Daikin EWWQ-L-SS Operation manuals

EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
1
Air and Water cooled scroll chillers & heat pump
D-EOMHW00106-15EN
OPERATION MANUAL
Water cooled ranges: EWWQ090G ÷ EWWQ720L - R410a - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers
Air cooled ranges: EWAQ-G 075155 SS - R410a - Air-cooled scroll chillers
EWAQ-G 080170 XS - R410a - Air-cooled scroll chillers EWYQ-G 075160 XS - R410a - Air-cooled scroll heat pumps
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
2
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Table of Contents
1 SAFETY CONSIDERATIONS .................................................................................................. 5
1.1 General ............................................................................................................................. 5
1.2 Avoid electrocution ........................................................................................................... 5
1.3 Safety Devices .................................................................................................................. 6
1.3.1 General safety devices .............................................................................................. 6
1.3.2 Circuit safety devices ................................................................................................. 6
1.3.3 Component safety devices ......................................................................................... 6
1.4 Available sensors .............................................................................................................. 8
1.4.1 Pressure transducers ................................................................................................. 8
1.4.2 Temperature sensors ................................................................................................. 8
1.4.3 Thermistors ................................................................................................................ 8
1.5 Available Controls ............................................................................................................. 8
1.5.1 Evaporator - Condenser pumps ................................................................................. 8
1.5.2 Compressors ............................................................................................................. 8
1.5.3 Expansion Valve ........................................................................................................ 8
1.5.4 Four Way Valve ......................................................................................................... 8
1.6 Abbreviations used ........................................................................................................... 9
1.7 Customer Terminal Block Connections ............................................................................. 9
1.7.1 Connections description and purpouse ...................................................................... 9
2 GENERAL DESCRIPTION .................................................................................................... 12
2.1 Overview ......................................................................................................................... 12
2.2 Controller Operating Limits ............................................................................................. 12
2.3 Controller Architecture .................................................................................................... 12
2.4 Communication Modules ................................................................................................ 13
3 Using the Controller ............................................................................................................... 14
3.1 General Recommendation .............................................................................................. 15
3.2 Browsing ......................................................................................................................... 15
3.3 Passwords ................................ ...................................................................................... 16
3.4 Editing ............................................................................................................................ 16
3.5 Basic Control System Diagnostic .................................................................................... 17
3.6 Controller maintenance ................................................................................................... 19
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
3
3.7 Software Update procedure ............................................................................................ 19
3.8 Optional Remote User Interface ...................................................................................... 22
3.9 Embedded Web Interface ............................................................................................... 24
4 Menu Structure ...................................................................................................................... 26
4.1 Main Menu ...................................................................................................................... 26
4.2 View/Set Unit .................................................................................................................. 27
4.2.1 Thermostat Ctrl ........................................................................................................ 27
4.2.2 Network Ctrl ............................................................................................................. 27
4.2.3 Unit Cond Ctrl (W/C only) ........................................................................................ 27
4.2.4 Pumps ..................................................................................................................... 28
4.2.5 Date/Time ................................................................................................................ 28
4.2.6 Power Conservation ................................................................................................ 28
4.2.7 Controller IP setup ................................................................................................... 29
4.3 View/Set Circuit .............................................................................................................. 29
4.3.1 Settings ................................................................................................................... 30
4.4 Tmp Setpoints................................................................................................................. 31
4.5 Temperatures ................................................................................................ ................. 32
4.6 Available Modes ............................................................................................................. 32
4.7 Timers ............................................................................................................................ 32
4.8 Alarms ................................ ............................................................................................ 32
4.9 Commission Unit ............................................................................................................. 33
4.9.1 Configure Unit .......................................................................................................... 33
4.9.2 Alarm Limits ............................................................................................................. 34
4.9.3 Calibrate Unit Sensors ............................................................................................. 34
4.9.4 Calibrate Circuit Sensors ......................................................................................... 34
4.9.5 Unit Manual Control ................................................................................................. 35
4.9.6 Circuit 1 Manual Control .......................................................................................... 35
4.9.7 Scheduled Maintenance .......................................................................................... 36
4.10 Save and Restore ................................................................................................ ........... 36
4.11 About this Chiller ............................................................................................................. 37
5 Working with this unit ............................................................................................................. 37
5.1 Unit Setup ................................ ....................................................................................... 37
5.1.1 Control Source ......................................................................................................... 37
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
4
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
5.1.2 Available Mode Setting ............................................................................................ 38
5.1.3 Temperature Setpoint Settings ................................................................................ 38
5.1.4 Thermostat Control Settings .................................................................................... 39
5.1.5 Alarm Settings ......................................................................................................... 41
5.1.6 Pumps ..................................................................................................................... 41
5.1.7 Power Conservation ................................................................................................ 42
5.2 Unit/Circuit Start-up ........................................................................................................ 44
5.2.1 Prepare the unit to start ................................ ........................................................... 44
5.2.2 Preparing circuits to start ......................................................................................... 46
5.3 Circuit Capacity Control .................................................................................................. 47
5.3.1 Low Evaporating Pressure ....................................................................................... 47
5.3.2 High Condensing Pressure ...................................................................................... 48
5.4 Mode Change-Over (H/P only) ........................................................................................ 48
5.5 Backup Heaters (A/C only).............................................................................................. 49
5.6 Condensation Control (W/C only).................................................................................... 49
5.6.1 Pressure (W/C only) ................................................................................................ 49
5.6.2 Cond In / Cond Out (W/C only) ................................................................................ 50
5.6.3 Fan Control (A/C only) ............................................................................................. 50
5.7 EXV Control .................................................................................................................... 50
5.8 Defrost (A/C only) ........................................................................................................... 51
5.9 Four Way Valve (H/P gas side reversal only) .................................................................. 52
6 Alarms ................................................................................................................................... 53
6.1.1 Unit Warning Alarms ................................................................................................ 53
6.1.2 Unit Pumpdown Stop Alarms ................................................................................... 55
6.1.3 Unit Rapid Stop Alarms ............................................................................................ 56
6.1.4 Circuit Warning Alarms ............................................................................................ 60
6.1.5 Circuit Pumpdown Stop Alarms ............................................................................... 61
6.1.6 Circuit Rapid Stop Alarms ........................................................................................ 61
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
5
RISK OF ELECTROCUTION: Even when the main circuit breaker or isolator is switched off, certain circuits may still be energized, since they may be connected to a separate power source.
RISK OF BURNS: Electrical currents cause components to get hot either temporarily or permanently. Handle power cable, electrical cables and conduits, terminal box covers and motor frames with great care.
ATTENTION: In accordance with the operating conditions the fans can be cleaned periodically. A fan can start at any time, even if the unit has been shut down.
1 SAFETY CONSIDERATIONS
1.1 General
Installation, start-up and servicing of equipment can be hazardous if certain factors particular to the installation are not considered: operating pressures, presence of electrical components and voltages and the installation site (elevated plinths and built-up up structures). Only properly qualified installation engineers and highly qualified installers and technicians, fully trained for the product, are authorised to install and start-up the equipment safely.
During all servicing operations, all instructions and recommendations, which appear in the installation and service instructions for the product, as well as on tags and labels fixed to the equipment and components and accompanying parts supplied separately, must be read, understood and followed.
Apply all standard safety codes and practices. Wear safety glasses and gloves. Use the proper tools to move heavy objects. Move units carefully and set them down gently.
1.2 Avoid electrocution
Only personnel qualified in accordance with IEC (International Electrotechnical Commission) recommendations may be permitted access to electrical components. It is particularly recommended that all sources of electricity to the unit be shut off before any work is begun. Shut off main power supply at the main circuit breaker or isolator.
IMPORTANT: This equipment uses and emits electromagnetic signals. Tests have shown that the equipment conforms to all applicable codes with respect to electromagnetic compatibility.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
6
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
The emergency stop causes all motors to stop, but does not switch off power to the unit. Do not service or operate on the unit without having switched off the main switch.
1.3 Safety Devices
Each unit is equipped with safety devices of three different kinds:
1.3.1 General safety devices
Safeties of this level of severity will shut down all the circuits and stop the entire unit. When a general safety device will occur a manual intervention on the unit will be required in order to re­establish the normal operability of the machine. There are exceptions to this general rule in case of alarms linked to temporary abnormal conditions.
Emergency Stop
A push button is placed on a door of the unit electrical panel. The button is highlighted by a red color in yellow background. A manual pressure of the emergency stop button stops all loads from rotating, thus preventing any accident which may occur. An alarm is also generated by the Unit Controller. Releasing the emergency stop button enables the unit, which may be restarted only after the alarm has been cleared on the controller.
1.3.2 Circuit safety devices
Safety of this level of severity will shut down the circuit they protect. The remaining circuits will keep running.
1.3.3 Component safety devices
Safety of this level of severity will shut down a component against abnormal running condition that could create permanent damages to it. An overview of the protecting devices is listed below:
Overcurrent/Overload Protections
Overcurrent/overload devices protect electrical motors used on compressors, and pumps in case of overload or short circuit. In case of inverter-driven motors, overload and overcurrent protection is integrated in the electronic drives. A further protection from short circuit is accomplished by fuses or circuit breakers installed upstream each load or group of loads.
Overtemperature Protections
Compressors are also protected from overheating by thermistors immersed into motor windings. Should the winding temperature exceed a fixed threshold, the thermistors will trip and cause the motor to stop.
Phase reversal, under/over voltage, ground fault protections
When one of those alarms occurs the unit is immediately stopped or even inhibited to start. The alarms clear automatically once the problem is fixed. This auto clear logic allows the unit to automatically recover in case of temporary conditions where the supply voltage reaches the upper or lower limit set on the protection device. In the other two cases a manual intervention
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
7
Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons.
on the unit will be required in order to solve the problem. In case of a phase reversal alarm two phases requires to be inverted.
In the event of a power supply outage, the unit will restart automatically without the need for an external command. However, any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or unit from restarting.
Flowswitch
The unit must be protected by a flowswitch. The flowswitch will stop the unit when the water flow becomes lower than the minimum allowed flow. When the water flow is restored the flow protection resets automatically. Exception is when the flowswitch opens with at least one compressor running, in this case the alarm shall be cleared manually.
Freezing protection
Antifreeze protection prevents the water to freeze in the evaporator. It is automatically activated when the water temperature (entering or leaving) at the evaporator drops below the antifreeze limit. In freeze condition if the unit is in standby the evaporator pump will be activated to prevent freezing of the evaporator. If the freeze condition will activate when the unit is running all the unit will shut down in alarm while the pump will keep running. Alarm will automatically clear when the freeze condition will clear.
Low pressure protection
If the circuit operates with a suction pressure lower than an adjustable limit for a certain time the circuit safety logic will shut down the circuit and generate an alarm. The alarm requires a manual action on the Unit Controller to be reset. Reset will take effect only if the suction pressure is no longer lower that the safety limit.
High Pressure Protection
If the discharge pressure becomes too high and exceeds a limit which is linked with the operational envelop of the compressor the circuit safety logic will try to prevent the alarm or, if the corrective actions have no effect, it will shut down the circuit before the Mechanical High Pressure switch will open. This alarm required a manual action on the Unit Controller to be reset.
Mechanical High Pressure Switch
Each circuit is equipped with at least one high pressure switch which tries to prevent the relief safety valve to open. When the discharge pressure becomes too high the Mechanical High Pressure switch will open and immediately stop the compressor cutting the power supply to the auxiliary relay. The alarm can be cleared as soon as the discharge pressure becomes normal
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
8
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
again. The alarm must be reset on the switch itself and on the Unit Controller. The triggering pressure value cannot be changed.
Relief Safety Valve
If the pressure becomes too high in the refrigerant circuit, the relief valve will open to limit the maximum pressure. If this happens switch off immediately the machine and contact your local service organization.
1.4 Available sensors
1.4.1 Pressure transducers
Two electronic sensors are used to measure the evaporating and condensing pressure of each circuit. The range of each sensor is clearly indicated on the sensor casing.
1.4.2 Temperature sensors
The evaporator and condenser water sensors are installed in the entering and leaving side. Additionally each circuit installs a suction temperature sensor to monitor and control the superheated refrigerant temperatures.
1.4.3 Thermistors
Each compressor is equipped with PTC thermistors which are immersed into motor windings for motor protection. Thermistors trip to a high value in case the motor temperature reaches a hazardous temperature.
1.5 Available Controls
In the following the different functions will be distinguished between Water Cooled (W/C) and Air Cooled (A/C) units and Cooling Only (C/O) and Heat Pumps (H/P). If not specified one specific function can apply to any W/C unit independently from being a C/O or H/P unit.
1.5.1 Evaporator - Condenser pumps
The controller can regulate one or two evaporator pumps and takes care of automatic change-over between pumps. It’s also possible to prioritize the pumps and temporarily disable one of the twos.
The controller can also regulate an unique condenser water pump (W/C units only).
1.5.2 Compressors
The controller can regulate two or four compressors installed on one or two independent refrigerant circuit. All the safeties of each compressor will be managed by the controller.
1.5.3 Expansion Valve
The controller can regulate an electronic expansion valve per each refrigerant circuit to guarantee the best operation for the refrigerant circuit.
1.5.4 Four Way Valve
The controller can command a four way valve per each refrigerant circuit where required. The valve is used to reverse the unit mode from Cool to Heat.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
9
UC
Unit controller
HMI
Human Machine Interface
A/C
Air Cooled
W/C
Water Cooled
C/O
Cooling Only
H/P
Heat Pump
CL
Condenser Less
CP
Condensing Pressure
EP
Evaporating Pressure
CSRT
Condensing Saturated Refrigerant Temperature
ESRT
Evaporating Saturated Refrigerant Temperature
ST
Suction Temperature
SSH
Suction SuperHeat
EXV
Electronic Expansion Valve
ELWT
Evaporator Leaving Water Temperature
EEWT
Evaporator Entering Water Temperature
CLWT
Condenser Leaving Water Temperature
CEWT
Condenser Entering Water Temperature
Description
Terminals
Notes
Evaporator Flow Switch (mandatory)
724, 708
For potential-free contacts Sampling voltage / current DC 24 V / 8 mA
Condenser Flow Switch (W/C mandatory)
794, 793
For potential-free contacts Sampling voltage / current DC 24 V / 8 mA
Cooling/Heating Remote switch (H/P units only)
743,744
For potential-free contacts Sampling voltage / current DC 24 V / 8 mA
Double setpoint
713,709
For potential-free contacts Sampling voltage / current DC 24 V / 8 mA
External Fault
884, 885
For potential-free contacts Sampling voltage / current DC 24 V / 8 mA
On-Off Remote
741, 742
For potential-free contacts Sampling voltage / current DC 24 V / 8 mA
General Alarm
525, 526
NO digital output (24…230 Vac ext supply)
Evaporator Pump #1 start
527,528
NO digital output (24…230 Vac ext supply)
Evaporator Pump #2 start
530, 531
NO digital output (24…230 Vac ext supply)
1.6 Abbreviations used
In this manual, the refrigeration circuits are called circuit #1 and circuit #2. The following abbreviations are used frequently:
1.7 Customer Terminal Block Connections
1.7.1 Connections description and purpouse
The contacts below are available at the user’s terminal block referred as MC24 or MC230 in the
wiring diagram. The following table summarizes the connections at the user’s terminal block.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
10
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Condenser Pump #1 start (W/C only)
520,521
NO digital output (24…230 Vac ext supply)
Condenser Pump #2 start (W/C only)
540,541
NO digital output (24…230 Vac ext supply)
Demand Limit
888, 889
4-20 mA analog input
Setpoint Override
886, 887
4-20 mA analog input
Condenser three way valve (W/C only)
772, 773
0-10V analog output
Condenser tower fan speed (W/C only)
772, 774
0-10V analog output
Master/Slave Water Temperature
890, 896
NTC10K temperature sensor
Master/Slave Bus Connection
900, 901
Serial communication
Operating the unit by-passing the flow switch input or without an appropriate flow switch may damage the water heat exchanger due to freezing. Operation of the flow switch must be checked prior to start up the unit.
1.7.1.1 Flow Switch
Although the flow switch is offered as an optional, it is mandatory to install one and connect it to the digital input terminals in order to enable chiller operation only when a minimum flow is sensed.
1.7.1.2 Double setpoint
This contact can be used to switch between two different LWT setpoints and, depending on the application, between different modes of operation.
Ice operation must be selected in case of ice storage application. In this case the UC will run the chiller in on/off mode switching all the chiller off as soon as the setpoint is reached. In this case the unit will run to full capacity and then will switch off applying an ice delay different chiller starts.
1.7.1.3 External Fault (optional)
This contact is available to report to the UC a fault or a warning from an external device. It could be an alarm coming from an external pump to inform the UC of the fault. This input can be configured as a fault (unit stop) or a warning (displayed on the HMI without any action on the chiller).
1.7.1.4 Remote On-Off
This unit can be started through a remote enable contact. The Q0 switch must be selected to “Remote”.
1.7.1.5 General Alarm
In case of a unit alarm, this output is closed thus indicating a fault condition to an externally connected BMS.
1.7.1.6 Evaporator Pump Start
Two digital outputs are enabled when the pumps (#1 or #2) are required to start. The output for the pump #2 requires a relay with less than 20 mA excitation current.
1.7.1.7 Setpoint override (optional)
This input allows to apply an offset on the Active Setpoint to adjust the operating point of the ELWT. This input can be used to maximize the comfort.
1.7.1.8 Demand Limit (optional)
This input allows to limit the maximum number of compressor in run state.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
11
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
12
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
2 GENERAL DESCRIPTION
2.1 Overview
The UC is a system for controlling single or dual-circuit W/C and A/C liquid chillers / heat-pump. The UC controls compressor start-up necessary to maintain the desired heat exchanger leaving water temperature.
On W/C units the UC can optionally controls a three way valve or a cooling tower to perform a condensing control. One of the following three variables can be selected as condensing target:
- Condenser leaving water temperature (W/C only)
- Condenser entering water temperature (W/C only)
- Condensing saturated refrigerant temperature
Safety devices are constantly monitored by the UC to ensure their safe operation. UC also gives access to a Test routine covering all inputs and outputs. The controller can work in accordance with three independent modes:
Local mode: the machine is controlled by commands from the user interface. Remote mode: the machine is controlled by remote contacts (volt-free contacts). Network mode: the machine is controlled by commands from a BAS system. In this case, a
data communication cable is used to connect the unit to the BAS.
When the UC operates autonomously (Local or Remote mode) it retains all of its own control capabilities but does not offer any of the command features of the Network mode (monitoring only).
2.2 Controller Operating Limits
Operation (IEC 721-3-3):
Temperature -40...+70 °C Restriction LCD -20… +60 °CRestriction Process-Bus -25….+70 °CHumidity < 90 % r.h (no condensation) Air pressure min. 700 hPa, corresponding to max. 3,000 m above sea level
Transport (IEC 721-3-2):
Temperature -40...+70 °C Humidity < 95 % r.h (no condensation) Air pressure min. 260 hPa, corresponding to max. 10,000 m above sea level.
2.3 Controller Architecture
The overall controller architecture is the following:
A unit controller (UC) I/O extensions as needed depending on the configuration of the unit Communications interface(s) as selected
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
13
Controller/
Extension Module
Siemens Part Number
Address
Usage
Main Controller
POL638.00/MCQ
n/a
Used on all configurations
EEXV Module 1
POL94E.00/MCQ
3
Used on all configurations
EEXV Module 2
POL94E.00/MCQ
5
Used when configured for 2 circuits
Option Module
POL965.00/MCQ
18
Used when options required
Maintain the correct G-G0 polarity when connecting the power supply directly to the extension boards. The peripheral bus communication will not operate and the boards may be damaged.
Module
Siemens Part Number
Usage
BacNet/IP
POL908.00/MCQ
Optional
Lon
POL906.00/MCQ
Optional
Modbus
POL902.00/MCQ
Optional
BACnet/MSTP
POL904.00/MCQ
Optional
Peripheral Bus is used to connect I/O extensions to the main controller.
All boards are supplied from a common 24 Vac sourced directly from the unit. Extension boards can be directly powered by the Unit Controller. All boards can be also supplied by a 24Vdc source. These are the limits for the two different power supplies available:
AC: 24V 20% (frequency 45 65Hz) DC: 24V 10%
2.4 Communication Modules
Any of the following modules can be connected directly to the left side of the main controller to allow a BAS or other remote interface to function. Up to three can be connected to the controller at a time. The controller should automatically detect and configure itself for new modules after booting up. Removing modules from the unit will require manually changing of the configuration.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
14
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Alarm status (from any page it links with the page with alarm list, alarm log and alarm snapshot if available)
INFO
Back to Main Page
ESC
Back to the previous level (it can be the Main Page)
Wheel Button
Used to scroll between the different menu pages, settings and data available on the HMI for the active password level. Rotating the wheel allows to navigate between lines on a screen (page) and to increase and decrease changeable values when editing. Pushing the wheel acts as an Enter Button and will jump from a link to the next set of parameters.
1
2 3
4
5
6
Separate documents contains all the information about the different protocols supported and how to setup a proper communication with a BMS.
3 Using the Controller
The control system consists of a unit controller (UC) equipped with a set of extension modules that implement additional features. All boards communicate via an internal peripheral bus with the UC. The UC continuously manages the information received from the various pressure and temperature probes installed on the unit. The UC incorporates a program that controls the unit.
Two different types of UC HMI are available as standard HMI:
1. Inbuilt HMI (A/C units)
This HMI is provided of three buttons and one wheel button.
2. External HMI (POL871.72) (W/C units)
This External HMI is provided of six buttons.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
15
1
i
Back to Main Page
2  Alarm status (from any page it links with the page with alarm list, alarm log and
alarm snapshot if available)
3
Back to the previous level (it can be the Main Page)
4 ▲ Go above
5 ▼ Go below
6  Confirm
M a i n M e n u 1 /
11 E n T e r P a s s w o r d
U n I t S t a t u s =
O F f : U n i t S W A c T i v e S e t p t = 7 . 0 °
C
M a i n M e n u 1 /  E n T e r P a s s w o r d
U n I t S t a t u s = O F f : U n i t S W
A c T i v e S e t p t = 7 . 0 °
C
3.1 General Recommendation
Before switching on the unit read the following recommendations:
When all the operations and all the settings have been carried out, close all the switchbox
panels
The switchbox panels can only be opened by trained personnel When the UC requires to be accessed frequently the installation of a remote interface is
strongly recommended
Compressor are protected from freezing by electrical heaters. These heaters are supplied
through unit main supply and temperature controlled by thermostat.
the LCD display of the unit controller may be damaged by extremely low temperatures. For
this reason, it is strongly recommended to never power off the unit during winter, especially in cold climates.
3.2 Browsing
When power is applied to the control circuit, the HMI screen will be active and display the Home screen.
An example of the HMI screens is shown in the following picture.
In the inbuilt HMI a ringing bell in the top right corner will indicate an active alarm, If the bell
doesn’t move it means that the alarm has been acknowledged but not cleared because the alarm
condition hasn’t been removed.
Same alarm indication is performed by the LED of the button 2 of the external HMI.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
16
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
E n t e r P a s s w o r d 2 / 2
E n t e r P W * * *
*
USER
5321
MAINTENANCE
2526
E n t E r P a s s w o r d 2 /
2
E n t e R P W 5 * * *
The active item is highlighted in contrast, in this example the item highlighted in Main Menu is a link to another page. By pressing the button 6, the HMI will jump to a different page. In this case the HMI will jump to the Enter Password page.
3.3 Passwords
The HMI structure is based on access levels that means that each password will disclose all the settings and parameters allowed to that password level. Basic information about the status including the active alarm list, active setpoint and controlled water temperature can be accessed without the need to enter the password.
The UC handles two level of passwords:
The following information will cover all data and settings accessible with the maintenance password. User password will disclose a subset of the settings explained in chapter 4.
In the Enter Password screen, the line with the password field will be highlighted to indicate that the field on the right can be changed. This represents a setpoint for the controller. Pressing the wheel or button 6 the individual field will be highlighted to allow an easy introduction of the numeric password. By changing all fields, the 4 digits password will be entered and, if correct, the additional settings available with that password level will be disclosed.
The password will time out after 10 minutes and is cancelled if a new password is entered or the control powers down. Entering an invalid password has the same effect as continuing without a password.
Once a valid password has been entered, the controller allows further changes and access without requiring the user to enter a password until either the password timer expires or a different password is entered. The default value for this password timer is 10 minutes.
3.4 Editing
Only line with highlighted value field can be edited, through the right buttons it is possible selected and modify the value.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
17
BSP LED
Mode
Solid Green
Application running
Solid Yellow
Application loaded but not running (*) or BSP Upgrade mode active
Solid Red
Hardware Error (*)
Flashing Green
BSP startup phase. The controller needs time for starting.
Flashing Yellow
Application not loaded (*)
Flashing Yellow/Red
Fail safe mode (in case that the BSP upgrade was interrupted)
Flashing Red
BSP Error (software error*)
Flashing Red/Green
Application/BSP update or inizialization
A parameter with an “R” is read only; it is giving a value or description of a condition. An “R/W
indicates a read and/or write opportunity; a value can be read or changed (providing the proper password has been entered).
Example 1: Check Status, for example -is the unit being controlled locally or by an external network? We are looking for the Unit Control Source since this a unit status parameter, start at Main Menu and select View/Set Unit and press the wheel or button 6 to jump to the next set of menus. There will be an arrow at the right side of the box, indicating that a jump to the next level is required.
In the new page rotate the wheel or use button 4/5 to highlight the Network Ctrl and press the wheel or the button 6 again to jump to the next menu where it is possible read the actual Control Source.
Example 2: Change a Set point, the chilled water set point for example. This parameter is designated as Cool LWT Set point 1 and is a unit set parameter. From the Main Menu select Active Setpt. The arrow indicated that there is a link to a further menu.
Press the wheel or button 6 and jump to the temperature setpoint page. Select Cool LWT 1 and press the wheel or button 6 to jump to the item change page. Rotate the wheel or use buttons 4 / 5 to adjust the set point to the desired value. When this is done press the wheel or button 6 again to confirm the new value. With the button ESC or 3 it will be possible to jump back to the main menu where the new value will be displayed.
Example 3: Clear an Alarm,. The presence of a new alarm is indicated with a Bell ringing on the top right of the display. If the Bell is frozen one or more alarm had been acknowledged but are still active. To view the Alarm menu from the Main Menu scroll down to the Alarms line. Note the arrow indicating this line is a link. Press the button 6 to jump to the next menu Alarms. There are two lines here; Alarm Active and Alarm Log. Alarms are cleared from the Active Alarm link. Press the button 6 to jump to the next screen. When the Active Alarm list is entered scroll to the item AlmClr which is set to off by default. Change this value to on to acknowledge the alarms. If the alarms can be cleared then the alarm counter will display 0 otherwise it will display the number of alarm still active. When the alarms are acknowledged the Bell on the top right of the display will stop to ring if some of the alarms are still active or will disappear if all the alarms are cleared.
3.5 Basic Control System Diagnostic
Unit controller, extension modules and communication modules are equipped with two status LED (BSP and BUS) to indicate the operational status of the devices. The BUS LED indicates the status of the communication with the controller. The meaning of the two status LED is indicated below.
UC BSP LED
(*) Contact Service.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
18
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
BSP LED
Mode
Solid Green
BSP running
Solid Red
Hardware Error (*)
Flashing Red
BSP Error (*)
Flashing Red/Green
BSP upgrade mode
BUS LED
Mode
Solid Green
Communication running, I/O working
Solid Yellow
Communication running but parameter from the application wrong or missing, or uncorrect factory calibration
Solid Red
Communication down (*)
BSP LED
Mode
Solid Green
BPS running, communication with controller
Solid Yellow
BSP running, no communication with controller (*)
Solid Red
Hardware Error (*)
Flashing Red
BSP Error (*)
Flashing Red/Green
Application/BSP update
BUS LED
Mode
Solid Green
Ready for Communication. (All Parameter loaded, Neuron configured). Doesn't indicate a communication with other devices.
Solid Yellow
Startup
Solid Red
No Communication to Neuron (internal error, could be solved by downloading a new LON application)
Flashing Yellow
Communication not possible to the Neuron. The Neuron must be configured and set online over the LON Tool.
BUS LED
Mode
Solid Green
Ready for Communication. The BACnet Server is started. It doesn't indicate a active communication
Solid Yellow
Startup
Solid Red
BACnet Server down. Automatically a restart after 3 seconds are initiated.
BUS LED
Mode
Solid Green
Ready for Communication. The BACnet Server is started. It doesn't indicate a active communication
Solid Yellow
Startup. The LED stays yellow until the module receives a IP Address, therefore a link must be established.
Solid Red
BACnet Server down. Automatic restart after 3 seconds is initiated.
BUS LED
Mode
Solid Green
All Communication running
Solid Yellow
Startup, or one configured channel not communicating to the Master
Solid Red
All configured Communications down. Means no communication to the Master. The timeout can be configured. In case that the timeout is zero the timeout is disabled.
Extension modules
BSP LED
BUS LED
Communication modules
BSP LED (same for all modules)
(*) Contact Service.
LON module BUS LED
Bacnet MSTP BUS LED
Bacnet IP BUS LED
Modbus BUS LED
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
19
On board real time clock settings are maintained thanks to a battery mounted on the controller. Make sure that the battery is replaced regularly each 2 years.
Battery is only used to supply the onboard real time clock. All the other settings are retained in a non volatile memory.
Actual BSP and software version installed on UC can be checked in the About Chiller page.
3.6 Controller maintenance
The UC requires to maintain the installed battery. Battery model is: BR2032 and it is produced by many different vendors.
To replace the battery gently remove the plastic cover of the controller display using a screw driver as shown in the following pictures:
Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper battery holder which is highlighted in the following picture, respecting the polarities indicated into the holder itself.
3.7 Software Update procedure
UC can be updated by using an SD card and an appropriate pin.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ-G - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
Operation Manual
20
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
The software for this specific range of units cannot be used with the Large UCs (POL687.xx/MCQ) used on other products. In case of doubts, please contact your Daikin Service reference.
SD card has to be FAT32 formatted before any update process can be started. Supported SD types are:
- SD standard
- High speed SD
- SDHC
The following SD cards have also been tested and found operational:
- 1 GByte SD V1.0 (Inmac)
- 2 GByte SD V2.0 SpeedClass 2 (SanDisk),
- 4 GByte SDHC V2.0 SpeedClass 6 (Hama High Speed Pro),
- 4 GByte SDHC V2.0 SpeedClass 4 (SanDisk Ultra II),
- 8 GByte micro SDHC SpeedClass 4 (Kingston)
In case an update is received all the files included in the archive are to be saved in the SD card with their original name. The standard software pack is composed with 6 files:
1. BSP file (operative system of the UC),
2. Code file,
3. HMI file,
4. OBH file (multilingual and protocol support),
5. HMI for Web (web interface),
6. Cloud file.
Before proceeding is required to disable the unit using the Q0 switch and perform a normal shutdown procedure.
To install the software, take care to make a copy of the controller settings on the SD card by using the Save/Restore menu (see Save and Restore menu for details).
Remove power to the controller using the Q12 switch and insert the SD card in its slot as shown in the picture with the contact strips looking toward you.
EWWQ090G ÷ EWWQ720L - R410a - W ater-cooled scroll chillers EWLQ090G ÷ EWLQ720L - R410a - Condenser less EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWAQ- - R410a - Air-cooled scroll chillers EWYQ- - R410a - Air-cooled scroll heat pumps
Operation
Manual
EWWQ - EWLQ - EWHQ EWAQ - EWYQ
Air or Water cooled scroll chiller & heat pump D-EOMHW00106-15EN
Operation Manual
21
Service microswitch is an electronic component. An excessive pressure on the service microswitch can permanently damage the UC. Please take care of not exceed with your strength to avoid damages to your unit.
Once this is done, insert the pin in the reset hole, gently push the service microswitch and keep it pressed until the update process is initiated.
With the service microswitch pressed, re-establish the power to the controller using the Q12 switch. After a short while the BSP led on the UC will start to blink between green and off. When this happen release the service microswitch and wait for the update process to start. Update process is indicated by the BSP led blinking between green and red.
Loading...
+ 47 hidden pages