 15 seconds or more, the system must
be vacuumed. Generally do not remove plastic, rubber
plugs and brass nuts from the valves, fittings, tubing and
coils until it is ready to connect suction or liquid line into
valves or fittings.
If any brazing work is required, ensure that nitrogen gas
•
is passed through coil and joints while the brazing work
is being done. This will eliminate soot formation on the
inside wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of pipe
•
cutter slowly. Extra force and a deep cut will cause more
distortion of pipe and therefore extra burr. See Figure I.
Remove burrs from cut edges of the pipes with remover. See
•
Figure II. Hold the pipe on top position and burr remover
at lower position to prevent metal chips from entering the
pipe. This will avoid unevenness on the flare faces which
will cause gas leak.
Insert the flare nuts, mounted on the connection parts
•
of both the indoor unit and outdoor unit, into the copper
pipes.
The exact length of pipe protruding from the top surface
•
of the swaging block is determined by the flaring tool.
See Figure III.
Fix the pipe firmly on the swaging block. Match the centers
•
of both the swaging block and the flaring punch, then
tighten the flaring punch fully.
The refrigerant pipe connection are insulated by closed
•
cell polyurethane.
Piping Connection To The Units
Align the center of the piping and tighten the flare nut
•
sufficiently with fingers. See Figure IV.
Finally, tighten the flare nut with torque wrench until the
•
wrench clicks.
When tightening the flare nut with the torque wrench,
•
ensure that the tightening direction follows the arrow
indicated on the wrench.
The refrigerant pipe connection are insulated by closed
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Firmly fix the wires with
the terminal screws.
Outdoor unit
Recommend using AWG14, stranded and insulated
wire for connections between indoor and outdoor units.
Local code always supersedes recommendation.
1
2
L1
L2
GR
SIG
English
Indoor
unit
Conduit mounting plate
Conduit
Back
Lock nut
Note: Take care to ensure that all wiring between
indoor unit and outdoor unit has a consistent
connection. Any splices can cause communication
errors.
! CAUTION
• Entire PCB replacement required if fuse failure occurs.
All wires must be firmly connected.
•
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
•
Make sure no external pressure is applied to the terminal connectors and wires.
•
Make sure all the covers are properly fixed to avoid any gap.
•
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
•
1
2
SIG
Firmly fix the
wires with the
terminal screws.
RXB09/12*, RKB09/12*15A
RXB18/24*, RKB18/24*20A
Ground
Safety devices in
accordance with
local and national
codes, i.e. a
circuit breaker
Power supply
60Hz 208-230V
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Attach insulation sleeve
Round crimp-style terminal
Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
•
Over tightening can damage the terminal screws.
•
Do not connect wire of different gauge to same terminal.
•
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
•
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Electric wire
Do not connect wires
of different gauges.
1-13
ELECTRICAL WIRING CONNECTION
09/12 class
[Method of mounting conduit]
A protection plate is fixed for protection from the high-voltage section.
•
Dismount the stop valve cover by removing the screw.
1)
Dismount the protection plate by removing the 2 screws.
2)
Dismount the conduit mounting cover by removing the 2 screws.
3)
Pass wires through the conduit and secure them with a lock nut.
4)
After completing the work, reattach the stop valve cover, the conduit mounting cover, and the protection plate to its
5)
original position.
Power supply
terminal block
SIG
Shape wires so that
the proctection plate
and conduit mounting
plate fit securely.
Conduit
mounting
plate
Lock nut
Conduit
18/24 class
[Method of mounting conduit]
Dismount the service lid by removing the screws.
1)
Pass wires through the conduit and secure them with a lock nut.
2)
After completing the work, reattach the service lid to its original position.
3)
Protection plate
SIG
Screws
Conduit
mounting
cover
Screws
SIG
Conduit
Conduit mounting plate
Power supply
terminal block
Shape wires so that
the proctection plate
and conduit mounting
plate fit securely.
Lock nut
1-14
Service lid
SIG
Screws
Screws
SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT
R410A is a new HFC refrigerant which does not damage the
ozone layer. The working pressure of this new refrigerant is
1.6 times higher than conventional refrigerant (R22), thus
proper installation/servicing is essential.
Never use refrigerant other than R410A in an air conditioner
•
which is designed to operate with R410A.
POE or PVE oil is used as lubricant for R410A compressor,
•
which is different from the mineral oil used for R22
compressor. During installation or servicing, extra precaution
must be taken not to expose the R410A system too long
to moist air. Residual POE or PVE oil in the piping and
components can absorb moisture from the air.
To prevent mischarging, the diameter of the service port
•
Use tools and materials exclusively for refrigerant R410A.
•
Tools exclusively for R410A are manifold valve, charging
hose, pressure gauge, gas leak detector, flare tools, torque
wrench, vacuum pump and refrigerant cylinder.
As an R410A air conditioner incurs higher pressure
•
than R22 units, it is essential to choose the copper pipes
correctly.
If the refrigerant gas leakage occurs during installation/
•
servicing, be sure to ventilate fully. If the refrigerant gas
comes into contact with fire, a poisonous gas may occur.
When installing or removing an air conditioner, do not
•
allow air or moisture to remain in the refrigerant cycle.
on the flare valve is different from that of R22.
VACUUMING AND CHARGING
Vacuuming is necessary to eliminate all moisture and air from the system.
Vacuuming The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant connection
pipes must be air-purged because the air containing moisture
that remains in the refrigerant cycle may cause malfunction
of the compressor.
Remove the caps from the valve and the service port.
•
Connect the center of the charging gauge to the vacuum
•
pump.
Connect the charging gauge to the service port of the 3-way
•
valve.
Start the vacuum pump. Evacuate for approximately 30
•
minutes. The evacuation time varies with different vacuum
pump capacity. Confirm that the charging gauge needle has
moved towards -14.7psi (-760mmHg).
Caution
If the gauge needle does not move to -14.7psi (-760mmHg),
•
be sure to check for leakage at flare type connection of
the indoor and outdoor unit and repair the leak before
proceeding to the next step.
Close the valve of the changing gauge and stop the vacuum
•
pump.
On the outdoor unit, open the suction valve (3 way) and
•
liquid valve (2 way) (in anti-clockwise direction) with
5/32" (4mm) key for hexagon sacked screw.
Allen key
Service Port
LOW PRESSURE GAUGE
-14.7psi (-760mmHg)
HANDLE LO
CHARGE HOSE
LIQUID VALVE
GAS VALVE
(3-WAY)
Flare nut
Outdoor Unit 3 ways valve
Refrigerant Piping
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
VACUUM PUMP
ADAPTER FOR
COUNTER FLOW
PREVENTION
CHECK VALVE
CONFIGURATION OF AIR
PURGE BY CHARGING
English
Charge Operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is topped-up
into the outdoor unit using the suction valve via the service
port.
Remove the service port cap.
•
Connect the low pressure side of the charging gauge to the
•
suction service port center of the cylinder tank and close
the high pressure side of the gauge. Purge the air from the
service hose.
Start the air conditioner unit.
•
Open the gas cylinder and low pressure charging valve.
•
When the required refrigerant quantity is pumped into
•
the unit, close the low pressure side and the gas cylinder
valve.
Disconnect the service hose from service port. Put back
•
the service port cap.
1-15
LOW PRESSURE GAUGE
-14.7psi (-760mmHg)
HANDLE LO
CHARGE HOSE
LIQUID VALVE
GAS VALVE
(3-WAY)
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
CHECK VALVE
CONFIGURATION OF AIR
PURGE BY CHARGING
ADDITIONAL CHARGE
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 25ft (7.6m), then additional charge after
vacuuming is not necessary. If the piping length is more than 25ft (7.6m), then use the additional charge value as indicated
in the table.
Additional refrigerant charge [oz (g)] per additional 3.28ft (1m) length as tabulated.
When an infrared remote control operating signal has been
transmitted, the signal receiver on the indoor unit will respond
as below to confirm acceptance of the signal transmission.
ON to OFF1 Long Beep
OFF to ON
Pump down / Cool force on
Others1 Short Beep
Cooling Unit/Heat Pump Unit
The table shows the LED indicator lights for the air conditioner
unit under normal operation and fault conditions. The LED
indicator lights are located at the side of the air conditioner
unit.
The heat pump units are equipped with an “auto” mode
sensor whereby it will provide reasonable room temperature
by switching automatically to either “cool” or “heat” mode
according to the temperature set by the user.
2 Short Beep
LED Indicator Lights for Cooling Unit/Heat Pump
Unit
ON/OFF
IR Receiver
Cool/Heat/Timer
IR Receiver
ON/OFF switch
LED Indicator Lights: Normal Operation And Fault Conditions For Cooling/Heat Pump Unit
Operation
Cool mode
Heat mode
Auto mode in Heating operation
Auto mode in Cooling operation
Timer on
Fan mode on
Dry mode on
Defrost operation
Unit error
Blinking
1-16
ON
COOL/HEAT/TIMER
(BLUE/RED/VIOLET)
BLUE
RED
RED
BLUE
VIOLET
BLUE
BLUE
RED
BLUE
OPERATING RANGE
Cooling Only Model
Model: FTKB 09/12 RKB 09/12Model: FTKB 18/24 RKB 18/24
COOLING
122/50
114.8/46
109.4/43
104/40
86/30
68/20
50/10
32/0
57.2/14 66.2/19 73.4/23
50/10 59/15
OUTDOOR TEMP (°F/°CDB)
68/20 77/25
INDOOR TEMP (°F/°CWB)
Heat Pump Model
Model: FTXB 09/12 RXB 09/12
COOLINGHEATING
122/50
114.8/46
109.4/43
104/40
86/30
68/20
50/10
32/0
57.2/14 66.2/19 73.4/23
50/10 59/15
OUTDOOR TEMP (°F/°CDB)
INDOOR TEMP (°F/°CWB)
68/20 77/25
DB: Dry bulb WB: Wet bulb
DB: Dry bulb WB: Wet bulb
COOLING
122/50
114.8/46
109.4/43
104/40
86/30
68/20
50/10
32/0
14/-10
-4/-20
50/10 59/1568/2077/25
OUTDOOR TEMP (°F/°CDB)
INDOOR TEMP (°F/°CWB)
68/20
64.4/18
50/10
32/0
14/-10
5/-15
-4/-20
50/10 59/1568/2077/2586/30
OUTDOOR TEMP (°F/°CWB)
INDOOR TEMP (°F/°CDB)
73.4/2366.2/1957.2/14
80.6/27
English
Model: FTXB 18/24 RXB 18/24
COOLINGHEATING
122/50
114.8/46
109.4/43
104/40
86/30
68/20
50/10
32/0
14/-10
-4/-20
50/10 59/1568/2077/25
OUTDOOR TEMP (°F/°CDB)
73.4/2366.2/1957.2/14
INDOOR TEMP (°F/°CWB)
DB: Dry bulb WB: Wet bulb
Open the front panel.
1.
Hold the panel at the recesses on the main unit
•
(2 recesses on right and left sides) and lift it until it
stops.
Recess on
main unit
AIR FILTER
Clean or replace each filter.
3.
•
Set the air filter and close the front panel.
4.
•
•
68/20
64.4/18
50/10
32/0
14/-10
5/-15
-4/-20
50/10 59/1568/20 77/2586/30
OUTDOOR TEMP (°F/°CWB)
80.6/27
INDOOR TEMP (°F/°CDB)
When shaking off remaining water, do not wring the
filter.
Insert claws of the filters into slots of the front panel.
Close the front panel slowly and push the panel at the
3 points. (1 on each side and 1 in the middle.)
The air filter have a symmetrical form in the horizontal
direction.
Pull out the air filters.
2.
Push a little upwards the tab at the center of each air
•
filter, then pull it down.
FRONT
1-17
SERVICE AND MAINTENANCE
Service PartsMaintenance ProceduresPeriod
Indoor air filterRemove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm
Indoor unitClean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in
1.
water (below 40°C/104°F) with a neutral cleaning detergent.
Rinse the filter well and dry before placing it back onto the unit.
2.
Do not use gasoline, volatile substances or chemicals to clean the filter.
3.
1.
lukewarm water (below 40°C/104°F) and a neutral detergent solution.
Do not use gasoline, volatile substances or chemicals to clean the indoor unit.
2.
At least once
every 2 weeks.
More frequently
if necessary.
At least once
every 2 weeks.
More frequently
if necessary.
! CAUTION
• Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a result
of chemical reaction.
Open the front panel.
1.
Hold the panel at the recesses on the main unit
•
(2 recesses on right and left sides) and lift it until it
stops.
Remove the front panel.
2.
While lifting the front panel further, slide it to the right
•
and pull it to the front side. The left rotating shaft is
detached. Slide the right rotating shaft to the left and
pull it to the front side to remove it.
Attach the front panel.
3.
Align the right and left rotating shafts of the front panel
•
with the grooves and push them all the way in.
Gently close the front panel. (Push both ends and the
•
center on the front panel.)
Rotating shaft
Recess on
main unit
Front Panel Opening & Closing Sequence
To open the front panel
1) Lift up the two tips of front panel 1 until it stops at the pre-fix position.
2) Lift up the two tips of front panel 2 to open it and access to inner parts.
To close the front panel, reverse the steps of opening sequence. Slot in the ribs (4 ribs at each side, total 8 ribs), carefully at
both left and right. Then, press the panel forward till it closes tight. Refer to 3
Step 1
Step 3Step 3
Step 2
1-18
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.